{{#Wiki_filter:TABLE 1 AFFECTED TECHNICAL SPECIFCATIONS This Table contains the Conditions within the scope of TSTF-505, Revision 2. These Conditions are eligible for inclusion in the Risk Informed Completion Time Program.
NOTE: The Action Numbers are in reference to Revision 3 of the STS NUREGs Action Number                      TS Title                Applicable NUREG                            Action Description 1.3                  Completion Times                        NUREG(s)- 1430 Only 5.5.18                Risk Informed Completion Time Program  NUREG(s)- 1430 Only Action 3.3.1.B.1      RPS Instrumentation                    NUREG(s)- 1430 Only Two channels inoperable.
One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.A.2    EFIC System Instrumentation            NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with one channel inoperable.
One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.B.2    EFIC System Instrumentation            NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with two channels inoperable.
One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.B.3    EFIC System Instrumentation            NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with two channels inoperable.
Action 3.3.11.C      EFIC System Instrumentation            NUREG(s)- 1430 Only One EFW Vector Valve Control channel inoperable.
One or more EFIC Function(s) with one or both manual initiation switches Action 3.3.12.A      EFIC Manual Initiation                  NUREG(s)- 1430 Only inoperable in one actuation channel.
One or more channel A(B) Functions inoperable with all channel B(A)
Action 3.3.13.A      EFIC Logic                              NUREG(s)- 1430 Only Functions OPERABLE.
Action 3.3.14.A      EFIC-EFW- Vector Valve Logic            NUREG(s)- 1430 Only One vector valve logic channel inoperable.
Action 3.3.5.A        ESFAS Instrumentation                  NUREG(s)- 1430 Only One or more paramters with one channel inoperable.
Action 3.3.6.A        ESFAS Manual Initiation                NUREG(s)- 1430 Only One or more ESFAS Functions with one channel inoperable.
Action 3.3.8.A        EDG LOPS                                NUREG(s)- 1430 Only One or more Functions with one channel per EDG inoperable.
Action 3.4.5.A        RCS Loops - MODE 3                      NUREG(s)- 1430 Only One RCS loop inoperable.
Action 3.5.2.A        ECCS - Operating                        NUREG(s)- 1430 Only One LPCI subsystem inoperable.
One or more penetration flow paths with one containment isolation valve Action 3.6.3.A        Containment Isolation Valves            NUREG(s)- 1430 Only inoperable (for paths with two or more isolation valves).
One or more penetration flow paths with one containment isolation valve Action 3.6.3.C        Containment Isolation Valves            NUREG(s)- 1430 Only inoperable (for paths with one isolation valve and a closed system).
Action 3.7.4.A        AVVs                                    NUREG(s)- 1430 Only One required AVV [line] inoperable.
One steam supply to turbine driven EFW pump inoperable or one turbine Action 3.7.5.A        EFW System                              NUREG(s)- 1430 Only driven EFW pump inoperable in Mode 3 following Refueling.
One EFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B        EFW System                              NUREG(s)- 1430 Only 2, or 3.
Enclosure 2
 
2 of 9 Action Number                  TS Title            Applicable NUREG                                Action Description Action 3.7.7.A  CCW System                            NUREG(s)- 1430 Only  One CCW train inoperable.
Action 3.7.8.A  SWS System                            NUREG(s)- 1430 Only  One SWS train inoperable.
Action 3.7.9.A  UHS                                  NUREG(s)- 1430 Only  [One or more cooling towers with one cooling tower fan inoperable.]
Action 3.8.1.A.3 AC Sources - Operating                NUREG(s)- 1430 Only  One [required] offsite circuit inoperable.
Action 3.8.1.B.4 AC Sources - Operating                NUREG(s)- 1430 Only  One [required] DG inoperable.
Action 3.8.1.C.2 AC Sources - Operating                NUREG(s)- 1430 Only  Two [required] offsite circuits inoperable.
Action 3.8.1.D  AC Sources - Operating                NUREG(s)- 1430 Only  One [required] offsite circuit inoperable and one [required] DG inoperable.
Action 3.8.1.F  AC Sources - Operating                NUREG(s)- 1430 Only  One [required][automatic loac sequencer] inoperable.
Action 3.8.4.A.3 DC Sources - Operating                NUREG(s)- 1430 Only  One [or two] battery charger[s on one train] inoperable.
Action 3.8.4.B  DC Sources - Operating                NUREG(s)- 1430 Only  One [or two] batter[y][ies on one train] inoperable.
One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C  DC Sources - Operating                NUREG(s)- 1430 Only  Condition A [or B].
Action 3.8.7.A  Inverters - Operating                NUREG(s)- 1430 Only  One [required] inverter inoperable.
Action 3.8.9.A  Distribution Systems - Operating      NUREG(s)- 1430 Only  One or more AC electrical power distribution subsystems inoperable.
Action 3.8.9.B  Distribution Systems - Operating      NUREG(s)- 1430 Only  One or more AC vital buses inoperable.
Action 3.8.9.C  Distribution Systems - Operating      NUREG(s)- 1430 Only  One or more DC electrical power distribution subsystems inoperable.
1.3              Completion Times                      NUREG(s)- 1431 Only 5.5.18          Risk Informed Completion Time Program NUREG(s)- 1431 Only Action 3.3.1.B  RTS Instrumentation                  NUREG(s)- 1431 Only  One Manual Reactor Trip channel Inoperable Action 3.3.1.C  RTS Instrumentation                  NUREG(s)- 1431 Only  One channel or train inoperable Action 3.3.1.E  RTS Instrumentation                  NUREG(s)- 1431 Only  One channel inoperable.
Action 3.3.1.J  RTS Instrumentation                  NUREG(s)- 1431 Only  One Source Range Neutron Flux channel inoperable.
Action 3.3.1.K  RTS Instrumentation                  NUREG(s)- 1431 Only  One channel inoperable.
Action 3.3.1.N  RTS Instrumentation                  NUREG(s)- 1431 Only  One Turbine Trip channel inoperable.
Action 3.3.1.O  RTS Instrumentation                  NUREG(s)- 1431 Only  One train inoperable.
Action 3.3.1.Q  RTS Instrumentation                  NUREG(s)- 1431 Only  One or more channels inoperable.
Action 3.3.1.S  RTS Instrumentation                  NUREG(s)- 1431 Only  One trip mechanism inoperable for one RTB.
Action 3.3.2.B  ESFAS Instrumentation                NUREG(s)- 1431 Only  One channel or train inoperable Action 3.3.2.C  ESFAS Instrumentation                NUREG(s)- 1431 Only  One train inoperable.
Action 3.3.2.D  ESFAS Instrumentation                NUREG(s)- 1431 Only  One channel inoperable.
Action 3.3.2.E  ESFAS Instrumentation                NUREG(s)- 1431 Only  One Containment Pressure channel inoperable.
Action 3.3.2.F  ESFAS Instrumentation                NUREG(s)- 1431 Only  One channel or train inoperable.
Action 3.3.2.G  ESFAS Instrumentation                NUREG(s)- 1431 Only  One train inoperable.
 
