ML17304B158 | 3 May 1989 | Special Rept 2-SR-89-004:on 890406,preplanned Alternate Sampling Program Initiated When RCS Reached Temp of 555 F on 890330.Temporary Mod Request to Isolate Demineralized Water Sys Approved & Addl Sampling Performed | Temporary Modification |
ML17304B190 | 3 May 1989 | Special Rept 3-SR-89-002:on 890418,radiation Monitor Inoperable for Greater than 72 H.Incident Result of Core Being off-loaded to Spent Fuel Pool for Refueling | |
ML17304B221 | 30 May 1989 | Special Rept 3-SR-89-004:on 890512,while Unit in Refueling Outage W/Core Offloaded to Spent Fuel Pool,Inservice Insp of Steam Generators Completed.Complete Results of Insp Will Be Submitted by 900512 | |
ML17304B245 | 5 June 1989 | Special Rept 3-SR-88-007-01:on 881024,inoperability of Both Channels of Reactor Vessel Water Level Sys Occurred for Period of Greater than 48 H.Caused by Malfunctioning of Communications Board.Replacement Board Installed | Reactor Vessel Water Level Post Accident Monitoring |
ML17304B326 | 14 July 1989 | Special Rept 2-SR-89-005:on 890712,load Shed Signal of 13.8 Kv Bus 2E-NAN-S02 Resulted in Deenergizing Reactor Coolant Pumps 1B & 2B & Reactor Trip.Caused by Less than Nominal Decay Heat.Unusual Event Declared.Ler Will Be Submitted | |
ML17304B378 | 3 August 1989 | Special Rept 1-SR-89-003-01:on 890402,72 H Limit for Inoperability of Condenser Evacuation Sys High Range Effluent Monitor Exceeded.Caused by Monitor Declared Inoperable on 890330 Due to Moisture Buildup in Monitor | |
ML17304B457 | 12 September 1989 | Special Rept 2-SR-89-006:on 890817,radiation Monitoring Unit Inoperable for Greater than 72 H.Caused by Monitor Spiking High.Radiation Monitor Calibr Per Approved Procedure & Found to Be within Calibr Requirements | |
ML17305A294 | 10 October 1989 | Special Rept 1-SR-89-009:on 890910,plant Vent High Range Effluent Monitor Inoperable for Greater than 72 H Due to Nonfunctional Skid Mounted Instrumenting Control Unit for Low Range Monitor.Suppl Describing Cause Will Be Issued | Post Accident Monitoring |
ML17305A318 | 17 October 1989 | Special Rept 3-SR-89-007 on 890930,radiation Monitoring Unit Inoperable for Greater than 72 H.Caused by Implementation of Design & Software Changes Needed to Improve Performance of Monitor.Corrective Actions Unnecessary.Operability Restored | |
ML17305A372 | 31 October 1989 | Special Rept 2-SR-89-007:on 891002,72 H Limit for Returning Fuel Bldg Ventilation Sys low-range Radioactive Gaseous Effluent Monitor & high-range Monitor to Operable Status Exceeded.Cause Under Investigation | |
ML17305A437 | 20 November 1989 | Special Rept 1-SR-89-003-02:on 890402,radiation Monitoring Unit Inoperable for More than 72 H.Caused by Questionable Accuracy of Gas Chamber & Lack of Addl Heat Tracing on Stated Monitors.Tracing to Be Installed | |
ML17305A440 | 30 November 1989 | Suppl 1 to Special Rept 2-SR-88-009 Re Radiation Monitoring Unit Inoperable for Greater than 72 H.Mod Implemented in Unit on Single Detector of Condenser Vacuum Pump/Gland Seal Exhaust Low Range Monitor.Mod to Be Completed by 900401 | Temporary Modification |
ML17305A453 | 16 December 1989 | Special Rept 2-SR-88-006,Suppl 1:on 881014,containment Bldg Atmosphere Process Monitor Inoperable for More than 72 H.On 881111,single Channel Analyzer Amplifier Board Could Not Be Adjusted within Specs.Approved Work Order Issued | |
ML17305A454 | 16 December 1989 | Special Rept 1-SR-89-005,Suppl 1:on 890505-08,radiation Monitoring Unit Inoperable for Greater than 72 H.Caused by Failure to Adequately Verify Configuration of Particulate Filter Assembly After Work Performed.Individual Counseled | |
ML17305A475 | 8 January 1990 | Special Rept 2-RS-89-011:on 891204,condenser Evacuation Sys low-range & high-range Radioactive Gaseous Effluent Monitors Declared Inoperable Due to Low Flow Condition & 72 H Limit for Monitor Inoperability Exceeded on 891207 | |
ML17305A482 | 15 January 1990 | Special Rept 3-SR-89-009:on 891215,containment High Range Area Radiation Monitor Unit RU-149 Inoperable for Greater than 72 H.Caused by Malfunctioning Logic Card Due to Inadequate Connection of Eprom to Socket.Card Replaced | |
