| title = NRC-014 - Letter from Michael Kiley, Florida Power & Light, to N.R.C., Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231 (Application to Revise Ultimate Heat Sink  
| title = NRC-014 - Letter from Michael Kiley, Florida Power & Light, to N.R.C., Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231 (Application to Revise Ultimate Heat Sink
| author name =  
| author name =  
| author affiliation = NRC/OGC
| author affiliation = NRC/OGC
Line 13: Line 13:
| document type = Legal-Pre-Filed Exhibits
| document type = Legal-Pre-Filed Exhibits
| page count = 10
| page count = 10
| project =
| stage = RAI
}}
}}


=Text=
=Text=
{{#Wiki_filter:0FPL10 CFR 50.90L-2014-236 July 24, 2014U.S. Nuclear Regulatory Commission ATTN: Document Control DeskWashington, DC 20555-0001 Turkey Point Units 3 and 4Docket Nos. 50-250 and 50-251Renewed Facility Operating License Nos. DPR-31 and DPR-41
{{#Wiki_filter:NRC-014 Submitted Nov. 10, 2015 0      FPL 10 CFR 50.90 L-2014-236 July 24, 2014 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Renewed Facility Operating License Nos. DPR-31 and DPR-41


==Subject:==
==Subject:==
Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to Revise Ultimate Heat Sink Temperature Limit


Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to ReviseUltimate Heat Sink Temperature Limit
==References:==
: 1. Florida Power & Light Company Letter L-2014-216, "License Amendment Request No.
231, Application to Revise Technical Specifications to Revise Ultimate Heat Sink Temperature Limit," July 10, 2014.
: 2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.
231, Application to Revise Ultimate Heat Sink Temperature Limit - Request for Emergency Approval," July 17, 2014.
: 3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Request for Additional Information - LAR 231 (TAC MF4392 and MF4393)," July 22, 2014.
In Reference 1, Florida Power & Light Company (FPL) requested an amendment to the Technical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.
The proposed amendment would revise the ultimate heat sink (UHS) water temperature limit from I100 °F to 104'F.
In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. Nuclear Regulatory Commission (NRC) to review and approve it on an emergency basis.
In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.
00 Florida Power & Light Company 9760 SW  34 4th  St.. Florida City, FL 33035


==References:==
Florida Power & Light Company                                                         L-2014-236 License Amendment Request No. 231 Response to SCVB Request for Additional Information                                     Page 2 of 2 The additional information provided in the enclosure to this letter does not impact the no significant hazards determination and environmental considerations previously provided in Reference 1.
: 1. Florida Power  
There are no new commitments made in this submission.
& Light Company Letter L-2014-216, "License Amendment Request No.231, Application to Revise Technical Specifications to Revise Ultimate Heat SinkTemperature Limit," July 10, 2014.2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.231, Application to Revise Ultimate Heat Sink Temperature Limit -Request forEmergency Approval,"
If you have any questions or require additional information, please contact Mr. Robert Tomonto at 305-246-7327.
July 17, 2014.3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Requestfor Additional Information
I declare under penalty of perjury that the foregoing is true and correct.
-LAR 231 (TAC MF4392 and MF4393),"
Executed on: July 24, 2014.
July 22, 2014.In Reference 1, Florida Power & Light Company (FPL) requested an amendment to theTechnical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.The proposed amendment would revise the ultimate heat sink (UHS) water temperature limitfrom I100°F to 104'F.In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. NuclearRegulatory Commission (NRC) to review and approve it on an emergency basis.In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.Florida Power & Light Company 009760 SW 344th St.. Florida City, FL 33035 Florida Power & Light CompanyLicense Amendment Request No. 231Response to SCVB Request for Additional Information L-2014-236 Page 2 of 2The additional information provided in the enclosure to this letter does not impact the nosignificant hazards determination and environmental considerations previously provided inReference 1.There are no new commitments made in this submission.
Very truly yours, Michael Kiley Vice President Turkey Point Nuclear Plant
If you have any questions or require additional information, please contact Mr. Robert Tomontoat 305-246-7327.
I declare under penalty of perjury that the foregoing is true and correct.Executed on: July 24, 2014.Very truly yours,Michael KileyVice President Turkey Point Nuclear Plant


==Enclosure:==
==Enclosure:==
Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limit cc:    USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant Ms. Cindy Becker, Florida Department of Health
Florida Power & Light Company                                              L-2014-236 Response to SCVB Request for Additional Information                          Enclosure Page 1 of 8 Response to Request for Additional Information from the Containment and Ventilation Branch Regarding Turkey Point Units 3 and 4 License Amendment Request No. 231 Application to Revise Ultimate Heat Sink Temperature Limit Enclosure
Florida Power & Light Company                                                            L-2014-236 Response to SCVB Request for Additional Information                                        Enclosure Page 2 of 8


Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limitcc: USNRC Regional Administrator, Region IIUSNRC Project Manager, Turkey Point Nuclear PlantUSNRC Senior Resident Inspector, Turkey Point Nuclear PlantMs. Cindy Becker, Florida Department of Health Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 1 of 8Response to Request for Additional Information from theContainment and Ventilation Branch Regarding Turkey Point Units 3 and 4License Amendment Request No. 231Application to Revise Ultimate Heat Sink Temperature LimitEnclosure Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 2 of 8Background By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &Light Company (FPL) submitted a license amendment request (LAR) for the Turkey PointNuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to theTurkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.SCVB RAI-1The LAR does not clearly describe changes in the current methodology for analyzing thecomponent cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In therevision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) datedApril 17, 2013, page 14.3.4-25, under the heading, "Noding Structure,"
===Background===
the last sentence states:"The recirculation system model uses GOTHIC component models for theresidual heat removal and component cooling water heat exchangers and pumps.Recirculation flow from the sump is modeled as a boundary condition.  
By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &
"Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,")
Light Company (FPL) submitted a license amendment request (LAR) for the Turkey Point Nuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to the Turkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."
states:"The calculation for CCW heat exchanger performance was revised using theHX3/HX4 computer program to demonstrate that the CCW heat exchangers canremove the necessary post-accident containment heat load for the LOCA andMSLB containment integrity analyses.  
The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.
"A. Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis?
SCVB RAI-1 The LAR does not clearly describe changes in the current methodology for analyzing the component cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In the revision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) dated April 17, 2013, page 14.3.4-25, under the heading, "Noding Structure," the last sentence states:
If so, please describe in detail how the HX3/HX4computer program replaces the GOTHIC modeling to determine the revised CCW supplytemperature to the ECCs and RHR HX, while considering the limiting values of all of thepost-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.
        "The recirculationsystem model uses GOTHIC component models for the residual heat removal and component cooling water heat exchangers andpumps.
FPL ResponseNo, the HX3/HX4 program does not replace the GOTHIC methodology to analyzecontainment for any over pressurization accident analysis (MSLB and LOCA). The Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 3 of 8GOTHIC containment model described in the UFSAR is one integrated model that includesthe component models for CCW pumps, CCW heat exchangers and RHR system.Furthermore, no inputs, assumptions, or changes of any kind are required or have beenmade to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature.
Recirculationflow from the sump is modeled as a boundary condition."
The current UFSAR methodology remains theGOTHIC analysis currently described in the UFSAR. All results (reported containment
Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,") states:
: pressure, CCW supply / return temperatures, CCW heat removal capability, andcontainment building sump temperatures) remain unchanged from the results currently described in the UFSAR.UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters,"
        "The calculationfor CCW heat exchangerperformance was revised using the HX3/HX4 computer program to demonstrate that the CCW heat exchangers can remove the necessarypost-accidentcontainment heat loadfor the LOCA and MSLB containment integrity analyses. "
currently states the intakecooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. TheCCW heat exchanger heat removal capability is defined by the combination of the ICWtemperature and the tube fouling factor (or tube resistance).
A.     Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis? If so, please describe in detail how the HX3/HX4 computer program replaces the GOTHIC modeling to determine the revised CCW supply temperature to the ECCs and RHR HX, while considering the limiting values of all of the post-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.
The input values contained inthe accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removalcapability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used aspart of the CCW heat exchanger surveillance and testing procedures to maintain thenecessary level of cleanliness (below the administrative limit) to satisfy the required heatremoval capability of the CCW heat exchangers.
FPL Response No, the HX3/HX4 program does not replace the GOTHIC methodology to analyze containment for any over pressurization accident analysis (MSLB and LOCA). The
As can be seen, this value for the tubefouling factor assumed in the accident analysis is higher than the tube fouling factorallowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance andmaintenance of the CCW heat exhangers assures that their heat removal capability remainsconservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.
 
Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tuberesistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and theanalyses performed for the RAI response.
Florida Power & Light Company                                                           L-2014-236 Response to SCVB Request for Additional Information                                       Enclosure Page 3 of 8 GOTHIC containment model described in the UFSAR is one integrated model that includes the component models for CCW pumps, CCW heat exchangers and RHR system.
Specifically, the original point labeled as safetyanalyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. Theassumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies inthe response to this RAI are also included.
Furthermore, no inputs, assumptions, or changes of any kind are required or have been made to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature. The current UFSAR methodology remains the GOTHIC analysis currently described in the UFSAR. All results (reported containment pressure, CCW supply / return temperatures, CCW heat removal capability, and containment building sump temperatures) remain unchanged from the results currently described in the UFSAR.
Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 4 of 8SCVB RAI-1 Figure 1Tube Resistance LimitsM.0050.0030.0020.0020.0010.002581100"F Umit0.002292104"F Umlt70 75 80 85 90 95 100 105 110ICW Temp (OF)B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF asinput, provide the CCW supply water temperature profiles to the ECCs and RHR HX forthe limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB)accident, and provide the CCW peak temperature values. The analysis should beperformed using the same inputs as in the current analysis, i.e., assuming the worst safetyrelated equipment heat loads, while using the proposed improved CCW HX tuberesistance.
UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," currently states the intake cooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. The CCW heat exchanger heat removal capability is defined by the combination of the ICW temperature and the tube fouling factor (or tube resistance). The input values contained in the accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030 hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removal capability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used as part of the CCW heat exchanger surveillance and testing procedures to maintain the necessary level of cleanliness (below the administrative limit) to satisfy the required heat removal capability of the CCW heat exchangers. As can be seen, this value for the tube fouling factor assumed in the accident analysis is higher than the tube foulingfactor allowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance and maintenance of the CCW heat exhangers assures that their heat removal capability remains conservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.
If any of the remaining inputs are revised, please justify.FPL ResponseTo provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with acorresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2 -F/BTU).The results presented below provide the results for the maximum CCW supplytemperature cases for LOCA (DEPS) and MSLB comparing the results from the current Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 5 of 8design basis (100°F UHS temperature with a 0.003 hr-ft2 -F/BTU tube resistance) to thesensitivity case (104'F UHS temperature with a 0.002714 hr-ft2-°F/BTU tube resistance).
Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tube resistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure 3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and the analyses performed for the RAI response. Specifically, the original point labeled as safety analyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. The assumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies in the response to this RAI are also included.
 
Florida Power & Light Company                                                            L-2014-236 Response to SCVB Request for Additional Information                                       Enclosure Page 4 of 8 SCVB RAI-1 Figure 1 Tube Resistance Limits M.005 0.003 0.002581          100"F Umit 0.002 0.002292          104"F Umlt 0.002 0.001 70        75   80           85     90       95       100       105       110 ICW Temp (OF)
B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF as input, provide the CCW supply water temperature profiles to the ECCs and RHR HX for the limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)
Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB) accident, and provide the CCW peak temperature values. The analysis should be performed using the same inputs as in the current analysis, i.e., assuming the worst safety related equipment heat loads, while using the proposed improved CCW HX tube resistance. If any of the remaining inputs are revised, please justify.
FPL Response To provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with a corresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2-F/BTU).
The results presented below provide the results for the maximum CCW supply temperature cases for LOCA (DEPS) and MSLB comparing the results from the current
 
Florida Power & Light Company                                                          L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 5 of 8 design basis (100°F UHS temperature with a 0.003 hr-ft2-F/BTU tube resistance) to the sensitivity case (104'F UHS temperature with a 0.002714 hr-ft2 -°F/BTU tube resistance).
No other inputs were changed other than UHS temperature and tube resistance.
No other inputs were changed other than UHS temperature and tube resistance.
The CCW temperature profile for the DEHL break is not provided since this is not thelimiting event for containment integrity and is analyzed only to the end of blowdown (25seconds) and poses no challenge to CCW heat removal capability.
The CCW temperature profile for the DEHL break is not provided since this is not the limiting event for containment integrity and is analyzed only to the end of blowdown (25 seconds) and poses no challenge to CCW heat removal capability. The conclusions from the results for the DEPS break discussed below are applicable to the DEHL.
The conclusions fromthe results for the DEPS break discussed below are applicable to the DEHL.LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC CaseSCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 1040F ICWtemperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.SCVB RAI-1 Figure 2CCW10OF ICW104F ICW170,, 160 ..............
LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC Case SCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.
16 --- iER 140 ..........
Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104 0F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.
130Supply Temperature 0 2000 4000 6000 8000Time (sec)10000 Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 6 of 8Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic modeladditional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.ICW Temperature  
SCVB RAI-1 Figure 2 CCW Supply Temperature 10OF  ICW 104F  ICW 170
(°F) 100 104Peak Containment Pressure (psig) 50.61 50.61Peak Containment Temperature  
    ,,   160 ..............
(°F) 275.8 275.8Peak Sump Temperature  
16     ----
(°F) 236.6 236.6Peak CCW supply Temperature  
50-i ER 140 ..........
(°F) 158.6 158.5As shown, there is no significant change in the peak values. Note, the inputs used for this caseensure CCW supply temperatures are maximized;  
130 0             2000         4000           6000           8000          10000 Time (sec)
: however, this will result in a lowercontainment pressure because more heat is removed from containment and transferred into theCCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limitingcontainment response licensing basis analysis.
 
MSLB Maximum CCW Supplv Temperature CaseSCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although thereare small temperature differences this temperature profile demonstrates the CCW heat removalperformance remains essentially the same at 104'F ICW temperatures when the tube resistance isreduced to 0.002714 hr-ft2-F/BTU.
Florida Power & Light Company                                                        L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 6 of 8 Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic model additional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.
Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 7 of 8SCVB RAI-1 Figure 3SLB: CCW100 degF ICW104 degF ICW1601,50-i-I140120 /.E .~/ -Supply Temperature Temperature Temperature 0 200 400 600Time (sec)For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in thetable below.ICW Temperature (OF) 100 104Peak Containment Pressure (psig) 53.14 53.16Peak Containment Temperature  
ICW Temperature (°F)                         100             104 Peak Containment Pressure (psig)           50.61           50.61 Peak Containment Temperature (°F)           275.8           275.8 Peak Sump Temperature (°F)                 236.6           236.6 Peak CCW supply Temperature (°F)           158.6           158.5 As shown, there is no significant change in the peak values. Note, the inputs used for this case ensure CCW supply temperatures are maximized; however, this will result in a lower containment pressure because more heat is removed from containment and transferred into the CCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limiting containment response licensing basis analysis.
(°F) 279.0 279.0Peak CCW supply Temperature  
MSLB Maximum CCW Supplv Temperature Case SCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104'F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2 -F/BTU.
(°F) 152.7 153.1Similarly, these results also demonstrate negligible changes between the reported results fromthe analysis of record.Conclusion Increasing the ICW temperature to 1040F while reducing the CCW heat exchanger fouling factorto 0.002714 hr-ft2-OF/BTU provides insignificant changes to the containment peak pressure and Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 8 of 8containment peak saturation temperatures.
 