3 of 9 Action Number                    TS Title                Applicable NUREG                                Action Description Action 3.3.2.H    ESFAS Instrumentation                      NUREG(s)- 1431 Only  One train inoperable.
Action 3.3.2.I    ESFAS Instrumentation                      NUREG(s)- 1431 Only  One channel inoperable.
Action 3.3.2.J    ESFAS Instrumentation                      NUREG(s)- 1431 Only  One Main Feedwater Pumps trip channel inoperable.
Action 3.3.2.L    ESFAS Instrumentation                      NUREG(s)- 1431 Only  One or more channels inoperable.
Action 3.3.5.A    LOP DG Start Instrumentation              NUREG(s)- 1431 Only  One or more Functions with one channel per bus inoperable.
Action 3.4.11.B.3 Pressurizer PORVs                          NUREG(s)- 1431 Only  One [or two] PORV[s] inoperable an not capable of being manually cycled Action 3.4.11.C.2 Pressurizer PORVs                          NUREG(s)- 1431 Only  One [or two] block valves(s) inoperable.
Action 3.4.5.A    RCS Loops - MODE 3                        NUREG(s)- 1431 Only  One required RCS loop inoperable.
[One required RCS loop not in operation with Rod control System capable Action 3.4.5.C    RCS Loops - MODE 3                        NUREG(s)- 1431 Only  of rod withdrawal.]
Action 3.6.10.A  HIS (Ice Condenser)                        NUREG(s)- 1431 Only  One HIS train inoperable.
Action 3.6.10.B  HIS (Ice Condenser)                        NUREG(s)- 1431 Only  One containment region with no OPERABLE hydrogen ignitor.
Action 3.6.14.A  ARS (Ice Condenser)                        NUREG(s)- 1431 Only  One ARS train inoperalbe.
One or more ice condenser doors inoperable for reasons other than Action 3.6.16.B.2 Ice Condenser Doors (Ice Condenser)        NUREG(s)- 1431 Only  condition A or not closed.
Action 3.6.17.A  Divider Barrier Integrity (Ice Condenser)  NUREG(s)- 1431 Only Containment Isolation Valves (Atmospheric,                      One or more penetration flow paths with one containment isolation valve Action 3.6.3.A    Subatmospheric, Ice Condenser, and Dual)  NUREG(s)- 1431 Only  inoperable (for paths with two or more isolation valves).
Containment Isolation Valves (Atmospheric,                      One or more penetration flow paths with one containment isolation valve Action 3.6.3.C    Subatmospheric, Ice Condenser, and Dual)  NUREG(s)- 1431 Only  inoperable (for paths with one isolation valve and a closed system).
Action 3.7.4.A    ADVs                                      NUREG(s)- 1431 Only  One required ADV line inoperable.
One steam supply to turbine driven AFW pump inoperable or one turbine Action 3.7.5.A    AFW System                                NUREG(s)- 1431 Only  driven AFW pump inoperable in Mode 3 following Refueling.
One AFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B    AFW System                                NUREG(s)- 1431 Only  2, or 3.
Action 3.7.7.A    CCW System                                NUREG(s)- 1431 Only  One CCW train inoperable.
Action 3.7.8.A    SWS                                        NUREG(s)- 1431 Only  One SWS train inoperable.
Action 3.7.9.A    UHS                                        NUREG(s)- 1431 Only  [One or more cooling towers with one cooling tower fan inoperable.]
Action 3.8.1.A.3  AC Sources - Operating                    NUREG(s)- 1431 Only  One [required] offsite circuit inoperable.
Action 3.8.1.B.4  AC Sources - Operating                    NUREG(s)- 1431 Only  One [required] DG inoperable.
Action 3.8.1.C.2  AC Sources - Operating                    NUREG(s)- 1431 Only  Two [required] offsite circuits inoperable.
Action 3.8.1.D    AC Sources - Operating                    NUREG(s)- 1431 Only  One [required] offsite circuit inoperable and one [required] DG inoperable.
Action 3.8.1.F    AC Sources - Operating                    NUREG(s)- 1431 Only  One [required][automatic loac sequencer] inoperable.
Action 3.8.4.A.3  DC Sources - Operating                    NUREG(s)- 1431 Only  One [or two] battery charger[s on one train] inoperable.
 
4 of 9 Action Number                      TS Title              Applicable NUREG                                Action Description Action 3.8.4.B      DC Sources - Operating                  NUREG(s)- 1431 Only  One [or two] batter[y][ies on one train] inoperable.
One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C      DC Sources - Operating                  NUREG(s)- 1431 Only  Condition A [or B].
Action 3.8.7.A      Inverters - Operating                    NUREG(s)- 1431 Only  One [required] inverter inoperable.
Action 3.8.9.A      Distribution Systems - Operating        NUREG(s)- 1431 Only  One or more AC electrical power distribution subsystems inoperable.
Action 3.8.9.B      Distribution Systems - Operating        NUREG(s)- 1431 Only  One or more AC vital buses inoperable.
Action 3.8.9.C      Distribution Systems - Operating        NUREG(s)- 1431 Only  One or more DC electrical power distribution subsystems inoperable.
1.3                  Completion Times                        NUREG(s)- 1432 Only 5.5.18              Risk Informed Completion Time Program    NUREG(s)- 1432 Only One or more Functions with one RPS trip unit or associated instrument Action 3.3.1.A.2.1  RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  achannel inoperalb eexcept for Condition C One or more Functions with one RPS trip unit or associated instrument Action 3.3.1.A.2.2  RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  channel inoperalbe except for Condition C One or more Functions with two RPS trip units or associated instrument Action 3.3.1.B.2    RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  channel inoperalbe except for Condition C One or more functions with one automatic bypass removal channel Action 3.3.1.D.2.2.1 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  inoperable.
One or more functions with one automatic bypass removal channel Action 3.3.1.D.2.2.2 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  inoperable.
One or more Functions with two automatic bypass removal channels Action 3.3.1.E.2.2  RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only  inoperable.
One Matrix Logic channel inoperable or Three Matrix Logic channels Action 3.3.4.A      RPS Logic and Trip Initiation (Analog)  NUREG(s)- 1432 Only  inoperable due to a common power source failure.
One or more Functions with one Auxiliary Feedwater Acutation Signal Action 3.3.5.A      ESFAS Logic and Manual Trip (Analog)    NUREG(s)- 1432 Only  (AFAS) Manual Trip or Actuation Logic channel inoperable.
One or more Functions with one Manual Trip or Actuation Logic channel Action 3.3.5.C      ESFAS Logic and Manual Trip (Analog)    NUREG(s)- 1432 Only  inoperalbe except AFAS.
Action 3.3.6.A.2.1  DG LOVS (Analog)                        NUREG(s)- 1432 Only  One or more Functions with one channel per DG inoperable.
Action 3.3.6.A.2.2  DG LOVS (Analog)                        NUREG(s)- 1432 Only  One or more Functions with one channel per DG inoperable.
Action 3.3.6.B.2.2  DG LOVS (Analog)                        NUREG(s)- 1432 Only  One or more Functions with two channels per DG inoperable.
One Matrix Logic channel inoperable or Three Matrix Logic channels Action 3.3.4.A      RPS Logic and Trip Initiation (Digital)  NUREG(s)- 1432 Only  inoperable due to a common power source failure.
One or more Functions with one Manual Trip or Initiation Logic channel Action 3.3.6.B      ESFAS Logic and Manual Trip (Digital)    NUREG(s)- 1432 Only  inoperable.
Action 3.3.6.D      ESFAS Logic and Manual Trip (Digital)    NUREG(s)- 1432 Only  One or more Functions with one Actuation Logic channel inoperable.
Action 3.4.11.B.3    Pressurizer PORVs                        NUREG(s)- 1432 Only  One PORV inoperable and capable of being manually cycled.
Action 3.4.11.C.2    Pressurizer PORVs                        NUREG(s)- 1432 Only  One block valve inoperable.
 
