ENS 41616: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 04/19/2005 20:52 EST
| event date = 04/19/2005 20:52 EST
| last update date = 04/19/2005
| last update date = 04/19/2005
| title = Technical Specificiation Required Shutdown Related To Pressure Boundary Leakage
| title = Technical Specificiation Required Shutdown Related to Pressure Boundary Leakage
| event text = The licensee "entered technical specification limiting condition for operation 3.0.3 due to pressure boundary leakage on a 3/4 inch pipe on the piping for the boron injection tank.  As a result of this, both trains of high head injection [have been declared] inoperable.  Unit shutdown began at 2105 [EDT].  All other safety systems are operable.  Current plans are to take the plant to mode 4 and isolate and replace the affected piping.  The current leakage is 780 cc/hr.
| event text = The licensee "entered technical specification limiting condition for operation 3.0.3 due to pressure boundary leakage on a 3/4 inch pipe on the piping for the boron injection tank.  As a result of this, both trains of high head injection [have been declared] inoperable.  Unit shutdown began at 2105 [EDT].  All other safety systems are operable.  Current plans are to take the plant to mode 4 and isolate and replace the affected piping.  The current leakage is 780 cc/hr.
The licensee discovered the leakage during operator rounds at approximately 0500 EDT.  Technical Specification 3.0.3 was entered at 2052 EDT.  Power reduction is currently in progress.  The licensee will be notifying the NRC Resident Inspector and Lower Alloways Creek Township.
The licensee discovered the leakage during operator rounds at approximately 0500 EDT.  Technical Specification 3.0.3 was entered at 2052 EDT.  Power reduction is currently in progress.  The licensee will be notifying the NRC Resident Inspector and Lower Alloways Creek Township.

Latest revision as of 22:21, 1 March 2018

ENS 41616 +/-
Where
Salem PSEG icon.png
New Jersey (NRC Region 1)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown
Time - Person (Reporting Time:+-3.88 h-0.162 days <br />-0.0231 weeks <br />-0.00531 months <br />)
Opened: Steve Sauer
21:59 Apr 19, 2005
NRC Officer: Bill Huffman
Last Updated: Apr 19, 2005
41616 - NRC Website