GNRO-2017/00053August25,2017 U.S.Nuclear Regulatory Commission ATTN: DocumentControlDesk Washington,DC20555-0001 Entergy Operations, Inc.P.O.Box756PortGibson,MS39150EricA.LarsonVicePresident, OperationsGrandGulfNuclearStationTel.(601)437-7500

SUBJECT:

ResponsetoESEBRAI-1,ResultsofIWEandIWL Inspections Grand Gulf NuclearStation-Unit1DocketNo.50-416LicenseNo.NPF-29

REFERENCES:

1.EntergylettertoNRC, License Amendment Request(LAR)forOneCycle Extension of Appendix JTypeA Integrated LeakageRateTestand Orywell BypassTestInterval, dated December29,2016 (GNRO-2016/00062)(ML 16364A338)2.NRCEmailtoEntergy, Grand Gulf-OfficialRAls[sic]forLAR AssociatedwithOneCycle Extension of Appendix JTypeA ILRTandOrywell Bypass Test Interval(CACNo.MF9461), dated August2,2017 (GNRI-2017/00049)(ML 17214A099)

DearSirorMadam:

In Reference1,Entergy Operations, Inc.requestedaonecycleextensiontothe10-year frequencyoftheGrand Gulf NuclearStation(GGNS)Unit1 IntegratedLeakageRateTest(ILRT),orTypeAtest,andtheDrywellBypassLeakRateTest(DWBT).

Reference2wasaRequestfor Additional Information(ESEBRAI-1)fromthe Structural Engineering Branch(ESEB)ofthe Nuclear Regulatory Commission(NRC)staff.GGNSwasrequestedtoprovidetheresultsoftheIWE InspectionpriortoRF20andtheresultsofthelasttwoIWLInspections.

Attachment1tothisletterprovidesthe responsetotheRAI.Attachments2and3providetheIWEInspectionresultsandtheIWL Inspectionresults,respectively.Thislettercontainsnonew Regulatory Commitments.Shouldyouhaveany questions concerning the contentofthisletter,pleasecontactDougNeveat(601)437-2103.Ideclareunderpenaltyofperjurythatthe foregoingistrueandcorrect.Executedonthe zs" dayofAugust,2017.

GNRO-2017/00053Page2of3";\"" Sincerely,EricA.Larson tv-GGNSSiteVice President EAUsas Attachment 1: GGNSResponsetoESEBRAI-1 Attachment 2: Containment Visual Inspection (IWE)Attachment 3: ContainmentBuildingVisual Inspection (IWL)cc:seenextpage GNRO-2017/00053Page3of3cc:U.S.Nuclear Regulatory CommissionATTN:Mr.SivaLinghamMailStopOWFN8B1Rockville,MD 20852-2738 U.S.Nuclear Regulatory CommissionATTN:Mr.ScottMorrisActingRegional Administrator,RegionIV1600EastLamarBoulevardArlington,TX76011-4511Mr.B.J.SmithDirector,Divisionof Radiological HealthMississippiState DepartmentofHealthDivisionof Radiological Health3150LawsonStreetJackson,MS39213 NRC Senior Resident InspectorGrandGulf Nuclear StationPortGibson,MS39150


Attachment1to GNRO-2017/00053 GGNSResponsetoESEBRAI-1 GNRO-2017/00053 Attachment 1ESEBRAI-1Section3.3.9oftheLAR providedtheresultsofthemostrecent(RF20)

Containment Visual Inspection pursuanttoSectionXIoftheAmerican Society of Mechanical EngineersBoilerand PressureVesselCode, SubsectionIWE,butdidnotprovidetheresultsofanyoftheIWL inspections performedtodate.In orderfortheNRCstafftoassesstheeffective implementationofthe licensee's IWElIWLCISIProgram,pleaseprovidea discussion oftheresultsfortheIWE inspection performedpriortoRF20,anda discussionoftheresultsforthelasttwoIWLinspectionperiods.ResponsetoESEBRAI-1ResultsofIWE inspectionpriortoRF20:TheIWE inspectionpriortotheIWE inspectionofRF20was performed duringRF19.Theresultsofthis inspection were characterizedas"Itemswere previously identified and evaluated.

No additional degradation noted.II In supportoftheresultsoftheRF19IWE inspectionasstatedabove,theinspectionitems identifiedduringtheRF19 inspectionareprovidedin Attachment2.TheRF20IWEinspectionresults (previously providedinLARTable3.3.9-2)arealsoprovidedwiththeadditionofthe inspection component identificationtopermitthe comparisonoftheRF19andRF20 inspections.ResultsofthelasttwoIWL inspections:ThelasttwoIWL inspections were performedinRF20andRF18.Theresultsof these inspections were characterized as"Indications were previously identified and evaluatedwithnochanges.

II In supportoftheresultsoftheRF20andRF18IWL inspectionsasstatedabove,the inspectionitemsidentifiedduringtheRF20andRF18 inspectionsareprovidedin Attachment3.Theinspectionresultsarealsoprovidedwiththe corresponding inspection component identificationtopermitthe comparisonoftheRF20andRF18 inspections.Followonresponsetotable numbering commentinLARSection3.3.8, Containment Inservice Inspection ProgramDuringthe conferencecallof August1,2017a clarification concerning the identification ofthetablesreferencedinLARSection3.3.8andtheir improper identificationasTable3.3.7etc.was identifiedbythereviewer.Entergypersonnel provided verificationthatthe reviewer's assumptionwascorrect.Asa follow-uptothis verification,thefollowing correctedpagesareprovided:

ML 16364A338 GNRO-2016-00062 Pg 26.pdf ML 16364A338 GNRO-2016-00062Pg31.pdf ML 16364A338 GNRO-2016-00062 Pg 33.pdf ML 16364A338 GNRO-2016-00062 Pg 36.pdfPage1of6 GNRO-2017/00053 Attachment 1 The identifiedpagesareas presentedinthe completeLAR.Revisionbarswereutilizedto identify the changes.Pleaseseethenextfourpagesofthis Attachment,labeledas"GNRO-2016/00062 Attachment 1."Page2of6 GNRO-2016/00062 Attachment 1andtheirintegral attachments and metallicshelland penetrationlinersofClassCC pressure retaining componentsandtheirintegral attachments are subjecttothe requirements of Subsection IWE.In accordance with IWA-1320andIWL-1100,ClassCCreinforced concreteand tensioning systems of concrete containments are subjecttothe requirements of Subsection IWL.ASMESectionXICodeofRecord In accordance with 10CFR50.55a(g),EntergyisrequiredtoupdatetheASMESectionXI(theCode)ContainmenfiSIProgramonceeverytenyears.Theupdated Containment lSIProgramisrequiredto complywiththe latesteditionand addendaoftheCode incorporated by referencein1OCFR50.55aoneyearpriortothestartoftheintervalper1OCFR50.55a(g)(4)(ii).ThepriorintervaldatesforGGNSwereJune2,1997throughMay31,2008[2ndInterval].Basedon"lockin"dateofMay 31,2007,the2001Editionwiththe2003 Addenda ofASMESectionXIistheversionofSectionXIthatEntergymustmeetforthe currentinterval[3rdInterval].ASMESectionXICodeCases Per 10CFR50.55a(g),ASMECode Casesthathavebeen determinedtobesuitableforuseinlSIProgramPlansbytheNRCarelistedinRG1.147"Inservice Inspection Code Case Acceptability-ASMESectionXI,Division1".Theuse ofCodeCases(otherthanthoselistedin RegulatoryGuide1.147)maybe authorizedbythe DirectoroftheOfficeof NuclearReactorRegulationuponrequest pursuant to 10CFR50.55a(a)(3).TheASMESectionXICodeCases incorporatedintothe ContainmentlSIProgramPlanarelistedinTable3.3.8-1.Atthetimethis ContainmentlSIProgramPlanwas originally issued,Revision15of RegulatoryGuide1.147wasthelatestrevision.Atthetimethis ContainmentlSIProgramPlanwasissued,Revision16of RegulatoryGuide1.147wasthelatestrevision.

TABLE 3.3.8-1CODECASES INCORPORATEDINTOTHECISIPROGRAMCodeCase Title/RG1.147Revision/

RegulatoryGuide1.147 ConditionsForRequestforAlternative UseN-532-4Alternative RequirementstoRepairand 15 Replacement Documentation RequirementsandInservice SummaryReportPreparationand Submission N-624 Successive Inspections 14 N-739 Alternative Qualification Requirements for 16PersonnelPerformingClassCCConcrete and PosttensioningSystemVisual ExaminationsN-753VisionTests 16 GNRO-2016/00062 Attachment 1 Per IWA-2430(d), for components inspectedunderProgramB,eachoftheinspectionintervalsmaybe extended or decreasedbyasmuchasoneyear.

Adjustmentsshallnot cause successive intervalstobealteredbymorethanoneyearfromtheoriginalpatternof intervals.

Per IWA-2430(e),inadditiontotheinterval adjustmentallowedper IWA-2430(d), forpowerunitsthatareoutofservice continuouslyfor6monthsormore,theinspectionintervalduringwhichtheoutage occurredmaybe extendedforaperiod equivalenttotheoutageandtheoriginalpatternofintervals extended accordingly for successive intervals.

Inspection Schedule-Subsection IWEPerIWA-2420, inspectionplansshallbe preparedforthefirstinserviceintervaland subsequent inspectionintervals.Per IWA-2420(b), an implementationschedulefor performance of examinationsandtestsshallbepreparedforeachinspectionplan.

Subarticle IWE-2400 includes the requirementsforthe scheduling of examination andtestsforClassMC componentsandMetallicLinersofClassCC components.

Specific schedulingcriteriaare included in IWE-2412forplants,whichareemploying InspectionProgramB.This paragraph references Table IWE-2412-1,whichincludesminimumand maximum percentages of examinationsrequiredtobe completedbyeachinspectionperiod.Table3.3.8-2 summarizes this information.Figure3.3.8-1providesinterval,periodand approximate outage dates.Per IWE-2412(a),thefollowing examinationslistedinTableIWE-2500-1as deferrable totheendofthe inspectionintervalarenotrequiredtomeetthecriteriainTable IWE-2412-1:

a)CategoryE-A,ItemNoE1.12-WettedSurfaceof Submerged Areas b)CategoryE-A,ItemNoE1.20-BWRVentSystem AccessibleSurfaceAreas TABLE 3.3.8-2 IWE COMPONENT SCHEDULING INSPECTION INSPECTION PERIOD MINIMUM MAXIMUM INTERVAL (CALENDAR YEARS EXAMINATIONS EXAMINATIONS OF SERVICE WITHIN COMPLETED,%CREDITED,%THE INTERVAL)3ra 3..16 50 3ra 7 50 1 75 3ra 10 100 100 1Ifthefirstperiod completion percentageforany examination categoryexceeds34%,at least 16%oftherequired examinationsshallbe performedinthesecondperiod.

GNRO-2016/00062 Attachment 1 Inspection Periods-Subsection IWL Subarticle IWL-2400 includes the requirementsforthe scheduling of examination andtestsforClassCC Concrete components.Table3.3.8-3 summarizes the Subsection IWL Examination periodsforGGNS.Concrete examinationsshallbe conductedevery5years(aperiod)as describedin2410(a)and(c).Forthe purposesofthisprogramsection,anIWL inspectionperiodshallbedefinedasthe windowoftimeallowedby IWL-2410forthe completionofonesetof IWL examinations.

Concretesurfaceareasaffectedby repair/replacement activitiesshallbeexaminedin accordance with IWL-2410(d).

Table 3.3.8-3 Projected IWL Examination Periods Period Start DateEndDate30Year 1/2/2011 1/2/201335Year 1/2/2016 1/2/201840Year 1/2/2021 1/2/202345Year 1/2/2026 1/2/202850Year 1/2/2031 1/2/203355Year 1/2/2036 1/2/203860Year 1/2/2041 1/2/2043SubsectionIWE Component Selection CriteriaClassMC componentsareselectedfor examinationperthe requirementsofthe2001Editionwiththe2003 AddendaofSectionXI,Table IWE-2412-1.

IWE-2420(a) statesthatthe sequence of component and component support examinations establishedduringthefirstintervalshallberepeatedduringthe successive intervalstotheextentpractical.Entergywillselectand examine a majorityoftheClassMC components and component supports in accordancewiththiscriteria.However,EntergyhasadoptedCodeCaseN-624asapprovedin RegulatoryGuide1.147,whichstatesthatthe sequence of examinationsmaybe modifiedprovidedthe percentage of requirements ofTableIWE-2412-1aremet.CodeCaseN-624allowsthe sequence of examinations establishedduringthefirstintervaltobemodifiedbyfactorssuchas scaffolding erection, radiological concerns,insulationremovalorother considerations.