5 of 9 Action Number                  TS Title                Applicable NUREG                                Action Description Action 3.4.5.A  RCS Loops - MODE 3                        NUREG(s)- 1432 Only  One RCS loop inoperable.
Action 3.5.2.A  ECCS - Operating                          NUREG(s)- 1432 Only  One LPCI subsystem inoperable.
Containment Isolation Valves (Atmospheric                      One or more penetration flow paths with one containment isolation valve Action 3.6.3.A  and Dual)                                NUREG(s)- 1432 Only  inoperable (for sump supply valves to ECCS and CS pumps).
Containment Isolation Valves (Atmospheric                      One or more penetration flow paths with one containment isolation valve Action 3.6.3.B  and Dual)                                NUREG(s)- 1432 Only  inoperable (for paths with two or more isolation valves).
Containment Isolation Valves (Atmospheric                      One or more penetration flow paths with one containment isolation valve Action 3.6.3.D  and Dual)                                NUREG(s)- 1432 Only  inoperable (for paths with one isolation valve and a closed system).
Action 3.7.10.A  ECW                                      NUREG(s)- 1432 Only  One ECW train inoperable.
Action 3.7.4.A  ADVs                                      NUREG(s)- 1432 Only  One required ADV line inoperable.
One steam supply to turbine driven AFW pump inoperable or one turbine Action 3.7.5.A  AFW System                                NUREG(s)- 1432 Only  driven AFW pump inoperable in Mode 3 following Refueling.
One AFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B  AFW System                                NUREG(s)- 1432 Only  2, or 3.
Action 3.7.7.A  CCW System                                NUREG(s)- 1432 Only  One CCW train inoperable.
Action 3.7.8.A  SWS                                      NUREG(s)- 1432 Only  One SWS train inoperable.
Action 3.7.9.A  UHS                                      NUREG(s)- 1432 Only  One or more cooling towers with one cooling tower fan inoperable.
Action 3.8.1.A.3 AC Sources - Operating                    NUREG(s)- 1432 Only  One AC train inoperable.
Action 3.8.1.B.4 AC Sources - Operating                    NUREG(s)- 1432 Only  One AC train inoperable.
Action 3.8.1.C.2 AC Sources - Operating                    NUREG(s)- 1432 Only  One AC train inoperable.
Action 3.8.1.D  AC Sources - Operating                    NUREG(s)- 1432 Only  One AC train inoperable.
Action 3.8.1.F  AC Sources - Operating                    NUREG(s)- 1432 Only  One AC train inoperable.
Action 3.8.4.A.3 DC Sources - Operating                    NUREG(s)- 1432 Only  One DC train inoperable.
Action 3.8.4.B  DC Sources - Operating                    NUREG(s)- 1432 Only  One DC train inoperable.
Action 3.8.4.C  DC Sources - Operating                    NUREG(s)- 1432 Only  One DC train inoperable.
Action 3.8.7.A  Inverters - Operating                    NUREG(s)- 1432 Only  One Inverters train inoperable.
Action 3.8.9.A  Distribution Systems - Operating          NUREG(s)- 1432 Only  One Distribution train inoperable.
Action 3.8.9.B  Distribution Systems - Operating          NUREG(s)- 1432 Only  One Distribution train inoperable.
Action 3.8.9.C  Distribution Systems - Operating          NUREG(s)- 1432 Only  One Distribution train inoperable.
One or more functions with one RPS trip unit or associated instrument Action 3.3.1.A  RPS Instrumentation - Operating (Analog)  NUREG(s)- 1432 Only  channel inoperable except Condition C One or more functions with two RPS trip units or associated instrument Action 3.3.1.B  RPS Instrumentation - Operating (Analog)  NUREG(s)- 1432 Only  channel inoperable except Condition C One or more Functions with one automatic bypass removal channel Action 3.3.1.D  RPS Instrumentation - Operating (Analog)  NUREG(s)- 1432 Only  inoperable.
One or more Functions with two automatic bypass removal channels Action 3.3.1.E  RPS Instrumentation - Operating (Analog)  NUREG(s)- 1432 Only  inoperable.
 
6 of 9 Action Number                      TS Title            Applicable NUREG                              Action Description One Matrix Logic channel inoperable OR Three Matrix Logic Channels Action 3.3.3.A      RPS Logic and Trip Initiation (Analog) NUREG(s)- 1432 Only  inoperable due to a common power source failure One or more Functions with one ESFAS trip unit or assoicated instrument Action 3.3.4.B      ESFAS Instrumentation (Analog)        NUREG(s)- 1432 Only  channel (except CSAS) inoperable.
One or more Functions with two ESFAS trip units or associated Action 3.3.4.C      ESFAS Instrumentation (Analog)        NUREG(s)- 1432 Only  instrumentat channels (except CSAS) inoperable.
One or more Functions with one automatic bypass removal channel Action 3.3.4.D      ESFAS Instrumentation (Analog)        NUREG(s)- 1432 Only  inoperable.
One or more Functions with two automatic bypass removal channels Action 3.3.4.E      ESFAS Instrumentation (Analog)        NUREG(s)- 1432 Only  inoperable.
One or more Functions with one Manual Trip or Actuation Logic channel Action 3.3.5.C      ESFAS Lofic and Manual Trip (Analog)  NUREG(s)- 1432 Only  inoperable except AFAS.
Action 3.3.6.A      DG - LOVS (Analog)                    NUREG(s)- 1432 Only  One or more Functions with one channel per DG inoperable.
Action 3.3.6.B      DG - LOVS (Analog)                    NUREG(s)- 1432 Only  One or more Functions with two channels per DG inoperable.
1.3                  Completion Times                      NUREG(s)- 1433 Only  One Completion train inoperable.
5.5.15              Risk Informed Completion Time Program  NUREG(s)- 1433 Only  One Risk train inoperable.
Action 3.1.7.B      SLC System                            NUREG(s)- 1433 Only  One SLC subsystem inoperable (for reasons other than Condition A).
Action 3.3.1.1.A    RPS Instrumentation                    NUREG(s)- 1433 Only  One or more required channels inoperable.
One or more Functions with one or more required channels inoperable in Action 3.3.1.1.B    RPS Instrumentation                    NUREG(s)- 1433 Only  both trip systems.
Feedwater and Main Turbine High Water Action 3.3.2.2.A    Level Trip Instrumentation            NUREG(s)- 1433 Only  One feedwater and main turbine high water level trip channel inoperable.
Action 3.3.4.2.A    ATWS-RPT Instrumentation              NUREG(s)- 1433 Only  One or more channels inoperable.
Action 3.3.5.1.B.3  ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.C.2  ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.D.2.1 ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.E.2  ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.F.2  ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.G.2  ECCS Instrumentation                  NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.2.B.2  RCIC System Instrumentation            NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.2-1.
Action 3.3.5.2.D.2.1 RCIC System Instrumentation            NUREG(s)- 1433 Only  As required by Required Action A.1 and referenced in Table 3.3.5.2-1.
 