The results have either the same or slight changes-some up, some down-from the previously reported results.
Florida Power & Light Company                                                        L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 7 of 8 SCVB RAI-1 Figure 3 SLB: CCW Supply Temperature 100 degF     ICW Temperature 104 degF     ICW Temperature 160 i-  1,50-I 140 120                  /.
These minor temperature changesprovide essentially no impact to the containment peak pressure and peak temperature response.
E         .~/     -
It is concluded that small temperature variations within the CCW supply water have aninsignificant impact on the containment response.
0           200         400           600 Time (sec)
The ICW temperature increase  
For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in the table below.
/ reducedfouling factor tradeoff results in CCW heat removal performance that is essentially the same,providing an acceptable response for the GOTHIC containment model. Therefore, the currentresults provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.SCVB RAI-2The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description ofAnalysis,"
ICW Temperature (OF)                     100           104 Peak Containment Pressure (psig)         53.14           53.16 Peak Containment Temperature (°F)       279.0           279.0 Peak CCW supply Temperature (°F)         152.7           153.1 Similarly, these results also demonstrate negligible changes between the reported results from the analysis of record.
states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment AnalysisParameters,"
Conclusion Increasing the ICW temperature to 104 0 F while reducing the CCW heat exchanger fouling factor to 0.002714 hr-ft2 -OF/BTU provides insignificant changes to the containment peak pressure and
provided the intake cooling water (ICW) temperature used for containment integrity as 1 00TF, which is proposed to be revised to 104'F as an input to the analysis.
 
TheTable does not explicitly state the assumed value of the CCW supply water temperature to theEECs and RHR HX in the GOTHIC analysis.
Florida Power & Light Company                                                           L-2014-236 Response to SCVB Request for Additional Information                                       Enclosure Page 8 of 8 containment peak saturation temperatures. The results have either the same or slight changes-some up, some down-from the previously reported results. These minor temperature changes provide essentially no impact to the containment peak pressure and peak temperature response.
Please confirm that based on the proposed ICW temperature of 104TF, and the revised worstvalue of the CCW supply water temperature (to be stated in response to this RAI) to RHR HXand ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.FPL ResponseAs stated in the response to SCVB RAI-1, these sensitivities validate that containment responsewould result in an insignificant change to the results presented in the UFSAR. The results of thesensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of0.002714 hr-ft2-F/BTU has an insignificant impact on the peak calculated containment  
It is concluded that small temperature variations within the CCW supply water have an insignificant impact on the containment response. The ICW temperature increase / reduced fouling factor tradeoff results in CCW heat removal performance that is essentially the same, providing an acceptable response for the GOTHIC containment model. Therefore, the current results provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.
: pressure, and containment temperature.
SCVB RAI-2 The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description of Analysis," states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," provided the intake cooling water (ICW) temperature used for containment integrity as 100TF, which is proposed to be revised to 104'F as an input to the analysis. The Table does not explicitly state the assumed value of the CCW supply water temperature to the EECs and RHR HX in the GOTHIC analysis.
Thus, CCW heat removal performance remains essentially thesame at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -°F/BTU. The current containment analyses for containment peak pressure, temperature and heatremoval are not affected and will remain as the licensing basis.
Please confirm that based on the proposed ICW temperature of 104TF, and the revised worst value of the CCW supply water temperature (to be stated in response to this RAI) to RHR HX and ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.
0FPL10 CFR 50.90L-2014-236 July 24, 2014U.S. Nuclear Regulatory Commission ATTN: Document Control DeskWashington, DC 20555-0001 Turkey Point Units 3 and 4Docket Nos. 50-250 and 50-251Renewed Facility Operating License Nos. DPR-31 and DPR-41
FPL Response As stated in the response to SCVB RAI-1, these sensitivities validate that containment response would result in an insignificant change to the results presented in the UFSAR. The results of the sensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of 0.002714 hr-ft2 - F/BTU has an insignificant impact on the peak calculated containment pressure, and containment temperature. Thus, CCW heat removal performance remains essentially the same at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -
°F/BTU. The current containment analyses for containment peak pressure, temperature and heat removal are not affected and will remain as the licensing basis.
 
NRC-014 Submitted Nov. 10, 2015 0      FPL 10 CFR 50.90 L-2014-236 July 24, 2014 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Renewed Facility Operating License Nos. DPR-31 and DPR-41


==Subject:==
==Subject:==
Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to Revise Ultimate Heat Sink Temperature Limit


Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to ReviseUltimate Heat Sink Temperature Limit
==References:==
: 1. Florida Power & Light Company Letter L-2014-216, "License Amendment Request No.
231, Application to Revise Technical Specifications to Revise Ultimate Heat Sink Temperature Limit," July 10, 2014.
: 2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.
231, Application to Revise Ultimate Heat Sink Temperature Limit - Request for Emergency Approval," July 17, 2014.
: 3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Request for Additional Information - LAR 231 (TAC MF4392 and MF4393)," July 22, 2014.
In Reference 1, Florida Power & Light Company (FPL) requested an amendment to the Technical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.
The proposed amendment would revise the ultimate heat sink (UHS) water temperature limit from I100 °F to 104'F.
In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. Nuclear Regulatory Commission (NRC) to review and approve it on an emergency basis.
In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.
00 Florida Power & Light Company 9760 SW  34 4th  St.. Florida City, FL 33035


==References:==
Florida Power & Light Company                                                         L-2014-236 License Amendment Request No. 231 Response to SCVB Request for Additional Information                                     Page 2 of 2 The additional information provided in the enclosure to this letter does not impact the no significant hazards determination and environmental considerations previously provided in Reference 1.
: 1. Florida Power  
There are no new commitments made in this submission.
& Light Company Letter L-2014-216, "License Amendment Request No.231, Application to Revise Technical Specifications to Revise Ultimate Heat SinkTemperature Limit," July 10, 2014.2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.231, Application to Revise Ultimate Heat Sink Temperature Limit -Request forEmergency Approval,"
If you have any questions or require additional information, please contact Mr. Robert Tomonto at 305-246-7327.
July 17, 2014.3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Requestfor Additional Information
I declare under penalty of perjury that the foregoing is true and correct.
-LAR 231 (TAC MF4392 and MF4393),"
Executed on: July 24, 2014.
July 22, 2014.In Reference 1, Florida Power & Light Company (FPL) requested an amendment to theTechnical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.The proposed amendment would revise the ultimate heat sink (UHS) water temperature limitfrom I100°F to 104'F.In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. NuclearRegulatory Commission (NRC) to review and approve it on an emergency basis.In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.Florida Power & Light Company 009760 SW 344th St.. Florida City, FL 33035 Florida Power & Light CompanyLicense Amendment Request No. 231Response to SCVB Request for Additional Information L-2014-236 Page 2 of 2The additional information provided in the enclosure to this letter does not impact the nosignificant hazards determination and environmental considerations previously provided inReference 1.There are no new commitments made in this submission.
Very truly yours, Michael Kiley Vice President Turkey Point Nuclear Plant
If you have any questions or require additional information, please contact Mr. Robert Tomontoat 305-246-7327.
I declare under penalty of perjury that the foregoing is true and correct.Executed on: July 24, 2014.Very truly yours,Michael KileyVice President Turkey Point Nuclear Plant


