05000321/LER-1979-082, Updated LER 79-082/03X-2:on 790825-27,attempt to Perform RCIC Pump Operability Procedure Unsuccessful When Turbine Failed to Trip Upon Manual Signal.Caused by Burned Out Turbine Trip Actuator Coils & Binding Assembly | 23 November 1982 | Updated LER 79-082/03X-2:on 790825-27,attempt to Perform RCIC Pump Operability Procedure Unsuccessful When Turbine Failed to Trip Upon Manual Signal.Caused by Burned Out Turbine Trip Actuator Coils & Binding Assembly | |
05000321/LER-1981-120, Updated LER 81-120/01T-1:on 811105,AE Advised That in Event of Main Steamline Break or Scram Discharge,Isolation of HPCI & Reactor Core Isolation Cooling Sys Could Occur.Caused by Erroneous Analysis.Event Would Not Occur | 3 August 1982 | Updated LER 81-120/01T-1:on 811105,AE Advised That in Event of Main Steamline Break or Scram Discharge,Isolation of HPCI & Reactor Core Isolation Cooling Sys Could Occur.Caused by Erroneous Analysis.Event Would Not Occur | |
05000366/LER-1980-096, Updated LER 80-096/03X-2:on 800619 & 27,w/reactor Mode Switch in Run,Reactor Bldg to Torus Vacuum Breaker Isolation Valve Failed to Open.Caused by Failure of D-P Switch to Actuate.Switch Replaced | 23 December 1982 | Updated LER 80-096/03X-2:on 800619 & 27,w/reactor Mode Switch in Run,Reactor Bldg to Torus Vacuum Breaker Isolation Valve Failed to Open.Caused by Failure of D-P Switch to Actuate.Switch Replaced | |
05000366/LER-1980-124, Updated LER 80-124/03X-1:on 800813 & 27,during Surveillance of Torus/Drywell Vacuum Breakers,J & I Breakers Failed to Give Proper Light Indication.Caused by Air Control Valves Being Out of Adjustment.Valves Adjusted & Breakers | 16 December 1982 | Updated LER 80-124/03X-1:on 800813 & 27,during Surveillance of Torus/Drywell Vacuum Breakers,J & I Breakers Failed to Give Proper Light Indication.Caused by Air Control Valves Being Out of Adjustment.Valves Adjusted & Breakers Tested | |
05000366/LER-1982-068, Updated LER 82-068/03X-1:on 820707 & 24,volumetric Weighted Average Drywell Air Temp Exceeded Tech Spec Limit of 135 F. Caused by High Ambient Temp & Failure of Alternate Chiller Fans 8B & 9B.New Chilling Units Installed | 26 October 1983 | Updated LER 82-068/03X-1:on 820707 & 24,volumetric Weighted Average Drywell Air Temp Exceeded Tech Spec Limit of 135 F. Caused by High Ambient Temp & Failure of Alternate Chiller Fans 8B & 9B.New Chilling Units Installed | |
05000366/LER-1983-040, Updated LER 83-040/03X-1:on 830709 & 14,control Rod Drive Low Pressure or High Level Alarm Received for HCV 2C11-26-31 & 02-29.Caused by Leaking EP-111 Nitrogen Charging Valves. Valves Replaced & HCVs Returned to Svc | 12 March 1984 | Updated LER 83-040/03X-1:on 830709 & 14,control Rod Drive Low Pressure or High Level Alarm Received for HCV 2C11-26-31 & 02-29.Caused by Leaking EP-111 Nitrogen Charging Valves. Valves Replaced & HCVs Returned to Svc | Time of Discovery |
05000366/LER-1983-055, Updated LER 83-055/03X-1:on 830713 & 21,RCIC Pump 2E51-C002 Would Not Deliver 600 Gpm Required Tech Spec Flow.Caused by Unadjusted Electric Governor Remote Actuator.Actuator Adjusted.W/Amended | 5 December 1983 | Updated LER 83-055/03X-1:on 830713 & 21,RCIC Pump 2E51-C002 Would Not Deliver 600 Gpm Required Tech Spec Flow.Caused by Unadjusted Electric Governor Remote Actuator.Actuator Adjusted.W/Amended | |