7 of 9 Action Number                    TS Title              Applicable NUREG                                Action Description Primary Containment Isolation Action 3.3.6.1.A  Instrumentation                        NUREG(s)- 1433 Only  One or more required channels inoperable.
Action 3.4.3.A    S/RVs                                  NUREG(s)- 1433 Only  [One [or two] [required] S/RVs ] inoperable.
One low pressure ECCS injection/spray subsystem inoperable or one LPCI Action 3.5.1.A    ECCS - Operating                        NUREG(s)- 1433 Only  pump in both LPCI subsystems inoperable.
Action 3.5.1.C    ECCS - Operating                        NUREG(s)- 1433 Only  HPCI system inoperable.
Action 3.5.1.D    ECCS - Operating                        NUREG(s)- 1433 Only  HPCI system inoperable and Condition A entered.
Action 3.5.1.E    ECCS - Operating                        NUREG(s)- 1433 Only  One ADS valve inoperable.
Action 3.5.1.F    ECCS - Operating                        NUREG(s)- 1433 Only  One ADS valve inoperable and Condition A entered.
Action 3.5.3.A.2  RCIC System                            NUREG(s)- 1433 Only    RCIC system inoperable.
One or more penetration flow paths with one PCIV inoperable for reasons Action 3.6.1.3.A  PCIVs                                  NUREG(s)- 1433 Only  other than Condition D or E (for paths with two [or more] PCIVs.
Reactor Building-to-Suppression Chamber                      One line with one or more reactor building-to-suppression chamber Action 3.6.1.7.C  Vacuum Breakers                        NUREG(s)- 1433 Only  vacuum breakers inoperable for opening.
Suppression Chamber-to-Drywell Vacuum                        One required suppression chamber-to-drywell vacuum breaker inoperable Action 3.6.1.8.A  Breakers                                NUREG(s)- 1433 Only  for opening.
Action 3.6.2.3.A  RHR Suppression Pool Cooling            NUREG(s)- 1433 Only  One RHR suppression pool cooling subsystem inoperable.
Action 3.6.2.4.A  RHR Suppression Pool Spray              NUREG(s)- 1433 Only  One RHR suppression pool spray subsystem inoperable.
Action 3.6.3.1.B.2 [Drywell Cooling system Fans]          NUREG(s)- 1433 Only  Two [required] [drywell cooling system fans] inoperable.
Action 3.7.1.B    RHRSW System                            NUREG(s)- 1433 Only  One RHRSW pump in each subsystem inoperable.
Action 3.7.1.C    RHRSW System                            NUREG(s)- 1433 Only  One RHRSW subsystem inoperable for reasons other than Condition A.
Action 3.7.2.B    [PSW] System and [UHS]                  NUREG(s)- 1433 Only  One [PSW] pump in each subsystem inoperable.
Action 3.7.2.C    [PSW] System and [UHS]                  NUREG(s)- 1433 Only  [One or more cooling towers with one cooling tower fan inoperable.].
One [PSW] subsystem inoperabl efor reasosn other than Condition[s] A Action 3.7.2.E    [PSW] System and [UHS]                  NUREG(s)- 1433 Only  [and C].
Action 3.8.1.A.3  AC Sources - Operating                  NUREG(s)- 1433 Only  One AC train inoperable.
Action 3.8.1.B.4  AC Sources - Operating                  NUREG(s)- 1433 Only  One [required] offsite circuit inoperable.
Action 3.8.1.C.2  AC Sources - Operating                  NUREG(s)- 1433 Only  One [required] DG inoperable.
Action 3.8.1.D    AC Sources - Operating                  NUREG(s)- 1433 Only  Two [required] offsite circuits inoperable.
Action 3.8.1.F    AC Sources - Operating                  NUREG(s)- 1433 Only  One [required] offsite circuit inoperable and one [required] DG inoperable.
Action 3.8.4.A.3  DC Sources - Operating                  NUREG(s)- 1433 Only  One [required][automatic loac sequencer] inoperable.
Action 3.8.4.B    DC Sources - Operating                  NUREG(s)- 1433 Only  One [or two] battery charger[s on one train] inoperable.
Action 3.8.4.C    DC Sources - Operating                  NUREG(s)- 1433 Only  One [or two] batter[y][ies on one train] inoperable.
One DC electrical power subsystem inoperable for reasons other than Action 3.8.7.A    Inverters - Operating                  NUREG(s)- 1433 Only  Condition A [or B].
 
8 of 9 Action Number                      TS Title            Applicable NUREG                                Action Description Action 3.8.9.A      Distribution Systems - Operating      NUREG(s)- 1433 Only  One [required] inverter inoperable.
Action 3.8.9.B      Distribution Systems - Operating      NUREG(s)- 1433 Only  One or more AC electrical power distribution subsystems inoperable.
Action 3.8.9.C      Distribution Systems - Operating      NUREG(s)- 1433 Only  One or more AC vital buses inoperable.
1.3                  Completion Times                      NUREG(s)- 1434 Only 5.5.15              Risk Informed Completion Time Program NUREG(s)- 1434 Only Action 3.1.7.B      SLC System                            NUREG(s)- 1434 Only  One SLC subsystem inoperable [for reasons other than Condition A]
Action 3.3.1.1.A    RPS Instrumentation                  NUREG(s)- 1434 Only  One or more required channels inoperable.
One or more Functions with one or more required channels inoperable in Action 3.3.1.1.B    RPS Instrumentation                  NUREG(s)- 1434 Only  both trip systems.
Action 3.3.4.2.A    ATWS-RPT Instrumentation              NUREG(s)- 1434 Only  One or more channels inoperable.
Action 3.3.5.1.B.3  ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.C.2  ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.D.2.1 ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.E.2  ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.F.2  ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.1.G.2  ECCS Instrumentation                  NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.1-1.
Action 3.3.5.2.B.2  RCIC System Instrumentation          NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.2-1.
Action 3.3.5.2.D.2.1 RCIC System Instrumentation          NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.2-1.
Primary Containment Isolation Action 3.3.6.1.A    Instrumentation                      NUREG(s)- 1434 Only  One or more required channels inoperable.
RHR Containment Spray System Action 3.3.6.3.B.2  Instrumentation                      NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.3-1.
RHR Containment Spray System Action 3.3.6.3.C.2  Instrumentation                      NUREG(s)- 1434 Only  As required by Required Action A.1 and referenced in Table 3.3.5.3-1.
Action 3.4.4.A      S/RVs                                NUREG(s)- 1434 Only  [One [required] S/RV inoperable.]
Action 3.5.1.A      ECCS - Operating                      NUREG(s)- 1434 Only  One low pressure ECCS injection/spray subsystem inoperable.
Action 3.5.1.B.2    ECCS - Operating                      NUREG(s)- 1434 Only  High Pressure Core Spray (HPCS) System inoperable.
Two ECCS injection subsystems inoperable OR One ECCS injection and Action 3.5.1.C      ECCS - Operating                      NUREG(s)- 1434 Only  one ECCS spray subsystem inoperable.
Action 3.5.1.E      ECCS - Operating                      NUREG(s)- 1434 Only  One ADS valve inoperable.
 
9 of 9 Action Number                      TS Title      Applicable NUREG                                Action Description One ADS valve inoperable AND One low pressure ECCS injection/spray Action 3.5.1.F    ECCS - Operating                NUREG(s)- 1434 Only  subsystem inoperable.
Action 3.5.3.A.2  RCIC System                      NUREG(s)- 1434 Only  RCIC System inoperable.
One or more penetration flow paths with one PCIV inoperable for reasons Action 3.6.1.3.A  PCIVs                            NUREG(s)- 1434 Only  other than Condition[s] D [and E] (for paths with two [or more] PCIVs.
Action 3.6.2.3.A  RHR Suppression Pool Cooling    NUREG(s)- 1434 Only  One RHR suppression pool cooling subsystem inoperable.
Action 3.6.2.4.C  SPMU System                      NUREG(s)- 1434 Only  One SPMU subsystem inoperable for reasons other than Condition A or B.
One or more penetration flow paths with one drywell isolation valve Action 3.6.5.3.A.1 Drywell Isolation Valves        NUREG(s)- 1434 Only  inoperable.
Action 3.7.1.A    [SSW] System and [UHS]          NUREG(s)- 1434 Only  [One or more cooling towers with one cooling tower fan inoperable.]
Action 3.7.1.C    [SSW] System and [UHS]          NUREG(s)- 1434 Only  One [SSW] subsystem inoperable [for reasons other than Condition A].
Action 3.8.1.A.3  AC Sources - Operating          NUREG(s)- 1434 Only  One [required] offsite circuit inoperable.
Action 3.8.1.B.4  AC Sources - Operating          NUREG(s)- 1434 Only  One [required] DG inoperable.
Action 3.8.1.C.2  AC Sources - Operating          NUREG(s)- 1434 Only  Two [required] offsite circuits inoperable.
Action 3.8.1.D    AC Sources - Operating          NUREG(s)- 1434 Only  One [required] offsite circuit inoperable and one [required] DG inoperable.
Action 3.8.1.F    AC Sources - Operating          NUREG(s)- 1434 Only  One [required][automatic loac sequencer] inoperable.
Action 3.8.4.A.3  DC Sources - Operating          NUREG(s)- 1434 Only  One [or two] battery charger[s on one train] inoperable.
Action 3.8.4.B    DC Sources - Operating          NUREG(s)- 1434 Only  One [or two] batter[y][ies on one train] inoperable.
One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C    DC Sources - Operating          NUREG(s)- 1434 Only  Condition A [or B].
Action 3.8.7.A    Inverters - Operating            NUREG(s)- 1434 Only  One [required] inverter inoperable.
Action 3.8.9.A    Distribution Systems - Operating NUREG(s)- 1434 Only  One or more AC electrical power distribution subsystems inoperable.
Action 3.8.9.B    Distribution Systems - Operating NUREG(s)- 1434 Only  One or more AC vital buses inoperable.
Action 3.8.9.C    Distribution Systems - Operating NUREG(s)- 1434 Only  One or more DC electrical power distribution subsystems inoperable.}}