The Containment Inspection Engineer selects examinationsforagivenintervalandforagivenperiodin accordancewiththe requirementsof1OCFR50.55aandASMESection XI.Examination selections are documentedinthe IDDEALdatabase.The implementing organization determines the appropriate schedule for completionofthe examinationswithinagivenperiod.

Examination CategoryE-ASelection GNRO-2016/00062 Attachment 1 remain essentially unchanged,theyno longer require Examination Category E-C examination.

10CFR50.55a Limitations and Modifications*The requirementsofTableIWE-2500-1 Examination CategoryE-C,are modifiedby1 OCFR50.55aasfollows:*Per 10CFR50.55a(b)(2)(ix)(G),theVT-1 examinationmethodmustbeused to conduct the examinationinItemE4.11ofTable IWE-2500-1.

The"owner-defined" visual examination provisionsinIWE-231 O(a)arenot approvedforuseforVT-1 examinations.*Per1 OCFR50.55a(b)(2)(ix)(I), the ultrasonic examination acceptance standard specified in IWE-3511.3forClassMC pressure-retaining componentsmustbeappliedto metalliclinersofClassCC pressure-retaining components.

IdentificationofIWE Augmented Examination of ContainmentSurfaceAreas Examination Category E-C Wheneveraplanthasanarea(s)requiring examination under CategoryE-C,theareashallbe identifiedintheI DDEALdatabase.Areasrequiring Category E-C examinationarelistedinTable3.3.8-4 Table 3.3.8-4 Areas Requiring Category E-C Examination Component Description Exam Requirements 10EC-01Corrodedlinerplateareaunder Ultrasonic ContainmentPenetration38.EC-02Corrodedplatearound Containment UltrasonicPenetration38.EC-03Corrodedlinerplateinexpansionfoam UltrasonicareaatAZ45degrees.

EC-04Corrodedlinerplateinexpansionfoam UltrasonicareaatAZ240 decrees.EC-05Corrodedlinerplateinexpansionfoam UltrasonicareaatAZ270degrees.

1-FP-02F-2 SuppressionPoolliner,Mech.Damage, Ultrasonicdentindication.

1-FP-08A-1 SuppressionPoolliner,Mech.Damage, Ultrasonicotherindication.

1-FP-08A-1 SuppressionPoolliner,Mech.Damage, Ultrasonicdentindication.

1-FP-04D-4 SuppressionPool-liner,Mech.Damage, Ultrasonicotherindication.

1-WP-01C-3 SuppressionPoolliner,Mech.Damage, Ultrasonicotherindication.

Attachment2to GNRO-2017/00053 Containment Visual Inspection (IWE)

GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.RF20,March2016 Suppression Pool Underwater Surfaces 1-FP-02F-2DentIndication.Random mechanical (mech.)damageaffectingReportto Engineering Approved substrate-30 Count-0.25in.dia.perIndication,In.xIn.area.Metalloss55mils.1-FP-08A-1OtherIndication.Randommech.damageaffectingsubstrate-1Reportto Engineering Approved Count-0.125in.x2in.perIndication,in.xin.area.Metalloss<11mils1-FP-08A-1DentIndication.Randommech.damageaffectingsubstrate-1Reportto Engineering Approved Count-0.25in.dia.perIndication,in.xin.area.Metalloss<30mlis 1-FP-040-4Otherindication.Randommech.damageaffecting substrate-Reportto Engineering Approved0.0625in.x10in.perIndication,in.xin.areaaffected,4PerSq.Ft.Metalloss<9mlls 1-WP-01C-3OtherIndication.Isolatedmech.damageaffecting substrate-0.25 in.Reportto Engineering Approveddia.perIndication,8in.x3in.areaaffected,9PerSq.Ft.Metalloss<12mlls ContainmentBuildingLinerLiner93-1 Uncoatedsurface,3places,lightrustonlinerweld,noevidenceofItemswere previously identified No additional degradation noted 181-VT-16-060pitting.

and evaluated acceptable.duringthis examination.Uncoatedsurfaceatlinerweld.Lightrustwithnoevidenceofpittinq.Liner93-2UncoatedsurfacewithlightrustThereisnoevidenceofpitting.Itemswere previously identified No additional degradation noted ISI-VT-16-061 and evaluated acceptable.duringthis examination.Weldonlinerisnotcoated.Rustwithnoevidenceofpitting.Uncoatedsurfaceareaapprox.3'0"x1'0".Haslightrustwithnoevidenceofpitting.Coatingappearstohavebeenremovedbymech.means.

Beam attachmentsarenot accessibleforvisualinspection.Thisappliesonlytobottomsection.Page1of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Liner 93-3 Uncoated surfaceonweld seams.Light corrosionwithno evidenceItemswere previously identified No additional degradation notedISI-VT-16-062ofpitting.

and evaluated acceptable.

during this examination.

Uncoated surfacewithlight corrosion.

No evidenceofpitting.

Uncoated surfaceswithlightto mediumrust.Thisis mainly around the welded connections and surroundingareainthe water box.Thereisno evidence of pitting.Uncoated surfaceswithlightto mediumrust(3 areas).Thereisno evidenceofpitting.

Uncoated surfacewithlight corrosion on embedplate.No evidenceofoittino.

Liner 93-4 Coatings removedinthisarea.This area is where suppression poolItemswere previously identified No additional degradation noted ISI-VT-16-063 instrument cable was attachedtoliner.There are areasoflightrust and evaluated acceptable.

during this examination.thathaveno evidenceofoittinq.

Liner 93-5 Coatings removedinthisarea.Thisareais where suppression poolItemswere previously identified No additional degradation noted ISI-VT-16-064 instrument cable was attachedtoliner.There are areasoflightrust and evaluated acceptable.

during this examination.thathaveno evidenceofoittinq.

Liner 93-6 Coating removedatwelds.Weldshavelightrust.Itemswere previously identified No additional degradation notedISI-VT-16-065 and evaluated acceptable.

during this examination.

Coatings removed in theseareas.Zincisinplace.

Coatings removedinthisarea.This area is where suppression pool instrumentcablewas attachedtoliner.Areashavelightrust.

Thereisno evidence of oittinq.Liner 93-8 Uncoated surface on linerweld.Lightrustwithno evidenceofItemswere previously identified No additional degradation notedISI-VT-16-067 pitting.and evaluated acceptable.

during this examination.

Uncoated surface.Endofweldhaslight corrosionwithno evidenceofpitting.

Liner 120-1 Uncoated surfacewithlightrust.

Thereisno evidenceofpitting.Itemswere previously identified No additional degradation noted ISI-VT-16-018 and evaluated acceptable.

durino this examination.Page2of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfaceontophalfofpenetration.Zinccoatingisintact.Thereisnoevidenceofpitting.Uncoatedsurfacewhere suppression pool instrumentsareinstalled.Lighttomediumrustinsomeareaswithnoevidenceofpitting.Uncoatedsurfacewith tiohtrust.Noevidenceofpittinq.Liner120-2Uncoatedsurface.Zincstillinplace.Surfaceis1

%" approx.Itemswere previouslyidentifiedNo additional degradation noted ISI-VT-16-019andevaluatedacceptable.duringthis examination.Uncoatedsurface.Weldshaveminorrust.No evidenceofpitting.Visibleruststreaks.Thesourceis inaccessibleforinspection.Uncoatedsurface.Lightrustatweldonembedplate.Noevidenceofpitting.Liner120-3Uncoated surfacewithnorust.Areaisapprox.1/8"x

%".Itemswere previously identified No additional degradation noted ISI-VT-16-020andevaluatedacceptable.duringthis examination.

Uncoated surfacewithnorust.Areaisapprox.

%" x%".Uncoatedsurfacewithnorust.Areaisapprox.

1%" x%".Thereisnoindicationofpittingonitemsshownabove.Liner120-4Uncoatedsurfaceapprox.

W'(chippedpaint).Itemswere previously identified No additional degradation noted ISI-VT-16-021andevaluatedacceptable.duringthis examination.Uncoatedsurfaceapprox.1 Y2" X 3,4"(chippedpaint).Thereisnoindicationofoittinqinremovalareas.Liner120-5Coatingsremovedinthisarea.Thisareaiswhere suppression poolItemswere previously identified No additional degradation noted ISI-VT-16-022 instrumentcablewasattachedtoliner.Rustinarea.andevaluatedacceptable.duringthis examination.Thisareaisusedforstorageduringrefueloutages.Therearemultipleareaswherecoatingshavebeenremoved(chipped,scratches).Lightrustinarea.Thereisnoindicationofpittinginareasoflightrust.

Page3of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Liner120-6Coatingsremovedinthisarea.Thisareaiswhere suppression poolItemswere previously identified No additional degradation noted 181-VT-16-023 instrumentcablewasinstalled.Lightrustinareas.andevaluated acceptable.duringthis examination.Visibleruststreaks.Thesourceis inaccessibleforinspection.Coatingremovedfrom3"area.Primerisstillintact.Thereisnoindicationofpittinginareasoflightrust.Liner120-7Uncoatedsurfaceswithlightandmediumrustwhere suppressionItemswere previously identified No additional degradation noted 181-VT-16-024 pool instrumentationcablesareattachedtoliner.Noevidenceofandevaluatedacceptable.duringthis examination.

pitting.Liner120-8Uncoatedsurfaceswithlightandmediumrustwhere suppressionItemswere previously identified No additional degradation noted 181-VT-16-025pool instrumentationcablesareinstalled.Rustinsomeareaswithandevaluatedacceptable.duringthis examination.noevidenceofpitting.Uncoatedsurfaceatendcap.Lightrustwithnoevidenceofpitting.Liner135-1Uncoatedsurfacesaroundremovalareaonembedplate.ThereisItemswere previously identified No additional degradation noted 181-VT-16-026lightrustwithnoevidenceofpitting.andevaluatedacceptable.duringthis examination.Uncoatedsurfacewithlightruston penetrationcover.Thereisnoevidenceofpitting.Uncoatedsurfacewithlightrust.Areasareapprox.1".Thereisno evidenceofpitting.Uncoatedsurfacewithlightrust.Thesearesmallareaswithnoevidenceofpitting(3places).Uncoatedsurfacewithlightrust.Areaisapprox.2"withnoevidenceofpitting.Uncoatedsurfaceonweld.Thereislighttomediumrustwithno evidenceofpittinq.Liner135-2Uncoatedsurfacewithlighttomediumrust.ThisareaextendstoItemswere previously identifiedNoadditional degradation noted 181-VT-16-027belowtheseamweldintotheexpansionjointat161'elev.Thisareaandevaluatedacceptable.duringthis examination.Page4of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.is inaccessibleforexamination.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(2places).Thisisnoindicationof pitting.Uncoatedsurfacewithlightrust.Thisisnoindicationofpitting.Uncoatedsurfacewithnorustorpitting.Paintinanareaofapprox.4"x2.5"haspeeled.Zincisstillintact.Uncoatedsurfacewithnorustorpitting.Paintinanareaofapprox.1.5"x2.5"haspeeled.Zincisstillintact.Uncoatedsurfacewithlightrust.Areaisapprox.2"inlength.Thereisnoindicationofpitting.Uncoatedsurfacewithnorustorpitting.Therearescatteredareasofchippedpaint.Zincisstillintact.Uncoatedsurfaceonportionsoftheweld.Thereisnorustorpittinq.Liner135-3Uncoatedsurfaceonplatetolinerweld.ThereislightrustwithnoItemswere previously identified No additional degradation notedISI-VT-16-028indicationofpitting.andevaluatedacceptable.duringthis examination.Uncoatedsurfaceonseamweld.Thereislightrustwithnoindicationofpitting.Item3.Uncoatedsurfacewithnorustandnopitting.Painthaschippedawayinanareaofapprox.1"x2".Zinccoatingisstill intact.Uncoatedsurfacewithnorustorpitting.Painthasflakedawayinthisarea.Zinccoatingisstillintact.Uncoatedsurfacewithnorustorpitting.Thereare numerous areasofchippedpaint.Zinccoatingisstillintact.Page5of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithlightrustontheweld.Thereisno indicationofpitting.

Uncoated surfaceonembedplate.Thereislightrustwithno indicationofpitting.

Uncoated surfacewithlightrust.Thereisno indicationofpitting.

Uncoatedsurfaceonseamweld.Thereislightrustwithno indicationofpitting.

Uncoatedsurfaceonthelineratthe expansionjoint.Thisdoesnotextendbehindthe expansionjoint.Thereisno evidenceofpitting.

Uncoated surfacewithnorustorpitting.Painthasflakedawayinanareaapprox,1"x1.5".Liner135-4 Uncoated surfacewithlightrust.Thereisno indicationofpitting(2Itemswere previously identified No additional degradation noted ISI-VT-16-029 places).and evaluated acceptable.

during this examination.

