ENS 42995: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 11/16/2006 00:18 EST
| event date = 11/16/2006 00:18 EST
| last update date = 11/17/2006
| last update date = 11/17/2006
| title = Reactor Trip Due To Turbine Trip And Discovery Of After-The-Fact Emergency Condition Of An Unsual Event
| title = Reactor Trip Due to Turbine Trip and Discovery of After-The-Fact Emergency Condition of an Unsual Event
| event text = At 0018 Calvert Cliffs Unit 2 experienced an automatic reactor trip due to a turbine trip.  "At the time a clearance order was being performed for upcoming maintenance on P-13000-2 [transformer].  As a result of the turbine trip, RCS pressure rose to approximately 2420 psia causing the PORV's to open.  Unexpectedly, a Pressurizer Safety Valve, RV-200 also lifted and reclosed when RCS pressure was lowered to approximately 1500 psia.  As a result of the pressure decrease, a Safety Injection Actuation Signal (SIAS) occurred.  Once the Pressurizer Safety Valve reclosed, RCS pressure began to rise to return to normal values.
| event text = At 0018 Calvert Cliffs Unit 2 experienced an automatic reactor trip due to a turbine trip.  "At the time a clearance order was being performed for upcoming maintenance on P-13000-2 [transformer].  As a result of the turbine trip, RCS pressure rose to approximately 2420 psia causing the PORV's to open.  Unexpectedly, a Pressurizer Safety Valve, RV-200 also lifted and reclosed when RCS pressure was lowered to approximately 1500 psia.  As a result of the pressure decrease, a Safety Injection Actuation Signal (SIAS) occurred.  Once the Pressurizer Safety Valve reclosed, RCS pressure began to rise to return to normal values.
Decay heat is being removed via normal methods through the Turbine Bypass Valves to the Condenser.
Decay heat is being removed via normal methods through the Turbine Bypass Valves to the Condenser.

Latest revision as of 22:17, 1 March 2018

ENS 42995 +/-
Where
Calvert Cliffs Constellation icon.png
Maryland (NRC Region 1)
Reporting
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation

10 CFR 50.72(b)(3)(iv)(A), System Actuation
LER: 05000318/LER-2006-001
Time - Person (Reporting Time:+-2.27 h-0.0946 days <br />-0.0135 weeks <br />-0.00311 months <br />)
Opened: Kevin Umphrey
03:02 Nov 16, 2006
NRC Officer: Bill Gott
Last Updated: Nov 17, 2006
42995 - NRC Website
Loading map...