05000440/FIN-2007005-09: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 1: Line 1:
{{finding
{{finding
| title = Adequacy Of Maintenance Associated With Emergency Service Water B Strainer Failure  
| title = Adequacy of Maintenance Associated with Emergency Service Water B Strainer Failure  
 
| docket = 05000440
| docket = 05000440
| inspection report = IR 05000440/2007005
| inspection report = IR 05000440/2007005
Line 13: Line 12:
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP 71111.19
| Inspection procedure = IP 71111.19
| Inspector = M Wilk, A Dahbur, G Wright, M Franke, J Cameronm, Wilk R, Jickling J, Robbins D, Reeser M, Franke B, Burgess J, Quichocho R, Leidy T, Mccall T, Taylo
| Inspector = M Wilk, A Dahbur, G Wright, M Franke, J Cameronm, Wilkr Jickling, J Robbins, D Reeser, M Franke, B Burgess, J Quichocho, R Leidy, T Mccall, T Taylor
| CCA = N/A for ROP
| CCA = N/A for ROP
| INPO aspect =  
| INPO aspect =  
| description = On December 27, 2007, an inspection port cover, about six inches wide and nine inches tall, associated with the B ESW pump discharge strainer fell off following a system test. The B ESW pump was started again and water discharged into the safety-related ESW pump house. ESW B was declared inoperable. The licensee determined during initial inspections that the cover fastener was potentially loose and that the cover had last been worked on during the refueling outage in April 2007. The licensee completed their initial investigation, repaired the B ESW strainer, and determined that no additional equipment damage had occurred due to the water discharge into the pump house. The licensee identified that a similar event occurred in year 1990 associated with the A ESW strainer. The licensee noted that some corrective actions associated with the year 1990 event were not maintained. In particular, a corrective design change was not completed and corrective periodic maintenance was not continued. The inspectors remained concerned about whether appropriate maintenance had been performed on the strainer and continued to evaluate the issue at the end of the inspection period.
| description = On December 27, 2007, an inspection port cover, about six inches wide and nine inches tall, associated with the B ESW pump discharge strainer fell off following a system test. The B ESW pump was started again and water discharged into the safety-related ESW pump house. ESW B was declared inoperable. The licensee determined during initial inspections that the cover fastener was potentially loose and that the cover had last been worked on during the refueling outage in April 2007. The licensee completed their initial investigation, repaired the B ESW strainer, and determined that no additional equipment damage had occurred due to the water discharge into the pump house. The licensee identified that a similar event occurred in year 1990 associated with the A ESW strainer. The licensee noted that some corrective actions associated with the year 1990 event were not maintained. In particular, a corrective design change was not completed and corrective periodic maintenance was not continued. The inspectors remained concerned about whether appropriate maintenance had been performed on the strainer and continued to evaluate the issue at the end of the inspection period.
}}
}}

Latest revision as of 23:03, 29 May 2018

09
Site: Perry FirstEnergy icon.png
Report IR 05000440/2007005 Section 1R19
Date counted Dec 31, 2007 (2007Q4)
Type: URI:
cornerstone No Cornerstone
Identified by: NRC identified
Inspection Procedure: IP 71111.19
Inspectors (proximate) M Wilk
A Dahbur
G Wright
M Franke
J Cameronm
Wilkr Jickling
J Robbins
D Reeser
M Franke
B Burgess
J Quichocho
R Leidy
T Mccall
T Taylor
INPO aspect
'