Lichtrustonweld.Thereisnoindicationofpitting.Liner135-5 Uncoated surfacewithlightrust.Thereisno evidenceofpitting.Itemswere previously identified No additional degradation noted ISI-VT-16-030 and evaluated acceptable.

during this examination.

Uncoated surfacewithlightrustaround penetrations.Thereisnot evidenceofpitting.

Uncoated surfacewithmediumtolightrust(7places).Thereisno evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.12"x2",Thereis no evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.14"x2".Thereis no evidenceofpitting.

Q Uncoatedsurfacewithliohtrust.Thereisno evidenceofpitting.Page6of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Uncoated surfacewithlightrust.Areaisapprox.4"x12".Thereis no evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.2" diameter.Thereisno evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.3" diameter.Thereisno evidenceofpitting.

Uncoated surfacewithlightrust.Thereisno evidenceofpitting.

Uncoated surfacewithlightrustatweld.Thereisno evidence of oittino.Liner135-6 Uncoated surfacewithlightrustbehind l-beam(3places).Itemswere previously identified No additional degradation noted ISI-VT-16-031 and evaluated acceptable.

during this examination.

Uncoated surfacewithlightrustatwelds.

Uncoated surfacewithlightrustapprox.3"sq.

Uncoated surfacewithlightrustapprox.10"x4".

Uncoated surfacewithlightrustapprox.4"x6".

Uncoated surfacewithlightrustthefulllengthoftheplate.Painthas chippedandorpeeled.Baremetalwithlightrust.Areasareapprox.3" diameter(4places).Baremetalwithlightrustapprox.3" diameter.Inaccessible areas behind vertical trays.No evidence of pittinqinareas identifiedashavinqliqhtrust.Liner135-7 Uncoated surfaceatembedtolinerweld.

ThereisliqhtrustwithnoItemswere previously identified No additional degradation notedPage7of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.ISI-VT-16-032indicationofpitting.andevaluatedacceptable.duringthis examination.Uncoatedsurfaceateyeboltwelds.Thereislightrustwithnoindicationofpitting.Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.24"x2".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.3"x4".Thereisnoindicationofpitting.Uncoatedsurfacewithnorustandnopitting.Locationisscatteredwithareasofchippedpaint.Zincisintact.Uncoatedsurfacewithlightrustonattachment.Thereisnoindicationofpitting.Thereisagougeapprox.3/4"x1/4"x1/32"deep.Thereislightrustwithnoindicationofpitting.Thereisascratchapprox.3/8"x1/4".Thereislightrustwithnoindicationof pittinq.Liner135-8Uncoatedsurfacewithlightrust.Areaisapprox.3"x1".ThereisnoItemswere previously identified No additional degradation noted ISI-VT-16-033indicationofpitting.andevaluatedacceptable.duringthis examination.Uncoatedsurfacewithlightrustonweld.Thereisnoindicationof pitting.Uncoatedsurfacewithlightrust.Areaisapprox.10"x4".Thereisnoindicationofpitting.Page8of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoated surfacewithlightruston penetration covers.Thereisno indicationofpitting.

Uncoated surfacewithlightruston attachmentwelds(8 places).Thereisno indicationofpitting.

Uncoated surfacewithliohtrust.Thereisno indicationofoittinq.

Liner 161-1 Uncoated surfacewithlightruston penetration surface.ThereisnoItemswere previously identified No additional degradation noted ISI-VT-16-034 indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoated surfacewithlightruston attachment welds.Thereisno indicationofpitting.

Uncoated surfacewithlightruston penetration cover and attachment welds.Thereisno indicationofpitting.

Uncoated surfacewithlightrustonstrain gauge(2places).

There is no indicationofpitting.

Uncoated surfacewithlightrust(3places).Areaisapprox.2" diameter.Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.31/2"x11/2".Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.4"x2".

Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.3"x2".

Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.5"x4".

Thereisno indicationofpitting.

Uncoated surfacewithliqhtrust(3places).

Thereisno indication ofPage9of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.pitting.Uncoated surlacewithlightrust(10places).Thereisnoindicationofpitting.Uncoatedsurlace.Thereisnumerousareasofchippedandpeeledpaint.Thereis liqhtrustinsomeareaswithnoindicationofpittinq.Liner161-2 Uncoated surlacewithlightrust.Areaisapprox.4"x3"(4places).Itemswere previously identified No additional degradation noted ISI-VT-16-035Thereisnoindicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoated surlacewithlightrustonthe penetrationcovers(3places).Thereisnoindicationofpitting.

Uncoated surlacewithlightrust.Thereisnoindicationofpitting.

Discernablebulgewitha diameterof8".Thisbulgeextendsoutwardapprox.1/2".Thereisnoflakingorpeelingofcoatingsinthisarea.

UT thickness measurements were perlormedintheareaonandaroundthebulge.ThereisnoreductionofbasematerialfromthatrecordedonNDEReport BOP-UT-07-008.

Uncoated surlacewithlightrust.Areaisapprox.1/2"x4".Thereisnoindicationofpitting.

Uncoated surlacewithlightrustorpitting.Painthasbeenchippedbutthezinccoatingisintact.

Uncoated surlacewithlightrust.Areaisapprox.4"diameter.Thereisnoindicationofpitting.

Uncoated surlacewithlightrustontheseamweld(2places).Thereisnoindicationofpitting.

Uncoated surlaceontheswaystrut attachmentweld.Thereisnoindicationof pittinq.Page 10 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Painthasflakedinareaapprox.1/2"x2".Zinc coatingisintact.Liner 161-3 Uncoated surfaceatT.S.attachmentwelds.ThereislightrustwithItemswere previously identified No additional degradation noted ISI-VT-16-036 no indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoatedsurfacewithlightruston penetrationcover.Thereisno indicationofpitting.

Uncoatedsurfacewithlightruston penetration coverandpipe.Thereisnoindicationofpitting.

Uncoatedsurfacewithllohtrust.Thereisno indicationofpittinQ.Liner161-4 Uncoated surfacewithlightrustandnopittingon penetrationcoversItemswere previously identified No additional degradation noted ISI-VT-16-037(5pieces).

and evaluated acceptable.duringthis examination.

Uncoatedsurfacewithlightrustandnopittingonthe attachment weld.Uncoatedsurfacewithlightrustandnopittingonthegaugemount.

Uncoatedsurfacewithlightrust.No indicationofpitting.

Uncoatedsurfacewithlightrustandnopittingonremovalareas(3 places).Uncoatedsurfacewithlightrustandnopittingatseamweld.Areaisapprox.6"inlenqth.

Liner 161-5 Uncoatedsurfacewithlightrustwhereunistrut attachestotheplateItemswere previously identified No additional degradation noted ISI-VT-16-038(6places).No indicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoated surfacewithlightrust.Areaisapprox.10"x4"(3places).Thereisnoindicationofpitting.

Uncoatedsurfacewithlightrust.Areaisapprox.6"x4"(2places).ThereisnoindicationofpittinQ.

Page 11 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Uncoated surfacewithlightrustonthe penetration coverandpipe(2places).Thereisno indicationofpitting.

Uncoatedsurfaceatthestraingaugeweld attachments(6places).Thereisnoindicationofpitting.

Uncoated surfacewithlightrust.No indicationofpitting.

Uncoated surfacewithlightrustatthe attachmentweld.No indicationofpitting.

Uncoatedsurfacewithlightrust.Areaisapprox.

7"x3"(2pieces).

No indicationofpitting.

Uncoated surfacesapprox.6"x3"(2places).Thereislightrustwith no indicationofpitting.

Uncoated surfacesapprox.6"x4"(2places).Thereislightrustwith no indicationofoittinc.

Liner 161-6 Uncoatedsurfaceon attachmentweldatstrain gauges(4places).Itemswere previously identified No additional degradation noted ISI-VT-16-039Thereislightrustwithno indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoatedsurfacewithlightrust.Areaisapprox.14"x8".Thereis no indicationofpitting.

Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.

Uncoatedsurfacewithfourareaswitharcstrikes.No indication of crackingorpitting.

Uncoated surface 360('aroundthe equipmenthatchflange.Lightrustwithno indicationofpitting.

Uncoatedsurfacewithliqhtrust.Areaisapprox.18"x6".Thereis Page 12 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)ComponentIDIndication Description Disposition Comments IReportNo.no indicationofpittinq.

Liner 161-7 Uncoated surfaceonpipe behind penetration cover (2 places).Itemswere previously identified No additional degradation noted ISI-VT-16-040 Thereislightrustwithno indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoated surface on attachmentweldat strain gauge.Thereislightrustwithno indication of pitting.Uncoated surface on attachment weld.Thereislightrustwithno indication of oittinq.Liner 161-8 Uncoated surface at strain gauge weld attachment.

ThereislightItemswere previously identified No additional degradation noted ISI-VT-16-041rustwithno indication of pitting.and evaluated acceptable.

during this examination.

Scattered areas of chippedpaint.Norust.Zinc coatingisintact.Angle removalareawithlightrust.No indication of pitting.Liner184-1 Uncoated surfacewithlightrust(3 places).Thereisno indicationofItemswere previously identified No additional degradation notedISI-VT-16-042 pitting.and evaluated acceptable.

during this examination.

Uncoated surface with strain gauge.There is mediumrustwithno indication of pitting.Uncoated surface at attachment weld.Thereislightrustwithno indicationofpitting.

Uncoated surfacewithlightrust(4 places).Thereisno indication of pitting.Uncoated surfacewithlightrust(7 places).Thereisno indication of pitting.Uncoated surfacewithnorust.Areaisanark strikewithno indication of cracksorpitting.

Uncoated surfacewithlightrust.

Thereisno indicationofpitting.

Page 13 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Gougewithareductionof0.060"fromnominalwall.Nominalwallis0.275".Reductionwascausedfromgrinding.Locationofgougeisat194'EL.Gougewithareductionof0.046"fromnominalwall.Nominalwallis0.268".Reductionwascausedfromlugremovalatlocation186'-5" EL.Gougewithareductionof0.0625"fromnominalwall.Nominalwallis0.268".Reductionwascausedfromlugremovalatlocation187'-5"EL.Liner184-2Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.Itemswere previously identified No additional degradation noted ISI-VT-16-043 and evaluated acceptable.duringthis examination.Uncoatedsurfacewithlightrust(10places).Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.4"x2".Uncoatedsurfacewithnorustorpitting.Thereare numerous areasofchippedpaint.Zinccoatingisintact.Liner184-3Gougewithreductionof0.078"fromnominalwall.NominalwallisItemswere previously identified No additional degradation noted ISI-VT-16-0440.282".Areaisapprox.1/2"diameter.Locationofgougeis189'-10" and evaluated acceptable.duringthis examination.

at AZ-11T.Uncoatedsurfacewithchippedpaintin numerousareas.Thereisnorustandthezinccoatingisintact.Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.Uncoatedsurfaceduetoarcstrikes(5places).Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaapprox.1"diameter.Thereisnoindicationofpitting.

Page 14 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithmediumrust(3places).Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.2"diameter.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(5places).Thereisnoindicationof pitting.Uncoatedsurfacewithmediumrustinanareaapprox.12"square.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustinanareaapprox.1"diameter.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(3places).Thereisnoindicationof pittinq.Liner184-4Uncoatedsurfaceat attachmentwithlightrust(2places).ThereisItemswere previously identifiedNoadditional degradation noted ISI-VT-16-047noindicationofpitting.

and evaluated acceptable.duringthis examination.Uncoatedsurfaceatpenetrationweld.Thereislightrustwithnoindicationofpitting.Uncoatedsurfacewithlightruston penetration(2places).Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.8"x5".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x5",Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.2" diameter (3places).Thereisnoindicationofpitting.

Page 15 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithlightrustatstraingauge.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x10".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x10".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.14"x18".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x4".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x6".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(9places).Thereisnoindicationof pitting.Uncoatedsurfaceonembedplatewithmediumrust.Thereisnoindicationofpitting.Uncoatedsurfaceonembedplatewithmediumrust.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(2places).Areaisapprox.12"x8".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.12"x8".Thereisnoindicationofpitting.Liner184-6Uncoatedsurfacewithlightrustandunistrut attachment(2places).Itemswere previously identified No additional degradation noted 181-VT-16-049Thereisnoindicationofpitting.andevaluatedacceptable.duringthis examination.

Page 16 of 46 GNRO-2017/00053 Attachment 2 ContainmentVisualInspection(IWE)

Component ID Indication Description Disposition Comments IReportNo.Uncoated surtacewithlightrustatstraingauge(2places).Thereis no indicationofpitting.

