LER 80-004/03L-0:on 800204,during Routine Surveillance, Reactor Protection Sys Channel B Trip Signal for RCP Underspeed Found Out of Specs.Caused by frequency-to-voltage Converter Being High & Unstable.Unit Replaced & Calibr
ML19294C227
Person / Time
Site: Millstone Dominion icon.png
Issue date: 03/03/1980
From: Bates R
NORTHEAST UTILITIES
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19294C220 List:
References
LER-80-004-03L-01, LER-80-4-3L-1, NUDOCS 8003070338