Latest revision as of 13:49, 29 October 2019

Draft Table 1 of TSTF-505, Revision 2, Affected Technical Specifications
ML17290A097
Person / Time
Site: Technical Specifications Task Force
Issue date: 06/14/2011
From:
Office of Nuclear Reactor Regulation
To:
Technical Specifications Task Force
Honcharik M
Shared Package
ML17290A003 List:
References
TSTF-505, Rev 2
Download: ML17290A097 (8)


Text

TABLE 1 AFFECTED TECHNICAL SPECIFCATIONS This Table contains the Conditions within the scope of TSTF-505, Revision 2. These Conditions are eligible for inclusion in the Risk Informed Completion Time Program.

NOTE: The Action Numbers are in reference to Revision 3 of the STS NUREGs Action Number TS Title Applicable NUREG Action Description 1.3 Completion Times NUREG(s)- 1430 Only 5.5.18 Risk Informed Completion Time Program NUREG(s)- 1430 Only Action 3.3.1.B.1 RPS Instrumentation NUREG(s)- 1430 Only Two channels inoperable.

One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.A.2 EFIC System Instrumentation NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with one channel inoperable.

One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.B.2 EFIC System Instrumentation NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with two channels inoperable.

One or more EFW Initiation, Main Steam Line Isolation, or MFW Isolation Action 3.3.11.B.3 EFIC System Instrumentation NUREG(s)- 1430 Only Functions listed in Table 3.3.11-1 with two channels inoperable.

Action 3.3.11.C EFIC System Instrumentation NUREG(s)- 1430 Only One EFW Vector Valve Control channel inoperable.

One or more EFIC Function(s) with one or both manual initiation switches Action 3.3.12.A EFIC Manual Initiation NUREG(s)- 1430 Only inoperable in one actuation channel.

One or more channel A(B) Functions inoperable with all channel B(A)

Action 3.3.13.A EFIC Logic NUREG(s)- 1430 Only Functions OPERABLE.

Action 3.3.14.A EFIC-EFW- Vector Valve Logic NUREG(s)- 1430 Only One vector valve logic channel inoperable.

Action 3.3.5.A ESFAS Instrumentation NUREG(s)- 1430 Only One or more paramters with one channel inoperable.

Action 3.3.6.A ESFAS Manual Initiation NUREG(s)- 1430 Only One or more ESFAS Functions with one channel inoperable.

Action 3.3.8.A EDG LOPS NUREG(s)- 1430 Only One or more Functions with one channel per EDG inoperable.

Action 3.4.5.A RCS Loops - MODE 3 NUREG(s)- 1430 Only One RCS loop inoperable.

Action 3.5.2.A ECCS - Operating NUREG(s)- 1430 Only One LPCI subsystem inoperable.

One or more penetration flow paths with one containment isolation valve Action 3.6.3.A Containment Isolation Valves NUREG(s)- 1430 Only inoperable (for paths with two or more isolation valves).

One or more penetration flow paths with one containment isolation valve Action 3.6.3.C Containment Isolation Valves NUREG(s)- 1430 Only inoperable (for paths with one isolation valve and a closed system).

Action 3.7.4.A AVVs NUREG(s)- 1430 Only One required AVV [line] inoperable.

One steam supply to turbine driven EFW pump inoperable or one turbine Action 3.7.5.A EFW System NUREG(s)- 1430 Only driven EFW pump inoperable in Mode 3 following Refueling.

One EFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B EFW System NUREG(s)- 1430 Only 2, or 3.

Enclosure 2

2 of 9 Action Number TS Title Applicable NUREG Action Description Action 3.7.7.A CCW System NUREG(s)- 1430 Only One CCW train inoperable.

Action 3.7.8.A SWS System NUREG(s)- 1430 Only One SWS train inoperable.

Action 3.7.9.A UHS NUREG(s)- 1430 Only [One or more cooling towers with one cooling tower fan inoperable.]

Action 3.8.1.A.3 AC Sources - Operating NUREG(s)- 1430 Only One [required] offsite circuit inoperable.

Action 3.8.1.B.4 AC Sources - Operating NUREG(s)- 1430 Only One [required] DG inoperable.

Action 3.8.1.C.2 AC Sources - Operating NUREG(s)- 1430 Only Two [required] offsite circuits inoperable.

Action 3.8.1.D AC Sources - Operating NUREG(s)- 1430 Only One [required] offsite circuit inoperable and one [required] DG inoperable.

Action 3.8.1.F AC Sources - Operating NUREG(s)- 1430 Only One [required][automatic loac sequencer] inoperable.

Action 3.8.4.A.3 DC Sources - Operating NUREG(s)- 1430 Only One [or two] battery charger[s on one train] inoperable.

Action 3.8.4.B DC Sources - Operating NUREG(s)- 1430 Only One [or two] batter[y][ies on one train] inoperable.

One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C DC Sources - Operating NUREG(s)- 1430 Only Condition A [or B].

Action 3.8.7.A Inverters - Operating NUREG(s)- 1430 Only One [required] inverter inoperable.

Action 3.8.9.A Distribution Systems - Operating NUREG(s)- 1430 Only One or more AC electrical power distribution subsystems inoperable.

Action 3.8.9.B Distribution Systems - Operating NUREG(s)- 1430 Only One or more AC vital buses inoperable.

Action 3.8.9.C Distribution Systems - Operating NUREG(s)- 1430 Only One or more DC electrical power distribution subsystems inoperable.

1.3 Completion Times NUREG(s)- 1431 Only 5.5.18 Risk Informed Completion Time Program NUREG(s)- 1431 Only Action 3.3.1.B RTS Instrumentation NUREG(s)- 1431 Only One Manual Reactor Trip channel Inoperable Action 3.3.1.C RTS Instrumentation NUREG(s)- 1431 Only One channel or train inoperable Action 3.3.1.E RTS Instrumentation NUREG(s)- 1431 Only One channel inoperable.

Action 3.3.1.J RTS Instrumentation NUREG(s)- 1431 Only One Source Range Neutron Flux channel inoperable.

Action 3.3.1.K RTS Instrumentation NUREG(s)- 1431 Only One channel inoperable.

Action 3.3.1.N RTS Instrumentation NUREG(s)- 1431 Only One Turbine Trip channel inoperable.

Action 3.3.1.O RTS Instrumentation NUREG(s)- 1431 Only One train inoperable.

Action 3.3.1.Q RTS Instrumentation NUREG(s)- 1431 Only One or more channels inoperable.

Action 3.3.1.S RTS Instrumentation NUREG(s)- 1431 Only One trip mechanism inoperable for one RTB.

Action 3.3.2.B ESFAS Instrumentation NUREG(s)- 1431 Only One channel or train inoperable Action 3.3.2.C ESFAS Instrumentation NUREG(s)- 1431 Only One train inoperable.

Action 3.3.2.D ESFAS Instrumentation NUREG(s)- 1431 Only One channel inoperable.

Action 3.3.2.E ESFAS Instrumentation NUREG(s)- 1431 Only One Containment Pressure channel inoperable.