==Enclosure:==
==Enclosure:==
Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limit cc:    USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant Ms. Cindy Becker, Florida Department of Health
Florida Power & Light Company                                              L-2014-236 Response to SCVB Request for Additional Information                          Enclosure Page 1 of 8 Response to Request for Additional Information from the Containment and Ventilation Branch Regarding Turkey Point Units 3 and 4 License Amendment Request No. 231 Application to Revise Ultimate Heat Sink Temperature Limit Enclosure
Florida Power & Light Company                                                            L-2014-236 Response to SCVB Request for Additional Information                                        Enclosure Page 2 of 8
===Background===
By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &
Light Company (FPL) submitted a license amendment request (LAR) for the Turkey Point Nuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to the Turkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."
The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.
SCVB RAI-1 The LAR does not clearly describe changes in the current methodology for analyzing the component cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In the revision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) dated April 17, 2013, page 14.3.4-25, under the heading, "Noding Structure," the last sentence states:
        "The recirculationsystem model uses GOTHIC component models for the residual heat removal and component cooling water heat exchangers andpumps.
Recirculationflow from the sump is modeled as a boundary condition."
Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,") states:
        "The calculationfor CCW heat exchangerperformance was revised using the HX3/HX4 computer program to demonstrate that the CCW heat exchangers can remove the necessarypost-accidentcontainment heat loadfor the LOCA and MSLB containment integrity analyses. "
A.      Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis? If so, please describe in detail how the HX3/HX4 computer program replaces the GOTHIC modeling to determine the revised CCW supply temperature to the ECCs and RHR HX, while considering the limiting values of all of the post-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.
FPL Response No, the HX3/HX4 program does not replace the GOTHIC methodology to analyze containment for any over pressurization accident analysis (MSLB and LOCA). The
Florida Power & Light Company                                                            L-2014-236 Response to SCVB Request for Additional Information                                        Enclosure Page 3 of 8 GOTHIC containment model described in the UFSAR is one integrated model that includes the component models for CCW pumps, CCW heat exchangers and RHR system.
Furthermore, no inputs, assumptions, or changes of any kind are required or have been made to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature. The current UFSAR methodology remains the GOTHIC analysis currently described in the UFSAR. All results (reported containment pressure, CCW supply / return temperatures, CCW heat removal capability, and containment building sump temperatures) remain unchanged from the results currently described in the UFSAR.
UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," currently states the intake cooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. The CCW heat exchanger heat removal capability is defined by the combination of the ICW temperature and the tube fouling factor (or tube resistance). The input values contained in the accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030 hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removal capability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used as part of the CCW heat exchanger surveillance and testing procedures to maintain the necessary level of cleanliness (below the administrative limit) to satisfy the required heat removal capability of the CCW heat exchangers. As can be seen, this value for the tube fouling factor assumed in the accident analysis is higher than the tube foulingfactor allowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance and maintenance of the CCW heat exhangers assures that their heat removal capability remains conservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.
Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tube resistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure 3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and the analyses performed for the RAI response. Specifically, the original point labeled as safety analyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. The assumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies in the response to this RAI are also included.


Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limitcc: USNRC Regional Administrator, Region IIUSNRC Project Manager, Turkey Point Nuclear PlantUSNRC Senior Resident Inspector, Turkey Point Nuclear PlantMs. Cindy Becker, Florida Department of Health Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 1 of 8Response to Request for Additional Information from theContainment and Ventilation Branch Regarding Turkey Point Units 3 and 4License Amendment Request No. 231Application to Revise Ultimate Heat Sink Temperature LimitEnclosure Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 2 of 8Background By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &Light Company (FPL) submitted a license amendment request (LAR) for the Turkey PointNuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to theTurkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.SCVB RAI-1The LAR does not clearly describe changes in the current methodology for analyzing thecomponent cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In therevision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) datedApril 17, 2013, page 14.3.4-25, under the heading, "Noding Structure,"
Florida Power & Light Company                                                           L-2014-236 Response to SCVB Request for Additional Information                                       Enclosure Page 4 of 8 SCVB RAI-1 Figure 1 Tube Resistance Limits M.005 0.003 0.002581          100"F Umit 0.002 0.002292          104"F Umlt 0.002 0.001 70        75   80           85     90       95       100       105       110 ICW Temp (OF)
the last sentence states:"The recirculation system model uses GOTHIC component models for theresidual heat removal and component cooling water heat exchangers and pumps.Recirculation flow from the sump is modeled as a boundary condition.
B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF as input, provide the CCW supply water temperature profiles to the ECCs and RHR HX for the limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)
"Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,")
Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB) accident, and provide the CCW peak temperature values. The analysis should be performed using the same inputs as in the current analysis, i.e., assuming the worst safety related equipment heat loads, while using the proposed improved CCW HX tube resistance. If any of the remaining inputs are revised, please justify.
states:"The calculation for CCW heat exchanger performance was revised using theHX3/HX4 computer program to demonstrate that the CCW heat exchangers canremove the necessary post-accident containment heat load for the LOCA andMSLB containment integrity analyses.
FPL Response To provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with a corresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2-F/BTU).
"A. Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis?
The results presented below provide the results for the maximum CCW supply temperature cases for LOCA (DEPS) and MSLB comparing the results from the current
If so, please describe in detail how the HX3/HX4computer program replaces the GOTHIC modeling to determine the revised CCW supplytemperature to the ECCs and RHR HX, while considering the limiting values of all of thepost-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.
 
