Revisions to Erds Data Point Library Reference File Due to the Installation of Emergency Response Data System Vpn
ML12152A097
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 05/30/2012
From: Helsel J
Susquehanna
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
PLA-6856
Download: ML12152A097 (74)


Text

Jeffrey M. Helsel PPL Susquehanna, LLC Nuclear Plant Manager 7 69 Salem Boulevard Berwick, P A 18603 Tel. 570.542.3510 Fax 570.542.1504 jmhelsel@pplweb.com U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 SUSQUEHANNA STEAM ELECTRIC STATION REVISIONS TO ERDS DATA POINT LIBRARY REFERENCE FILE DUE TO THE INSTALLATION OF EMERGENCY RESPONSE DATA SYSTEM VPN Docket Nos. 50-387 PLA-6856 and 50-388 In accordance with 10 CFR 50, Appendix E, Section VI.3, attached is the revision to the Emergency Response Data System (ERDS) Data Point Library as a result of the installation of the ERDS VPN that was placed into service on 5/1/2012.

Please contact Mr. John L. Tripoli, Manager- Nuclear Regulatory Affairs at 570) 542-3100 if there are any questions concerning this letter.

Attachment:

ERDS Data Point Library Copy: NRC Region I (Attn: Chief, Emergency Preparedness Branch- DRS)

Mr. P. W. Finney, NRC Sr. Resident Inspector Mr. R. R. Janati, DEP/BRP Ms. C. J. Sanders, NRC Project Manager

Attachment to PLA-6856 ERDS Data Point Library

I PCAF #2003-4310 I

pp,.....

Page 4 of 4

\ I I

,\\:J/~ ER-005

~...***l+' .. SAFETY RELATED 0 CSD

~ OTHER QUALITY [81 FILE No. N/A i:::.. CRXTICAL SOFTWARE (C) 1 of 72 PAGE

.-.. ... NON -QUALITY 0

~ .. TM I

COMPUTER SYSTEM DOCUMENT EMERGENCY RESPONSE DATA SYSTEM (ERDS)

DATA POINT LIBRARY (DPL)

PPL SUSQUEHANNA, LLC - UNITS 1 AND 2 Qualifications: The signatures of preparer, reviewer, and approver below must be qualified as follows:

4. SQA Plan Documents: EG900
5. Computer Test of Validation Procedures: EG900 and EG903
6. Computer System Requirements Specifications: "EG900 All other types of CSDs do not require any qualification.

8 5/17/12 Editorial changes G. Campbell N/A w. DeLuca ]J

~6 7 5/1/12 Revised for ERDS VPN - Final G. Campbell N/A w. DeLuca 6 3/1/12 Revised Point Library to use G. Campbell N/A w. DeLuca equivalent PPC point names per Plant Computer Upgrade - EC 933698 and 933699, and for the transition to ERDS VPN.

5 1/21/04 Iodine and Particulate H.A. Clatch N/A w. DeLuca Elimination -DCP 296398 4 05/23/02 Admin. Correction-DCN 98-0656 was H.A. Clatch N/A W.A. DeLuca incorporated into Rev. 3; Addition of LEFM Pts. To Unit 1 3 06/01/01 Addition of LEFM Pts. To Unit 2 H.A. Clatch N/A W.A. DeLuca 2 05/13/98 Addition of Unit 1 PICSY H;A. Clatch N/A G.J. Krupko 1 11/14/95 Addition of Unit 2 PICSY M.L. Orloski N/A Henry P.

Seager 0 11/30/92 Initial Issue J.L. N/A D.D. Kelley Angstadt REV, DA'l'E DESCRIPTION

  • PREPARED BY VERIFI APPROVED FORM NSEI-AD-505-1, Rev. 3, Page 1 of 1 (Electronic Form}

CSD-ER-005 Revision 8 Page 2 of 72 Procedure Change Summary TITLE: EMERGENCY RESPONSE DATA SYSTEM {ERDS} DATA POINT LIBRARY (DPL)

1) Appendix C changes -
a. Revised Point Library in Appendix C to use equivalent FPC point names per Plant Computer Upgrade

- EC 933698 and 933699:

PAGE Old Point Name New Point Name

1. 9 PWR SPAOOl_E
2. 27 RWL SPA011_E
3. 32 RXPR SPA012_E
4. 36 LPCS SPAOlO_E
5. 39 EGRNRXl VSN01B_E
6. 40 EGRNTB1 VSN02B_E
7. 41 EGRNSBGTS VSN03B_E
8. 42 EGRNRX2 VSN04B_E
9. 43 EGRNTB2 VSN05B_E
10. 44 EGRNSITE VST01C_E
11. 47 PCA SPA022_E
12. 52 DWPR SPA014_E
13. 53 DWT SPA015_E
14. 54 SPT SPA018_E
15. 55 SPWL SPA016_E
16. 56 HYDGN SPA020_E
17. 57 OXYGN SPA019_E
18. '60 METULS VMA07_E
19. 61 METLLS VMA06_E
20. 62 METULD VMA04_E
21. 63 METLLD VMA03_E
22. 64 MET STAB VMA20C_E
23. 65 EXERCISE DUlOO_E
24. All other points were suffixed with \'E" or

"_E~'

CSD ... ER-005 Revision 8 Page 3 of 72 Emergency Response Data System (ERDS}

Data Point Library (DPL)

Table.of*Contents Section 1.0 Scope . 4 Section 2.0 General Information 4 Section 3.0 References 5 Appendix A 6 Appendix B .. . . . . " . . 6 Appendix c 7 Appendix D 66 Appendix E 70

CSD-ER-005 Revision 8 l?age 4 of 72 1.0 SCOPE This CSD documents the Emergency Response System Data Point Library (DPL) submitted to the U.S. Nuclear Regulatory Commission to meet the DPL requirements of NUREG-1394 Rev.1, Emergency Response Data System (ERDS) Implementation.

2.0 General Information The Appendices of this CSD have been named to correspond to the Appendices of NUREG-1394, Rev. 1. Not all of the information required by NUREG 1394, Rev. 1 appendix is included in this document.

>NOTICE

  • Changes to :.App~ndix :*c _:or.:*E of .this. *.C~D.-: *

-~y r~quire .t:h~t .:.th~ N.Rc 1>~ notif:i.ed *o~ : .

. the cha,nge~. R~feren~ei *(;!~D-:-~IC.-759.:f~r '**: ..
  • ...a.e~.a~

t:io~a,i :Q-u;taance ~ ._: , .', \ :*** * **

~ . . .. .. : .. . . .. . ..::. ';. . : ..

\ ~: . : ~ :  :. .. . . .

CSO-ER-005 Revision B Page 5 of 72 The following list identifies the NUREG Appendices, and where the information (if any) required by that Appendix is provided:

Appendix Description Response A Emergency Response Data System PP&L response provided in ERDS Transmission/Reception Plan letter PLA~3704 dated December 20, 1991.

B ERDS Communication Description and Survey Questionnaire PP&L response provided in letter PLA-3672 dated C Data Point Library October 24r 1991.

D Data Point Library Reference Included in this CSD. tll File Definitions No response required.

