ML13169A238: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 2: Line 2:
| number = ML13169A238
| number = ML13169A238
| issue date = 06/14/2013
| issue date = 06/14/2013
| title = ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) Fpe 14
| title = NRR E-mail Capture - ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) Fpe 14
| author name = Feintuch K
| author name = Feintuch K
| author affiliation = NRC/NRR/DORL
| author affiliation = NRC/NRR/DORL
Line 18: Line 18:


=Text=
=Text=
{{#Wiki_filter:1 NRR-PMDAPEm Resource From:Feintuch, Karl Sent: Friday, June 14, 2013 5:21 PM To: Bob.Murrell@nexteraenergy.com; Swenzinski, Laura Cc: Faria-Ocasio, Carolyn
{{#Wiki_filter:NRR-PMDAPEm Resource From:                       Feintuch, Karl Sent:                       Friday, June 14, 2013 5:21 PM To:                         Bob.Murrell@nexteraenergy.com; Swenzinski, Laura Cc:                         Faria-Ocasio, Carolyn


==Subject:==
==Subject:==
ME6818-DAEC- Adoption of NFPA 805- Request fo r Additional Information (RAI) FPE 14 Follow Up Flag:
ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) FPE 14 Follow Up Flag:             Follow up Due By:                     Monday, July 01, 2013 1:30 PM Flag Status:                 Flagged By letter to the U.S. Nuclear Regulatory Commission (NRC) dated August 5, 2011 (Agencywide Documents Access and Management System Accession No. ML11221A280), NextEra Energy Duane Arnold, LLC (the Licensee) submitted a license amendment request (LAR). The licensee requested to transition their fire protection licensing basis at the Duane Arnold Energy Center (DAEC), from Title 10 of the Code of Federal Regulations (CFR), Section 50.48(b), to 10CFR50.48(c), National Fire Protection Association Standard 805 (NFPA 805).
Follow up Due By: Monday, July 01, 2013 1:30 PM Flag Status:
FlaggedBy letter to the U.S. Nuclear Regulatory Commission (NRC) dated August 5, 2011 (Agencywide Documents Access and Management System Accession No. ML11221A280), NextEra Energy Duane Arnold, LLC (the Licensee) submitted a license amendment request (LAR). The licensee requested to transition their fire protection licensing basis at the Duane Arnold Energy Center (DAEC), from Title 10 of the Code of Federal Regulations (CFR), Section 50.48(b), to 10CFR50.48(c), National Fire Protection Association Standard 805 (NFPA 805).  
 
The NRC staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed below. A clarification call was held with your staff on June 10, 2013.
The NRC staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed below. A clarification call was held with your staff on June 10, 2013.
Attending the June 10, 2013 conference call were:
Attending the June 10, 2013 conference call were:
Line 30: Line 27:
* For DAEC - Laura Swenzinski, William Cross, Jeff Kuehl, Roy Hanson, Thomas Carmody, and Mike Saunders (ERIN Eng)
* For DAEC - Laura Swenzinski, William Cross, Jeff Kuehl, Roy Hanson, Thomas Carmody, and Mike Saunders (ERIN Eng)
Fire Protection Request for Additional Information (RAI) FPE 14 With regards to how DAEC complies with the requirements of NFPA 805 Section 3.11.5:
Fire Protection Request for Additional Information (RAI) FPE 14 With regards to how DAEC complies with the requirements of NFPA 805 Section 3.11.5:
: 1. There appears to be discrepancies between LAR Attachment A, Table 4-3 and Attachment C with regard to Electrical Raceway Fire Barrier Systems (ERFBS) credited at DAEC. Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS) (page 138 of 138), states that DAEC complies with the requirement and states that "Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC". This product was tested to meet Generic Letter 86-10 Supplement 1". No other ERFBS is discussed.
: 1.     There appears to be discrepancies between LAR Attachment A, Table 4-3 and Attachment C with regard to Electrical Raceway Fire Barrier Systems (ERFBS) credited at DAEC.
However , Table 4-3, NFPA 805 Ch 4 Required FP Systems/Features and Attachment C, NEI 04-02 Table B Fire Area Transition both discuss an additional 3-hour ERFBS.
Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS) (page 138 of 138),
* Table 4-3, Fire Area TB1, Turbine Building, Fire Zones ID 07C (page 64) and 07H (page 66) list "Concrete Chase - Separation Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power."
states that DAEC complies with the requirement and states that Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC. This product was tested to meet Generic Letter 86-10 Supplement 1. No other ERFBS is discussed.
* Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries - Mechanical, includes a Comment "Feeders and control power to portions of the Div 2 electrical distribution credit a 3 hr ERFBS."
However, Table 4-3, NFPA 805 Ch 4 Required FP Systems/Features and Attachment C, NEI 04-02 Table B Fire Area Transition both discuss an additional 3-hour ERFBS.
2* Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries - Electrical includes a Comment "Div 2 RHRSW pumps, Div 2 River Water pumps and Div 2 ESW pump credit a 3 hr ERFBS."
* Table 4-3, Fire Area TB1, Turbine Building, Fire Zones ID 07C (page 64) and 07H (page 66) list Concrete Chase - Separation Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power.
* Attachment C, Fire Area TB1 (page 163 of 165), Required Fire Protection Systems and Features table lists "Passive, Concrete Chase, Separati on, Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power." Any ERFBS credited to meet NFPA 805 separation requirements using either a deterministic approach under NFPA 805 Section 4.2.3 or a performance-based approach under NFPA 805 Section 4.2.4 must meet the ERFBS requirements of NFPA 805 Section 3.11.5.
* Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries -
 
