{{#Wiki_filter:Moving Towards more Realistic Cabinet Damage Rob Cavedo
{{#Wiki_filter:Moving Towards more Realistic Cabinet Damage Rob Cavedo


Potential Realism Improvement Moving towards more Realistic Cabinet Damage 1 All trains and functions that can be affected by a fire are assumed to occur at the cabinet ignition frequency.
Potential Realism Improvement All trains and functions that can be affected by a fire are assumed to occur at the cabinet ignition frequency.
 
For most cabinets, this is a mildly conservative assumption (e.g. breaker goes open/breaker goes closed).
For most cabinets, this is a mildly conservative assumption (e.g. breaker goes open/breaker goes closed).
For cabinets that control multiple trains from different power supplies, this can be overly conservative.
For cabinets that control multiple trains from different power supplies, this can be overly conservative.
Industry events of cabinets with multiple trains do not show the loss of all trains (e.g. single alarm card damaged others functional, single HS malfunction, etc.).
1 Moving towards more Realistic Cabinet Damage


Industry events of cabinets with multiple trains do not show the loss of all trains (e.g. single alarm card damaged others functional, single HS malfunction, etc.).
Identification of Relevant Guidance NUREG/CR-6850 Section 8.5.1.2 (pg. 8-10) 2  Moving towards more Realistic Cabinet Damage


Identification of Relevant Guidance Moving towards more Realistic Cabinet Damage 2 NUREG/CR-6850 Section 8.5.1.2 (pg. 8
Proposed Approach to Enhance Realism Use a 25% chance all functions in a cabinet are lost and a 75% chance a single function is lost. This is based on a review of the sixteen control cabinet scenarios in the Fire Events Database (FEDB) only three are considered to represent broad damage to the cabinet.
-10)
A train is defined as any equipment in the cabinet powered from the same ultimate external power supply to the cabinet.
Proposed Approach to Enhance Realism Moving towards more Realistic Cabinet Damage 3 Use a 25% chance all functions in a cabinet are lost and a 75% chance a single function is lost. This is based on a review of the sixteen control cabinet scenarios in the Fire Events Database (FEDB) only three are considered to represent broad damage to the cabinet. A train is defined as any equipment in the cabinet powered from the same ultimate external power supply to the cabinet.
If all equipment in the cabinet is powered from the same external source, then this method cannot be applied.
If all equipment in the cabinet is powered from the same external source, then this method cannot be applied.
This would only apply to scenarios with NO EXTERNAL damage. If the fire is large enough to damage external equipment, then larger internal losses are expected.
This would only apply to scenarios with NO EXTERNAL damage. If the fire is large enough to damage external equipment, then larger internal losses are expected.
3  Moving towards more Realistic Cabinet Damage