Appendix duplicated in 2

E Critical Safety Function this CSD for convenience. < >

Parameters Included in this CSD. 13 >

F Engineering Units Coding Scheme' 4 >

No response required.

G Zero Reference Coding Scheme (Sl Reference NUREG 1394, Rev. 1 for details.

H Coding Scheme fo"r Unit Name and No response required.

Unit ID Reference NUREG 1394, Rev. 1 for details.

I Computer Point Selection <6 >

No response required.

Reference NUREG 1394, Rev. 1 for details.

No response required.

Reference NUREG 1394, Rev. 1 for details.

(1)

This Appendix provides detailed information for each point listed in Appendix E.

(2)

This Appendix provides a description of each field in the Data Point Library and the fields maximum character length.

(3)

This Appendix provides a summary of all the computer points that are utilized for ERDS. Reference Appendix C of NQREG-1394 for additional guidance on Data Point Library entries.

(4}

This Appendix provides the preferred engineering units abbreviations for use in the Engineering Units field of the Data Point Library entries.

(5}

This Appendix provides the accepted abbreviations for the Zero Reference Point field of the entries in the Data Point Library that require this field.

(6}

This Appendix provides guidance on the selection of computer points to satisfy the ERDS requirements.

3.0 REFERENCES

3.1 NUREG-1394 1 Rev. 1, Emergency Response Data System (ERDS)

Implementation 3.2 NSEP-QA-500, Process Computer Quality Assurance and Design Control Program

CSD-ER-005 Revision 8 Page 6 of 72 APPENDIX A & B Appendix A & B are not included in this CSD.

Reference Section 2.0 for more information on these appendices.

CSD-ER-005 Revision 8 Page 7 of 72 APPENDIX C DATA POINT LIBRARY

CSD-ER-005 Revision 8 Page 8 of 72 SUSQUEHANNA STEAM ELEC~RIC STATION UNJ:'l'S 1 &:: 2 ERDS DATA POINT LIBRARY REFERENCE FILE Pate: 05/1.3/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Paramete:r-: NI POWER RNG Point ID: SPA001_E Plant Spec Point Desc.! REACTOR POWER Gene:r-ic/Cond Desa.: Nuclear Instruments, Power Range Analog/Digital: A Engr Units/Dig States:  %

Engr units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Rang~: 125 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: p Number of Sensors: 6 How P:r:ocesaed: Averaged (ref. Unique System Desa.)

Sensor Locations: Each APRM has 21 to 22 LPRMs as inputs Alar.m/Trip Set Points: Reference Unique System Desc. (:t.l NI Detector Power Supply CUt-of£ Power Level: N/A NI Detector Power Supply TUrn~on Power Level: N/A Instrument Failure Mode: Low, High Temperatu:r:e Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.~ A Supplier proprietary algorithm basically averages the highest number of on-scale APRMs whose values are in agreement.

(i)_ Various trip set points exist for the APRMs depending on the plant Condition (i.e. Condition 1-5).

Note: PWR .is a composite SPDS parameter 'llrith the following points as inputs: NM551, NM552, NM553, NM554, NM555 1 NM556.

CSD-ER-005 Revision 8 Page 9 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NN109_E Plant Spec Point Desc.: IRM A FLUX (% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng A Analog/Digital: A Engr Units/Dig states:  %

Engr Units Conversion~ N/A Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. {tl NI Detector Po-v1er Supply cut-off Power Level~ N/A NI Detector Power Supply Turn ...:on Powet- Level: N/A Instrument Failure Mode: L0\'1 1 High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: The electrical full--'in limit, positions the detector 18" above the active fuel center. line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the.core is 16-53.

111 - When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block= 86.2%, and a downscale neutron flux/Rod Block= 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 8 Page 10 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE D~te: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NN112_E Plant Spec Point Desc.: IRM D FLUX {% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng D Analog/Digital: A Engr Units/Dig States:  %

Engr Units Conversion: N/A Minimum Ins tr Range: 0 *0 lo1aximum Instr Range: 100.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. (l)

NI Detector Power Supply Cut~off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position} of the detector in the core is 32-37.

<1}_ When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block= 86.2%, and a downscale neutron flux/Rod Block= 4.2%. These blocks/trips are bypassed in condition 1.

CSD-ER-005 Revision 8 Page 11 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NN115_E Plant Spec Point Desc.: IRM G FLUX {%OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng G Analog/Digital: A Engr Units/Dig States:  %

  • Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors ~ 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

111 Alarm/Trip Set Points: Reference Unique System Desc.

NI Detector Power Supply CUt-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.~ The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation {full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 48-13.

(ll_ When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block~ 86.2%, and a downscale. neutron flux/Rod Block= 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 8 Page 12 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID; NN116_E Plant Spec Point Desc. t IRM H FLUX (% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng H Analog/Digital: A Engr units/Dig States:  %

Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 100. 0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 Hmli' Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. (ll NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High

  • Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-13.

(ll_ When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip ~ 95.8%, an upscale neutron flux/Rod Block = 86.2%, and a downscale neutron flux/Rod Block= 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 8 Page 13_of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Paran1eter: Not Listed Point ID: NNX01_E Plant Spec Point Desc.: IRMA RANGE SWITCH POSN Generic/Cond Desc.: IRMA Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr units Conversion: N/A Minimum Instr Range: 1 Maximum Instr Range: 10 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 10 How Processed: Reference Unique System Desc.

Sensor Locations: Panel 1C651 {l) -11D IRM range switch A Alarm/Trip-Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

(l} - Panel 1C651 is for SQ1, Panel 2C651 is for SQ2

CSD-ER-005 Revision 8 Page 14 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/l3/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNX04_E Plant Spec Point Desc.: IRM D RANGE SWITCH*POSN Generic/Cond Desc.: IRM D Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr Units Conversion: N/A ldinirnum Ins tr Range : 1 Maximum Instr Range: 10 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 10 How Processed: Reference Unique System Desc.

Sensor Locations: Panel 1C651 !11 -11D IRM range switch D Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

!1 l - Panel 1C651 is for SQ1, Panel 2C651 is for SQ2

CSD-ER-005 Revision 8 Page 15 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date~ 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID ~ NNX07 _E Plant Spec Point Desc.: IRM GRANGE SWITCH POSN Generic/Cond Desc.: IRM GRange Switch Position Analog/Digital: A Engr units/Pig States: N/A.

Engr Units Conversion: N/A Minimmu Instr Range: 1 Maximum Instr Range: 10 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: p*

Number o£ Sensors: 10 How Processed: Reference Unique System Desc.

Sensor Locations: Panel 1C651 11 l-11D IRM range switch G Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-o££ Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The analog value £or switch position is calculated £rom the IRM switch position digital inputs.

'1 > - Panel 1C651 is for SQ1 1 Panel 2C651 is for SQ2

CSD-ER-005 Revision 8 Page 16 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC EROS Parameter: Not Listed Point ID: NNX08_E Plant Spec Point Desc.: IRM H RANGE SWITCH POSN Generic/Cond Desc.: IRM H Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Bngr Units Conversion: N/A l'Iinirnurn Ins tr Range: 1 Maximum Instr Range: 10 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 10 How Processed: Reference unique System Desc.