05000366/LER-1983-099, Updated LER 83-099/03X-1:on 830925 & 1005,hydrogen Dioxide Analyzer a Declared Inoperable During Procedure HNP-2-3882 & Out of Calibr,Respectively.Caused by Worn Diaphragms in Sample Pump a & Instrument Drift | 28 October 1983 | Updated LER 83-099/03X-1:on 830925 & 1005,hydrogen Dioxide Analyzer a Declared Inoperable During Procedure HNP-2-3882 & Out of Calibr,Respectively.Caused by Worn Diaphragms in Sample Pump a & Instrument Drift | Post Accident Monitoring |
05000366/LER-1983-126, Amended LER 83-126/03L-0:on 831113,safety Relief Valve Tailpipe Temp Recorder 2B21-B614 Observed Stamping Erratically.Caused by Component Failure.Advancing Mechanism, Solenoid & Arm & Hub Assembly Replaced | 5 December 1983 | Amended LER 83-126/03L-0:on 831113,safety Relief Valve Tailpipe Temp Recorder 2B21-B614 Observed Stamping Erratically.Caused by Component Failure.Advancing Mechanism, Solenoid & Arm & Hub Assembly Replaced | |
05000366/LER-1983-127, Amended LER 83-127/03L-0:on 831108,while Pumping Water from Drywell Equipment Drain Sump,Pump Discharge Valve 2G11-F018 Would Not Open.Sys Declared Inoperable.Caused by Blown Fuse in Valve Control Circuit | 5 December 1983 | Amended LER 83-127/03L-0:on 831108,while Pumping Water from Drywell Equipment Drain Sump,Pump Discharge Valve 2G11-F018 Would Not Open.Sys Declared Inoperable.Caused by Blown Fuse in Valve Control Circuit | |
05000366/LER-1984-001, Revised LER 84-001-01:on 840203,plant Personnel Detected Fracture in 66-inch Vent Header in Bay 5.Caused by Brittle Fracture of Vent Header Matl.Vent Header Will Be Repaired Prior to Startup | 21 March 1984 | Revised LER 84-001-01:on 840203,plant Personnel Detected Fracture in 66-inch Vent Header in Bay 5.Caused by Brittle Fracture of Vent Header Matl.Vent Header Will Be Repaired Prior to Startup | |
HL-0476, Special Rept 2-95-01:on 950110 Unit 2 Drywell High Range Radiation Inoperable Longer than 7 Days.Caused by Exceeding Procedural Limits of 34SV-SUV-019-2S.Technicians Checked High Voltage Power Supply Which Powers Radiation Detectors | 17 January 1995 | Special Rept 2-95-01:on 950110 Unit 2 Drywell High Range Radiation Inoperable Longer than 7 Days.Caused by Exceeding Procedural Limits of 34SV-SUV-019-2S.Technicians Checked High Voltage Power Supply Which Powers Radiation Detectors | |
HL-1191, Monthly Operating Repts for Aug 1990 for Hatch Units 1 & 2 | 31 August 1990 | Monthly Operating Repts for Aug 1990 for Hatch Units 1 & 2 | |
HL-1259, Special Rept 90-001:on 900730,fire-rated Assembly Declared Inoperable for More than 14 Days.Caused by Personnel Error. Hourly Fire Watch Initiated | 29 August 1990 | Special Rept 90-001:on 900730,fire-rated Assembly Declared Inoperable for More than 14 Days.Caused by Personnel Error. Hourly Fire Watch Initiated | Safe Shutdown Continuous fire watch Fire Watch Hourly Fire Watch |
HL-1316, Monthly Operating Repts for Jan 1993 for Ei Hatch Nuclear Plant,Units 1 & 2 | 31 January 1993 | Monthly Operating Repts for Jan 1993 for Ei Hatch Nuclear Plant,Units 1 & 2 | |
HL-1353, Special Rept 2-90-003 Re fire-rated Assemblies Inoperable W/O Hourly Fire Watch Maintained.Caused by Personnel Error. License Condition 2-90-332 Initiated | 15 November 1990 | Special Rept 2-90-003 Re fire-rated Assemblies Inoperable W/O Hourly Fire Watch Maintained.Caused by Personnel Error. License Condition 2-90-332 Initiated | Safe Shutdown Continuous fire watch Fire Watch Hourly Fire Watch |
HL-1360, Monthly Operating Repts for Hatch Units 1 & 2 for Oct 1990 | 31 October 1990 | Monthly Operating Repts for Hatch Units 1 & 2 for Oct 1990 | |