ML17305A483 | 16 January 1990 | Special Rept 2-SR-89-009:on 891212,Channel a of Quality SPDS Could Not Be Calibr & Declared Inoperable.On 891215, Trouble Alarm Received from Power Supply to Channel A.Sys Inoperable for More than 7 Days | Reactor Vessel Water Level Post Accident Monitoring |
ML17305A488 | 20 January 1990 | Special Rept 1-SR-88-008-01:on 881014,loose Parts Detection Sys Channel 5 Declared Inoperable Due to Repeated Spurious Alarms & Not Returned to Operable Status within 30 Days. Alarm Setpoint Will Be Reset & Channel Returned to Svc | |
ML17305A497 | 29 January 1990 | Supplemental Special Rept 2-SR-89-007:on 890929,radioactive Gaseous Effluent Monitors Declared Inoperable Due to Frequent Low Flow Alarms.Monitors Returned to Operable Status on 891002,violating 72 H Limit | |
ML17305A525 | 6 February 1990 | Special Rept 3-SR-90-001:on 900105,plant Vent Sys Radioactive Gaseous Effluent low-range Monitor RU-143 Declared Inoperable & Remained Out of Svc for More than 72 H.Caused by Anomaly in Check Source Circuitry | |
ML17305A559 | 23 February 1990 | Special Rept 3-SR-90-002:on 900118,loose-part Detection Sys Inoperable for More than 30 Days.Engineering Investigation of loose-parts Detection Sys Response & Troubleshooting to Determine If Problem Is Hardware Deficiency in Progress | |
ML17305A656 | 4 April 1990 | Special Rept 3-SR-90-003:on 900302,radiation Monitoring Unit RU-1 Removed from Svc for More than 72 H Due to Differences in Indicated 10 Minute & 1 H Average Particulate Channel Radiation Levels.Alternate Monitor Installed | |
ML17305A659 | 2 April 1990 | Suppl 1 to Special Rept 2-SR-89-010:updates 891105 Incident When post-accident Sampling Sys Declared Inoperable & Not Returned to Svc within 7-day Required Period.Caused by Leakage in Check Valve.Leaking Check Valve Replaced | |
ML17305A662 | 2 April 1990 | Special Rept 2-SR-88-009:on 881209,radiation Monitoring Unit Inoperable for Greater That 72 H to Perform Corrective Maint on Low Range Monitor.Plant Change Request Initiated to Make Temporary Mod Permanent Design | Temporary Modification |
ML17305A684 | 6 April 1990 | Special Rept 1-SR-90-001:radiation Monitor Inoperable for Greater than 72 H.Caused by Inability to Sample Refueling Bldg Ventilation Exhaust Since All Fuel Bldg Ventilation Out of Svc to Perform Scheduled Maint.Fuel Bldg Sampled | |
ML17305A686 | 12 April 1990 | Special Rept 2-SR-90-001:on 900323,Train B Class 1E 4,160 Volt Bus Deenergized in Order to Perform Scheduled Maint. Preplanned Alternate Sampling Program Initiated to Monitor Plant Vent & Fuel Bldg Ventilation Sys.Sys Returned to Svc | |
ML17305A716 | 21 April 1990 | Special Rept 1-SR-90-002:on 900327,radiation Monitoring Unit Was Inoperable Greater than 72 H in Order to Implement Mods Required to Improve Performance of Monitors.Monitors Declared Operable on 900410 | |
ML17305A729 | 2 May 1990 | Special Rept 3-SR-90-002-01:on 900118,loose Part Detection Sys in Alarm Condition Since Startup.Channels Will Be Reworked & Returned to Svc During Next Scheduled Refueling Outage | Temporary Modification |
ML17305A730 | 2 May 1990 | Special Rept 1-SR-89-009,Suppl 1:on 890907,radiation Monitoring Unit Inoperable in Excess of 72 H.Caused by Failure of Sys Board Zero Insertion Connecting Socket to Ensure Solid Contact.Engineering Evaluation Completed | Post Accident Monitoring |
ML17305A772 | 11 May 1990 | Special Rept 1-SR-90-003:on 900421,condenser Evacuation Sys high-range Radiation Monitor RU-141 Declared Inoperable for More than 72 H Due to Unstable Sample Flow.Caused by Moisture Accumulation in Flow Element.Heat Tracing Added | |
ML17305A782 | 15 May 1990 | Suppl 3 to Special Rept 2-SR-88-009:on 881209,radiation Monitoring Units Inoperable for Greater than 72 H.Caused by Corrective Maint.Radiation Monitors RU-143 & RU-144 Returned to Svc on 890322 & RU-141 & RU-142 Returned on 900623 | Temporary Modification |
ML17305A823 | 24 May 1990 | Special Rept 1-SR-90-004:on 900418,post-accident Sampling Sys Inoperable Greater than 7 Days.Event Caused as Result of Failure to Communicate Plant Status.Engineering Evaluation of Components Exposed to RCS Fluid & Pressure Begun | |
ML17305A868 | 5 June 1990 | Special Rept 3-SR-90-004:on 900509,radiation Monitoring Unit Inoperable Greater than 72 H.Caused by Inability to Maintain Detector Parameters to Meet Surveillance Testing Acceptance Criteria.Evaluation of New Detectors Being Performed | |