Sensor Locations: Panel 1C651 !1>_11D IRM range switch H Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-of£ Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters! N/A Level Reference Leg: N/A Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

Cll - Panel 1C651 is for SQ1, Panel 2C651 is for SQ2

CSD-ER-005 Revision 8 Page 17 of 72 SUSQUEHAt'IDA STEAl'! ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point !D: NNZ54_E Plant Spec Point Desc.: IRM DET NOT FULL IN POS Generic/Cond Desc.: IRM Det(s) not full in Position Analog/Digital: D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Minimum Xnstr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Full in limit switch on IRM drive unit Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value Yes (i.e. Not In)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: This parameter is a logical 'or' of the Plant's eight (8) IRM detectors such that if any detector is not in the full in position this parameter will be true (YES}.

CSP-ER-005 Revision B Page 18 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNZ59_E Plant Spec Point Desc.: IRM BYPASS Generic/Cond Desc.: IRM Bypass Analog/Digital! D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

.N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Panel 1C651 m -11D IRM bypass switch Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value No (i.e. not Bypassed)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: This parameter is a logical 'or' of the Plant's eight (8} IRM detectors bypass status such that if any detector is bypassed this parameter will be true (YES} . --

{l) - Panel 1C651 is for SQ1 1 Panel 2C651 is for SQ2

CSD-ER-005 Revision 8 Page 19 of 72 SUSQUEHANNA STEAM ELECTRIC STATION

'UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ~D: NN1001ZE Plant Spec Point Desc.: SRM A LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng A Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range! .1 Maximum Instr Range: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

11 Alarm/Trip Set Points: Reference Unique System Desc. )

NI Detector Power Supply CUt-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line; The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate {radial position) of the detector in the core is 16-45.

( 1 )- When the plant is in Condition 2 - 5, there is an upscale alarm/rod block ~ 1 x 10 5 CPS, an upscale/non-coincident trip = 2 x 10 5 CPS, and a downscale/rod block = 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 8 Page 20 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date~ 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NN1002ZE Plant Spec Point Desc.: . SRM B LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng B Analog/Digital: ~

Engr units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Range: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. {l)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on PO\'Ter Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A 11 unique System Desc.: The electrical full-in limit, positions the detector 18 above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24 11 below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 40-45.

(ll_ When the plant is in Condition 2 - 5, there is an upscale alarm/rod 5

block = 1 x 10 5 CPS, an upscale/non-coincident trip = 2 X 10 CPS, and a downscale/rod block= 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Rev~sion 8 Page 21 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NN1003ZE Plant Spec ,point Desc. : SRM C LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng C Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Range: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Procepsed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. (l!

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The.location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position} of the detector in the core is 40-21.

(l}- When the plant is in condition 2 - 5, there is an upscale alarm/rod block ~ 1 x 10 5 CPS, an upscale/non-coincident trip = 2 X 10 CPS, and a 5

downscale/rod block= 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 8

Page 22 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NN1004ZE Plant Spec Point Desc. : Sill1 D LOG RATE Generic/Cond Desc.: Nucl~ar Instruments, Sourc Rng D Analog/Digital: A Engr units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Rar1ge: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors : 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

1 Alarm/Trip Set Points: Reference Unique System Desc. < )

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in lirnit, positions the detector 18" above the active fuel center line. The mechanical full~in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-21.

1

( ) - When the plant is in Condition 2 - 5, there is an upscale alarm/rod block ~ 1 x 10 5 CPS, an upscale/non-coincident trip ~ 2 X 10 5 CPS, and a downscale/rod block = 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 R~vision 8 Page 23 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NPY001ZE Plant Spec Point Desc.: SRM POSITION A Generic/Cond Desc.: SRM Position A Analog/Digital: D Engr units/Dig States: NOT IN,IN Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range:* N/A Zero Point Referencet N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor ~ocations: SRM drive motor limit switch Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Levelt N/A

.NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value 'Not In' Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision 8 Page 24 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit; SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NPY002ZE Plant Spec Point Desc.: SRM POSITION B Generic/Cond Desc.: SRM Position B Analog/Digital: D Engr Units/Dig States: NOT IN,IN Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s NuiDber of Sensors: 1 How Processed: N/A Sensor Locations: SRM drive .n1otor limit switch Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value 'Not In' Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision 8 Page 25 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NPY003ZE Plant Spec Point Desc.: SRM POSITION C Generic/Cond Desc.: SRM Position C Analog/Digital: D Engr Units/Dig States: NOT IN, IN Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: SRM drive motor limit switch Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value 'Not In' Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision B P~ge 26 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed

  • Point ID: NPY004ZE Plant Spec Point Desc.: SRtil POSI'l'ION D Generic/Cond Desc.: SRM Position D Analog/Digital: D Engr Units/Dig States: NOT IN, IN Engr units Conversion: N/A Minimum Instr Range: N/A Ha:x:imum Instr Range~ N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed~ N/A Sensor Locations: SRM drive motor limit switch Alarm/Trip Set Points: N/A NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value 'Not In' Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc. :

CSD-ER-005 Revision 8 Page 27 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date! 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: REAC VES LEV Point ID: SPA011_E Plant Spec Point Desc.: REACTOR WATER LEVEL Generic/Cond Desc.: Reactor Vessel Water Level Analog/Digital: A Engr Units/Dig States: INCHES Engr Units Conversion: N/A Minirnum Ins tr Range: -310 Maximum Instr Range: 500 Zero Point

Reference:

BDSKRT Reference Point Notes: BDSKRT near bottom of dryer skirt (ll PROC or SENS: P Number of sensors: Reference Unique System Desc.

How Processed: Reference Unique System Desc.

Sensor Locations: Reactor Bldg Elevation 749' Alarm/Trip Set Points: Reference Unique System Desc. (2 }

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Povrer Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N Level Reference Leg: Wet Unique System Desc.: SPDS has 13 Rx water level inputs in 6 different range groups,* narrow, wide, extended, upset, shutdown & fuel zone. A Supplier proprietary algorithm will arrive at a value for SPAOll_E by either averaging only valid signals in the most appropriate range group* or by selection of a single level signal.

(l}_ zero point reference is 527.5" above vessel zero (bottom drain 0.0").

TAF is at 366.31".

{Zl_ various initiations or trips will occur at Level 1 (-149"), Level 2

( -38 "), Level 3 (+12. 5") and Level 8 (+54 1' }

Note: SPA011_E is a composite SPDS parameter with the following points as inputs: NFL001Z, NFL002Z, NFL003Z, NFL004Z, NFL005Z, NFL007Z, NBL001Z, NBL002Z, NBL003Z, NBL004z; NBL005Z, NBL006Z, and NBL007Z.

CSD-ER-005 Revision 8 Page 28 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/23/02 Reactor unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter! MAIN FD FLOW Point ID: NFF77_E Plant Spec Point Desc.: FW FLOW A Generic/Cond Desc.! Feedwater Flow A into React Syst Analog/Digital: A Engr Units/Dig States: MLBS/H Engr Units Conversion: N/A Minimum Instr Range* 0.0 Maximum Instr Range: 8,000 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low - downscale Temperature Compensation For DP Transmitters:. N/A Level Reference Leg: N/A Unique System Desc,: Flow is measured on discharge line of Pump A prior to common feedwater header.