Uncoated surtacewithlightrustat attachmentweld.Thereisno indicationofpitting.

Uncoated surtacewithlightrust.Areaisapprox.3" diameter.Thereisno indicationofpitting.

Uncoated surtacewithlightrust.Areaisapprox.4" diameter.Thereisno indicationofpitting.

Uncoated surtacewithmediumrustatstraingauge.Thereisno indicationofpitting.Liner184-7 Uncoated surtacewithlightrustat attachmentweld.ThereisnoItemswere previously identified No additional degradation noted 181-VT-16-050 indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoated surtacewithlightrust.Areaisapprox.2" diameter.Thereisno indicationofpitting.

Uncoated surtacewithlightrust.Areaisapprox.1/2" diameter.Thereisno indicationofpitting.

Uncoated surtacewithlightrust.Areaisapprox.11/2"x1".Thereisno indicationofpittino.Liner184-8 Uncoated surtacewithlightrustat attachmentweld(2places).Itemswere previously identified No additional degradation noted 181-VT-16-051Thereisno indicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoated surtacewithlightrust(6places).Thereisno indication of pitting.Uncoated surtacewithlightrust.Areaisapprox.2"diameter.Thereisno indicationofpitting.

Uncoated surtacewithliqhtrust.Areaisapprox.8"x6".Thereisno Page 17 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.12"x12".

There is no indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.3"x2".

Thereisno indication of pitting.Uncoated surfacewithlightrust.Areaisapprox.6"x4".

Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.6"x2".

Thereisno indicationofpitting.

Uncoated surfacewithlightrust(2 places).Thereisno indication of pitting.Uncoated surfacewithlightrust(2 places).Thereisno indication of oittino.Liner 208-1 Uncoated surfacewithlightrust.

Where structural steel welds to Items were previously identified No additional degradation noted ISI-VT-16-052 embed plate.Thereisno indicationofpitting.

and evaluated acceptable.

during this examination.

Uncoated surfacewithlightrust.Areaisapprox.1/12"x1/2".

Thereisno indicationofpitting.

Uncoated surfacewithnorustorpitting.

Numerous areas of chippedpaint.Zincisintact.

Comments: Thereareafew previously identified gougesinthe lowerlinerplate.

In 8/2003aUTwas performed to verify the thicknessofthe linerplate.The average thicknessofthe linerplateinthisareais.297".

Gouqesdonot exceed.037".Liner 208-2 Uncoated surfacewithlightrust where structural steel weldstoItemswere previously identified No additional degradation noted ISI-VT-16-053 embed plate.Thereisno indicationofpitting.

and evaluated acceptable.

during this examination.

Page 18 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithlightrust.Areaisapprox.1 1/2"x1/2".Thereisnoindicationofpitting.

Uncoatedsurfacewithnorustorpitting.

Numerousareasofchippedpaint.Zincisintact.

Uncoatedsurfacewithlightrust(2places4"x8").Thereisno indicationofpitting.

Comments:Thereareafew previouslyidentifiedgougesinthelowerlinerplate.

In 08/2003aUTwas performedtoverifythe thicknessofthelinerplate.Theaveragethicknessofthelinerplateinthisareais.297".Gouqesdonotexceed0.37".Liner208-3 Uncoatedsurfacewithlightrust.Areaisapprox.1"diameter.ThereItemswere previously identified No additional degradation noted ISI-VT-16-054isnoindicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoatedsurfacewithlightrust.Areaisapprox.2"x6".Thereisnoindicationofpitting.

Uncoatedsurfacewithmediumrustat unistrutweld.Thereisnoindicationofpitting.

Uncoatedsurfacewithlightrust.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustonseamweld.Areaisapprox.1"long.Thereisnoindicationofpitting.

Uncoatedsurfacewithnorustorpitting.Zincisintact.Uncoatedsurfacewithlightrust.Smallareasofchippedpaint.Thereisnoindicationofpitting.Uncoatedsurfacewithnorustorpitting.Zincisintact.

Page 19 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoated suriacewithnorustorpitting.Numerousareasofchippedpaint.Zincisintact.

Uncoated suriacerepairedarea.Thereisnoindicationofrust.

Comments:Thereafew previouslyidentifiedgougesinthelowerlinerplate.The average thicknessofthelinerplateinthisareais.297".Gougesdonotexceed0.37"Liner208-4UncoatedsurfacewithmediumrustwherestructuralsteelweldstoItemswere previously identified No additional degradation noted 181-VT-16-055embedplate(2places).Thereisnoindicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoated suriacewithlightrustwherestructuralsteelweldtoembed.Thereisnoindicationofpitting.

Uncoated suriacewithnorustorpitting.Numerousareasofchippedpaint.Zincisintact.

Comments:Thereareafew previouslyidentifiedgougesinthelowerlinerplate.

On 08/2003aUTwas periormedtoverifythethicknessofthelinerplate.Theaveragethicknessofthelinerplateinthisareais.297".Gouqesdonotexceed0.37".Liner208-5 Uncoated suriacewithlightrustatstraingauge(2places).ThereisItemswere previously identified No additional degradation noted 181-VT-16-056noindicationofpitting.

and evaluated acceptable.duringthis examination.

Uncoated suriacewithlightrustonembedplate(2places).Thereisnoindicationofpitting.

Uncoated suriacewithnorustorpitting.Uncoatedsurfacewithnorustorpitting.Therearenumerousareasofchippedpaint.

Uncoated suriacebehindT.8.Thereisnorustoroittino.

Page 20 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithbaremetal(1place-11/2" X3")withnorustorpitting.Uncoatedsurface(baremetal)withnorustorpittingbehindpipe support.Liner 208-6Uncoatedsurfacewithlightrustonembedplate.Areaisapprox.3"Itemswere previouslyidentifiedNo additional degradation noted ISI-VT-16-057x1".Thereisnoindicationofpitting.

and evaluated acceptable.

during this examination.UncoatedsurfacewithlightrustatT.S.toembedwelds.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Coatingiscrackedandpeeling.Thereisnoindicationofpitting.Uncoatedsurfacewherepaintisflakingandpeeling.Thereisnopitting.Zincisintact.Uncoatedsurfacewherepaintispeeling.Thereisnorustorpitting.Zincisintact.Liner208-7 Uncoatedsurfacewithmediumrustonembedplateweldtoliner.Itemswere previously identified No additional degradation notedISI-VT-16-058Areaisapprox.12"long.Thereisnoindicationofpitting.

and evaluated acceptable.duringthis examination.Uncoatedsurfacewithlightrust.Areaisapprox.1"x1/2".Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustwherestructuralsteelweldstoembed.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.1"diameter.Thereisnoindicationofpitting.Uncoatedsurfacewithnorustorpitting.Numerousareashavechippedpaint.Zinccoatingisintact.

Page 21 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithnorustorpitting.

Numerousareashavechippedpaint.Zinccoatingisintact.Uncoatedsurface(1/2"x12")withnorustorpitting.Zinccoatingis intact.Liner208-8UncoatedsurfacewithlightrustwhereT.S.isweldedtoembed.Itemswere previously identified No additional degradation notedISI-VT-16-059Thereisnoindicationofpitting.

and evaluatedacceptable.duringthis examination.Uncoatedsurfacewithlightrustwherestructuralsteelweldstoembed.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustwherestructuralsteelweldstoembed.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustonembedplate.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust(5places).Thereisnoindicationof pitting.Uncoatedsurfacewithlightrust(2places).Areasareapprox.5"x9".Thereisnoindicationofpitting.Uncoatedsurfacewithnorustorpitting.Thereare numerous areaswherepainthaspeeledorchipped.Zincinintact.

ContainmentDomeLiner Liner 0-3Uncoatedsurfacewithlightrustonseamweld.Areaisapprox.1 0"Itemswere previously identified No additional degradation notedISI-VT-15-005long.Thereisnoindicationofpitting.andevaluatedacceptable.duringthis examination.UncoatedsurfacewithlightrustAreaisapprox.3"diameter.Thereisnoindicationofpitting.UncoatedsurfacewithlightrustAreaisapprox.6'9x4".Thereisnoindicationofpitting.

Page 22 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Uncoated surfacewithlightrustAreaisapprox.4"x12".

Thereisno indicationofpitting.

Liner 0-4 UncoatedsurfacewithlightrustAreaisapprox.2" diameter(2Itemswere previously identified No additional degradation noted ISI-VT-15-002places).Thereisno evidenceofpitting.

and evaluated acceptable.

during this examination.

Uncoated surfacewithlightrustAreais approx.11/2" diameter (2 places).Thereisno evidenceofpitting.

Uncoated surfacewithlightrustAreais approx.12"x3".Thereisno evidenceofpitting.

UncoatedsurfacewithlightrustAreaisapprox.4"x12".

Thereisno evidenceofpitting.

Uncoated surfacewithlightrustAreaisapprox.2"diameter.Thereisno evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.6"x4".Thereisno evidenceofoittinq.Liner0-1 Uncoated surfacewithlightrust.Areaisapprox.2" diameter(2Itemswere previously identified No additional degradation noted ISI-VT-15-003 places).Thereisnoindicationofpitting.

and evaluated acceptable.

during this examination.

UncoatedsurfacewithmediumrustAreaisapprox.4"x1" diameter.Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.3"diameter.Thereisno indicationofpitting.

Uncoated surfacewithmediumrustAreaisapprox.6"x1" diameter.Thereisno indicationofpitting.

UncoatedsurfacewithmediumrustAreaisapprox.1"diameter.Thereisnoindicationofpitting.

Liner 0-2 Uncoated surfacewithlightrustatplateto stiffenertoembedplate.Itemswere previously identified No additional degradation noted ISI-VT-15-004Thereisno evidenceofpitting.

and evaluated acceptable.

durinq this examination.

Page 23 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoated surfacewithlightrustat clevistolinerweld.Areaisapprox.6"x6" diameter.Thereisno evidenceofpitting.

Uncoated surfacewithlightrust.Areaisapprox.11/2"x3/4".

Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.2" diameter.Thereisno indicationofpittinq.

Lower Personnel Airlock SA-119 AL Uncoated surfacewithlightrust.Areaaround anglesarenotItemswere previously identified No additional degradation noted ISI-VT-16-068 painted.Thereisno indicationofpitting.(4 places)and evaluated acceptable.

during this examination.

Uncoated surfacewithlightrust.

There are numerousareasof chippedpaint.Thereisno indicationofpitting.

Uncoated surfacewithlightrust.

Instrument tubing bracketsarenot painted.Thereisno indicationofpitting.

Uncoated surfacewithlightrust.Paintremovefromwear.

There is no indicationofpitting.

Uncoated surfacewithlightrust.

There are severalareasof chipped paint.Thereisno indicationofpitting.

Uncoated surfacewithlightrustonflange.Thereisno indication of pitting.Uncoated surfacewithlightrust.Paintintheseareasare chippedwithno indicationofpitting.

Uncoated surfacewithlightrustonsideofthedoor.Thereisno indicationofpitting.

Uncoated surface(1"x 4")with liQhtrust.Thereisno indication of Page 24 of 46 GNRO-2017/00053 Attachment 2 ContainmentVisualInspection(IWE)

Component IDIndicationDescription Disposition Comments IReportNo.pitting.Uncoatedsurfacewithlightrustonsealclamp,thereisno indicationofpitting.

Uncoated surfacewithlightrust.Areaisapprox.6 Ix6".Thereisno indicationofpitting.

Uncoated surfacewithlightrustonunistrutplate.Thereisno indicationofpitting.

Uncoated surfacewithrustatT.8.weld.Thereisno indication of pitting.Uncoated surfacewithlightrustonsealclamp.Thereisno indicationofpitting.

Uncoatedsurfacewithlightrustonsealclamp.Thereisno indicationofpitting.

Uncoatedsurfacewithlightrustonunistrutbracket.Thereisno indicationofpitting.

Uncoatedsurfacewithlightruston instrumenttubingbracket.Thereisno indicationofpitting.

Uncoated surfacewithlightrustonsealclamp.Thereisno indicationofoittinq,UpperPersonnelAirlock 8A-212 AL Uncoated surfacewithlightrustonangleclips.ThereisnoItemswere previously identified No additional degradation noted 181-VT-16-069 indicationofpitting.(4places) and evaluated acceptable.duringthis examination.

Uncoatedsurfacewithlightrustontheleftsidefacing containment.Thereisno indicationofpitting.

Page 25 of 46'-.

GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Uncoatedsurfacewithlightruston instrumenttubingbrackets.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.Paintremovedfromwear.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Uncoatedsurfacewithlightruston instrumentbracket.Thereisnoindicationofpitting.Uncoatedsurfacewithlightruston 1.8.weld.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrust.Areaisapprox.5'x5'.Thereisnoindicationofpitting.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Uncoatedsurface.Paintremovedfromwear.Thereisnorustof pitting.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Uncoatedsurfaceduetochippedpaint.Thereisnumerousareas.Thereisnorustorpitting.Uncoatedsurfacewithlighttomediumrust.Thereisnoindicationof pitting.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.

Page 26 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.RF19,March2014Liner184-1Item1.

Uncoatedsurfacewithlightrust(3places).ThereisnoItemswere previously No additional degradation noted.ISI-VT-14-022 indicationofpitting.

identified and evaluated.Item2.Uncoatedsurfacewithstraingauge.Thereismediumrustwithno indicationofpitting.Item3.Uncoatedsurfaceat attachmentweld.Thereislightrustwith no indicationofpitting.Item4.Uncoatedsurfacewithlightrust(4places).Thereisno indicationofpitting.Item5.Uncoatedsurfacewithlightrust(7places).Thereisno indicationofpitting.Item6.Uncoatedsurfacewithnorust.Areaisanarkstrikewithno indicationofcracksofpitting.Item7.Uncoatedsurfacewithlightrust.Thereisnoindicationof pitting.Item8.Gougewithareductionof.060"fromnominalwall.Nominalwallis.275".Reductionwascausefromgrinding.Locationofgougeisat194'el.Item9.Gougewithareductionof.046"fromnominalwall.Nominalwallis.268".Reductionwascausefromlugremoval.Locationofgougeisat186'-5"el.Item10.Gougewithareductionof.0625"fromnominalwall.Nominalwallis.268".Reductionwascausefromlugremoval.Locationofqouqeisat187"-5"el.Liner120-1Item1.

Uncoatedsurfacewithlightrust.Thereisno evidence ofItemswere previously No additional degradation noted.ISI-VT-14-023 pitting.identified and evaluated.Item2.Uncoatedsurfaceareaontophalfof penetration.

Zinc coatingisintact.Thereisno evidenceofpitting.Item3.Uncoatedsurfacewhere suppression pool instruments areinstalled.Lighttomediumrustinsomeareaswithno evidence of pittinq, Page 27 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item4.Uncoated surlacewithlightrust.Noevidenceofpitting.Liner184-2Item1.Uncoated surlacewithlightrust.ThereisnoindicationofItemswere previously No additional degradation noted.ISI-VT-14-024 pitting.identifiedandevaluated.Item2.Uncoated surlacewithlightrust(10places).Thereisnoindicationofpitting.Item3.Uncoated surlacewithlightrust.Areaisapprox.4"x2".Item4.Uncoated surlacewithnorustorpitting.Thereare numerousareasofchippedpaint.Zinccoatinoisintact.Liner184-3Item1.Gougewithreductionof.078"fromnominalwall.NominalItemswere previously No additional degradation noted.ISI-VT-14-025wallis.282".Areaisapprox.1/2"indiameter.Locationofgougeisidentifiedandevaluated.189'-10"atAZ-117degrees.Item2.Uncoated surlacewithchippedpaintinnumerousareas.ThereisnorustandZinccoatingisinintact.Item3.Uncoated surlacewithlightrust.Thereisnoindicationof pitting.Item4.Uncoated surlaceduetoarcstrikes(5places).Thereisnoindicationofpitting.Item5.Uncoated surlacewithlightrust.Areaapprox.1"diameter.Thereisnoindicationofpitting.Item6.Uncoatedsurlacewithmediumrust(3places),Thereisnoindicationofpitting.Item7.Uncoated surlacewithlightrust.Areaisapprox.2"diameter.Thereisnoindicationofpitting.Item8.Uncoated surlacewithlightrust(5places).Thereisnoindicationofpitting.Item9.Uncoated surlacewithmediumrust.Areaisapprox.12"x12".Thereisnoindicationofpitting.Item1 O.Uncoated surlacewithlightrust.Areaisapprox.1"diameter.Thereisnoindicationofpitting.Item11.Uncoated surlacewithlightrust(3places).Thereisnoindicationofpitting.Liner208-4Item1.Uncoated surlacewithmediumrustwherestructuralsteelItemswere previouslyNoadditional degradation noted.ISI-VT-14-026weldstoembedplate(2places).Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoated surlacewithlightrustwherestructuralsteelweldtoembed.Thereisnoindicationofpitting.

Page 28 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item3.Uncoatedsurfacewithnorustorpitting.Numerousareasofchippedpaint.Zincisintact.Comments:Therearefewgougesinthelowerlinerplate(noadditionalgougenotedforRF-19).On 08/2003aUTwasperformedtoverifythe thickness of thelinerplate.Theaverage thickness ofthelinerplateinthisareais.297".Gougesdonotexceed0.37"M&TE:UT-DL26:SIN92053303, Transducer0791:5.0I.312SIN 19806.Liner184-6Item1.Uncoatedsurfacewithlightrustandunistrut attachment (2Itemswere previously No additional degradation noted.ISI-VT-14-027places).Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrustatstraingauge(2places).Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrustat attachmentweld.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewithlightrust.Areaisapprox.3"diameter.Thereisnoindicationofpitting.Item5.Uncoatedsurfacewithlightrust.Areaisapprox.4"diameter.Thereisnoindicationofpitting.Item6.Uncoatedsurfacewithmediumrustatstraingauge.Thereisnoindicationof pittinq,Liner184-7Item1.Uncoatedsurfacewithlightrustat attachmentweld.ThereisItemswere previously No additional degradation noted.ISI-VT-14-028noindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust.Areaisapprox.2"diameter.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.

1/2"diameter.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewithlightrust.Areaisapprox.1 1/2"x1".Thereisnoindicationofpitting.Liner184-8Item1.Uncoatedsurfacewithlightrustat attachmentweld(2Itemswere previously No additional degradation noted.1SI-VT-14-029places).Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust(6places).Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.2"diameter.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewith tiqhtrust.Areaisaoorox.8"x6".

Page 29 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Thereisnoindicationofpitting.Item5.Uncoatedsurfacewithlightrust.Areaisapprox.12"x12".Thereisnoindicationofpitting.Item6.Uncoatedsurfacewithlightrust.Areaisapprox.3"x2".Thereisnoindicationofpitting.Item7.Uncoatedsurfacewithlightrust.Areaisapprox.6"x4".Thereisnoindicationofpitting.Item8.Uncoatedsurfacewithlightrust.Areaisapprox.6"x2".Thereisnoindicationofpitting.Item9.Uncoatedsurfacewithlightrust(2places).Thereisnoindicationofpitting.Item10.Uncoatedsurfacewithlightrust(2places).Thereisno indicationofpitting.Liner161-1Item1.Uncoatedsurfaceonpenetrationcover.ThereislightrustItemswere previously No additional degradation noted.ISI-VT-14-030withnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightruston attachmentwelds.Thereisnoindicationofpitting.Item3.Uncoatedsurfaceon penetrationcoverand attachmentswelds.Thereislightrustwithnoindicationofpitting.Item4.Uncoatedsurfacewithrustonstraingauge(2places).Thereisnoindicationofpitting.Item5.Uncoatedsurfacewithlightrust(3places).Areaisapprox.2"indiameter.Thereisnoindicationofpitting.Item6.Uncoatedsurfacewithlightrust.Areaisapprox.31/2"x11/2".Thereisnoindicationofpitting.Item7.Uncoatedsurfacewithlightrust.Areaisapprox.4"x2".Thereisnoindicationofpitting.Item8.Uncoatedsurfacewithlightrust.Areaisapprox.3"x2".Thereisnoindicationofpitting.Item9.Uncoatedsurfacewithlightrust.Areaisapprox.5"x4".Thereisnoindicationofpitting.Item10.Uncoatedsurfacewithlightrust(3places).Thereisnoindicationofpitting.Item11.Uncoatedsurfacewithlightrust(10places).Thereisnoindicationofpitting.

Page 30 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item12.Uncoatedsurface.Thereare numerousareasofchippedandpeeledpaint.Thereislightrustinsomeareaswithnoindicationofoittino.Liner161-2Item1.Uncoatedsurfacewithlightrust.Areaisapprox.4"x3"(4Itemswere previously No additional degradation noted.ISI-VT-14-031places).Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrustonthe penetrationcovers(3places).Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.Thereisnoindicationof pitting.Item4.Discernablebulgewitha diameterof8".Thisbulgeextendsoutwardapprox.1/2".Thereisnoflakingorpeelingofcoatingsinthisarea.UT thicknesswasperformedinareaonandaroundbulge.Thereisnoreductionofbasematerial.Seereport#BOP-07-008.Item5.Uncoatedsurfacewithlightrust.Areaisapprox.1/2"x4".Thereisnoindicationofpitting.Item6.Uncoatedsurfacewithnorustorpitting.Painthasbeenchipped,butthezinccoatingisintact.Item7.Uncoatedsurfacewithlightrust.Areaisapprox.4"indiameter.Thereisnoindicationofpitting.Item8.Uncoatedsurfaceontheseamweld(2places).Thereislightrustwithnoindicationofpitting.Item9.Uncoatedsurfaceontheswaystrut attachmentweld.Thereisnoindicationofpitting.Item10.Painthasflakedinareaapprox.1/2"x2".Zinccoatingis intact.Liner161-3Item1.Uncoatedsurfaceat attachmentwelds.ThereislightrustItemswere previously No additional degradation noted.ISI-VT-14-032withnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrustonpenetrationcover.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrustonpenetrationcoverandpipe.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewithlightrust.Thereisnoindicationof pittinq.Liner161-4Item1.Uncoatedsurfaceonthepenetrationcovers.ThereislightItemswere previously No additional degradation noted.ISI-VT-14-033rustwithnoindicationofpitting(5pieces).identifiedandevaluated.

Page 31 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item2.Uncoated surfaceonthe attachmentweld.Thereislightrustwithno indicationofpitting.Item3.Uncoated surfaceatstraingaugemount.

Thereislightrustwithno indicationsofpitting.

Item 4.Uncoated surfacewithlightrust.Thereisno indication of pitting.Item5.Uncoated surfaceonremovalareas(3places).

Thereislightrustwithno indicationofpitting.Item6.Uncoated surfaceatseamweld.Thereislightrustwithno indicationofpitting.Areaisapprox,6"inlength.Liner161-5Item1.

Uncoated surface where unistrut attachestotheplate(6Itemswere previously No additional degradation noted.ISI-VT-14-034places).Thereislightrustwithno indicationofpitting.

identified and evaluated.Item2.Uncoated surfacewithlightrust.Areaisapprox.10"x4"(3 places)Thereisno indicationofpitting.Item3.Uncoated surfacewithlightrust.Areaisapprox.6"x4"(2 places).Thereisno indicationofpitting.Item4.Uncoated surfacewithlightrustonthe penetration cover andpipe(2places).

Thereisno indicationofpitting.Item5.Uncoated surfaceatthestraingaugeweld attachments (6 places).Thereisno indicationofpitting.Item6.Uncoated surface.Thereislightrustwithno indication of pitting.Item7.Uncoated surfaceatthe attachment weld.Thereislightrustwithno indicationofpitting.Item8.Uncoated surfacewithlightrust.Areaisapprox.7"x3"(2 places).Thereisno indicationofrust.Item9.Uncoated surfacesapprox.6"x3"(2places).

Thereislightrustwithno indicationofpitting.Item10.Uncoated surfacesapprox.6"x4"(2places).

Thereislightrustwithno indicationofpitting.

Liner 161-6Item1.Uncoated surface on attachmentweldatstrain gauges (4Itemswere previously No additional degradation noted.ISI-VT-14-035 places).Thereislightrustwithno indicationofpitting.

identified and evaluated.Item2.Uncoated surfacewithlightrust.Areaisapprox.14"x8".

Thereisno indicationofpitting.Item3.Uncoated surfacewithliqhtrust.

Thereisno indication of Page 32 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.pitting.Item4.Uncoated surface.Therearefourareaswitharcstrikes.Thereisno indication of crackingorpitting.

Item 5.Uncoated surface 360 degrees around the Equipment Hatch flange.Thereislightrustwithno indicationofpitting.Item6.Uncoated surfacewithlightrust.Areaisapprox.18"x6",Thereisno indicationofpitting.Liner161-7Item1.

Uncoated surfaceonpipe behind penetration cover (2Itemswere previously No additional degradation noted.ISI-VT-14-036 places).Thereislightrustwithno indicationofpitting.

identified and evaluated.Item2.Uncoated surface on attachmentweldatstraingauge.Thereislightrustwithno indicationofpitting.Item3.Uncoated surface on attachment weld.Thereislightrustwithno indicationofQitting.

Liner 161-8Item1.Uncoated surfaceatstraingaugeweld attachment.