Data for Proposed Approach to Enhance Realism Moving towards more Realistic Cabinet Damage 4 Data (3-of-16 is wide spread damage):
Data for Proposed Approach to Enhance Realism Data (3-of-16 is wide spread damage):
FireIDSpecific ComponentChallenging DeterminationEvent DateFire CharacterizationFire Characterization TypeExtent Source DamagePower Effect 69Control Cabinet4 U(NC-PC)8/29/1994Fire damaged cables in control cabinet (located in the Switchyard). Fire caused by breakdown of insulation in a control cable. The insulation breakdown was located where the insulation came in contact with a protruding tap of a wire wound power resistor.
Specific        Challenging FireID Component      Determination Event Date Fire Characterization                                              Fire Characterization Type      Extent Source Damage            Power Effect 69  Control Cabinet  4 U(NC-PC)   8/29/1994 Fire damaged cables in control cabinet (located in the Switchyard). Other (specify)                  Unknown                          Scram Fire caused by breakdown of insulation in a control cable. The insulation breakdown was located where the insulation came in contact with a protruding tap of a wire wound power resistor.
Insulation breakdown due to aging (25 years) and water intrusion. Other (specify)UnknownScram 98Control Cabinet2-PC10/8/1998During a 24 hour post maintenance run of the EDGSmoldering combustion - internal to componentConfined to the object of originEntered an LCO 187Control Cabinet2-PC8/16/1999thick grey smoke observedFlaming combustion - internal to componentConfined to the object of origin (broad/extensive damage)None 303Control Cabinet2-PC3/1/2000Electrical short resulting in burning insulation and paint in Plant Heating Boiler Control Cabinet.Flaming combustion - external to componentConfined to the object of origin (broad/extensive damage)None 20272Relay Rack4 U(NC-PC)9/10/1990UnknownOther (specify)Confined to the object of originUnknown 30276Other2-PC7/24/2006Lighting battery box smoking, flames observed coming out near transformerFlaming combustion - internal to componentConfined to the object of originNone 30281Relay Rack1-CH6/5/2008Failed relay in controm room cabinet due to overheating. Evidence of smoke, opened panel and saw relay with failed insulation. No flaming observed.Smoldering combustion - external to componentConfined to the object of origin (localized/single subcomponent)None 30338Control Cabinet2-PC3/30/2006Discovered fire in blower. Extinguished using CO2. Contacted electricians to investigate problem. Electricians disconnected the blower from its power source and removed the blower from the cabinet. Blower found to be full of dust and dirt. Smoke detecter in cabinet did not alarm while the area inside the panel was hazy with smoke.Flaming combustion - internal to componentConfined to the object of origin (localized/single subcomponent)None 30478Control Cabinet2-PC9/9/2005Source of fire a bunch of relays, wiring sustained significant damage to insulationFlaming combustion - internal to componentConfined to the object of origin (broad/extensive damage)None 30513Control Cabinet2-PC5/27/2008Voltage transformer overheated and ignited combustible material located inside transformer housingFlaming combustion - internal to componentConfined to the object of originNone 30522Control Cabinet2-PC9/12/2000fire kept to electrical cabinet. Damage to internals with noticable charring and smoke damage, external box had some heat and smoke damage.Flaming combustion - internal to componentConfined to the object of originNone 50473Wall Mounted2-PC6/26/2000small flames from relay with smoke, water intrusion, sparking and smoke before power removedFlaming combustion - internal to componentConfined to the object of originNone 50784Relay Rack2-PC11/20/2005Testing relay, started to smoke - fuses pulled and shot with extinguisherFlaming combustion - external to componentConfined to the object of origin (localized/single subcomponent)None 50811Control Cabinet2-PC1/9/2001relay burning, found extinguisher and put outFlaming combustion - internal to componentConfined to the object of origin (localized/single subcomponent)None83-1Wall Mounted2-PC4/4/1996Smoke was discovered in the back boards area of the control room by a security offer who was performing an hourly fire watch.
Insulation breakdown due to aging (25 years) and water intrusion.
Smoke was emitting from the emergency lightning UPS. Damage limited to cabinet involved and adjoining cablesFlaming combustion - internal to componentConfined to the object of origin (localized/single subcomponent)None83-2Wall Mounted2-PC4/4/1996DC EQUP room fire - fire limited to transformer enclosure and involved only internals. Flaming combustion - internal to componentConfined to the object of origin (localized/single subcomponent)None Example Moving towards more Realistic Cabinet Damage 5 Flow controllers for Pump A and B are in Cabinet X.
98  Control Cabinet    2-PC      10/8/1998 During a 24 hour post maintenance run of the EDG                    Smoldering combustion - internal Confined to the object of origin Entered an LCO to component 187  Control Cabinet    2-PC      8/16/1999 thick grey smoke observed                                          Flaming combustion - internal to Confined to the object of origin None component                        (broad/extensive damage) 303  Control Cabinet    2-PC      3/1/2000 Electrical short resulting in burning insulation and paint in Plant Flaming combustion - external to Confined to the object of origin None Heating Boiler Control Cabinet.                                    component                        (broad/extensive damage) 20272  Relay Rack      4 U(NC-PC)   9/10/1990 Unknown                                                            Other (specify)                 Confined to the object of origin Unknown 30276  Other              2-PC      7/24/2006 Lighting battery box smoking, flames observed coming out near       Flaming combustion - internal to Confined to the object of origin None transformer                                                        component 30281  Relay Rack          1-CH      6/5/2008 Failed relay in controm room cabinet due to overheating.           Smoldering combustion - external Confined to the object of origin None Evidence of smoke, opened panel and saw relay with failed         to component                    (localized/single subcomponent) insulation. No flaming observed.
30338  Control Cabinet    2-PC      3/30/2006 Discovered fire in blower. Extinguished using CO2. Contacted       Flaming combustion - internal to Confined to the object of origin None electricians to investigate problem. Electricians disconnected the component                        (localized/single subcomponent) blower from its power source and removed the blower from the cabinet. Blower found to be full of dust and dirt. Smoke detecter in cabinet did not alarm while the area inside the panel was hazy with smoke.
30478  Control Cabinet    2-PC      9/9/2005 Source of fire a bunch of relays, wiring sustained significant     Flaming combustion - internal to Confined to the object of origin None damage to insulation                                              component                        (broad/extensive damage) 30513  Control Cabinet    2-PC      5/27/2008 Voltage transformer overheated and ignited combustible material     Flaming combustion - internal to Confined to the object of origin None located inside transformer housing                                component 30522  Control Cabinet    2-PC      9/12/2000 fire kept to electrical cabinet. Damage to internals with noticable Flaming combustion - internal to Confined to the object of origin None charring and smoke damage, external box had some heat and         component smoke damage.
50473  Wall Mounted        2-PC      6/26/2000 small flames from relay with smoke, water intrusion, sparking and   Flaming combustion - internal to Confined to the object of origin None smoke before power removed                                        component 50784  Relay Rack          2-PC      11/20/2005 Testing relay, started to smoke - fuses pulled and shot with       Flaming combustion - external to Confined to the object of origin None extinguisher                                                      component                        (localized/single subcomponent) 50811  Control Cabinet    2-PC      1/9/2001 relay burning, found extinguisher and put out                      Flaming combustion - internal to Confined to the object of origin None component                        (localized/single subcomponent) 83-1  Wall Mounted        2-PC      4/4/1996 Smoke was discovered in the back boards area of the control room Flaming combustion - internal to    Confined to the object of origin None by a security offer who was performing an hourly fire watch.       component                        (localized/single subcomponent)
Smoke was emitting from the emergency lightning UPS. Damage limited to cabinet involved and adjoining cables 83-2  Wall Mounted        2-PC      4/4/1996 DC EQUP room fire - fire limited to transformer enclosure and       Flaming combustion - internal to Confined to the object of origin None involved only internals.                                          component                        (localized/single subcomponent) 4 Moving towards more Realistic Cabinet Damage