Action 3.3.2.F ESFAS Instrumentation NUREG(s)- 1431 Only One channel or train inoperable.

Action 3.3.2.G ESFAS Instrumentation NUREG(s)- 1431 Only One train inoperable.

3 of 9 Action Number TS Title Applicable NUREG Action Description Action 3.3.2.H ESFAS Instrumentation NUREG(s)- 1431 Only One train inoperable.

Action 3.3.2.I ESFAS Instrumentation NUREG(s)- 1431 Only One channel inoperable.

Action 3.3.2.J ESFAS Instrumentation NUREG(s)- 1431 Only One Main Feedwater Pumps trip channel inoperable.

Action 3.3.2.L ESFAS Instrumentation NUREG(s)- 1431 Only One or more channels inoperable.

Action 3.3.5.A LOP DG Start Instrumentation NUREG(s)- 1431 Only One or more Functions with one channel per bus inoperable.

Action 3.4.11.B.3 Pressurizer PORVs NUREG(s)- 1431 Only One [or two] PORV[s] inoperable an not capable of being manually cycled Action 3.4.11.C.2 Pressurizer PORVs NUREG(s)- 1431 Only One [or two] block valves(s) inoperable.

Action 3.4.5.A RCS Loops - MODE 3 NUREG(s)- 1431 Only One required RCS loop inoperable.

[One required RCS loop not in operation with Rod control System capable Action 3.4.5.C RCS Loops - MODE 3 NUREG(s)- 1431 Only of rod withdrawal.]

Action 3.6.10.A HIS (Ice Condenser) NUREG(s)- 1431 Only One HIS train inoperable.

Action 3.6.10.B HIS (Ice Condenser) NUREG(s)- 1431 Only One containment region with no OPERABLE hydrogen ignitor.

Action 3.6.14.A ARS (Ice Condenser) NUREG(s)- 1431 Only One ARS train inoperalbe.

One or more ice condenser doors inoperable for reasons other than Action 3.6.16.B.2 Ice Condenser Doors (Ice Condenser) NUREG(s)- 1431 Only condition A or not closed.

Action 3.6.17.A Divider Barrier Integrity (Ice Condenser) NUREG(s)- 1431 Only Containment Isolation Valves (Atmospheric, One or more penetration flow paths with one containment isolation valve Action 3.6.3.A Subatmospheric, Ice Condenser, and Dual) NUREG(s)- 1431 Only inoperable (for paths with two or more isolation valves).

Containment Isolation Valves (Atmospheric, One or more penetration flow paths with one containment isolation valve Action 3.6.3.C Subatmospheric, Ice Condenser, and Dual) NUREG(s)- 1431 Only inoperable (for paths with one isolation valve and a closed system).

Action 3.7.4.A ADVs NUREG(s)- 1431 Only One required ADV line inoperable.

One steam supply to turbine driven AFW pump inoperable or one turbine Action 3.7.5.A AFW System NUREG(s)- 1431 Only driven AFW pump inoperable in Mode 3 following Refueling.

One AFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B AFW System NUREG(s)- 1431 Only 2, or 3.

Action 3.7.7.A CCW System NUREG(s)- 1431 Only One CCW train inoperable.

Action 3.7.8.A SWS NUREG(s)- 1431 Only One SWS train inoperable.

Action 3.7.9.A UHS NUREG(s)- 1431 Only [One or more cooling towers with one cooling tower fan inoperable.]

Action 3.8.1.A.3 AC Sources - Operating NUREG(s)- 1431 Only One [required] offsite circuit inoperable.

Action 3.8.1.B.4 AC Sources - Operating NUREG(s)- 1431 Only One [required] DG inoperable.

Action 3.8.1.C.2 AC Sources - Operating NUREG(s)- 1431 Only Two [required] offsite circuits inoperable.

Action 3.8.1.D AC Sources - Operating NUREG(s)- 1431 Only One [required] offsite circuit inoperable and one [required] DG inoperable.

Action 3.8.1.F AC Sources - Operating NUREG(s)- 1431 Only One [required][automatic loac sequencer] inoperable.

Action 3.8.4.A.3 DC Sources - Operating NUREG(s)- 1431 Only One [or two] battery charger[s on one train] inoperable.

4 of 9 Action Number TS Title Applicable NUREG Action Description Action 3.8.4.B DC Sources - Operating NUREG(s)- 1431 Only One [or two] batter[y][ies on one train] inoperable.

One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C DC Sources - Operating NUREG(s)- 1431 Only Condition A [or B].

Action 3.8.7.A Inverters - Operating NUREG(s)- 1431 Only One [required] inverter inoperable.

Action 3.8.9.A Distribution Systems - Operating NUREG(s)- 1431 Only One or more AC electrical power distribution subsystems inoperable.

Action 3.8.9.B Distribution Systems - Operating NUREG(s)- 1431 Only One or more AC vital buses inoperable.

Action 3.8.9.C Distribution Systems - Operating NUREG(s)- 1431 Only One or more DC electrical power distribution subsystems inoperable.

1.3 Completion Times NUREG(s)- 1432 Only 5.5.18 Risk Informed Completion Time Program NUREG(s)- 1432 Only One or more Functions with one RPS trip unit or associated instrument Action 3.3.1.A.2.1 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only achannel inoperalb eexcept for Condition C One or more Functions with one RPS trip unit or associated instrument Action 3.3.1.A.2.2 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only channel inoperalbe except for Condition C One or more Functions with two RPS trip units or associated instrument Action 3.3.1.B.2 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only channel inoperalbe except for Condition C One or more functions with one automatic bypass removal channel Action 3.3.1.D.2.2.1 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only inoperable.

One or more functions with one automatic bypass removal channel Action 3.3.1.D.2.2.2 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only inoperable.

One or more Functions with two automatic bypass removal channels Action 3.3.1.E.2.2 RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only inoperable.

One Matrix Logic channel inoperable or Three Matrix Logic channels Action 3.3.4.A RPS Logic and Trip Initiation (Analog) NUREG(s)- 1432 Only inoperable due to a common power source failure.

One or more Functions with one Auxiliary Feedwater Acutation Signal Action 3.3.5.A ESFAS Logic and Manual Trip (Analog) NUREG(s)- 1432 Only (AFAS) Manual Trip or Actuation Logic channel inoperable.

One or more Functions with one Manual Trip or Actuation Logic channel Action 3.3.5.C ESFAS Logic and Manual Trip (Analog) NUREG(s)- 1432 Only inoperalbe except AFAS.

Action 3.3.6.A.2.1 DG LOVS (Analog) NUREG(s)- 1432 Only One or more Functions with one channel per DG inoperable.

Action 3.3.6.A.2.2 DG LOVS (Analog) NUREG(s)- 1432 Only One or more Functions with one channel per DG inoperable.

Action 3.3.6.B.2.2 DG LOVS (Analog) NUREG(s)- 1432 Only One or more Functions with two channels per DG inoperable.

One Matrix Logic channel inoperable or Three Matrix Logic channels Action 3.3.4.A RPS Logic and Trip Initiation (Digital) NUREG(s)- 1432 Only inoperable due to a common power source failure.

One or more Functions with one Manual Trip or Initiation Logic channel Action 3.3.6.B ESFAS Logic and Manual Trip (Digital) NUREG(s)- 1432 Only inoperable.

Action 3.3.6.D ESFAS Logic and Manual Trip (Digital) NUREG(s)- 1432 Only One or more Functions with one Actuation Logic channel inoperable.

Action 3.4.11.B.3 Pressurizer PORVs NUREG(s)- 1432 Only One PORV inoperable and capable of being manually cycled.

Action 3.4.11.C.2 Pressurizer PORVs NUREG(s)- 1432 Only One block valve inoperable.

5 of 9 Action Number TS Title Applicable NUREG Action Description Action 3.4.5.A RCS Loops - MODE 3 NUREG(s)- 1432 Only One RCS loop inoperable.