There isItemswere previously No additional degradation noted.ISI-VT-14-037lightrustwithno indicationofpitting.

identified and evaluated.Item2.Scatteredareasof chippedpaint.Norust.Zinc coating is intact.Item3.Angleremovalareawithlightrust.No indicationofoittinq.

Liner 135-1Item1.Uncoated surfacearoundremovalareaonembedplate.Itemswere previously No additional degradation noted.ISI-VT-14-038Thereislightrustwithno evidenceofpitting.

identified and evaluated.Item2.Uncoated surfacewithlightruston penetrationcover.Thereisno evidenceofpitting.Item3.Uncoated surfacewithlightrust.Areasareapprox.1".Thereisno evidence of pitting(2places).Item4.Uncoated surfacewithlightrust.

Thesearesmallareaswith no evidence of pitting(3places).

Item 5.Uncoated surfacewithlightrust.Areaisapprox.2"withno evidenceofpitting.Item6.Uncoated surfaceonweld.Thereislightto mediumrustwith no evidenceofpitting.Liner 135-2Item1.Uncoated surfacewithlightto mediumrust.ThisareaItemswere previously No additional degradation noted.ISI-VT-14-039 extends to belowtheseamweldintothe expansionjointat161' identified and evaluated.elev.Thisareais inaccessible for examination.

Thereisno indicationofpitting.Item2.Uncoated surfacewithlightrust(2places).Thereisno Page 33 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.indicationofpitting.Item3.Uncoatedsurfacewithlightrust.Thereisnoindicationof pitting.Item4.Uncoatedsurfacewithnorustorpitting.Paintinanareaofapprox.4"x2.5"haspeeled.Zincisstillintact.Item5.Uncoatedsurfacewithnorustorpitting.Paintinanareaofapprox.1.5"x2.5"haspeeled.Zincisstillintact.Item6.Uncoatedsurfacewithlightrust.Areaisapprox.2"inlength.Thereisnoindicationofpitting.Item7.Uncoatedsurfacewithnorustorpitting.Thereare scatteredareasofchippedpaint.Zincisstillintact.Item8.Uncoatedsurfaceonportionsoftheweld.Thereisnorustor pittinq,Liner135-3Item1.Uncoatedsurfaceonplatetolinerweld.ThereislightrustItemswere previously No additional degradation noted.ISI-VT-14-040withnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfaceonseamweld.Thereislightrustwithnoindicationofpitting.Item3.Uncoatedsurfacewithnorustandnopitting.Painthaschippedawayinanareaofapprox.1"x2".Zincisstillintact.Item4.Uncoatedsurfacewithnorustandnopitting.Painthasflakedawayinthisarea.Zinccoatingisintact.Item5.Uncoatedsurfacewithnorustandnopitting.Thereare numerousareasofchippedpaint.Zinccoatingisintact.Item6.Uncoatedsurfacewithlightrustontheweld.Thereisnoindicationofpitting.Item7.Uncoatedsurfaceonembedplate.Thereislightrustwithnoindicationofpitting.Item8.Uncoatedsurfacewithlightrust.Thereisnoindicationof pitting.Item9.Uncoatedsurfaceonseamweld.Thereislightrustwithnoindicationofpitting.Item1 O.Uncoatedsurfaceonthelineratthe expansionjoint.Thisdoesnotextendbehindtheexpansionjoint.Thereisno evidence of pitting.Item11.Uncoatedsurfacewithnorustorpitting.Painthasflaked Page 34 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.awayinanareaapprox,1"x1.5".

Liner135-4Item1.

Uncoated suriacewithlightrust.

Thereisno indicationofItemswere previously No additional degradation noted.ISI-VT-14-041 pitting.identified and evaluated.Item2.Uncoated suriacewithlightrust.

Thereisno indication of pitting.Item3.tlqhtrustonweld.

Thereisno indication of plttinq.Liner135-5Item1.

Uncoated suriacewithlightrust.

Thereisno evidence ofItemswere previously No additional degradation noted.ISI-VT-14-042 pitting.identified and evaluated.Item2.Uncoated suriacewithlightrust around penetrations.

Thereisno evidenceofpitting.Item3.Uncoated suriace with mediumtolightrust(7 places).Thereisno evidenceofpitting.Item4.Uncoated suriacewithlightrust.Areaisapprox.12"x2".

Thereisno evidenceofpitting.Item5.Uncoated suriacewithlightrust.Areaisapprox.14"x2".

Thereisno evidenceofpitting.Item6.Uncoated suriacewithlightrust.

Thereisno evidence of pitting.Item7.Uncoated suriacewithlightrust.Areaisapprox.4"x12" Thereisno evidenceofpitting.Item8.Uncoated suriacewithlightrust.Areaisapprox.2" diameter.Thereisno evidenceofpitting.Item9.Uncoated suriacewithlightrust.Areaisapprox.3" diameter.Thereisno evidenceofpitting.Item10.Uncoated suriacewithlightrust.

Thereisno evidence of pitting.Item11.Uncoated suriacewithlightrustatweld.

Thereisno evidence of pittinq.Liner 135-6Item1.Uncoated suriacewithlightrust behind I-beam (3 places).Itemswere previously No additional degradation noted.ISI-VT-14-043Item2.Uncoated suriacewithlightrustatwelds.

identified and evaluated.Item3.Uncoated suriacewithlightrustapprox.3"x3".Item4.Uncoated suriacewithlightrustapprox.10"x4".Item5.Uncoated suriacewithlightrustapprox.4"x6".Item6.Uncoated suriacewithlightrustthefulllengthoftheplate.Painthas chippedandorpeeled.

Page 35 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Item7.Baremetalwithlightrust.Areasareapprox.3"in diameter(4places).Item8.Baremetalwithlightrustapprox.3"in diameter.Item9.Inaccessible areas behind vertical trays.Noteno evidence of pittinq in areas identified as havinqliqhtrust.

Liner 135-7Item1.Uncoated surface at embedtolinerweld.

ThereislightrustItemswere previously No additional degradation noted.ISI-VT-14-044withno indicationofpitting.

identified and evaluated.Item2.Uncoated surfaceateyeboltwelds.

Thereislightrustwith no indicationofpitting.Item3.Uncoated surfacewithlightrust.

Thereisno indication of pitting.Item4.Uncoated surfacewithlightrust.

Thereisno indication of pitting.Item5.Uncoated surfacewithlightrust.Areaisapprox.24"x2".Thereisno indicationofpitting.Item6.Uncoated surfacewithlightrust.Areaisapprox.3"x4".

Thereisno indicationofpitting.Item7.Uncoated surfacewithnorustandnopitting.

Location is scattered with areas of chippedpaint.Zincisintact.Item8.Uncoated surfacewithlightruston attachment.Thereisno indicationofpitting.Item9.Thereisa gougeapprox.3/4x1/4x1/32depth.Thereislightrustwithno indicationofpitting.Item10.Thereisa scratchapprox.3/8x1/4".Thereislightrustwith no indicationofoittino,Liner135-8Item1.Uncoated surfacewithlightrust.Areaisapprox.3"x1".Itemswere previously No additional degradation noted.ISI-VT-14-045Thereisno indicationofpitting.

identified and evaluated.Item2.Uncoated surfacewithlightrustonweld.Thereisno indicationofpitting.Item3.Uncoated surfacewithlightrust.Areaisapprox.10"x4".

Thereisno indicationofpitting.Item4.Uncoated surfacewithlightruston penetration covers.Thereisno indicationofpitting.Item5.Uncoated surfacewithlightruston attachmentwelds(8 places).Thereisno indication of pittlnq.Page 36 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item6.Uncoatedsurfacewithlightrust.

Thereisno indication of pittinq.Liner120-2Item1.Uncoatedsurface.Zincstillinplace.

Surfaceis11/2"Itemswere previously No additional degradation noted.ISI-VT-14-046 approx.identified and evaluated.Item2.Uncoated surface.Welds have minorrust.No evidence of pitting.Item3.Visibleruststreaks.Thesourceis inaccessible for inspection.Item4.Uncoatedsurface.Lightrustatweldonembedplate.No evidenceofpitting.Liner120-3Item1.

Uncoatedsurfacewithnorust.Areaisapprox.1/8"x1/2".Itemswere previously No additional degradation noted.ISI-VT-14-047Item2.Uncoatedsurfacewithnorust.Areaisapprox.1/2"x1/2".

identified and evaluated.Item3.Uncoatedsurfacewithnorust.Areaisapprox.11/2"x1/2".Note:Thereisno indicationofpittingonitemsabove.Liner120-4Item1.Uncoatedsurfaceapprox.1/4" (Chipped paint).Itemswere previously No additional degradation noted.ISI-VT-14-048Item2.Uncoatedsurfaceapprox.11/2"x3/4" (Chipped paint).identified and evaluated.Note:Thereisno evidence ofinremovalareas.Liner120-5Item1.Coatingsremovedinthisarea.ThisareaiswhereItemswere previously No additional degradation noted.ISI-VT-14-049 suppressionpoolinst.cablewasattachedtoliner.Rustinarea.

identified and evaluated.Item2.Thisareaisusedfor storageduringrefueloutages.Therearemultipleareaswhere coatingshavebeenremoved,chipped, scratches.Lightrustinareas.Note:Thereisno evidenceofpittinginareasofliqhtrust.Liner120-6Item1.Coatingsremovedinthisarea.ThisareaiswhereItemswere previously No additional degradation noted.ISI-VT-14-050 suppressionpoolinst.cablewasinstalled.Lightrustinareas.

identifiedandevaluated.Item2.Visibleruststreaks.The source is inaccessible for inspection.Note:Thereisno evidenceofpittinginareasoflightrust.Item3.Coatingremovedfrom3"area.Primerisstillintact.Liner120-7Item1.Uncoated surfaceswithrustwhere suppression poolItemswere previously No additional degradation noted.ISI-VT-14-051 instrumentationcablesare attachedtoliner.No evidence of pittinq.identified and evaluated.Liner120-8Item1.Uncoated surface where suppressionpoolinst.cablesareItemswere previously No additional degradation noted.ISI-VT-14-052installed.Rustinsomeareaswithno evidenceofpitting.

identified and evaluated.Item2.Uncoatedsurfaceatendofcap.Lightrustwithno evidenceofpitting.

Page 37 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Liner93-2Item1.Uncoatedsurfacewithlightrust.Thereisno evidenceofItemswere previously No additional degradation noted.ISI-VT-14-053 pitting.identified and evaluated.Item2.Weldonlinerisnotcoated.Lightrustwithno evidence of pitting.Item3.Uncoatedsurfaceareaapprox.3'0"x1'0"haslightrustwith no evidenceofpitting.Item4.Beam attachmentsarenot accessibleforvisual inspection.Thisonly appliesonlytobottomsection.Liner93-1 Uncoated surface(3places),lightrustonlinerweld.No evidence ofItemswere previously No additional degradation noted.ISI-VT-14-054 pitting.identified and evaluated.Item2.Uncoatedsurfaceatplatetolinerweld.Lightrustwithno evidenceofpitting.Liner93-3Item1.Uncoatedsurfaceonweldseams.LightcorrosionwithnoItemswere previously No additional degradation noted.ISI-VT-14-055 evidenceofpitting.

identified and evaluated.Item2.Uncoatedsurfacewithlight corrosion.

No evidenceofpitting.Item3.Uncoatedsurfacewithlighttomediumrust.Thisismainly aroundthewelded connections and surroundingareainthewaterbox.Thereisno evidenceofpitting.Item4.Uncoated surfaceswithlighttomediumrust(3areas).Thereisno evidenceofpitting.Item5.Uncoatedsurfacewithlight corrosiononembedplate.Thisisin additiontoitem1above.No evidenceofoittino,Liner93-4Item1.Uncoatedsurface11/2"x1/2".Itemswere previously No additional degradation noted.ISI-VT-14-056Item2.Uncoatedsurface18"x6"approx.

Coating appearstohave identified and evaluated.beenremovedbymech.means.Item3.Uncoatedsurface.Scrapemarkapprox.2'0"long.Note:Aboveareasexhibitsomelightrust.Thereisno evidence of pitting.Liner93-5Item1.Coatingsremovedinthisarea.ThisareaiswhereItemswere previously No additional degradation noted.ISI-VT-14-057 suppression pool instrumentcablewas attachedtoliner.Thereare identified and evaluated.areasoflightrustthathaveno evidenceofpitting.Liner93-6Item1.Coatingremovedatwelds(4places).Weldshavelightrust.Itemswere previously No additional degradation noted.ISI-VT-14-058Item2.Coatingremovedintheseareas(2places).Zincisinplace.

identified and evaluated.Item3.Coatingremovedinthisarea.Thisareaiswhere suppressionpoolinst.cablewas attachedtoliner.Areashavelight Page 38 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.rust.Note:Thereisno evidenceofpitting.Liner93-8Item1.Uncoatedsurfaceonlinerweld.LightrustwithnoevidenceItemswere previously No additional degradation noted.ISI-VT-14-060ofpitting.identifiedandevaluated.Item2.Uncoatedsurface.Endofweldhaslightcorrosionwithno evidenceofpitting.Liner208-1Item1.Uncoatedsurfacewithlightrust.WherestructuralsteelItemswere previously No additional degradation noted.ISI-VT-14-061weldstoembedplate.Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust.Areaisapprox.