CSD-ER-005 Revision 8 Page 29 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNI'I'S .1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/23/02 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: l1AIN FD FLOW Point ID: NFF78_E Plant Spec Point Desc.: FW FLOW B Generic/Cond Desc.: Feedwater Flow B into React Syst Analog/Digital: A Engr Units/Dig States: MLBS/H Engr Units Conversion: N/A Minimum rnstr Range: 0.0 Maximum Instr Range: 8.000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low - downscale Temperature compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique system Desc.: Flow is measured on discharge line of Pump B prior to common feedwater header.

CSD-ER-005*

Revision 8 Page 30 of 72 SUSQUEHANNA STEA11 ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/23/02 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERD~ Parameter: MAIN FD FLOW Point ID: NFF79_E_

Plant Spec Point Desc. ~ FW FLOW C Generic/Cond Desc.: Feedwater Flow C into React Syst Analog/Digital: A Engr Units/Dig States: MLBS/H Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 8.000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N/A NI Detector Power SUpply Cut-off Power Level: N/A Nl Detector power Supply Turn-on Power Level: NiA Instrument Failure Mode: Low - downscale Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: Flow is measured on discharge line of Pump C prior to common feedwater header.

CSD-ER-005 Revision 8 Page 31 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: RCIC FLOW Point ID: NIF01_E Plant Spec Point Desc.; RCIC FLOW Generic/Cond Desc.: Reactor Core Isolat Cooling Flow

  • Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion:. N/A Minimum lnstr Range: 0.0 Maximum Instr Range: 700.0 Zero Point

Reference:

N/A Reference Point Notes! N/A PROC or SENS: S Number of Sensors: i

  • How Processed: N/A Sensor Locations: Between RCIC pump and pump discharge. valve {l)

Alarm/Trip Set Points: Alarm, Low Flow at 60 GPM NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument. Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc. : Ill - Reactor Building Elevation 645'

CSD-ER-005 Revision 8 Page 32 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: RCS PRESSURE Point ID: SPA012_E Plant Spec Point Desc.: REACTOR PRESSURE Generic/Cond Desc.: Reactor Coolant System Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 1500 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: Reference Unique System Desc.

How Processed: Reference unique System Desc.

Sensor Locations: Reactor Bldg Elevation 749' Alarm/Trip Set Points: Alarm@ 1020 PSIG,'Trip@ 1037 'PSIG NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: A Supplier proprietary algorithm arrives at a value for SPA012_E by either selecting a single signal or by averaging signals depending on the results of validation and verification of the five sensed pressure signal inputs.

Note: SPA012_E is a composite SPDS parameter with the following points as inputs: NFP001Z, NFP002Z, NFP003Z, NFP005Z, and NFP006Z.

CSD-ER-005 Revision 8 Page 33 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: HPCI FLOW Point ID: NGFOl_E Plant Spec Point Desc.~ HPCI PP DSCH LINE FLOW Generic/Cond Desc.: High Pressure Coolant Injec Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 6000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Nunlher of S~nsors: 1 How Processed: N/A Sensor Locations: Pump discharge line - Rx Bldg Elev. 645' Alarm/Trip Set Points: Alarm, Low Flow at 300 GPM NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure lilode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision 8 Page 34 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: LPCI FLOW Poi_nt ID: NHF01_E Plant Spec Point Desc. : RHR SYS A FLOW Generic/Cond Desc.: Low Press Coolant Inject A Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 30000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Description Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Flow sensed by a flow element in the RHR distribution piping downstream of the RHR heat exchanger.

CSD-:ER-005 Revision 8 Page 35 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2*

ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: LPCI FLOW Point ID: NHF02_E Plant Spec Point Desc.: RHR SYS B FLOW Generic/Cond Desc.: Low Press Coolant Inject B Flow Analog/Digital: A Engr units/Dig States: GPM Engr Units Conversion: N/A

~1inimum Instr Range: 0. 0 Maximum Instr Range: 30000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level~ N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Flow sensed by a flow element in the RHR distribution piping dmmstream of the ~HR heat exchanger.

CSD-ER-005 Revision 8 Page 36 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERpS Parameter: CR SPRAY FL Point ID: SPA010_E Plant Spec Point Desc.: TOTAL CORE SPRAY FLOW Generic/Cond Desc.: Core Spray Cooling System Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 10,000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors ! 2 How Processed: Sum (Reference Unique System Desc.)

Sensor Locations: Reference Unique System Description(!)

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A Nl Detector Power Supply Turn-9n Power Level: N/A Instrument Failure Mode: Hlgh 1 Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: A Supplier proprietary algorithm calculates LPCS as the sum of the CS Loop A and Loop B flows. The algorithm utilizes the position of the CS Test Isolation Valve as well as d~1ell pressure, reactor vessel pressure, and reactor water level in the selection and validation of each loop's flow.

The algorithm selects a value for flow for each loop from either the measured loop flow or the calculated loop flow (based on loop pressure and pump-head performance curve) depending on the algorithm logic table.

(l)_Downstream of Pump A & C (Loop A) Discharge connection and Pump B & D Loop B) Discharge connection.

Note: SPAOlO_E is a composite SPDS parameter with the following points as inputs: NSF001Z, NSF002Z, NSPO.OlZ, and NSP002Z.

CSD-ER-005 Revision 8 Page 37 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT L~BRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW FD SMP LV Point ID: RLL004ZE Plant Spec Point Desc.: A DRWL SUMP LEVEL Generic/Cond Desc.: Drywell Floor Drain Sump Level A Analog/Digital: A Engr Units/Dig States:  %

Engr Units Conversion: Each 1% r:::t 1 Gallon(ll Minimum Instr Range: 37.5 Maximum Instr Range: 100 Zero Point

Reference:

BTSUMP = Bottom of Sump Reference Point Notes: Reference Unique System Desc. (Z)

PROC or SEWS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: D~ell Floor Drain Elev. 704 1 Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: 111 Instrumentation output is level switch driven, each step is approximately 15 gals.

(7.l Input referenced to bottom of sump. Actual instrument zero is .25" below input reference point.

Upon containment isolation output of smnp is also isolated.

CSD-ER-005 Revision 8 Page 38 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW FD SMP LV Point ID: RLL005ZE Plant Spec Point Desc.: B DRWL SUMP LEVEL Generic/Cond Desc.: Drywell Floor Drain Sump Level B Analog/Digital: A Engr Units/Dig States:  %

Engr Units Conversion: Each 1% r::: 1. 2 Gallon for SQ1 (l)

Each 1% ~ 1 Gallon for SQ2 Minimum Instr Range: 37.5 Maximum Instr Range: 100 Zero Point

Reference:

BTSUMP = Bottom of Sump 2

Reference Point Notes: Reference Unique System Desc. < >

PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Drywell Floor Drain Elev. 704' Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: en Instrumentation output is level switch driven, each step is approximately 16 gals for Unit 1 {SQ1} and 15 gals for Unit 2 (SQ2}.

cal Input referenced to bottom of smnp. Actual inst1:ument zero is . 25" below input reference point.