Action 3.5.2.A ECCS - Operating NUREG(s)- 1432 Only One LPCI subsystem inoperable.

Containment Isolation Valves (Atmospheric One or more penetration flow paths with one containment isolation valve Action 3.6.3.A and Dual) NUREG(s)- 1432 Only inoperable (for sump supply valves to ECCS and CS pumps).

Containment Isolation Valves (Atmospheric One or more penetration flow paths with one containment isolation valve Action 3.6.3.B and Dual) NUREG(s)- 1432 Only inoperable (for paths with two or more isolation valves).

Containment Isolation Valves (Atmospheric One or more penetration flow paths with one containment isolation valve Action 3.6.3.D and Dual) NUREG(s)- 1432 Only inoperable (for paths with one isolation valve and a closed system).

Action 3.7.10.A ECW NUREG(s)- 1432 Only One ECW train inoperable.

Action 3.7.4.A ADVs NUREG(s)- 1432 Only One required ADV line inoperable.

One steam supply to turbine driven AFW pump inoperable or one turbine Action 3.7.5.A AFW System NUREG(s)- 1432 Only driven AFW pump inoperable in Mode 3 following Refueling.

One AFW train inoperable [for reasons other than Conidtion A] in Mode 1, Action 3.7.5.B AFW System NUREG(s)- 1432 Only 2, or 3.

Action 3.7.7.A CCW System NUREG(s)- 1432 Only One CCW train inoperable.

Action 3.7.8.A SWS NUREG(s)- 1432 Only One SWS train inoperable.

Action 3.7.9.A UHS NUREG(s)- 1432 Only One or more cooling towers with one cooling tower fan inoperable.

Action 3.8.1.A.3 AC Sources - Operating NUREG(s)- 1432 Only One AC train inoperable.

Action 3.8.1.B.4 AC Sources - Operating NUREG(s)- 1432 Only One AC train inoperable.

Action 3.8.1.C.2 AC Sources - Operating NUREG(s)- 1432 Only One AC train inoperable.

Action 3.8.1.D AC Sources - Operating NUREG(s)- 1432 Only One AC train inoperable.

Action 3.8.1.F AC Sources - Operating NUREG(s)- 1432 Only One AC train inoperable.

Action 3.8.4.A.3 DC Sources - Operating NUREG(s)- 1432 Only One DC train inoperable.

Action 3.8.4.B DC Sources - Operating NUREG(s)- 1432 Only One DC train inoperable.

Action 3.8.4.C DC Sources - Operating NUREG(s)- 1432 Only One DC train inoperable.

Action 3.8.7.A Inverters - Operating NUREG(s)- 1432 Only One Inverters train inoperable.

Action 3.8.9.A Distribution Systems - Operating NUREG(s)- 1432 Only One Distribution train inoperable.

Action 3.8.9.B Distribution Systems - Operating NUREG(s)- 1432 Only One Distribution train inoperable.

Action 3.8.9.C Distribution Systems - Operating NUREG(s)- 1432 Only One Distribution train inoperable.

One or more functions with one RPS trip unit or associated instrument Action 3.3.1.A RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only channel inoperable except Condition C One or more functions with two RPS trip units or associated instrument Action 3.3.1.B RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only channel inoperable except Condition C One or more Functions with one automatic bypass removal channel Action 3.3.1.D RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only inoperable.

One or more Functions with two automatic bypass removal channels Action 3.3.1.E RPS Instrumentation - Operating (Analog) NUREG(s)- 1432 Only inoperable.

6 of 9 Action Number TS Title Applicable NUREG Action Description One Matrix Logic channel inoperable OR Three Matrix Logic Channels Action 3.3.3.A RPS Logic and Trip Initiation (Analog) NUREG(s)- 1432 Only inoperable due to a common power source failure One or more Functions with one ESFAS trip unit or assoicated instrument Action 3.3.4.B ESFAS Instrumentation (Analog) NUREG(s)- 1432 Only channel (except CSAS) inoperable.

One or more Functions with two ESFAS trip units or associated Action 3.3.4.C ESFAS Instrumentation (Analog) NUREG(s)- 1432 Only instrumentat channels (except CSAS) inoperable.

One or more Functions with one automatic bypass removal channel Action 3.3.4.D ESFAS Instrumentation (Analog) NUREG(s)- 1432 Only inoperable.

One or more Functions with two automatic bypass removal channels Action 3.3.4.E ESFAS Instrumentation (Analog) NUREG(s)- 1432 Only inoperable.

One or more Functions with one Manual Trip or Actuation Logic channel Action 3.3.5.C ESFAS Lofic and Manual Trip (Analog) NUREG(s)- 1432 Only inoperable except AFAS.

Action 3.3.6.A DG - LOVS (Analog) NUREG(s)- 1432 Only One or more Functions with one channel per DG inoperable.

Action 3.3.6.B DG - LOVS (Analog) NUREG(s)- 1432 Only One or more Functions with two channels per DG inoperable.

1.3 Completion Times NUREG(s)- 1433 Only One Completion train inoperable.

5.5.15 Risk Informed Completion Time Program NUREG(s)- 1433 Only One Risk train inoperable.

Action 3.1.7.B SLC System NUREG(s)- 1433 Only One SLC subsystem inoperable (for reasons other than Condition A).

Action 3.3.1.1.A RPS Instrumentation NUREG(s)- 1433 Only One or more required channels inoperable.

One or more Functions with one or more required channels inoperable in Action 3.3.1.1.B RPS Instrumentation NUREG(s)- 1433 Only both trip systems.

Feedwater and Main Turbine High Water Action 3.3.2.2.A Level Trip Instrumentation NUREG(s)- 1433 Only One feedwater and main turbine high water level trip channel inoperable.

Action 3.3.4.2.A ATWS-RPT Instrumentation NUREG(s)- 1433 Only One or more channels inoperable.

Action 3.3.5.1.B.3 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.C.2 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.D.2.1 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.E.2 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.F.2 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.G.2 ECCS Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.2.B.2 RCIC System Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

Action 3.3.5.2.D.2.1 RCIC System Instrumentation NUREG(s)- 1433 Only As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

7 of 9 Action Number TS Title Applicable NUREG Action Description Primary Containment Isolation Action 3.3.6.1.A Instrumentation NUREG(s)- 1433 Only One or more required channels inoperable.

Action 3.4.3.A S/RVs NUREG(s)- 1433 Only [One [or two] [required] S/RVs ] inoperable.

One low pressure ECCS injection/spray subsystem inoperable or one LPCI Action 3.5.1.A ECCS - Operating NUREG(s)- 1433 Only pump in both LPCI subsystems inoperable.

Action 3.5.1.C ECCS - Operating NUREG(s)- 1433 Only HPCI system inoperable.

Action 3.5.1.D ECCS - Operating NUREG(s)- 1433 Only HPCI system inoperable and Condition A entered.

Action 3.5.1.E ECCS - Operating NUREG(s)- 1433 Only One ADS valve inoperable.

Action 3.5.1.F ECCS - Operating NUREG(s)- 1433 Only One ADS valve inoperable and Condition A entered.

Action 3.5.3.A.2 RCIC System NUREG(s)- 1433 Only RCIC system inoperable.

One or more penetration flow paths with one PCIV inoperable for reasons Action 3.6.1.3.A PCIVs NUREG(s)- 1433 Only other than Condition D or E (for paths with two [or more] PCIVs.

Reactor Building-to-Suppression Chamber One line with one or more reactor building-to-suppression chamber Action 3.6.1.7.C Vacuum Breakers NUREG(s)- 1433 Only vacuum breakers inoperable for opening.

Suppression Chamber-to-Drywell Vacuum One required suppression chamber-to-drywell vacuum breaker inoperable Action 3.6.1.8.A Breakers NUREG(s)- 1433 Only for opening.