FPL ResponseNo, the HX3/HX4 program does not replace the GOTHIC methodology to analyzecontainment for any over pressurization accident analysis (MSLB and LOCA). The Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 3 of 8GOTHIC containment model described in the UFSAR is one integrated model that includesthe component models for CCW pumps, CCW heat exchangers and RHR system.Furthermore, no inputs, assumptions, or changes of any kind are required or have beenmade to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature.
Florida Power & Light Company                                                          L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 5 of 8 design basis (100°F UHS temperature with a 0.003 hr-ft2-F/BTU tube resistance) to the sensitivity case (104'F UHS temperature with a 0.002714 hr-ft2 -°F/BTU tube resistance).
The current UFSAR methodology remains theGOTHIC analysis currently described in the UFSAR. All results (reported containment
: pressure, CCW supply / return temperatures, CCW heat removal capability, andcontainment building sump temperatures) remain unchanged from the results currently described in the UFSAR.UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters,"
currently states the intakecooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. TheCCW heat exchanger heat removal capability is defined by the combination of the ICWtemperature and the tube fouling factor (or tube resistance).
The input values contained inthe accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removalcapability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used aspart of the CCW heat exchanger surveillance and testing procedures to maintain thenecessary level of cleanliness (below the administrative limit) to satisfy the required heatremoval capability of the CCW heat exchangers.
As can be seen, this value for the tubefouling factor assumed in the accident analysis is higher than the tube fouling factorallowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance andmaintenance of the CCW heat exhangers assures that their heat removal capability remainsconservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.
Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tuberesistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and theanalyses performed for the RAI response.
Specifically, the original point labeled as safetyanalyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. Theassumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies inthe response to this RAI are also included.
Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 4 of 8SCVB RAI-1 Figure 1Tube Resistance LimitsM.0050.0030.0020.0020.0010.002581100"F Umit0.002292104"F Umlt70 75 80 85 90 95 100 105 110ICW Temp (OF)B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF asinput, provide the CCW supply water temperature profiles to the ECCs and RHR HX forthe limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB)accident, and provide the CCW peak temperature values. The analysis should beperformed using the same inputs as in the current analysis, i.e., assuming the worst safetyrelated equipment heat loads, while using the proposed improved CCW HX tuberesistance.
If any of the remaining inputs are revised, please justify.FPL ResponseTo provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with acorresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2 -F/BTU).The results presented below provide the results for the maximum CCW supplytemperature cases for LOCA (DEPS) and MSLB comparing the results from the current Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 5 of 8design basis (100°F UHS temperature with a 0.003 hr-ft2 -F/BTU tube resistance) to thesensitivity case (104'F UHS temperature with a 0.002714 hr-ft2-°F/BTU tube resistance).
No other inputs were changed other than UHS temperature and tube resistance.
No other inputs were changed other than UHS temperature and tube resistance.
The CCW temperature profile for the DEHL break is not provided since this is not thelimiting event for containment integrity and is analyzed only to the end of blowdown (25seconds) and poses no challenge to CCW heat removal capability.
The CCW temperature profile for the DEHL break is not provided since this is not the limiting event for containment integrity and is analyzed only to the end of blowdown (25 seconds) and poses no challenge to CCW heat removal capability. The conclusions from the results for the DEPS break discussed below are applicable to the DEHL.
The conclusions fromthe results for the DEPS break discussed below are applicable to the DEHL.LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC CaseSCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 1040F ICWtemperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.SCVB RAI-1 Figure 2CCW10OF ICW104F ICW170,, 160 ..............
LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC Case SCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.
16 --- iER 140 ..........
Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104 0F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.
130Supply Temperature 0 2000 4000 6000 8000Time (sec)10000 Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 6 of 8Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic modeladditional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.ICW Temperature  
SCVB RAI-1 Figure 2 CCW Supply Temperature 10OF  ICW 104F  ICW 170
(°F) 100 104Peak Containment Pressure (psig) 50.61 50.61Peak Containment Temperature  
    ,,   160 ..............
(°F) 275.8 275.8Peak Sump Temperature  
16     ----
(°F) 236.6 236.6Peak CCW supply Temperature  
50-i ER 140 ..........
(°F) 158.6 158.5As shown, there is no significant change in the peak values. Note, the inputs used for this caseensure CCW supply temperatures are maximized;  
130 0             2000         4000           6000           8000          10000 Time (sec)
: however, this will result in a lowercontainment pressure because more heat is removed from containment and transferred into theCCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limitingcontainment response licensing basis analysis.
 
MSLB Maximum CCW Supplv Temperature CaseSCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although thereare small temperature differences this temperature profile demonstrates the CCW heat removalperformance remains essentially the same at 104'F ICW temperatures when the tube resistance isreduced to 0.002714 hr-ft2-F/BTU.
Florida Power & Light Company                                                        L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 6 of 8 Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic model additional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.
Florida Power & Light CompanyResponse to SCVB Request for Additional Information L-2014-236 Enclosure Page 7 of 8SCVB RAI-1 Figure 3SLB: CCW100 degF ICW104 degF ICW1601,50-i-I140120 /.E .~/ -Supply Temperature Temperature Temperature 0 200 400 600Time (sec)For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in thetable below.ICW Temperature (OF) 100 104Peak Containment Pressure (psig) 53.14 53.16Peak Containment Temperature  
ICW Temperature (°F)                         100             104 Peak Containment Pressure (psig)           50.61           50.61 Peak Containment Temperature (°F)           275.8           275.8 Peak Sump Temperature (°F)                 236.6           236.6 Peak CCW supply Temperature (°F)           158.6           158.5 As shown, there is no significant change in the peak values. Note, the inputs used for this case ensure CCW supply temperatures are maximized; however, this will result in a lower containment pressure because more heat is removed from containment and transferred into the CCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limiting containment response licensing basis analysis.
(°F) 279.0 279.0Peak CCW supply Temperature  
MSLB Maximum CCW Supplv Temperature Case SCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104'F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2 -F/BTU.
(°F) 152.7 153.1Similarly, these results also demonstrate negligible changes between the reported results fromthe analysis of record.Conclusion Increasing the ICW temperature to 1040F while reducing the CCW heat exchanger fouling factorto 0.002714 hr-ft2-OF/BTU provides insignificant changes to the containment peak pressure and Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 8 of 8containment peak saturation temperatures.
 
The results have either the same or slight changes-some up, some down-from the previously reported results.
Florida Power & Light Company                                                        L-2014-236 Response to SCVB Request for Additional Information                                     Enclosure Page 7 of 8 SCVB RAI-1 Figure 3 SLB: CCW Supply Temperature 100 degF     ICW Temperature 104 degF     ICW Temperature 160 i-  1,50-I 140 120                  /.
These minor temperature changesprovide essentially no impact to the containment peak pressure and peak temperature response.
E         .~/     -
It is concluded that small temperature variations within the CCW supply water have aninsignificant impact on the containment response.
0           200         400           600 Time (sec)
The ICW temperature increase  
For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in the table below.
/ reducedfouling factor tradeoff results in CCW heat removal performance that is essentially the same,providing an acceptable response for the GOTHIC containment model. Therefore, the currentresults provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.SCVB RAI-2The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description ofAnalysis,"
ICW Temperature (OF)                     100           104 Peak Containment Pressure (psig)         53.14           53.16 Peak Containment Temperature (°F)       279.0           279.0 Peak CCW supply Temperature (°F)         152.7           153.1 Similarly, these results also demonstrate negligible changes between the reported results from the analysis of record.
states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment AnalysisParameters,"
Conclusion Increasing the ICW temperature to 104 0 F while reducing the CCW heat exchanger fouling factor to 0.002714 hr-ft2 -OF/BTU provides insignificant changes to the containment peak pressure and
provided the intake cooling water (ICW) temperature used for containment integrity as 1 00TF, which is proposed to be revised to 104'F as an input to the analysis.
 
TheTable does not explicitly state the assumed value of the CCW supply water temperature to theEECs and RHR HX in the GOTHIC analysis.
Florida Power & Light Company                                                           L-2014-236 Response to SCVB Request for Additional Information                                       Enclosure Page 8 of 8 containment peak saturation temperatures. The results have either the same or slight changes-some up, some down-from the previously reported results. These minor temperature changes provide essentially no impact to the containment peak pressure and peak temperature response.
Please confirm that based on the proposed ICW temperature of 104TF, and the revised worstvalue of the CCW supply water temperature (to be stated in response to this RAI) to RHR HXand ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.FPL ResponseAs stated in the response to SCVB RAI-1, these sensitivities validate that containment responsewould result in an insignificant change to the results presented in the UFSAR. The results of thesensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of0.002714 hr-ft2-F/BTU has an insignificant impact on the peak calculated containment  
It is concluded that small temperature variations within the CCW supply water have an insignificant impact on the containment response. The ICW temperature increase / reduced fouling factor tradeoff results in CCW heat removal performance that is essentially the same, providing an acceptable response for the GOTHIC containment model. Therefore, the current results provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.
: pressure, and containment temperature.
SCVB RAI-2 The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description of Analysis," states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," provided the intake cooling water (ICW) temperature used for containment integrity as 100TF, which is proposed to be revised to 104'F as an input to the analysis. The Table does not explicitly state the assumed value of the CCW supply water temperature to the EECs and RHR HX in the GOTHIC analysis.
Thus, CCW heat removal performance remains essentially thesame at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -°F/BTU. The current containment analyses for containment peak pressure, temperature and heatremoval are not affected and will remain as the licensing basis.}}
Please confirm that based on the proposed ICW temperature of 104TF, and the revised worst value of the CCW supply water temperature (to be stated in response to this RAI) to RHR HX and ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.
FPL Response As stated in the response to SCVB RAI-1, these sensitivities validate that containment response would result in an insignificant change to the results presented in the UFSAR. The results of the sensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of 0.002714 hr-ft2 - F/BTU has an insignificant impact on the peak calculated containment pressure, and containment temperature. Thus, CCW heat removal performance remains essentially the same at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -
°F/BTU. The current containment analyses for containment peak pressure, temperature and heat removal are not affected and will remain as the licensing basis.}}