Upon containment isolation output of sump is also isolated.

CSD-ER-005 Revision 8 Page 39 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE

~ate: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC EROS Parameter: EFF GAS RAD Point ID: VSNOlB_E Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-RX 1 VENT Geperic/Cond Desc.: Rad of Released NBLGAS-Rx 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors : 1 How Processed: Average Sensor Locations: Reference unique System Desc. (ll Alarm/Trip Set Points: N/A NI Detector Power Supply CUt-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. VSN01B_E is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. VSN01B_E is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of VSNOlB_E \'Till be transmitted each minute for a given fifteen minute period until the next update is available.

(l}- Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 8 Page 40 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: VSN02B~E Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-TB 1 VENT Generic/Cond Desc.: Rad of Released NBLGAS-TB 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc.<ll Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. VSN02B_E is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. VSN02B_E is updated each quarter hour {i.e. it is not a sliding 15 min average). Therefore, the same value of VSN02B_E will be transmitted each minute for a given fifteen minute period until the next update is available.

(l)_ Isokinetic sample dra*qn @ Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 8 Page 41 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: VSN03B_E Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-SGTS VENT Generic/Cond Desc.: Rad of Released NBLGAS-SGTS Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average 111 Sensor Locations: Reference Unique System Desc.

Alarm/Trip set Points: N/A NI Detector Pm'ler Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. VSN03B_E is created by averaging the properly selected Noble Gas range {low, mid or high} 1 min average releases for a 15 min period. VSN03B~E is updated each quarter hour (i.e. it is not a sliding 15 min average) . Therefore, the same value of VSN03B_E will be transmitted each minute for a given fifteen minute period until the next update is available.

<ll- Isokinetic sample drawn @ SGTS vent near Rx Bldg roof.

CSD-ER-005 Revision 8 Page 42 of 72 SUSQUEHANNA STE~l ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: VSN04B_E Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-RX 2 VENT Generic/Cond Desc.: Rad of Released NBLGAS-Rx 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/.trlin Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average 11 Sensor Locations: Reference unique system Desc. '

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. VSN04B_E is created by averaging the properly selected Noble Gas range (low, mid or high} 1 min average releases for a fifteen min period. VSN04B_E is updated each quarter hour {i.e. it is not a sliding 15*min average). Therefore, the same value of VSN04B_E will be transmitted each minute for a given fifteen minute period until-the next update is available.

(l}- !sokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 8 Page 43 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: VSNOSB_E Plant Spec Point Desc.; RAD OF RELEASED NBLGAS-TB 2 VENT Generic/Cond Desc.: Rad of Released NBLGAS-TB 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc. (ll Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. VSN05B~E is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. VSN05B_E is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of VSNOSB_E will be transmitted each minute for a given fifteen minute period until the next update is available.

{l)_ Isokinetic sample drawn @Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 8 Page 44 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: VST01C_E Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-SITE TOTL Generic/Cond Desc.: Rad of Released NBLGAS-Site Totl Analog/Digital: A Engr Units/Dig States: uCI/Min Engr units conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 5 How Processed: Reference UniqUe System Desc.

Sensor Locations: N/A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Site Total 1 min average for the Noble Gas release component is created by summing the Noble Gas 1 min averages of the Rx 1, TB 1, SGTS, Rx 2 and TB 2 vents. VSTOlc_E is created by averaging the Site Total 1 min averages for a 15 min period. VST01c_E is updated each quarter hour (i.e. it is not a sliding 15 min average) . Therefore, the same value for VST01C_E will be transmitted each minute for a given fifteen minute period until the next update is available.

CSD-ER-005 Revision 8 Page 45 of 72 SUSQUEHANNA STEAM ELECTRIC STATION

' UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF LIQ RAD Point ID: VDR001ZE Plant Spec Point Desc.: LRW DSCH RAD MON Generic/Cond Desc. : Radioactivity of Released Liq'ds Analog/Digital: A Engr Units/Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: 10 Maximum Ins tr Range: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: Ref. Unique System Desc. (1.}

Alarm/Trip Set Points: Varies - Ref. Unique System Desc. (2 )

NI Detector Power Supply Cut-off Povrer Level: N/A Nl Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: U) Sample dravm from LRW discharge pipe prior to release to environment.

The Liquid Radwaste Effluent Monitor is a microprocessor based NMC Liquid Radiation Monitor. A single gamma scintillation detector is exposed to the sample of the discharge stream. Discharge is governed by Radiation Effluent release permit.

2

( ) Detector alarm settings are determined for each release based upon tank activity & background values at the sample unit.

CSD-ER-005 Revision 8 Page 46 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98

  • Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: VDF001ZE Plant Spec Point Desc.: LRW DISCHARGE FLOW Generic/Cond Desc.: LRW Discharge Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units conversion: N/A Minimum Xnstr Range: 0 Maximum Instr Range: 100 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc. !l)

Alarm/Trip Set Points: N/A NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: 11 > On Liquid Radwaste discharge line prior to environment. The liquid radwaste line discharges into the cooling tower discharge pipe. The cooling to\'ter discharge pipe goes to the Susquehanna River.

CSD-ER-005 Revision 8 Page 47 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIB~RY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW RAD Point ID: SPA022_E Plant Spec Point Desc. : PRIMARY CONTAINMEN'l' ACTIVITY Generic/Cond Desc.: Radiation Level in the Drywell Analog/Digital: A Engr Units/Dig States: R/HR Engr units Conversion: ~/A Minimum Instr Range: 1 Maximum Instr Range; 1E8 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

Sensor Locations: Drywell on Bioshield Wall Alarm/Trip Set Points: Alarm 400 R/HR and 2000 R/HR NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm selects the point with the higher value if the difference between the two points exceeds a predefined delta.

Note: SPA022_E is a composite SPDS parameter with the following points as inputs: MAR001Z and MAR002Z.

CSD-ER-005 Revision 8 Page 48 of 72

$USQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LI~RARY.REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: MN STEAM RAD Point ID: NAR01_E Plant Spec Point Desc. : MAIN STEAH LINE RAD A Generic/Cond Desc.: Radiation Lvl of Main Stm Line A Analog/Digital:. A Engr Units/Dig States: MR/H Engr Units Conversion: N/A Minimum Instr Range: 1.000*

Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference UniqUe System Desc. (l)

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Pm'ler Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters:' N/A Level Reference Leg: N/A Unique Systent Desc.: Standard BWR .Main Steam Line Radiation Monitoring design and configuration.

(ll - The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 8 Page 49 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: MN STEAM RAD Point ID: NAR02_E Plant Spec Point Desc.: MAIN STEAM LINE RAD B Generic/Cond Desc. : Radiation Lvl of Main Stm Line B Analog/Digital: A Engr Units/Dig States: MR/H E~gr Units Conversion; N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc. (l}

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and configuration.