Mechanical, includes a Comment Feeders and control power to portions of the Div 2 electrical distribution credit a 3 hr ERFBS.
Provide additional information regarding the compliance status of the "concrete chase" used as an ERFBS in the Turbine Building with regard to NFPA 805 Section 3.11.5. Discuss the testing performed on this ERFBS, including the test rating obtained.
1
: 2. Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS), states that DAEC complies with the requirement and states that "Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC. This product was tested to meet Generic Letter 86-10 Supplement 1." There is no discussion regarding the results of the testing. NFPA 805 Section 3.11.5 states that "TheERFBS needs to adequately address the design requirements and limitations of supports and intervening items and their impact on the fire barrier system rating. The fire barrier's ability to maintain the required nuclear safety circuits free of fire damage for a specific thermal exposure, barrier design, raceway size and type, cable size, fill and type shall be demonstrated.
* Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries -
 
Electrical includes a Comment Div 2 RHRSW pumps, Div 2 River Water pumps and Div 2 ESW pump credit a 3 hr ERFBS.
* Attachment C, Fire Area TB1 (page 163 of 165), Required Fire Protection Systems and Features table lists Passive, Concrete Chase, Separation, Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power.
Any ERFBS credited to meet NFPA 805 separation requirements using either a deterministic approach under NFPA 805 Section 4.2.3 or a performance-based approach under NFPA 805 Section 4.2.4 must meet the ERFBS requirements of NFPA 805 Section 3.11.5.
Provide additional information regarding the compliance status of the concrete chase used as an ERFBS in the Turbine Building with regard to NFPA 805 Section 3.11.5. Discuss the testing performed on this ERFBS, including the test rating obtained.
: 2.     Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS), states that DAEC complies with the requirement and states that Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC. This product was tested to meet Generic Letter 86-10 Supplement 1.
There is no discussion regarding the results of the testing. NFPA 805 Section 3.11.5 states that The ERFBS needs to adequately address the design requirements and limitations of supports and intervening items and their impact on the fire barrier system rating. The fire barriers ability to maintain the required nuclear safety circuits free of fire damage for a specific thermal exposure, barrier design, raceway size and type, cable size, fill and type shall be demonstrated.
Provide a discussion on the results of the fire barrier testing performed in accordance with Generic Letter 86-10, Supplement 1 to meet NFPA 805 Section 3.11.5.
Provide a discussion on the results of the fire barrier testing performed in accordance with Generic Letter 86-10, Supplement 1 to meet NFPA 805 Section 3.11.5.
It was agreed that you would provide a response by July 3, 2013. The NRC considers that timely responses to requests for additional information help ensure sufficient time is available for the NRC staff review and contribute toward the NRC's goal of efficient and effective use of staff resources. Please contact Carolyn Faría at (301) 415-4050, if you have any questions.
It was agreed that you would provide a response by July 3, 2013. The NRC considers that timely responses to requests for additional information help ensure sufficient time is available for the NRC staff review and contribute toward the NRC's goal of efficient and effective use of staff resources.
Sincerely, Karl Feintuch  
Please contact Carolyn Faría at (301) 415-4050, if you have any questions.
Sincerely, Karl Feintuch Project Manager USNRC 2