Given a per panel ignition frequency of 1E
Example Flow controllers for Pump A and B are in Cabinet X.
-4, the conservative and more realistic results are:
Given a per panel ignition frequency of 1E-4, the conservative and more realistic results are:
Conservative full Cabinet Improved Cabinet Only Loss      Modeling benefit is in Case  Description                          Impact                            Frequency      Frequency the Fire X1    Fire within Cabinet                  Both FC A and B Lost                7.00E-05      1.75E-05    within a X2    Fire within Cabinet                  FC A lost; FC B functional            N/A        2.63E-05    cabinet X3    Fire within Cabinet                  FC B lost; FC A functional            N/A        2.63E-05    region X4    Fire Damages cabinet and Target      FCs A and B Lost and 1st Target    2.80E-05      2.80E-05 X5    Fire Damages whole room              Whole Room Lost                    2.00E-06      2.00E-06 Sum Check    1.00E-04      1.00E-04 5 Moving towards more Realistic Cabinet Damage


Only benefit is in the Fire within a cabinet region Conservative full Cabinet LossImproved Cabinet ModelingCaseDescriptionImpactFrequencyFrequency X1Fire within CabinetBoth FC A and B Lost7.00E-051.75E-05 X2Fire within CabinetFC A lost; FC B functionalN/A2.63E-05 X3Fire within CabinetFC B lost; FC A functionalN/A2.63E-05 X4Fire Damages cabinet and TargetFCs A and B Lost  and 1st Target2.80E-052.80E-05 X5Fire Damages whole roomWhole Room Lost2.00E-062.00E-06Sum Check1.00E-041.00E-04 Industry Benefit Moving towards more Realistic Cabinet Damage 6 Maximum site benefit is 20% CDF reduction. The average industry benefit is 2%.
Industry Benefit Maximum site benefit is 20% CDF reduction. The average industry benefit is 2%.
6  Moving towards more Realistic Cabinet Damage


Questions Moving towards more Realistic Cabinet Damage 7}}
Questions 7 Moving towards more Realistic Cabinet Damage}}

Latest revision as of 19:07, 2 December 2019

Meeting Presentation, Moving Towards Mmre Realistic Cabinet Damage
ML17340B101
Person / Time
Site: Nuclear Energy Institute
Issue date: 12/13/2017
From: Cavedo R
Exelon Generation Co, Nuclear Energy Institute
To:
Document Control Desk, Office of Nuclear Reactor Regulation
Shared Package
ML17340B096 List:
References
Download: ML17340B101 (8)


Text

Moving Towards more Realistic Cabinet Damage Rob Cavedo

Potential Realism Improvement All trains and functions that can be affected by a fire are assumed to occur at the cabinet ignition frequency.