HL-1398, Monthly Operating Repts for Nov 1990 for Hatch Units 1 & 2 | 30 November 1990 | Monthly Operating Repts for Nov 1990 for Hatch Units 1 & 2 | |
HL-1434, Monthly Operating Repts for Dec 1990 for Hatch Units 1 & 2 | 31 December 1990 | Monthly Operating Repts for Dec 1990 for Hatch Units 1 & 2 | |
HL-1470, Special Rept:On 901119,discrepancy Noted in Number of SRM & IRM Detectors During Inventory.Caused by Inadequate Recordkeeping Controls.Responsibility for Control & Accountability of Detectors Returned to Reactor Engineering | 14 February 1991 | Special Rept:On 901119,discrepancy Noted in Number of SRM & IRM Detectors During Inventory.Caused by Inadequate Recordkeeping Controls.Responsibility for Control & Accountability of Detectors Returned to Reactor Engineering | |
HL-1476, Monthly Operating Repts for Jan 1991 for Hatch Units 1 & 2 | 31 January 1991 | Monthly Operating Repts for Jan 1991 for Hatch Units 1 & 2 | |
HL-1488, Ro:On 910212,potential Malfunction of SRVs Suspected.Caused by Turbine Trip & Re Actor Scram.Investigation of Malfunction Planned | 13 February 1991 | Ro:On 910212,potential Malfunction of SRVs Suspected.Caused by Turbine Trip & Re Actor Scram.Investigation of Malfunction Planned | |
HL-1492, Ro:On 910214,potential Malfunction of SRVs Suspected. Caused by Turbine Trip & Reactor Scram Valve Testing. Investigation of Malfunction Planned | 15 February 1991 | Ro:On 910214,potential Malfunction of SRVs Suspected. Caused by Turbine Trip & Reactor Scram Valve Testing. Investigation of Malfunction Planned | |
HL-1523, Monthly Operating Repts for Feb 1991 for Hatch Nuclear Plant Units 1 & 2 | 28 February 1991 | Monthly Operating Repts for Feb 1991 for Hatch Nuclear Plant Units 1 & 2 | |
HL-1542, Special Rept:On 910301,battery-powered Emergency Lighting Units Inoperable for Period Greater than 72 H.Caused by Personnel Error.Units Restored to Operable Status on 910302 & Surveillance Procedure 42SV-FPX-003-0S Revised | 25 March 1991 | Special Rept:On 910301,battery-powered Emergency Lighting Units Inoperable for Period Greater than 72 H.Caused by Personnel Error.Units Restored to Operable Status on 910302 & Surveillance Procedure 42SV-FPX-003-0S Revised | Emergency Lighting Missed surveillance |
HL-1547, Special Rept 1-91-003:on 910318,during Monthly Insp of Fire Door 1L48-1C22,discovered That Door Inoperable for More than 14 Days Due to Worn Hinges,Plates & Shins.Caused by Normal Wear.Fire Watch Established & New Door Ordered | 2 April 1991 | Special Rept 1-91-003:on 910318,during Monthly Insp of Fire Door 1L48-1C22,discovered That Door Inoperable for More than 14 Days Due to Worn Hinges,Plates & Shins.Caused by Normal Wear.Fire Watch Established & New Door Ordered | Safe Shutdown Continuous fire watch Fire Watch Hourly Fire Watch |
HL-1576, Monthly Operating Repts for Mar 1991 for Hatch Nuclear Plant Units 1 & 2 | 31 March 1991 | Monthly Operating Repts for Mar 1991 for Hatch Nuclear Plant Units 1 & 2 | |
HL-1630, Monthly Operating Repts for Apr 1991 for Hatch Nuclear Plant Units 1 & 2 | 30 April 1991 | Monthly Operating Repts for Apr 1991 for Hatch Nuclear Plant Units 1 & 2 | |
HL-1649, Special Rept:On 910420,fire Barrier Assemblies Inoperable for Period Longer than 14 Days Discovered During Insp.Caused by Personnel Error.Penetrations 2Z43-H66OC & 2Z43-HO27C Resealed & Partially Drilled Hole Repaired | 21 May 1991 | Special Rept:On 910420,fire Barrier Assemblies Inoperable for Period Longer than 14 Days Discovered During Insp.Caused by Personnel Error.Penetrations 2Z43-H66OC & 2Z43-HO27C Resealed & Partially Drilled Hole Repaired | Safe Shutdown Fire Barrier Hourly Fire Watch |