Project Manager USNRC Hearing Identifier: NRR_PMDA Email Number: 725   Mail Envelope Properties   (26E42474DB238C408C94990815A02F09CAC511BA41)
Hearing Identifier:     NRR_PMDA Email Number:           725 Mail Envelope Properties     (26E42474DB238C408C94990815A02F09CAC511BA41)


==Subject:==
==Subject:==
ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) FPE 14 Sent Date:   6/14/2013 5:21:10 PM Received Date: 6/14/2013 5:21:12 PM From:   Feintuch, Karl Created By:   Karl.Feintuch@nrc.gov Recipients:     "Faria-Ocasio, Carolyn" <Carolyn.Faria-Ocasio@nrc.gov> Tracking Status: None "Bob.Murrell@nexteraenergy.com" <Bob.Murrell@nexteraenergy.com> Tracking Status: None "Swenzinski, Laura" <Laura.Swenzinski@fpl.com> Tracking Status: None Post Office:   HQCLSTR01.nrc.gov
ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI)
 
FPE 14 Sent Date:             6/14/2013 5:21:10 PM Received Date:         6/14/2013 5:21:12 PM From:                   Feintuch, Karl Created By:             Karl.Feintuch@nrc.gov Recipients:
Files     Size     Date & Time MESSAGE   4894     6/14/2013 5:21:12 PM
"Faria-Ocasio, Carolyn" <Carolyn.Faria-Ocasio@nrc.gov>
 
Tracking Status: None "Bob.Murrell@nexteraenergy.com" <Bob.Murrell@nexteraenergy.com>
Options Priority:     Standard   Return Notification:   No   Reply Requested:   No   Sensitivity:     Normal Expiration Date:     Recipients Received:   Follow up By 7/1/2013 1:30:00 PM}}
Tracking Status: None "Swenzinski, Laura" <Laura.Swenzinski@fpl.com>
Tracking Status: None Post Office:           HQCLSTR01.nrc.gov Files                           Size                     Date & Time MESSAGE                         4894                     6/14/2013 5:21:12 PM Options Priority:                       Standard Return Notification:           No Reply Requested:               No Sensitivity:                   Normal Expiration Date:
Recipients Received:           Follow up By 7/1/2013 1:30:00 PM}}

Latest revision as of 12:11, 5 December 2019

NRR E-mail Capture - ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) Fpe 14
ML13169A238
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 06/14/2013
From: Feintuch K
Division of Operating Reactor Licensing
To: Swenzinski L
NextEra Energy Duane Arnold
References
ME6818
Download: ML13169A238 (3)


Text

NRR-PMDAPEm Resource From: Feintuch, Karl Sent: Friday, June 14, 2013 5:21 PM To: Bob.Murrell@nexteraenergy.com; Swenzinski, Laura Cc: Faria-Ocasio, Carolyn

Subject:

ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI) FPE 14 Follow Up Flag: Follow up Due By: Monday, July 01, 2013 1:30 PM Flag Status: Flagged By letter to the U.S. Nuclear Regulatory Commission (NRC) dated August 5, 2011 (Agencywide Documents Access and Management System Accession No. ML11221A280), NextEra Energy Duane Arnold, LLC (the Licensee) submitted a license amendment request (LAR). The licensee requested to transition their fire protection licensing basis at the Duane Arnold Energy Center (DAEC), from Title 10 of the Code of Federal Regulations (CFR), Section 50.48(b), to 10CFR50.48(c), National Fire Protection Association Standard 805 (NFPA 805).

The NRC staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed below. A clarification call was held with your staff on June 10, 2013.