Latest revision as of 05:44, 31 October 2019

NRC-014 - Letter from Michael Kiley, Florida Power & Light, to N.R.C., Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231 (Application to Revise Ultimate Heat Sink
ML15314A492
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 07/24/2014
From:
NRC/OGC
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
50-250-LA, 50-251-LA, ASLBP 15-935-02-LA-BD01, RAS 28491
Download: ML15314A492 (10)


Text

NRC-014 Submitted Nov. 10, 2015 0 FPL 10 CFR 50.90 L-2014-236 July 24, 2014 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Renewed Facility Operating License Nos. DPR-31 and DPR-41

Subject:

Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to Revise Ultimate Heat Sink Temperature Limit

References:

1. Florida Power & Light Company Letter L-2014-216, "License Amendment Request No.

231, Application to Revise Technical Specifications to Revise Ultimate Heat Sink Temperature Limit," July 10, 2014.

2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.

231, Application to Revise Ultimate Heat Sink Temperature Limit - Request for Emergency Approval," July 17, 2014.

3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Request for Additional Information - LAR 231 (TAC MF4392 and MF4393)," July 22, 2014.

In Reference 1, Florida Power & Light Company (FPL) requested an amendment to the Technical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.

The proposed amendment would revise the ultimate heat sink (UHS) water temperature limit from I100 °F to 104'F.

In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. Nuclear Regulatory Commission (NRC) to review and approve it on an emergency basis.

In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.

00 Florida Power & Light Company 9760 SW 34 4th St.. Florida City, FL 33035

Florida Power & Light Company L-2014-236 License Amendment Request No. 231 Response to SCVB Request for Additional Information Page 2 of 2 The additional information provided in the enclosure to this letter does not impact the no significant hazards determination and environmental considerations previously provided in Reference 1.

There are no new commitments made in this submission.

If you have any questions or require additional information, please contact Mr. Robert Tomonto at 305-246-7327.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on: July 24, 2014.

Very truly yours, Michael Kiley Vice President Turkey Point Nuclear Plant

Enclosure:

Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limit cc: USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant Ms. Cindy Becker, Florida Department of Health

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 1 of 8 Response to Request for Additional Information from the Containment and Ventilation Branch Regarding Turkey Point Units 3 and 4 License Amendment Request No. 231 Application to Revise Ultimate Heat Sink Temperature Limit Enclosure

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 2 of 8

Background

By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &

Light Company (FPL) submitted a license amendment request (LAR) for the Turkey Point Nuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to the Turkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."

The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.

SCVB RAI-1 The LAR does not clearly describe changes in the current methodology for analyzing the component cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In the revision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) dated April 17, 2013, page 14.3.4-25, under the heading, "Noding Structure," the last sentence states:

"The recirculationsystem model uses GOTHIC component models for the residual heat removal and component cooling water heat exchangers andpumps.

Recirculationflow from the sump is modeled as a boundary condition."

Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,") states:

"The calculationfor CCW heat exchangerperformance was revised using the HX3/HX4 computer program to demonstrate that the CCW heat exchangers can remove the necessarypost-accidentcontainment heat loadfor the LOCA and MSLB containment integrity analyses. "

A. Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis? If so, please describe in detail how the HX3/HX4 computer program replaces the GOTHIC modeling to determine the revised CCW supply temperature to the ECCs and RHR HX, while considering the limiting values of all of the post-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.

FPL Response No, the HX3/HX4 program does not replace the GOTHIC methodology to analyze containment for any over pressurization accident analysis (MSLB and LOCA). The

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 3 of 8 GOTHIC containment model described in the UFSAR is one integrated model that includes the component models for CCW pumps, CCW heat exchangers and RHR system.

Furthermore, no inputs, assumptions, or changes of any kind are required or have been made to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature. The current UFSAR methodology remains the GOTHIC analysis currently described in the UFSAR. All results (reported containment pressure, CCW supply / return temperatures, CCW heat removal capability, and containment building sump temperatures) remain unchanged from the results currently described in the UFSAR.

UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," currently states the intake cooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. The CCW heat exchanger heat removal capability is defined by the combination of the ICW temperature and the tube fouling factor (or tube resistance). The input values contained in the accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030 hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removal capability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used as part of the CCW heat exchanger surveillance and testing procedures to maintain the necessary level of cleanliness (below the administrative limit) to satisfy the required heat removal capability of the CCW heat exchangers. As can be seen, this value for the tube fouling factor assumed in the accident analysis is higher than the tube foulingfactor allowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance and maintenance of the CCW heat exhangers assures that their heat removal capability remains conservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.

Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tube resistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure 3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and the analyses performed for the RAI response. Specifically, the original point labeled as safety analyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. The assumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies in the response to this RAI are also included.

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 4 of 8 SCVB RAI-1 Figure 1 Tube Resistance Limits M.005 0.003 0.002581 100"F Umit 0.002 0.002292 104"F Umlt 0.002 0.001 70 75 80 85 90 95 100 105 110 ICW Temp (OF)

B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF as input, provide the CCW supply water temperature profiles to the ECCs and RHR HX for the limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)

Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB) accident, and provide the CCW peak temperature values. The analysis should be performed using the same inputs as in the current analysis, i.e., assuming the worst safety related equipment heat loads, while using the proposed improved CCW HX tube resistance. If any of the remaining inputs are revised, please justify.

FPL Response To provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with a corresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2-F/BTU).

The results presented below provide the results for the maximum CCW supply temperature cases for LOCA (DEPS) and MSLB comparing the results from the current

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 5 of 8 design basis (100°F UHS temperature with a 0.003 hr-ft2-F/BTU tube resistance) to the sensitivity case (104'F UHS temperature with a 0.002714 hr-ft2 -°F/BTU tube resistance).

No other inputs were changed other than UHS temperature and tube resistance.

The CCW temperature profile for the DEHL break is not provided since this is not the limiting event for containment integrity and is analyzed only to the end of blowdown (25 seconds) and poses no challenge to CCW heat removal capability. The conclusions from the results for the DEPS break discussed below are applicable to the DEHL.

LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC Case SCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.

Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104 0F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.

SCVB RAI-1 Figure 2 CCW Supply Temperature 10OF ICW 104F ICW 170

,, 160 ..............

16 ----

50-i ER 140 ..........

130 0 2000 4000 6000 8000 10000 Time (sec)

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 6 of 8 Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic model additional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.

ICW Temperature (°F) 100 104 Peak Containment Pressure (psig) 50.61 50.61 Peak Containment Temperature (°F) 275.8 275.8 Peak Sump Temperature (°F) 236.6 236.6 Peak CCW supply Temperature (°F) 158.6 158.5 As shown, there is no significant change in the peak values. Note, the inputs used for this case ensure CCW supply temperatures are maximized; however, this will result in a lower containment pressure because more heat is removed from containment and transferred into the CCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limiting containment response licensing basis analysis.

MSLB Maximum CCW Supplv Temperature Case SCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104'F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2 -F/BTU.

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 7 of 8 SCVB RAI-1 Figure 3 SLB: CCW Supply Temperature 100 degF ICW Temperature 104 degF ICW Temperature 160 i- 1,50-I 140 120 /.

E .~/ -

0 200 400 600 Time (sec)

For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in the table below.