HL-1667, Special Rept 1-91-004:on 910502 & 06,listed battery-powered Emergency Lighting Units Inoperable for More than 72 H. Affected battery-powered Emergency Lighting Units Verified Operable by Performing Monthly Insp | 6 June 1991 | Special Rept 1-91-004:on 910502 & 06,listed battery-powered Emergency Lighting Units Inoperable for More than 72 H. Affected battery-powered Emergency Lighting Units Verified Operable by Performing Monthly Insp | Emergency Lighting |
HL-1674, Special Rept 2-91-001:on 910320 & 0401,fire-rated Assemblies Inoperable for More than 14 Days Due to Reloading of Reactor Core & Planned Maint Activity,Respectively.Hourly Fire Watch Initiated & Set Room Walls Reinstalled | 7 June 1991 | Special Rept 2-91-001:on 910320 & 0401,fire-rated Assemblies Inoperable for More than 14 Days Due to Reloading of Reactor Core & Planned Maint Activity,Respectively.Hourly Fire Watch Initiated & Set Room Walls Reinstalled | Safe Shutdown Fire Barrier Continuous fire watch Fire Watch Hourly Fire Watch |
HL-1682, Rev 2 to Special Rept 1-91-005:on 910515,discovered That Cable Penetration Seal Assembly Not Installed Per Mfg Instructions & Barrier Inoperable for More than 14 Days. Hourly Fire Watch Established & Thermolag Barrier Installed | 9 October 1991 | Rev 2 to Special Rept 1-91-005:on 910515,discovered That Cable Penetration Seal Assembly Not Installed Per Mfg Instructions & Barrier Inoperable for More than 14 Days. Hourly Fire Watch Established & Thermolag Barrier Installed | Fire Barrier Hourly Fire Watch |
HL-1684, Monthly Operating Repts for May 1991 for Hatch Nuclear Plant Units 1 & 2 | 31 May 1991 | Monthly Operating Repts for May 1991 for Hatch Nuclear Plant Units 1 & 2 | |
HL-1691, Special Rept:On 910526,fixed Water Spray Nozzles Inoperable for Longer than 14 Days Identified During Insp of Fire Sprinkler Sys.Cause Indeterminate.Conduits Routed Away from Vicinity of Spray Nozzles | 21 June 1991 | Special Rept:On 910526,fixed Water Spray Nozzles Inoperable for Longer than 14 Days Identified During Insp of Fire Sprinkler Sys.Cause Indeterminate.Conduits Routed Away from Vicinity of Spray Nozzles | Safe Shutdown Fire Barrier Continuous fire watch |
HL-1730, Monthly Operating Repts for June 1991 for Ei Hatch Units 1 & 2 | 30 June 1991 | Monthly Operating Repts for June 1991 for Ei Hatch Units 1 & 2 | |
HL-1766, Monthly Operating Repts for Jul 1991 for Ei Hatch Nuclear Plant,Units 1 & 2 | 31 July 1991 | Monthly Operating Repts for Jul 1991 for Ei Hatch Nuclear Plant,Units 1 & 2 | |
HL-1828, Monthly Operating Repts for Aug 1991 for Plant Hatch,Units 1 & 2 | 31 August 1991 | Monthly Operating Repts for Aug 1991 for Plant Hatch,Units 1 & 2 | |
HL-1861, Special Rept 1-91-007:on 910909 & 16,fire Barrier Assemblies Inoperable for More than 14 Days When Unsealed Drilled Hole & Unsealed Penetration Discovered.Caused by Personnel Error.Hole Repaired & Penetration Sealed | 8 October 1991 | Special Rept 1-91-007:on 910909 & 16,fire Barrier Assemblies Inoperable for More than 14 Days When Unsealed Drilled Hole & Unsealed Penetration Discovered.Caused by Personnel Error.Hole Repaired & Penetration Sealed | Safe Shutdown Fire Barrier Temporary Modification Hourly Fire Watch |
HL-1868, Monthly Operating Repts for Sept 1991 for Hatch,Units 1 & 2 | 30 September 1991 | Monthly Operating Repts for Sept 1991 for Hatch,Units 1 & 2 | |