1/12" x 1/2".Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithnorustorpitting.Numerousareasof chippedpaint.Zincisintact.

Comments:Thereareafewgougesinthelowerlinerplate(noadditionalgougenotedforRF-15).In 8/2003aUTwas performedtoverifythe thicknessofthelinerplate.Theaverage thicknessofthelinerplateinthisareais.297".Gougesdonotexceed.037".M&TE:UT-DL26:SIN92053303, Transducer0791:5.0 I.312,SIN19806.Liner208-2Item1.UncoatedsurfacewithlightrustwherestructuralsteelweldsItemswere previously No additional degradation noted.ISI-VT-14-062toembedplate.Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust.Areaisapprox.1 1/2" x 1 12".Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithnorustorpitting.Numerousareasofchippedpaint.Zincisintact.Item4.Uncoatedsurfacewithlightrust(2places4"x8").Thereisnoindicationofpitting.

Comments:Thereareafewgougesinthelowerlinerplate(noadditionalgougenotedforRF-15).In 08/2003aUTwas performedtoverifythe thicknessofthelinerplate.Theaverage thicknessofthelinerplateinthisareais.297".Gougesdonotexceed0.37".M&TE:UT-DL26:SIN920533303, Transducer0791:5.0 I3.12,SIN19806.Liner208-3Item1.Uncoatedsurfacewithlightrust.Areaisapprox.1"diameter.Itemswere previously No additional degradation noted.ISI-VT-14-063Thereisnoindicationofpitting.identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust.Areais approx,2"x6".Page 39 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithmediumrustatunistrutweld.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewithlightrust.Thereisnoindicationof pitting.Item5.Uncoatedsurfacewithlightrustonseamweld.Areaisapprox.1"long.Thereisnoindicationofpitting.Item6.Uncoatedsurfacewithnorustorpitting.Zincisintact.Item7.Uncoatedsurfacewithlightrust.Smallareasofchippedpaint.Thereisnoindicationofpitting.Item8.Uncoatedsurfacewithnorustorpitting.Zincisintact.Item9.Uncoatedsurfacewithnorust orpitting.Numerousareasofchippedpaint.Zincisintact.Item10.Uncoated surfacerepairedarea.Thereisnoindicationof rust.Comments:Therearefewgougesinthelowerlinerplate.AUTwasperformedtoverifythethicknessofthelinerplate.Theaverage thicknessofthelinerplateinthisareais.297".Gougesdonotexceed0.37"M&TE:UT-DL26:SIN92053303, Transducer0791:5.0 I.312SIN 19806.Liner208-5Item1.Uncoatedsurfacewithlightrustatstraingauge(2places).Itemswere previously No additional degradation noted.I SI-VT-14-064Thereisnoindicationofpitting.

identifiedandevaluated.Item2.Uncoated surfacewithlightrustonembedplate(2places).Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithnorustorpitting.Item4.Uncoatedsurfacewithnorustorpitting.Thereare numerousareasofchippedpaint.Item5.UncoatedsurfacebehindT.S.Thereisnorust or pitting.Item6.Uncoatedsurfacewithbaremetal(1place-1 1/2" X3")withnorustorpitting.Item7.Uncoatedsurface(baremetal)withnorust orpittingbehindpipesupport.Liner208-6Item1.Uncoatedsurfacewithlightrustonembedplate.AreaisItemswere previously No additional degradation noted.ISI-VT-14-065approx.3"x1".Thereisnoindicationofpittinq.identifiedandevaluated.

Page 40 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component IDIndicationDescription Disposition Comments IReportNo.Item2.Uncoated surfacewithlightrustat 1.S.to embed welds.Thereisno indicationofpitting.Item3.Uncoated surfacewithlightrust.

Coating is cracked and peeling.Thereisno indicationofpitting.Item4.Uncoated surfacewherepaintisflakingandpeeling.

Thereisnopitting.Zincisintact.Item5.Uncoated surfacewherepaintispeeling.

Thereisnorustorpittino.Zincisintact.

Liner 208-7Item1.Uncoated surface with mediumruston embedplateweldtoItemswere previously No additional degradation noted.ISI-VT-14-066liner.Areaisapprox.12"long.

Thereisno indication of identified and evaluated.

pitting.Item2.Uncoated surfacewithlightrust.Areaisapprox.1"x1/2".

Thereisno indicationofpitting.Item3.Uncoated surfacewithlightrustwhere structuralsteelweldstoembed.Thereisno indicationofpitting.Item4.Uncoated surfacewithlightrust.Areaisapprox.1" diameter.Thereisno indicationofpitting.Item5.Uncoated surfacewithnorustorpitting.

Numerous areas have chippedpaint.Zinc coatingisintact.Item6.Uncoated surfacewithnorustorpitting.

Numerous areas have chippedpaint.Zinccoatingisintact.Item7.Uncoated surface(1/2"x12")withnorustorpitting.Zinc coatingisintact.Liner 208-8Item1.Uncoated surfacewithlightrustwhereT.S.isweldedtoItemswere previously No additional degradation noted.ISI-VT-14-067 embed.Thereisno indicationofpitting.

identified and evaluated.Item2.Uncoated surfacewithlightrustwhere structuralsteelweldstoembed.Thereisno indicationofpitting.Item3.Uncoated surfacewithlightrustwhere structuralsteelwelds to embed.Thereisno indicationofpitting.Item4.Uncoated surfacewithlightruston embedplate.Thereisno indicationofpitting.Item5.Uncoated surfacewithlightrust(5places).Thereisno indicationofpitting.Item6.Uncoated surfacewithlightrust(2places).Areasareapprox.5"x9".

Thereisno indicationofpitting.

Page 41 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item7.Uncoatedsurfacewithnorustorpitting.Thereare numerousareaswherepainthaspeeledorchipped.Zincinintact.Liner184-4Item1.

Uncoatedsurfaceat attachmentwithlightrust(2places).Itemswere previously No additional degradation noted.ISI-VT-14-068Thereisno indicationofpitting.

identified and evaluated.Item2.Uncoatedsurfaceat penetrationweld.Thereislightrustwith no indicationofpitting.Item3.Uncoatedsurfacewithlightruston penetration(2places).Thereisno indicationofpitting.Item4.Uncoated surfacewithlightrust.Areaisapprox.8"x5".Thereisno indicationofpitting.Item5.Uncoatedsurfacewithlightrust.Areaisapprox.12"x5" IThereisno indicationofpitting.Item6.Uncoatedsurfacewithlightrust.Areaisapprox.2" diameter(3places).Thereisno indicationofpitting.Item7.Uncoatedsurfacewithlightrustatstraingauge.Thereisno indicationofpitting.Item8.Uncoatedsurfacewithlightrust.Areaisapprox.12"x10".Thereisno indicationofpitting.

Item 9.Uncoatedsurfacewithlightrust.Areaisapprox.12"x10".Thereisno indicationofpitting.Item10.Uncoated surfacewithlightrust.Areaisapprox.14"x18".Thereisnoindicationofpitting.Item11.Uncoated surfacewithlightrust.Areaisapprox.12"x4".Thereisnoindicationofpitting.Item12.Uncoated surfacewithlightrust.Areaisapprox.12"x6".Thereisnoindicationofpitting.Item13.Uncoated surfacewithlightrust (9places).Thereisno indicationofpitting.Item14.Uncoatedsurfaceonembedplatewithmediumrust.Thereisno indicationofpitting.Item15.Uncoatedsurfaceonembedplatewith mediumrust.Thereisno indicationofpitting.Item16.Uncoated surfacewithlightrust(2places).Areaisapprox.12"x8".Thereisno indicationofpitting.Item17.Uncoated surfacewithliqhtrust.Areaisaoorox,12"x8".

Page 42 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Thereisno indicationofpitting.Liner0-1Item1.Uncoated surfacewithlightrust.Areaisapprox.2" diameterItemswere previously No additional degradation noted.ISI-VT-14-070(2places).Thereisno indicationofpitting.

identified and evaluated.Item2.Uncoatedsurfacewithmediumrust.Areaisapprox.4"x1" diameter.Thereisno indicationofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.3" diameter.Thereisno indicationofpitting.Item4.Uncoatedsurfacewithmediumrust.Areaisapprox.6"x1" diameter.Thereisno indicationofpitting.

Item 5.Uncoatedsurfacewithmediumrust.Areaisapprox.1" diameter.Thereisno indicationofpitting.

Liner 0-2Item1.Uncoatedsurfacewithlightrustatplateto stiffenertoembedItemswere previously No additional degradation noted.ISI-VT-14-071plate.Thereisno evidenceofpitting.

identified and evaluated.Item2.Uncoatedsurfacewithlightrustatclevistolinerweld.Areaisapprox.6"x6"diameter.Thereisno evidenceofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.11/2"x3/4".Thereisno indicationofpitting.Item4.Uncoated surfacewithlightrust.Areaisapprox.2" diameter.Thereisno indicationofpitting.

Liner 0-3Item1.Uncoated surfacewithlightrustonseamweld.AreaisItemswere previously No additional degradation noted.ISI-VT-14-072approx.10"long.Thereisno indicationofpitting.

identified and evaluated.Item2.Uncoatedsurfacewithlightrust.Areaisapprox.3" diameter.Thereisno indicationofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.6"x4".Thereisno indicationofpitting.Item4.Uncoatedsurfacewithlightrust.Areaisapprox.4"x12".Thereisno indicationofpitting.

Page 43 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Liner 0-4Item1.Uncoatedsurfacewithlightrust.Areaisapprox.2" diameterItemswere previously No additional degradation noted.ISI-VT-14-073(2places).Thereisnoevidenceofpitting.

identifiedandevaluated.Item2.Uncoatedsurfacewithlightrust.Areaisapprox.11/2" diameter(2places).Thereisnoevidenceofpitting.Item3.Uncoatedsurfacewithlightrust.Areaisapprox.12"x3".Thereisno evidenceofpitting.Item4.Uncoatedsurfacewithlightrust.Areaisapprox.4"x12".Thereisno evidenceofpitting.Item5.Uncoatedsurfacewithlightrust.Areaisapprox.2"diameter.Thereisno evidenceofpitting.Item6.Uncoatedsurfacewithlightrust.Areaisapprox.6"x4".Thereisno evidenceofpitting.Liner184-5Thisinspectionwas previouslyperformedand documented inItemswere previously No additional degradation noted.ISI-VT-14-074reportsNOEN 0440-000-2007 and NOEN-0132-000-2007.

Theidentifiedandevaluated.

Indications identifiedinthosereports,havenotchanged,donotexceedthe acceptancecriteriastatedinCEP-CII-003,AppendixEandareacceptable.

SA-212-ALItem1.Uncoatedsurfacewithlightrustonangleclips.ThereisnoItemswere previously No additional degradation noted.ISI-VT-14-075indicationofpitting.(4places)identifiedandevaluated.Item2.Uncoatedsurfacewithlightrustontheleftsidefacing containment.Thereisnoindicationofpitting.Item10.Uncoatedsurfacewithlightrustoninstrumenttubingbrackets.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.Paintremovedfromwear.Thereisnoindicationofpitting.Item4.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Item5.Uncoatedsurfacewithlightruston instrument bracket.Thereisnoindicationofpitting.Item6.UncoatedsurfacewithlightrustonT.S.weld.Thereisnoindicationofpitting.Item7.Uncoatedsurfacewithlightrust.Areaisapprox.5'x5'.Thereisnoindicationofpitting.Item8.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpittinq.

Page 44 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component ID Indication Description Disposition Comments IReportNo.Item9.Uncoatedsurface.Paintremovedfromwear.Thereisnorustofpitting.Item11.Uncoated surfacewithlightrustonsealclamp.Thereisno indicationofpitting.

ReferencePage6Item12.Uncoated surfacedueto chippedpaint.Thereis numerousareas.Thereisnorustorpitting.Item13.Uncoatedsurfacewithlighttomediumrust.Thereisno indicationofpitting.Item13.Uncoated surfacewithlightrustonsealclamp.

