StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 04/19/2005 20:52 EST | | event date = 04/19/2005 20:52 EST | ||
| last update date = 04/19/2005 | | last update date = 04/19/2005 | ||
| title = Technical Specificiation Required Shutdown Related | | title = Technical Specificiation Required Shutdown Related to Pressure Boundary Leakage | ||
| event text = The licensee "entered technical specification limiting condition for operation 3.0.3 due to pressure boundary leakage on a 3/4 inch pipe on the piping for the boron injection tank. As a result of this, both trains of high head injection [have been declared] inoperable. Unit shutdown began at 2105 [EDT]. All other safety systems are operable. Current plans are to take the plant to mode 4 and isolate and replace the affected piping. The current leakage is 780 cc/hr. | | event text = The licensee "entered technical specification limiting condition for operation 3.0.3 due to pressure boundary leakage on a 3/4 inch pipe on the piping for the boron injection tank. As a result of this, both trains of high head injection [have been declared] inoperable. Unit shutdown began at 2105 [EDT]. All other safety systems are operable. Current plans are to take the plant to mode 4 and isolate and replace the affected piping. The current leakage is 780 cc/hr. | ||
The licensee discovered the leakage during operator rounds at approximately 0500 EDT. Technical Specification 3.0.3 was entered at 2052 EDT. Power reduction is currently in progress. The licensee will be notifying the NRC Resident Inspector and Lower Alloways Creek Township. | The licensee discovered the leakage during operator rounds at approximately 0500 EDT. Technical Specification 3.0.3 was entered at 2052 EDT. Power reduction is currently in progress. The licensee will be notifying the NRC Resident Inspector and Lower Alloways Creek Township. |
Latest revision as of 22:21, 1 March 2018
Where | |
---|---|
Salem New Jersey (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
Time - Person (Reporting Time:+-3.88 h-0.162 days <br />-0.0231 weeks <br />-0.00531 months <br />) | |
Opened: | Steve Sauer 21:59 Apr 19, 2005 |
NRC Officer: | Bill Huffman |
Last Updated: | Apr 19, 2005 |
41616 - NRC Website
| |