(l) -The detectors {A-D). are located in the steam tunnel as close as practical to the containment.* The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 8 Page 50 of 72 SUSQUEHANNA STEAl-1 ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: MN STEAM RAD Point ID: NAR03_E Plant Spec Point Desc.: MAIN STEAM.LINE RAD C Generic/Cond Desc.: Radiation Lvl of Main Stm Line C Analog/Digital: A Engr Units/Dig States: ~ffi/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc. (l)

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector PO\'ter Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and configuration.

(ll - The detectors {A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 8 Page 51 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC EROS Parameter: MN STEAM RAD Poinj:: ID ~ NAR04_E Plant Spec Point Desc.: MAIN STEAM LINE RAD D Generic/Cond Desc.: Radiation Lvl of Main Stm LineD Analog/Digital: A Engr Units/Dig States: MR/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc. (l}

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and configuration.

(ll - The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 8 Page 52 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parmneter: DW PRESS Point ID: SPA014_E Plant Spec Point Desc.: DRYWELL PRESSURE Generic/Cond Desc.~ Drywell Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: -15.0 Maximum Instr Range: 250.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 5 How Processed: Reference unique System Desc.

Sensor Locations: Reactor Bldg. Elevation 719' Alarm/Trip Set Points: Trip @ 1. 72 PSIG NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm selects the value for SPA014_]5 by using up to five inputs, one Narrow Range (NR) signal (-3.0 to +3.0 PSIG), two Intermediate Range (IR) signals {-15.0 to +65.0 PSIG), and two Wide Range (WR) signals {0 to +250.0 PSIG). If the NR signal is onscale then it is selcted for SPA014_E. If the NR signal is invalid and the IR signal{s) are onscale then they are utilized for SPA014_E. If both NR and IR signals are invalid then the WR signals will be utilized for SPA014_E.

Note: SPA014_E is a composite SPDS parameter with the following points as inputs: MAPOOlZ, MAP003Z, MAP004Z, MAP005Z, and MAP006Z.

CSD-ER-005 Revision 8 Page 53 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW TEMP Point ID: SPA015_E Plant Spec Point Desc.: DRYWELL TEMPERATURE Generic/Cond Desc.: Drywell Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 40 Maximum Ins tr Range: 440 Zero Point Re.ference: N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 8 How Processed: Average (Reference Unique System Desc.}

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Alarm 135°F NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm uses the Technical Specification method for calculating drywell average air temperature which selects the higher valid signal from a minimum of 3 of the following dr~vell areas: top, middle 1 bottom and pedestal. SPA015_E is then calculated as the average of the 3 or 4 valid signals selected. If there is less than 3 valid signals then the algorithm cannot calculate an average value.

Sensor Locations (elevation, azimuth): (797' 8", 295°), (797' 8", 110°),

(752' 2",270°), (752' 2",90°L (737',300°}, {737',150°), {711',270°),

{720 1 1 85°} .

Note: SPA015_E is a composite SPDS parameter with the following points as inputs: MATOOlZ, MAT002Z, MAT003Z, MAT004Z, MAT005Z,' MAT006Z, 1~T007Z, and MATOOBZ.

($D-ER-005 Revision 8 Page 54 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERD8 DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: SP TEMP Point ID: SPA018__E Plant Spec Point Desc.: SUP~RESSION POOL TEMPERATURE Generic/Cond Desc. : Suppression Pool Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 30 Maximum Instr Range: 230 zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average Sensor Locations: Reference Unique System Desc.

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algoritmn calculates SPA018_E as the average of the two inputs if they are valid and agree, otherwise the higher of the two signals is selected. Each of the inputs to the algorithm is provided by a Suppression Pool Temperature Monitoring System (SPOTMOS). The SPOTMOS unit uses up to 8 temperature inputs to calculate the average temperature. The RTD inputs to SPOTMOS that are used to calculate the average temperature are located at appoximately the 21 foot level in the suppression pool.

Note: SPA018_E is a composite SPDS parameter with the following points as inputs: MAT012Z and MAT013Z.

CSD-ER-005 Revision 8 Page 55 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: SP LEVEL Point ID: SPA016_E Plant Spec Point Desc.: SUPPRESSION POOL WATER LEVEL Generic/Cond Desc. : Suppression Pool Water Level Analog/Digital: A Engr Units/Dig States: FEET Engr Units Conversion: N/A Minimum Ins tr Range: 4.5 Ma:x:imum Ins tr Range: 49 Zero Point

Reference:

TNKBOT Reference Point Notes: N/A PROC or SENS: P Number of Sensors : 4 How Processed: Reference Unique System Desc.

Sensor Locations: Rx Bldg Elev. 645.'

Alarm/Trip Set Points: High 2 23.75 ft, Lm'l ~ 22.25 ft NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: Wet unique System Desc.: A Supplier proprietary algorithm uses 2 Narrow Range (NR), 18-26.5 ft, and 2 Wide Range (WR), 4.5-49 ft 1 signals to arrive at a value for SPA016_E L.

The NR signals are given preference over the WR signals. In cases in which NR signals do not agree and are not confirmed by WR signals, a signal (or average of signals)-with greater deviation from Normal Water Level (NWL}, measured at 23ft, is used because it is a critical safety concern. A WR signal (or average of WR signals) may be chosen over a NR signal if it is verified'as having a greater deviated value from the NWL than the NR signal.

Note: SPA016_E is a composite SPDS parameter with the following points as inputs: MALOOlZ, MAL002Z, MAL003Z, and MAL004Z.

CSD-ER-005 Revision 8 Page 56 of 72 SUSQUEHANNA STEAM ELECTRIC S'rATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: H2 CONC Point ID: SPA020_E Plant Spec Point Desc.: CONTNMNT. HYDROGEN CONCENTRATION Generic/Cond Desc.: Drywell Hydrogen Concentration Analog/Digital: A Engr units/Dig States:  %

Engr Units Conversion: N/A Minimum Ins tr Range: 0 Maximum Instr Range: 30 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

Sensor Locations: Reference Unique System Desc. {l}

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Povrer Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Each of the inputs has dual range capability and \'Till have a range of 0-10%* or 0-30%. A Supplier proprietary algorithm will calculate SPA020_E as the average of the two inputs if they are both on the same range and agree. Any other combination of valid points (e.g. points disagree, are on different ranges, only one on-scale) will cause the algorithn1 to select only one of the two inputs for the value of SPA020_E.

(l}- Sample drawn from drywell or suppression chamber and measured at Panel 1C226A & B for SQl and 2C226A & B for SQ2, Reactor Building Elev. 719'.

Note: SPA020_E is a composite SPDS parameter with the following points as inputs: MAC003Z and MAC004Z.

CSD-ER-005 Revision 8

Page 57 of 7 2 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: 02 CONC Point ID~ SPA019_E Plant Spec Point Desc.: CONT~~T. OXYGEN CONCENTRATION Generic/Cond Desc.: Drywell Oxygen Concentration Analog/Digital: A Engr Units/Dig States:  %

Engr units conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 25 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

Sensor Locations: Reference Unique System Desc. ' 11 Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Each of the inputs has dual range capability and will have a range of 0-10% or 0-25%. A Supplier proprietary algorithm will calculate SPA019_E as the average of the two inputs if they are both on the same range and agree . . Any other combination of valid points (e.g. points disagree, are on different ranges, only one on-scale) will cause the algorithm to select only one of the two inputs for the value of SPA019~E.