Action 3.6.2.3.A RHR Suppression Pool Cooling NUREG(s)- 1433 Only One RHR suppression pool cooling subsystem inoperable.

Action 3.6.2.4.A RHR Suppression Pool Spray NUREG(s)- 1433 Only One RHR suppression pool spray subsystem inoperable.

Action 3.6.3.1.B.2 [Drywell Cooling system Fans] NUREG(s)- 1433 Only Two [required] [drywell cooling system fans] inoperable.

Action 3.7.1.B RHRSW System NUREG(s)- 1433 Only One RHRSW pump in each subsystem inoperable.

Action 3.7.1.C RHRSW System NUREG(s)- 1433 Only One RHRSW subsystem inoperable for reasons other than Condition A.

Action 3.7.2.B [PSW] System and [UHS] NUREG(s)- 1433 Only One [PSW] pump in each subsystem inoperable.

Action 3.7.2.C [PSW] System and [UHS] NUREG(s)- 1433 Only [One or more cooling towers with one cooling tower fan inoperable.].

One [PSW] subsystem inoperabl efor reasosn other than Condition[s] A Action 3.7.2.E [PSW] System and [UHS] NUREG(s)- 1433 Only [and C].

Action 3.8.1.A.3 AC Sources - Operating NUREG(s)- 1433 Only One AC train inoperable.

Action 3.8.1.B.4 AC Sources - Operating NUREG(s)- 1433 Only One [required] offsite circuit inoperable.

Action 3.8.1.C.2 AC Sources - Operating NUREG(s)- 1433 Only One [required] DG inoperable.

Action 3.8.1.D AC Sources - Operating NUREG(s)- 1433 Only Two [required] offsite circuits inoperable.

Action 3.8.1.F AC Sources - Operating NUREG(s)- 1433 Only One [required] offsite circuit inoperable and one [required] DG inoperable.

Action 3.8.4.A.3 DC Sources - Operating NUREG(s)- 1433 Only One [required][automatic loac sequencer] inoperable.

Action 3.8.4.B DC Sources - Operating NUREG(s)- 1433 Only One [or two] battery charger[s on one train] inoperable.

Action 3.8.4.C DC Sources - Operating NUREG(s)- 1433 Only One [or two] batter[y][ies on one train] inoperable.

One DC electrical power subsystem inoperable for reasons other than Action 3.8.7.A Inverters - Operating NUREG(s)- 1433 Only Condition A [or B].

8 of 9 Action Number TS Title Applicable NUREG Action Description Action 3.8.9.A Distribution Systems - Operating NUREG(s)- 1433 Only One [required] inverter inoperable.

Action 3.8.9.B Distribution Systems - Operating NUREG(s)- 1433 Only One or more AC electrical power distribution subsystems inoperable.

Action 3.8.9.C Distribution Systems - Operating NUREG(s)- 1433 Only One or more AC vital buses inoperable.

1.3 Completion Times NUREG(s)- 1434 Only 5.5.15 Risk Informed Completion Time Program NUREG(s)- 1434 Only Action 3.1.7.B SLC System NUREG(s)- 1434 Only One SLC subsystem inoperable [for reasons other than Condition A]

Action 3.3.1.1.A RPS Instrumentation NUREG(s)- 1434 Only One or more required channels inoperable.

One or more Functions with one or more required channels inoperable in Action 3.3.1.1.B RPS Instrumentation NUREG(s)- 1434 Only both trip systems.

Action 3.3.4.2.A ATWS-RPT Instrumentation NUREG(s)- 1434 Only One or more channels inoperable.

Action 3.3.5.1.B.3 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.C.2 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.D.2.1 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.E.2 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.F.2 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.1.G.2 ECCS Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.1-1.

Action 3.3.5.2.B.2 RCIC System Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

Action 3.3.5.2.D.2.1 RCIC System Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

Primary Containment Isolation Action 3.3.6.1.A Instrumentation NUREG(s)- 1434 Only One or more required channels inoperable.

RHR Containment Spray System Action 3.3.6.3.B.2 Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.3-1.

RHR Containment Spray System Action 3.3.6.3.C.2 Instrumentation NUREG(s)- 1434 Only As required by Required Action A.1 and referenced in Table 3.3.5.3-1.

Action 3.4.4.A S/RVs NUREG(s)- 1434 Only [One [required] S/RV inoperable.]

Action 3.5.1.A ECCS - Operating NUREG(s)- 1434 Only One low pressure ECCS injection/spray subsystem inoperable.

Action 3.5.1.B.2 ECCS - Operating NUREG(s)- 1434 Only High Pressure Core Spray (HPCS) System inoperable.

Two ECCS injection subsystems inoperable OR One ECCS injection and Action 3.5.1.C ECCS - Operating NUREG(s)- 1434 Only one ECCS spray subsystem inoperable.

Action 3.5.1.E ECCS - Operating NUREG(s)- 1434 Only One ADS valve inoperable.

9 of 9 Action Number TS Title Applicable NUREG Action Description One ADS valve inoperable AND One low pressure ECCS injection/spray Action 3.5.1.F ECCS - Operating NUREG(s)- 1434 Only subsystem inoperable.

Action 3.5.3.A.2 RCIC System NUREG(s)- 1434 Only RCIC System inoperable.

One or more penetration flow paths with one PCIV inoperable for reasons Action 3.6.1.3.A PCIVs NUREG(s)- 1434 Only other than Condition[s] D [and E] (for paths with two [or more] PCIVs.

Action 3.6.2.3.A RHR Suppression Pool Cooling NUREG(s)- 1434 Only One RHR suppression pool cooling subsystem inoperable.

Action 3.6.2.4.C SPMU System NUREG(s)- 1434 Only One SPMU subsystem inoperable for reasons other than Condition A or B.

One or more penetration flow paths with one drywell isolation valve Action 3.6.5.3.A.1 Drywell Isolation Valves NUREG(s)- 1434 Only inoperable.

Action 3.7.1.A [SSW] System and [UHS] NUREG(s)- 1434 Only [One or more cooling towers with one cooling tower fan inoperable.]

Action 3.7.1.C [SSW] System and [UHS] NUREG(s)- 1434 Only One [SSW] subsystem inoperable [for reasons other than Condition A].

Action 3.8.1.A.3 AC Sources - Operating NUREG(s)- 1434 Only One [required] offsite circuit inoperable.

Action 3.8.1.B.4 AC Sources - Operating NUREG(s)- 1434 Only One [required] DG inoperable.

Action 3.8.1.C.2 AC Sources - Operating NUREG(s)- 1434 Only Two [required] offsite circuits inoperable.

Action 3.8.1.D AC Sources - Operating NUREG(s)- 1434 Only One [required] offsite circuit inoperable and one [required] DG inoperable.

Action 3.8.1.F AC Sources - Operating NUREG(s)- 1434 Only One [required][automatic loac sequencer] inoperable.

Action 3.8.4.A.3 DC Sources - Operating NUREG(s)- 1434 Only One [or two] battery charger[s on one train] inoperable.

Action 3.8.4.B DC Sources - Operating NUREG(s)- 1434 Only One [or two] batter[y][ies on one train] inoperable.

One DC electrical power subsystem inoperable for reasons other than Action 3.8.4.C DC Sources - Operating NUREG(s)- 1434 Only Condition A [or B].

Action 3.8.7.A Inverters - Operating NUREG(s)- 1434 Only One [required] inverter inoperable.

Action 3.8.9.A Distribution Systems - Operating NUREG(s)- 1434 Only One or more AC electrical power distribution subsystems inoperable.

Action 3.8.9.B Distribution Systems - Operating NUREG(s)- 1434 Only One or more AC vital buses inoperable.

Action 3.8.9.C Distribution Systems - Operating NUREG(s)- 1434 Only One or more DC electrical power distribution subsystems inoperable.