Attending the June 10, 2013 conference call were:

  • For DAEC - Laura Swenzinski, William Cross, Jeff Kuehl, Roy Hanson, Thomas Carmody, and Mike Saunders (ERIN Eng)

Fire Protection Request for Additional Information (RAI) FPE 14 With regards to how DAEC complies with the requirements of NFPA 805 Section 3.11.5:

1. There appears to be discrepancies between LAR Attachment A, Table 4-3 and Attachment C with regard to Electrical Raceway Fire Barrier Systems (ERFBS) credited at DAEC.

Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS) (page 138 of 138),

states that DAEC complies with the requirement and states that Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC. This product was tested to meet Generic Letter 86-10 Supplement 1. No other ERFBS is discussed.

However, Table 4-3, NFPA 805 Ch 4 Required FP Systems/Features and Attachment C, NEI 04-02 Table B Fire Area Transition both discuss an additional 3-hour ERFBS.

  • Table 4-3, Fire Area TB1, Turbine Building, Fire Zones ID 07C (page 64) and 07H (page 66) list Concrete Chase - Separation Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power.
  • Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries -

Mechanical, includes a Comment Feeders and control power to portions of the Div 2 electrical distribution credit a 3 hr ERFBS.

1

  • Attachment C, Fire Area TB1 (page 154 of 165), under Performance Goal 4, Vital Auxiliaries -

Electrical includes a Comment Div 2 RHRSW pumps, Div 2 River Water pumps and Div 2 ESW pump credit a 3 hr ERFBS.

  • Attachment C, Fire Area TB1 (page 163 of 165), Required Fire Protection Systems and Features table lists Passive, Concrete Chase, Separation, Required to protect cables for RHR Service Water, River Water, ESW and Division 2 AC Power.

Any ERFBS credited to meet NFPA 805 separation requirements using either a deterministic approach under NFPA 805 Section 4.2.3 or a performance-based approach under NFPA 805 Section 4.2.4 must meet the ERFBS requirements of NFPA 805 Section 3.11.5.

Provide additional information regarding the compliance status of the concrete chase used as an ERFBS in the Turbine Building with regard to NFPA 805 Section 3.11.5. Discuss the testing performed on this ERFBS, including the test rating obtained.

2. Attachment A, Element 3.11.5, Electrical Raceway Fire Barrier Systems (ERFBS), states that DAEC complies with the requirement and states that Limited amounts of Darmat KM1 are utilized for ERFBS at DAEC. This product was tested to meet Generic Letter 86-10 Supplement 1.

There is no discussion regarding the results of the testing. NFPA 805 Section 3.11.5 states that The ERFBS needs to adequately address the design requirements and limitations of supports and intervening items and their impact on the fire barrier system rating. The fire barriers ability to maintain the required nuclear safety circuits free of fire damage for a specific thermal exposure, barrier design, raceway size and type, cable size, fill and type shall be demonstrated.

Provide a discussion on the results of the fire barrier testing performed in accordance with Generic Letter 86-10, Supplement 1 to meet NFPA 805 Section 3.11.5.

It was agreed that you would provide a response by July 3, 2013. The NRC considers that timely responses to requests for additional information help ensure sufficient time is available for the NRC staff review and contribute toward the NRC's goal of efficient and effective use of staff resources.

Please contact Carolyn Faría at (301) 415-4050, if you have any questions.

Sincerely, Karl Feintuch Project Manager USNRC 2

Hearing Identifier: NRR_PMDA Email Number: 725 Mail Envelope Properties (26E42474DB238C408C94990815A02F09CAC511BA41)

Subject:

ME6818-DAEC- Adoption of NFPA 805- Request for Additional Information (RAI)

FPE 14 Sent Date: 6/14/2013 5:21:10 PM Received Date: 6/14/2013 5:21:12 PM From: Feintuch, Karl Created By: Karl.Feintuch@nrc.gov Recipients:

"Faria-Ocasio, Carolyn" <Carolyn.Faria-Ocasio@nrc.gov>

Tracking Status: None "Bob.Murrell@nexteraenergy.com" <Bob.Murrell@nexteraenergy.com>

Tracking Status: None "Swenzinski, Laura" <Laura.Swenzinski@fpl.com>

Tracking Status: None Post Office: HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 4894 6/14/2013 5:21:12 PM Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:

Recipients Received: Follow up By 7/1/2013 1:30:00 PM