(ll_ Sample drawn from drywell or suppression chamber and measured at Panel 1C226A & B for SQ1 and 2C226A & B for SQ2, Reactor Building Elev. 719'.

Note: SPA019_E is a composite SPDS parameter with the following points as inputs:. MAC001Z and MAC002Z.

CSD-ER-005 Revision B Page 58 of 72 SUSQUEHANNA STEAM ELECTRIC STA'l'ION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date; 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: CST LEVEL Point ID: CSL01_E Plant Spec Point Desc.: COND STORAGE TANK 1 LVL Generic/Cond Desc. : Condensate Storage Tank 1 Level Analog/Digital: A Engr units/Dig states:  %

Engr Units Conversion: Each 1% ~ 3,000 Gallons Minimum Ins tr Range; 0. 0 Maximum lnstr Range: 100.0 zero Point

Reference:

TNKBOT Reference Point Notes: Zero is 13.5 inches above tank bottom PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: 7.5 inches below zero reference Alarm/Trip Set Points: Low level at 0% (ref. Unique System Desc.}

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn~on Power Level: N/A Instrument Failure Mode: Low or High (on LI, LR and Computer point}

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Zero is 10,000 gallons above HPCI suction.

The RWST and both CSTs can be manuallY cross connected. The capacity of each CST is 300,000 gallons and the RWST capacity is 680,000 gallons.

CSD-ER-005 Revision 8 Page 59 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 EROS DATA POINT LIBRARY REFERENCE FILE Date: 05/~3/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: CST LEVEL Point ID: CSL02_E Pla:n,t Spec Point Desc. : COND STORAGE TANK 2 LVL Generic/Cond Desc.: Condensate Storage Tank 2 Level Analog/Digital: A Engr Units/Dig States:  %

Engr Units Conversion: Each 1% ~ 3,000 gallons Minimum lnstr Range: 0.0 Maximum rnstr Range: 100.0 Zero Point

Reference:

TNKBOT Reference Point Notes: Zero is 13.5 inches above tank bottom PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: 7.5 inches below zero reference Alarm/Trip Set Points: Low level at 0% (ref. Unique System Desc.}

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply TUrn-on Power Level: N/A Instrument Failure Mode:* Low or High {on LI, LR and Computer point)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Zero is 10,000 gallons above HPCI suction.

The RWST and both CSTs can be manually cross connected. The capacity of each CST is 300,000 gallons and the RWST capacity is 680,000 gallons.

CSD-ER-005 Revision 8 Page 60 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: WIND SPEED Point ID: VMA07_E Plant Spec Point Desc.: WIND SPEED-60M Generic/Cond Desc.: Wind Speed at Reactor Site -60M Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 1.0 Maximum Instr Range: 50.0 Zero Point Reference~ N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: 15 min average (ref. Unique System Desc)

Sensor Locations: :t1et Tower is :=:< 11200 ft. ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply cut-of£ Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc:: 15 min ave1.*age is a sliding 15 min average.

CSD-ER-005 Revision 8 Page 61 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98

  • Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter~ WIND SPEED Point ID: VMA06_E Plant Spec Point Desc.: WIND SPEED-10M Generic/Cond Desc.: Wind Speed at Reactor Site -10M Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 1.0 Maximum Instr Range: 50.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors : 1 How Processed: 15 min average (ref. Unique System Desc)

Sensor Locations: Met Tower is :::~ 1, 200 ft ..ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 8 Page 62 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parrurreter: WIND DIR Point ID: VMA04_E Plant Spec Point Desc.: WIND DIR ~ 60 M Generic/Cond Desc.: Wind Dir at the React Site -60M Analog/Digital: A Engr Units/Dig States: DEGFR Engr Units Conversion: N/A Minimum Instr Range: 0 lilaximum Instr Range: 360 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: 15 min vector average 11 !

sensor Locations: Met Tower is 1!:1 1,200 ft. ESE of Rx B).dg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure l.fode t Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique system Desc. : (l) - 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 8 Page 63 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS. DATA POINT LIBRARY REFERENCE FILE Date; 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder~ N/A NRC ERDS Parameter: WIND DIR Point ID: VMA03_E Plant Spec Point Desc.: WIND DIR - 10 M Generic/Cond Desc.: Wind nir at the React Site -1m1 Analog/Digital: A Engr Units/Dig States: DEGFR Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 360 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: p Number of Sensors: 1 How Processed: 15 min vector average!ll Sensor Locations: Met Tower is ~ 1,200 ft. ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode~ Low Temperature Compensati~n For DP Transmitters: N/A Level Reference Leg: N/A I

Unique System Desc.: II> - 15 min average is a sliding 15 min average.

I

CSD-ER-005 Revision 8 Page 64 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder; N/A NRC ERDS Parameter: STAB CLASS Point ID: VMA20C_E Plant Spec Point Desc.: AIR STABILITY AT 'THE REACT SITE Generic/Cond Desc.: Air Stability at the React Site Analog/Digital: A Engr Units/Dig States: STABI Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Reference Unique System Desc.

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Reference Unique System Desc.

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The parameter is derived from the Delta Temperature between the 10 meter and 60 meter levels. If the Delta Temperature signal is invalid then the parameter is derived from the Sigma Theta of wind direction.

A value of 1 through 7 which corresponds to a stability class of A through F, or 9 (invalid) will be transmitted for VMA20C_E.

CSD-ER-005 Revision 8 Page 65 of 72 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: DU100_E Plant Spec Point Desc.: EXERCISE DATA Generic/Cond Desc.: Exercise Data Al1alog/Digital: D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Ninimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors: 1 How Processed: N/A Sensor Locations: RDAS variable {i.e. pseudo point)

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode; N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: This parameter is a constant whose value is equal to 0 when actual

. plant data is being transmitted and 1 when exercise/drill data is being transmitted.

CSD-ER-005 Revision 8 Page 66 of 72 APPENDIX D DATA POINT LIBRARY REFERENCE FILE DEFINITIONS

CSD-ER-005 Revision 8 Page 67 of 72 APPENDIX D DATA POINT LIBRARY REFERENCE FILE DEFINITIONS Date: The date that this form is filled out or modified. (Eight characters}

Reactor Unit: The nuclear power plant name and abbreviation from the enclosed list of sites. (Three characters)

Data Feeder: If there is more than one data feeder for your systemJ enter the acronym for the data feeder from which the point comes.

If there is only one data feeder, enter "N/A in this field (Ten characters}

11 NRC ERDS Parameter: One of the parameters from the enclosed BWR or PWR parameter list. A single value should be transmitted for each parameter for each loop. If not on the list, insert "Not Listedu or NL 11 11

  • (Twelve characters)

Point ID: Alphanumeric point description used to label the point during transmission.

{Twelve characters)

Plant-Specific Point

Description:

Licensee computer point description for the transmitted point. (Forty characters}

Generic Or Condensed

Description:

Parameter description from the enclosed list of points for a BWR or PWR. If not on the list, condense the plant-specific point description. (Thirty-two characters)

A:nalog/Digital: 11 A11 if the signal is analog or numerical or D if the signal is off/on.