ML17305A870 | 12 June 1990 | Special Rept 2-SR-90-003:on 900503,cathodic Protection Sys Inoperable Over 30 Days.Caused by Insufficient Voltage Shift Due to One Anode in Sys Not Having Sufficient Current Capacity Due to Installation of Steel Between Bldgs | |
ML17305A903 | 22 June 1990 | Suppl 2 to Special Rept 2-SR-89-007:on 890929,radioactive Gaseous Effluent Monitors Declared Inoperable for Greater than 72 H Due to Frequent Low Flow Alarms.Caused by Limit Switch Out of Adjustment.Limit Switch Readjusted | |
ML17305A928 | 11 July 1990 | Suppl 4 to Special Rept 2-SR-88-009:on 881206,condenser Vacuum Pump/Gland Seal Exhaust Low & High Range Monitors Declared Inoperable.Capacitive Feedback Path Will Be Eliminated to Prevent Spurious Output Pulses | Temporary Modification |
ML17305A929 | 11 July 1990 | Special Rept 2-SR-90-004:on 900613,radiation Monitors RU-145 & RU-146 Inoperable for More than 72 H.Caused by Tech Spec Calibr,Installation of Temporary Mod & Detector Replacement. Monitors Returned to Svc on 900626 | Temporary Modification |
ML17305A996 | 9 August 1990 | Special Rept 2-SR-89-009:on 891212,Channel a Reactor Vessel Water Level Sys Declared Inoperable & 7-day Limit Exceeded on 891219.Modem Found to Have Drifted Out of Tolerance. Channel a Modem Replaced & Calibr | Reactor Vessel Water Level Post Accident Monitoring Temporary Modification |
ML17305A997 | 9 August 1990 | Special Rept 2-SR-89-010:on 891201,post-accident Sampling Sys Inoperable for More than 7 Days.Probably Caused by Leak Booster Pump Seals.Replacement Booster Pump Installed & Clogged Valve Replaced | |
ML17305B009 | 16 August 1990 | Special Rept 2-SR-90-005:on 900719,plant Vent Sys High Range Effluent Monitor Inoperable Greater than 72 H.Caused by Length of Surveillance Test Procedure.Surveillance Test Successfully Completed & Radiation Monitors Returned to Svc | |
ML17305B019 | 21 August 1990 | Special Rept 1-SR-90-005:on 900725,performance of Loose Parts Detection Sys Might Result in Alarm Condition.Cause of Spurious Alarms Due to Sensitivity of Sys.Engineering Evaluation Determined Sys Operating Properly | |
ML17305B101 | 3 October 1990 | Special Rept 1-SR-90-006:on 900905,radiation Monitor Inoperable for More than 72 H.Caused by End of Life Failure of Blower Fan.Blower Replaced & Test Procedure Revised to Include Appropriate Acceptance Criteria | |
ML17305B169 | 27 October 1990 | Suppl to Special Rept 2-SR-88-009:on 881206,radiation Monitoring Unit Inoperable for More than 72 H | Temporary Modification |
ML17305B181 | 12 November 1990 | Special Rept 1-SR-90-006:on 900905,containment Atmosphere Radiation Monitor Inoperable for Greater than 72 H.Caused by End of Life Failure of Blower Fan.Blower Replaced & Test Procedure Revised | |
ML17305B315 | 10 January 1991 | Special Rept 2-SR-90-007:on 901212,diesel Generator Valid Test Failure Occurred.Caused by Air in Diesel Generator Fuel Lines.Maint Bulletins Distributed to Plant Maint & Work Control Groups | |
ML17305B330 | 16 January 1991 | Special Rept 1-SR-90-007:on 901221,containment Bldg Atmosphere Radiation Monitor RU-1 Inoperable for More than 72 H.On 901218,monitor Declared Inoperable Due to High Flow Conditions.Caused by Failure of Flow Totalizer | |
ML17305B334 | 16 January 1991 | Corrected Copy of Special Rept 1-SR-90-007.On 901221, Containment Bldg Radiation Monitor RU-1 Inoperable for More than 72 H.On 901218,monitor Declared Inoperable Due to High Flow Conditions.Caused by Failure of Flow Totalizer | |
ML17305B355 | 4 February 1991 | Special Rept 1-SR-91-001:on 910111,fuel Bldg Ventilation Sys high-range Radioactive Gaseous Effluent Monitor Inoperable for More than 72 H.Caused by Need to Replace Power Supply. Monitors Returned to Operable Status on 910113 | |
ML17305B609 | 20 June 1991 | Special Rept 3-SR-91-003:on 910619,inadvertent Containment Spray Actuation Sys Signal Received,Resulting in Inoperability of Both Trains of Containment Spray Sys. Containment Spray Pump Restored & Agencies Notified | |
ML17305B655 | 17 July 1991 | Special Rept 3-SR-91-005:on 910712,unidentified Leakage Exceeded TS 3.4.5.2 LCO for RCS Leakage Limit of One (1) Gallon Per Minute Due to Leakage from Reactor Coolant Pump Seal Injection Hx.Leakage Reduced to Allowable Limit |