ICW Temperature (OF) 100 104 Peak Containment Pressure (psig) 53.14 53.16 Peak Containment Temperature (°F) 279.0 279.0 Peak CCW supply Temperature (°F) 152.7 153.1 Similarly, these results also demonstrate negligible changes between the reported results from the analysis of record.

Conclusion Increasing the ICW temperature to 104 0 F while reducing the CCW heat exchanger fouling factor to 0.002714 hr-ft2 -OF/BTU provides insignificant changes to the containment peak pressure and

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 8 of 8 containment peak saturation temperatures. The results have either the same or slight changes-some up, some down-from the previously reported results. These minor temperature changes provide essentially no impact to the containment peak pressure and peak temperature response.

It is concluded that small temperature variations within the CCW supply water have an insignificant impact on the containment response. The ICW temperature increase / reduced fouling factor tradeoff results in CCW heat removal performance that is essentially the same, providing an acceptable response for the GOTHIC containment model. Therefore, the current results provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.

SCVB RAI-2 The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description of Analysis," states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," provided the intake cooling water (ICW) temperature used for containment integrity as 100TF, which is proposed to be revised to 104'F as an input to the analysis. The Table does not explicitly state the assumed value of the CCW supply water temperature to the EECs and RHR HX in the GOTHIC analysis.

Please confirm that based on the proposed ICW temperature of 104TF, and the revised worst value of the CCW supply water temperature (to be stated in response to this RAI) to RHR HX and ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.

FPL Response As stated in the response to SCVB RAI-1, these sensitivities validate that containment response would result in an insignificant change to the results presented in the UFSAR. The results of the sensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of 0.002714 hr-ft2 - F/BTU has an insignificant impact on the peak calculated containment pressure, and containment temperature. Thus, CCW heat removal performance remains essentially the same at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -

°F/BTU. The current containment analyses for containment peak pressure, temperature and heat removal are not affected and will remain as the licensing basis.

NRC-014 Submitted Nov. 10, 2015 0 FPL 10 CFR 50.90 L-2014-236 July 24, 2014 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Renewed Facility Operating License Nos. DPR-31 and DPR-41

Subject:

Response to Containment and Ventilation Branch Request for Additional Information, Regarding License Amendment Request No. 231, Application to Revise Ultimate Heat Sink Temperature Limit

References:

1. Florida Power & Light Company Letter L-2014-216, "License Amendment Request No.

231, Application to Revise Technical Specifications to Revise Ultimate Heat Sink Temperature Limit," July 10, 2014.

2. Florida Power & Light Company Letter L-2014-226, "License Amendment Request No.

231, Application to Revise Ultimate Heat Sink Temperature Limit - Request for Emergency Approval," July 17, 2014.

3. Email from A. Klett (NRC) to R. Tomonto, et al. (FPL), "Turkey Point 3 and 4 Request for Additional Information - LAR 231 (TAC MF4392 and MF4393)," July 22, 2014.

In Reference 1, Florida Power & Light Company (FPL) requested an amendment to the Technical Specifications (TS) for the Turkey Point Nuclear Plant (Turkey Point), Units 3 and 4.

The proposed amendment would revise the ultimate heat sink (UHS) water temperature limit from I100 °F to 104'F.

In Reference 2, FPL supplemented the July 10, 2014 application requesting the U.S. Nuclear Regulatory Commission (NRC) to review and approve it on an emergency basis.

In Reference 3, the NRC Containment and Ventilation Branch (SCVB) staff requested additional information (RAI). The enclosure to this letter provides the FPL response to the RAI.

00 Florida Power & Light Company 9760 SW 34 4th St.. Florida City, FL 33035

Florida Power & Light Company L-2014-236 License Amendment Request No. 231 Response to SCVB Request for Additional Information Page 2 of 2 The additional information provided in the enclosure to this letter does not impact the no significant hazards determination and environmental considerations previously provided in Reference 1.

There are no new commitments made in this submission.

If you have any questions or require additional information, please contact Mr. Robert Tomonto at 305-246-7327.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on: July 24, 2014.

Very truly yours, Michael Kiley Vice President Turkey Point Nuclear Plant

Enclosure:

Response to Request for Additional Information Regarding LAR No. 231, Application to Revise Ultimate Heat Sink Temperature Limit cc: USNRC Regional Administrator, Region II USNRC Project Manager, Turkey Point Nuclear Plant USNRC Senior Resident Inspector, Turkey Point Nuclear Plant Ms. Cindy Becker, Florida Department of Health

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 1 of 8 Response to Request for Additional Information from the Containment and Ventilation Branch Regarding Turkey Point Units 3 and 4 License Amendment Request No. 231 Application to Revise Ultimate Heat Sink Temperature Limit Enclosure

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 2 of 8

Background

By letter dated July 10, 2014, as supplemented by letter dated July 17, 2014, Florida Power &

Light Company (FPL) submitted a license amendment request (LAR) for the Turkey Point Nuclear Generating Station Unit Nos. 3 and 4 (Turkey Point). FPL requested revisions to the Turkey Point Technical Specifications (TS), Section 3/4.7.4, "Ultimate Heat Sink."

The U.S. Nuclear Regulatory Commission's (NRC) Containment and Ventilation Branch (SCVB) staff reviewed the information provided and determined that additional information is needed to complete the review. The NRC staff request for additional information (RAI) and the FPL response follows.

SCVB RAI-1 The LAR does not clearly describe changes in the current methodology for analyzing the component cooling water (CCW) supply cooling water temperature to the emergency containment coolers (ECCs) and residual heat removal (RHR) heat exchanger (HX). In the revision of the Turkey Point Updated Final Safety Analysis Report (UFSAR) dated April 17, 2013, page 14.3.4-25, under the heading, "Noding Structure," the last sentence states:

"The recirculationsystem model uses GOTHIC component models for the residual heat removal and component cooling water heat exchangers andpumps.

Recirculationflow from the sump is modeled as a boundary condition."

Page 13 of 17 of the LAR enclosure (under the heading, "Safety Analysis Scenarios,") states:

"The calculationfor CCW heat exchangerperformance was revised using the HX3/HX4 computer program to demonstrate that the CCW heat exchangers can remove the necessarypost-accidentcontainment heat loadfor the LOCA and MSLB containment integrity analyses. "

A. Does the HX3/HX4 computer program replace the currently used GOTHIC methodology in the current licensing basis analysis? If so, please describe in detail how the HX3/HX4 computer program replaces the GOTHIC modeling to determine the revised CCW supply temperature to the ECCs and RHR HX, while considering the limiting values of all of the post-accident CCW HX heat loads. Please include the analysis inputs and assumptions used in the revised method justifying their conservatisms.

FPL Response No, the HX3/HX4 program does not replace the GOTHIC methodology to analyze containment for any over pressurization accident analysis (MSLB and LOCA). The

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 3 of 8 GOTHIC containment model described in the UFSAR is one integrated model that includes the component models for CCW pumps, CCW heat exchangers and RHR system.

Furthermore, no inputs, assumptions, or changes of any kind are required or have been made to the containment analysis as the result of the proposed increase to the allowable ultimate heat sink (UHS) temperature. The current UFSAR methodology remains the GOTHIC analysis currently described in the UFSAR. All results (reported containment pressure, CCW supply / return temperatures, CCW heat removal capability, and containment building sump temperatures) remain unchanged from the results currently described in the UFSAR.

UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," currently states the intake cooling water (ICW) (UHS) temperature used for containment integrity is 1 00'F. The CCW heat exchanger heat removal capability is defined by the combination of the ICW temperature and the tube fouling factor (or tube resistance). The input values contained in the accident analysis calculations are I 00°F ICW temperature and a corresponding 0.0030 hr-ft2Z-OF/BTU CCW heat exchanger fouling factor. The same heat exchanger heat removal capability assumed in the accident analysis can be assured with a higher ICW temperature by maintaining a lower tube fouling factor. The HX3/HX4 computer program is used as part of the CCW heat exchanger surveillance and testing procedures to maintain the necessary level of cleanliness (below the administrative limit) to satisfy the required heat removal capability of the CCW heat exchangers. As can be seen, this value for the tube fouling factor assumed in the accident analysis is higher than the tube foulingfactor allowed by the "HX3/HX4 Program Line" shown in the application (FPL letter L-2014-216) Figure 3.5-1 (included below as SCVB RAI-1 Figure 1). The surveillance and maintenance of the CCW heat exhangers assures that their heat removal capability remains conservatively bounding of that assumed in the safety analysis over a range of allowable UHS temperatures and associated tube resistance.

Figure 3.5-1 in the July 10, 2014 FPL application has a typographical error for the tube resistance at I 00°F on the HX3/HX4 program line. SCVB RAI- 1 Figure 1 replaces Figure 3.5-1. Additionally, the figure has been updated to provide additional clarifying information to assist the NRC staff in understanding the current analyses of record and the analyses performed for the RAI response. Specifically, the original point labeled as safety analyses is clarified to reflect that it is the AFT Fathom thermal-hydraulic model. The assumptions used in the GOTHIC analysis of record and the GOTHIC sensitivity studies in the response to this RAI are also included.

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 4 of 8 SCVB RAI-1 Figure 1 Tube Resistance Limits M.005 0.003 0.002581 100"F Umit 0.002 0.002292 104"F Umlt 0.002 0.001 70 75 80 85 90 95 100 105 110 ICW Temp (OF)

B. Using the current GOTHIC model and the proposed ICW water temperature of 104TF as input, provide the CCW supply water temperature profiles to the ECCs and RHR HX for the limiting Double-Ended Pump Suction (DEPS) and Double-Ended Hot Leg (DEHL)

Break Loss-of-Coolant Accidents (LOCAs) and Main Steam Line Break (MSLB) accident, and provide the CCW peak temperature values. The analysis should be performed using the same inputs as in the current analysis, i.e., assuming the worst safety related equipment heat loads, while using the proposed improved CCW HX tube resistance. If any of the remaining inputs are revised, please justify.

FPL Response To provide additional assurance that the accident analysis is not affected, two sensitivity cases were run to demonstrate the impact of a UHS temperature increase with a corresponding reduction in heat exchanger tube resistance (0.002714 hr-ft2-F/BTU).

The results presented below provide the results for the maximum CCW supply temperature cases for LOCA (DEPS) and MSLB comparing the results from the current

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 5 of 8 design basis (100°F UHS temperature with a 0.003 hr-ft2-F/BTU tube resistance) to the sensitivity case (104'F UHS temperature with a 0.002714 hr-ft2 -°F/BTU tube resistance).

No other inputs were changed other than UHS temperature and tube resistance.

The CCW temperature profile for the DEHL break is not provided since this is not the limiting event for containment integrity and is analyzed only to the end of blowdown (25 seconds) and poses no challenge to CCW heat removal capability. The conclusions from the results for the DEPS break discussed below are applicable to the DEHL.

LOCA (DEPS) CCW Maximum Supply Temperature GOTHIC Case SCVB RAI- 1 Figure 2 presents the CCW supply temperature profile for LOCA.

Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104 0F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2-°F/BTU.

SCVB RAI-1 Figure 2 CCW Supply Temperature 10OF ICW 104F ICW 170

,, 160 ..............

16 ----

50-i ER 140 ..........

130 0 2000 4000 6000 8000 10000 Time (sec)

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 6 of 8 Additionally, since the licensing basis GOTHIC model is an integrated thermal hydraulic model additional containment parameters are available from this sensitivity case run. Peak containment pressure and temperature results are included with the peak CCW temperature in the table below.

ICW Temperature (°F) 100 104 Peak Containment Pressure (psig) 50.61 50.61 Peak Containment Temperature (°F) 275.8 275.8 Peak Sump Temperature (°F) 236.6 236.6 Peak CCW supply Temperature (°F) 158.6 158.5 As shown, there is no significant change in the peak values. Note, the inputs used for this case ensure CCW supply temperatures are maximized; however, this will result in a lower containment pressure because more heat is removed from containment and transferred into the CCW system. Nevertheless, a similar insignificant impact is expected for the UFSAR limiting containment response licensing basis analysis.

MSLB Maximum CCW Supplv Temperature Case SCVB RAI-1 Figure 3 presents the CCW supply temperature profile for MSLB. Although there are small temperature differences this temperature profile demonstrates the CCW heat removal performance remains essentially the same at 104'F ICW temperatures when the tube resistance is reduced to 0.002714 hr-ft2 -F/BTU.

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 7 of 8 SCVB RAI-1 Figure 3 SLB: CCW Supply Temperature 100 degF ICW Temperature 104 degF ICW Temperature 160 i- 1,50-I 140 120 /.

E .~/ -

0 200 400 600 Time (sec)

For consistency we are also providing the respective peak containment pressure and temperature results corresponding to this case. They are included with the peak CCW temperature in the table below.

ICW Temperature (OF) 100 104 Peak Containment Pressure (psig) 53.14 53.16 Peak Containment Temperature (°F) 279.0 279.0 Peak CCW supply Temperature (°F) 152.7 153.1 Similarly, these results also demonstrate negligible changes between the reported results from the analysis of record.

Conclusion Increasing the ICW temperature to 104 0 F while reducing the CCW heat exchanger fouling factor to 0.002714 hr-ft2 -OF/BTU provides insignificant changes to the containment peak pressure and

Florida Power & Light Company L-2014-236 Response to SCVB Request for Additional Information Enclosure Page 8 of 8 containment peak saturation temperatures. The results have either the same or slight changes-some up, some down-from the previously reported results. These minor temperature changes provide essentially no impact to the containment peak pressure and peak temperature response.

It is concluded that small temperature variations within the CCW supply water have an insignificant impact on the containment response. The ICW temperature increase / reduced fouling factor tradeoff results in CCW heat removal performance that is essentially the same, providing an acceptable response for the GOTHIC containment model. Therefore, the current results provided in the UFSAR remain valid for the increase in ICW temperature to 104'F.

SCVB RAI-2 The Turkey Point UFSAR Revision dated April 17, 2013, Sectionl4.3.4.3.3, "Description of Analysis," states that the containment response for a LOCA or MSLB accident is performed using GOTHIC computer code. The UFSAR Table 14.3.4.3-1, "Containment Analysis Parameters," provided the intake cooling water (ICW) temperature used for containment integrity as 100TF, which is proposed to be revised to 104'F as an input to the analysis. The Table does not explicitly state the assumed value of the CCW supply water temperature to the EECs and RHR HX in the GOTHIC analysis.

Please confirm that based on the proposed ICW temperature of 104TF, and the revised worst value of the CCW supply water temperature (to be stated in response to this RAI) to RHR HX and ECCs, all current containment analyses for containment peak pressure and temperature response and for containment heat removal are not affected and will remain as the licensing basis.

FPL Response As stated in the response to SCVB RAI-1, these sensitivities validate that containment response would result in an insignificant change to the results presented in the UFSAR. The results of the sensitivity analysis show that the use of 104'F ICW temperature with a reduced fouling factor of 0.002714 hr-ft2 - F/BTU has an insignificant impact on the peak calculated containment pressure, and containment temperature. Thus, CCW heat removal performance remains essentially the same at the 104°F ICW temperature when the fouling factor is reduced to 0.002714 hr-ft -

°F/BTU. The current containment analyses for containment peak pressure, temperature and heat removal are not affected and will remain as the licensing basis.