11 (One character)

Engineering Units Or Digital Engineering units used by the licensee for States display on licensee output devices. Use the engineering units abbreviations from the enclosed list when possible. When specifying pressure, use "PSIA" *or nPSIG" rather than "PSI 11

  • For digital signals, give the 11 0FF" and 1tQN 11 state descriptors.

(Twelve characters)

Engineering units Conversion: Notes about any special features of the A/D conversion and scaling. (Forty characters}

Minimum Instrument Range: Engineering units value below which data cannot go (bottom-of-scale value) . {Ten characters)

CSD-ER-005 Revision 8 Page 68 of 72 Maximum Instrument Range: Engineering units value above which data cannot go {top-of-scale value} . (Ten characters)

Zero Reference Point: Zero-point of engineering units scale used primarily for levels or heights. Use the zero reference point abbreviations from the enclosed list when possible. (Six characters)

Reference Point Notes: Notes about the reference point*or other important and special features of the parameter. (Forty characters)

PROC or SENS: Is the poin't formed by processing more than one signal, or is the source a single sensor

( llpn or usn)? {One character)

Number of Sensors: The number of signals processed in a full calculation assuming no bypassed or inoperative sensors. {Three characters)

How Processed: The processing algorithm (sum, average, weighted average, highest, lowestr or a short description). (Forty characters)

Sensor Locations: Description of the location(s) of the instrument(s) used. (Forty characters)

Alarm or Trip.Setpoints: The most important setpoints for the parameter. State whether the limit is high or low. (Forty characters)

NI Detector Power Supply Cut-Off The power level at which the power supply Power Level: for the NI detector switches off. (Fifteen characters}

NI Detector Power Supply Turn-On The power level at which the power supply Power Level: for the NI detector switches on. (Fifteen characters)

Instrument Failure Mode: The mode in which this instrument fails.

Possible answers are HIGH, MEDIUM, OR LOW.

If available, provide the numeric value at which the.instrument fails. (Thirty characters)

Temperature Compensation For DP This question ~ertains to differential Transmitters:* pressure transmitters. Possible answers are "YES 11 or uNO" ("Y" or "N"}. If the answer is "N0 11 1 please attach a copy of the correction curve. {One character)

CSD-ER-005 Revision 8 Page 6g of 72 Level Reference Leg: The type of level measurement (dry or wet) used on the level reference leg. (Three characters}

unique System

Description:

Additional important information which will assist the NRC Operations Center personnel in understanding how the plant team interprets the data. (600 characters)

PICSY Plant Integrated Computer System - Unit 2

CSD-ER-005 Revision 8 Page 70 of 72 APPENDIX E CRITICAL SAFETY FUNCTION PARAMETERS f'

CSD ER-005 Revision a*

Page 71 of 72 CRITICAL SAFETY FUNCTION PARAMETERS EROS

~ARM~TER DESCRIPTION NI POl~R RNG Nuclear Instruments, Power Range  %

N.I INTER RNG Nuclear lnst:rumenta, Intex- Rng A  %

Nl INTER RNG Nuclear Instruments, Inter Rng D  %

Nl lNTER RNG Nuclear Instruments, Inter Rng G  %

NI INTER RNG Nuclear Instruments, Inter Rng H  %

Not Listed I~I A Range Switch Position Not Listed IRM D Range SWitch Position Not Listed IRM G Range Switch Position Not Listed IRM H Range Switch Position Not Listed IRI-1 Det{s) not Full in Position NO/YES Not Listed IRM Bypass NO/YES NI SOURC RNG Nuclear Instruments, Sourc Rng A CPS NI SOURC RNG Nuclear Instruments, Sourc,Rng B CPS N.I SOURC RNG Nuclear Instruments, Sourc Rng C CPS NI SOURC RNG Nuclear Instruments, Sourc Rng D CPS Not Listed SRI-J X'osidon A NOT IN/IN Not Listed SRM Position B NO'l' :J:N/XN Not :r.isted SRH Position C NOT IN/IN Not Listed SRlof l?osition D NOT IN/IN CORE COOi.lNG REAC VES LEV Reactor Vessel Water Level NAlN FD FLOW Feedwater Flow A into React Syst l.U.BS/H MAIN FD FLOW Feedwater Flow B into React Syst MLBS/H MAIN FP FLOW ~eedwater Flow C into React Syst l>!L:SS/H RCIC FLOW Reactor Core lsolat Cooling Flow GPM RCS IN'l'EGRITY RCS PRESSURlil Reactor Coolant System Pressure :PSIG HPCI FLOW High Pressure Coolant Injec Flow GPM Ll?CI FLOW Low Press Cool~t Inject A Flow GP1o1 LPCI FLOW Low Press Coolant rnject B Flow GPM CR SPRAY FL Core Spray Cooling System Flow GPM DW FD SMP LV D~ell Floor Drain Sump Level A  %

DW FD SMP LV Drywall Floor Drain Sump Level B  %

CSD ER-005 Revision 8 Page 72 of 72 RADIOACTIVX~Y CONTROL l?ll'i'F GAS RAD Rad of Released NBLGAS-Rx 1 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-TB 1 Vent uC!/MIN lilFF GAS RAD Rad of Released NBLGAS-SGTS Vent uCI/MIN EFF GAS RAD Rad of Released WBLGAS-Rx 2 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-TB 2 Vent uCI/Z.IIN EFF GAS RAD Rad of Released NBLGAS-Site Totl uCI/MIN EFF LIQ RAn Radioactivity of Released Liq*ds CPM Not Listed LR?T Discharge Fl.ow GPM Cl'lD A/E Rl\D Condenser Air Ejector Radioactivity DW RAD Radiation Level in the D~ell R/liR Z.m' STEAI>J RAD Radiation L~l of Main Stm Line A 1-iR/ll MN STEM! RAD Radiation Lvl of Matn Stm Line B HR/H t-lN STEAM RAD Radiation Lvl of Main Stm Line C MR/H MN STEM! RAD Radiation Lvl. of Main Stm Line b MR/H CONTAim~ENT CONDITIONS m'l PRESS P;I;",YI'Iell Pressure l:?SIG D~l TEMP Drywall T$rnperature DEGF SP TEUP Suppression Pool Temperature Pl'i:GF SP LEVEL Suppression Pool. Water Level FEET H2 CONC Drywall Hydrogen Concentration  %

02 CONC Drywell Oxygen concentration  %

MISCELLANEOUS PARAMETERS CST LEVEL Condensate Storage Tank 1 Level  %

CST Ll?JVEL condensate Storage Tank 2 Level  %

WIND SPEED Wind Speed at ReactoJ;" Site -60M MPH WIND SPEEP \'find Speed at Reactor Site -10M Z.JPH w:mn biR Wind Dix- at the React Site -601-! DEGFR WIND DIR Wind Dir at the Reaet Site -10M DEGFR STAB CLASS Air Stability at the React Site STABA lil>O!lRCISE DATA Exercise Data NO/Yl:S