HL-1891, Special Rept 2-91-003:on 911003,during Performance of Battery Discharge Test,Two Emergency Lighting Units Failed to Illuminate for 8 H & Could Not Be Restored within 72 H. Lighting Units Repaired & Discharge Test Performed | 31 October 1991 | Special Rept 2-91-003:on 911003,during Performance of Battery Discharge Test,Two Emergency Lighting Units Failed to Illuminate for 8 H & Could Not Be Restored within 72 H. Lighting Units Repaired & Discharge Test Performed | Emergency Lighting |
HL-1916, Special Rept 1-91-008:on 911014,four Suppression Sys Flooding Valves in Fixed Water Suppression Sys Not Surveilled Once Per 18 Months.Caused by Less than Adequate Procedure.Valves Tested & Inspected Per Revised Procedures | 8 November 1991 | Special Rept 1-91-008:on 911014,four Suppression Sys Flooding Valves in Fixed Water Suppression Sys Not Surveilled Once Per 18 Months.Caused by Less than Adequate Procedure.Valves Tested & Inspected Per Revised Procedures | Missed surveillance Continuous fire watch |
HL-1922, Monthly Operating Repts for Oct 1991 for Ei Hatch,Units 1 & 2 | 31 October 1991 | Monthly Operating Repts for Oct 1991 for Ei Hatch,Units 1 & 2 | |
HL-1941, Special Rept 1-91-009:from 910929-1029,all Fuel Removed from Reactor Vessel & Fire Barriers Inoperable for More than 14 Days.Caused by Need to Install Support Plates,Platforms & Conduits.Structural Beams Restored to Operable Status | 22 November 1991 | Special Rept 1-91-009:from 910929-1029,all Fuel Removed from Reactor Vessel & Fire Barriers Inoperable for More than 14 Days.Caused by Need to Install Support Plates,Platforms & Conduits.Structural Beams Restored to Operable Status | Safe Shutdown Fire Barrier Continuous fire watch Hourly Fire Watch |
HL-1967, Special Rept 1-91-010:on 911121,discovered That Blue Pen of post-accident Effluent Monitoring Sys Recorder 1D11-R631 Spiking Upscale at Regular Interval.Caused by Failed Flow Transducer.Flow Transducer Replaced | 5 December 1991 | Special Rept 1-91-010:on 911121,discovered That Blue Pen of post-accident Effluent Monitoring Sys Recorder 1D11-R631 Spiking Upscale at Regular Interval.Caused by Failed Flow Transducer.Flow Transducer Replaced | Grab sample |
HL-1971, Monthly Operating Repts for Nov 1991 for Ei Hatch Nuclear Plant Unit 1 | 30 November 1991 | Monthly Operating Repts for Nov 1991 for Ei Hatch Nuclear Plant Unit 1 | |
HL-2010, Monthly Operating Repts for Dec 1991 for Ei Hatch Nuclear Plant Unit 1 | 31 December 1991 | Monthly Operating Repts for Dec 1991 for Ei Hatch Nuclear Plant Unit 1 | |
HL-2040, Monthly Operating Repts for Jan 1992 for Ei Hatch Nuclear Plant Units 1 & 2 | 31 January 1992 | Monthly Operating Repts for Jan 1992 for Ei Hatch Nuclear Plant Units 1 & 2 | |
HL-2074, Ei Hatch Nuclear Plant - Units 1 & 2 Annual Operating Rept, 1991 | 31 December 1991 | Ei Hatch Nuclear Plant - Units 1 & 2 Annual Operating Rept, 1991 | Safe Shutdown Shutdown Margin High Radiation Area Anticipated operational occurrence Weld Overlay Operating Basis Earthquake Nondestructive Examination Abnormal operational transient Design basis earthquake Process Control Program Earthquake Fire Protection Program |
HL-2107, Monthly Operating Repts for Feb 1992 for Ei Hatch Units 1 & 2 | 29 February 1992 | Monthly Operating Repts for Feb 1992 for Ei Hatch Units 1 & 2 | |
HL-2172, Monthly Operating Repts for Mar 1992 for Ei Hatch Nuclear Plant Units 1 & 2 | 31 March 1992 | Monthly Operating Repts for Mar 1992 for Ei Hatch Nuclear Plant Units 1 & 2 | |