Thereisno indication of pittinq, SA-119-ALItem1.Uncoated surfacewithlightrust.AreaaroundanglesarenotItemswere previously No additional degradation noted.ISI-VT-14-076painted.Thereisno indicationofpitting.(4places) identified and evaluated.Item2.Uncoatedsurfacewithlightrust.Thereare numerous areasofchippedpaint.Thereisnoindicationofpitting.Item3.Uncoatedsurfacewithlightrust.

Instrument tubing bracketsarenotpainted.

Thereisno indicationofpitting.Item4.Uncoatedsurfacewithlightrust.Paintremovedfromwear.Thereisno indicationofpitting.Item5.Uncoatedsurfacewithlightrust.

Thereareseveralareasof chippedpaint.Thereisno indicationofpitting.Item6.Uncoatedsurfacewithlightrustonflange.Thereisno indicationofpitting.Item7.Uncoated surfacewithlightrust.Paintintheseareasare chippedwithno indicationofpitting.Item8.Uncoatedsurfacewithlightrustonsideofthedoor.Thereis no indicationofpitting.Item9.Uncoatedsurface(1"x4")withlightrust.Thereisno indicationofpitting.Item10.Uncoatedsurfacewithlightrustonsealclamp,thereisno indicationofpitting.Item11.Uncoated surfacewithlightrust.Areaisapprox.6 Ix6".Thereisno indicationofpitting.Item12.Uncoated surfacewithlightrustonunistrutplate.Thereis no indicationofoittinq.

Page 45 of 46 GNRO-2017/00053 Attachment 2 Containment Visual Inspection (IWE)Component 10 Indication Description Disposition Comments IReportNo.Item13.Uncoatedsurfacewithrustat 1.8.weld.Thereisnoindicationofpitting.Item14.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Item15.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.Item16.Uncoatedsurfacewithlightrustonunistrutbracket.Thereisnoindicationofpitting.Item17.Uncoatedsurfacewithlightrustoninstrumenttubingbracket.Thereisnoindicationofpitting.Item18.Uncoatedsurfacewithlightrustonsealclamp.Thereisnoindicationofpitting.

Page 46 of 46 Attachment3to GNRO-2017/00053 ContainmentBuildingVisualInspection(IWL)

GNRO-2017/00053 Attachment 3 ContainmentBuildingVisual Inspections (IWL)Component ID Indication Description Disposition Comments IReportNo.RF20,March2016 WS-1 1 3,411 X 1 3,411 X%11 deep indication.

Staining I ndications were previously identified Accepted by examination.

ISI-VT-16-076 above penetrations.

and evaluated.

No chances.WS-2 Surface cracks,.005 11orless.Indications were previously identified Accepted by examination.

ISI-VT-16-104 and evaluated.

No chances.WS-3 Rust stains noted from grating above, Indications were previously identified Accepted by examination.ISI-VT-16-077 present in 2006aswell.and evaluated.

No chances.WS-5 8 11x2 11 X.5 11 deep indication at elevation Indications were previously identified Accepted by examination.

ISI-VT-16-078 110 1*and evaluated.

No chances.WS-7 Construction damage,.5 11x1 11 X.375 11 I ndications were previously identified Accepted by examination.ISI-VT-16-080 deep.and evaluated.

No changes.Construction damage,.5 11x1.5 11 X.250 11 deep.Stairuno from floor above, not structural.

WS-8 Surface cracks,.005 11and.004 11*I ndications were previously identified Accepted by examination.

ISI-VT-16-081 Licht rust stalninq at penetration19.and evaluated.

No chances.WS-9 Construction damage, 2 11x4 11 X.5 11 deep Indications were previously identified Accepted by examination.ISI-VT-16-082 indication.

and evaluated.

No chances.WS-11 Fine surface crack, no growthofrust.Indications were previously identified Accepted by examination.ISI-VT-16-084 Constructionvoid,2.5 11x4.5 11 X.375 11*and evaluated.

No chances.WS-12 Voids: Few voids were noticedinthisarea.

Indications were previously identified The voids have noISI-VT-16-085 Theyareall verylocalin nature andtheand evaluated.

No changes.significant impactonthe maximumsizeofthe voids noticedis3 11 x structural integrity or11/2"x3/8" deep.functional capabilityofthe containment.Page1of6 GNRO-2017/00053 Attachment 3 Containment Building Visual Inspections (IWL)Component 10 Indication Description Disposition Comments I Report No.W8-14 Rust staining below penetration 38.Indications were previously identified Accepted by examination.

181-VT-16-087 and evaluated.

No changes.W8-16Lightruststain.

I ndications were previously identified Accepted by examination.

181-VT-16-106 and evaluated.

No changes.W8-17 Penetration62,rustwithnopitting.

I ndications were previously identified Accepted by examination.

181-VT-16-089 Liqht staining.and evaluated.

No changes.W8-18Lightstaining.

Indications were previously identified Accepted by examination.

181-VT-16-090 Penetrations unpainted,lightrustwithno and evaluated.

No changes.pitting.W8-19Lightstainsfromfloorabove.

Indications were previously identified Accepted by examination.

181-VT-16-091 and evaluated.

No changes.W8-20Lightrust staining.Indications were previously identified Accepted by examination.

181-VT-16-092 and evaluated.

No changes.W8-21Lightrust stainsfromfloorabove.

Indications were previously identified Accepted by examination.

181-VT-16-093 and evaluated.

No changes.W8-22Lightstaining.

Indications were previously identified Accepted by examination.

181-VT-16-094Areaof moderatetoheavystainingaround and evaluated.

No changes.penetrations 210, 108,205,211,63.W8-23 Minor chipping from construction at Indications were previously identified Accepted by examination.

181-VT-16-095 penetration61.and evaluated.

No changes.W8-24Lightrust staining.I ndications were previously identified Accepted by examination.

181-VT-16-096 Previously identifiedvoidedareashaveand evaluated.

Repaired and painted.beenrepairedandpainted.

W8-25Lightruststains.

Indications were previously identified Accepted by examination.

181-VT-16-097 and evaluated.

No changes.W8-26Ruststainsfromfloorabove.

Indications were previously identified Accepted by examination.

181-VT-16-098 and evaluated.

No chances,Page2of6 GNRO-2017/00053 Attachment 3 Containment Building Visual Inspections (IWl)Component 10 Indication Description Disposition Comments IReportNo.WS-27 Surface cracking (typical)Indications were previously identified Accepted by examination.

ISI-VT-16-107 and evaluated.

No changes.WS-28 Surface cracking(typical).All surface Indications were previously identified Accepted by examination.

ISI-VT-16-099 crackslessthan.005".

and evaluated.

No changes.WS-29Seamarearoughfrom construction.

I ndications were previously identified Accepted by examination.

ISI-VT-16-108Formrod exposed.and evaluated.

No changes.3"x3" X4"void,formrod exposed.3/8"x1"x3/4"voidwithformrod exposed.3/4"x3/8"x3/4"void.3"x3" X4"voidwithformrod exposed.WS-30Void,3" diameter,1/2"deep.Indications were previously identified Accepted by examination.

ISI-VT-16-100 Efflorescence(EFF),6 1*and evaluated.

No changes.EFF,10".Voids,3at3"x1/2"deep.Formrodfrom construction.Voids,3at3"x3".

WS-31Void,6"x5"x3/8-1/4 variable.Indications were previously identified Accepted by examination.

ISI-VT-16-109 and evaluated.

No chances.WS-32 Construction voids along construction joint.Indications were previously identified Accepted by examination.

ISI-VT-16-101 EFF,6 1*and evaluated.

No changes.Formrodwithvoid2"x1"deep.Voidwithformrod3"deep.RF-18,April2012 WS-1 1 3,4"x1 3,4" X%" deep indication.

Staining Previously identified indications still Accepted by examination.

ISI-VT-12-042 above penetrations.exist-unchanqed.Page3of6 GNRO-2017/00053 Attachment 3 Containment Building Visual Inspections (IWl)Component 10 Indication Description Disposition Comments I Report No.WS-2 Surfacecracks,.005 11orless.I ndications previously identified and Accepted by examination.

ISI-VT-12-075 evaluated.

WS-3Minorruststainsfromgratingabove.

Previously identified indications still Accepted by examination.

ISI-VT-12-043exist-unchanqed.

WS-5 8 11x2 11 X.5 11 deep indication at elevation Previously identified indications still Accepted by examination.

ISI-VT-12-044 110 1*exist-unchanged.

WS-7 Construction damage,.5 11x1 11 X.375 11 Indications were previously identified Accepted by examination.

ISI-VT-12-072 deep.and evaluated.

No changes.Construction damage,.5 11x1.5 11 X.250 11 deep.Stainingfromfloorabove,not structural.

WS-8 Surfacecracks,.005 11and.004 11*Surface cracksasnotedon WS-08.Accepted by examination.

ISI-VT-12-046Lightrust staining at penetration 19.Lightrust stainsnotedon WS-08.WS-9 Construction damage.Previously identified indications still Accepted by examination.

ISI-VT-12-057exist-unchanqed.

WS-11 Fine surfacecrack,nogrowthofrust.

Previously identified indications still Accepted by examination.

ISI-VT-12-047 2.5 11x4.5 11 X.375 11 construction void.exist-unchanqed, WS-12Voids:Fewvoidswerenoticedinthisarea.

Previously identified indications still Accepted by examination.

ISI-VT-12-048Theyareallverylocalinnatureandtheexist-unchanged.

maximumsizeofthevoidsnoticedis 3 11x11/2" X3/8"deep.WS-14 Rust staining below penetration 38.Previously identified indications still Accepted by examination.ISI-VT-12-050exist-unchanged.

WS-16Lightruststain.

Previously identified indications still Accepted by examination.

ISI-VT-12-052exist-unchanged.

WS-17 Penetration62,rustwithnopitting.

Indications were previously identified Accepted by examination.

ISI-VT-12-074Lightstaining.

and evaluated.

No changes.Page4of6 GNRO-2017/00053 Attachment 3 Containment Building Visual Inspections (IWL)Component ID Indication Description Disposition Comments I Report No.WS-18 Light staining.Indications were previously reported Accepted by examination.

ISI-VT-12-069 Penetrations unpainted,lightrustwithnoandare unchanged.

pitting.WS-19 Light stains from floor above.Staining indications recorded previously Accepted by examination.

ISI-VT-12-055 remain, unchanged.

WS-20Lightrust staining.Staining indications recorded previously Accepted by examination.

ISI-VT-12-056 remain, unchanged.

WS-21Lightrust stainsfromfloorabove.

Indications previously recorded remain Accepted by examination.ISI-VT-12-059 unchanged.

WS-22 Light staining.Staining previously recorded remains Accepted by examination.

ISI-VT-12-060Areaof moderate to heavy staining around unchanged.

penetrations210,108,205,211,63.

WS-23 Minor chipping from construction at Minor chips around penetration from Accepted by examination.

ISI-VT-12-070 penetration 61.construction.

WS-24Lightrust staining.Indications were previously reported Accepted by examination.

ISI-VT-12-062andare unchanged.

WS-25Lightruststains.

Indications were previously reported Accepted by examination.

ISI-VT-12-062andare unchanged.

WS-26 Rust stains from floor above.Indications were previously reported Accepted by examination.

ISI-VT-12-064andare unchanged.

WS-27 Surface cracking (typical).

Indications Indications were previously reported as Accepted by examination.ISI-VT-12-053rangefrom.005 11-.010 11*"surface cracking (tvpical)".

WS-28 Surface cracking (typical).

Indications Indications were previously reported as Accepted by examination.ISI-VT-12-054rangefrom.005 11-.010 11*"surface cracking (typical)".Page5of6 GNRO-2017/00053 Attachment 3 Containment Building Visual Inspections (IWL)Component 10 Indication Description Disposition Comments I Report No.WS-29Seamarearoughfrom construction.

Indications were previously identified Accepted by examination.

ISI-VT-12-088Formrodexposed.

and evaluated.Nochanges.3"x3" X4"void,formrodexposed.3/8"x1"x3/4"voidwithformrodexposed.3/4"x3/8"x3/4"void.

3"x3" X4"voidwithformrodexposed.

WS-30Void,3"diameter,1/2"deep.

Indications were previously identified Accepted by examination.

ISI-VT-12-081 EFF,6 1*and evaluated.Nochanges.EFF,10".Voids,3at3"x1/2"deep.Formrodfrom construction.Voids,3at3"x3".

WS-31Void,6"x5"x3/8-1/4"variable.

Indications were previously identified Accepted by examination.

ISI-VT-12-085andevaluated.Nochanges.

WS-32Voidsalong construction joint.Indications were previously identified Accepted by examination.ISI-VT-12-080 EFF,6 1*andevaluated.Nochanges.Formrodwithvoid1"deep.Voidwithformrod21/2" X3"deep.Page6of6