For most cabinets, this is a mildly conservative assumption (e.g. breaker goes open/breaker goes closed).

For cabinets that control multiple trains from different power supplies, this can be overly conservative.

Industry events of cabinets with multiple trains do not show the loss of all trains (e.g. single alarm card damaged others functional, single HS malfunction, etc.).

1 Moving towards more Realistic Cabinet Damage

Identification of Relevant Guidance NUREG/CR-6850 Section 8.5.1.2 (pg. 8-10) 2 Moving towards more Realistic Cabinet Damage

Proposed Approach to Enhance Realism Use a 25% chance all functions in a cabinet are lost and a 75% chance a single function is lost. This is based on a review of the sixteen control cabinet scenarios in the Fire Events Database (FEDB) only three are considered to represent broad damage to the cabinet.

A train is defined as any equipment in the cabinet powered from the same ultimate external power supply to the cabinet.

If all equipment in the cabinet is powered from the same external source, then this method cannot be applied.

This would only apply to scenarios with NO EXTERNAL damage. If the fire is large enough to damage external equipment, then larger internal losses are expected.

3 Moving towards more Realistic Cabinet Damage

Data for Proposed Approach to Enhance Realism Data (3-of-16 is wide spread damage):

Specific Challenging FireID Component Determination Event Date Fire Characterization Fire Characterization Type Extent Source Damage Power Effect 69 Control Cabinet 4 U(NC-PC) 8/29/1994 Fire damaged cables in control cabinet (located in the Switchyard). Other (specify) Unknown Scram Fire caused by breakdown of insulation in a control cable. The insulation breakdown was located where the insulation came in contact with a protruding tap of a wire wound power resistor.

Insulation breakdown due to aging (25 years) and water intrusion.

98 Control Cabinet 2-PC 10/8/1998 During a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> post maintenance run of the EDG Smoldering combustion - internal Confined to the object of origin Entered an LCO to component 187 Control Cabinet 2-PC 8/16/1999 thick grey smoke observed Flaming combustion - internal to Confined to the object of origin None component (broad/extensive damage) 303 Control Cabinet 2-PC 3/1/2000 Electrical short resulting in burning insulation and paint in Plant Flaming combustion - external to Confined to the object of origin None Heating Boiler Control Cabinet. component (broad/extensive damage) 20272 Relay Rack 4 U(NC-PC) 9/10/1990 Unknown Other (specify) Confined to the object of origin Unknown 30276 Other 2-PC 7/24/2006 Lighting battery box smoking, flames observed coming out near Flaming combustion - internal to Confined to the object of origin None transformer component 30281 Relay Rack 1-CH 6/5/2008 Failed relay in controm room cabinet due to overheating. Smoldering combustion - external Confined to the object of origin None Evidence of smoke, opened panel and saw relay with failed to component (localized/single subcomponent) insulation. No flaming observed.

30338 Control Cabinet 2-PC 3/30/2006 Discovered fire in blower. Extinguished using CO2. Contacted Flaming combustion - internal to Confined to the object of origin None electricians to investigate problem. Electricians disconnected the component (localized/single subcomponent) blower from its power source and removed the blower from the cabinet. Blower found to be full of dust and dirt. Smoke detecter in cabinet did not alarm while the area inside the panel was hazy with smoke.

30478 Control Cabinet 2-PC 9/9/2005 Source of fire a bunch of relays, wiring sustained significant Flaming combustion - internal to Confined to the object of origin None damage to insulation component (broad/extensive damage) 30513 Control Cabinet 2-PC 5/27/2008 Voltage transformer overheated and ignited combustible material Flaming combustion - internal to Confined to the object of origin None located inside transformer housing component 30522 Control Cabinet 2-PC 9/12/2000 fire kept to electrical cabinet. Damage to internals with noticable Flaming combustion - internal to Confined to the object of origin None charring and smoke damage, external box had some heat and component smoke damage.

50473 Wall Mounted 2-PC 6/26/2000 small flames from relay with smoke, water intrusion, sparking and Flaming combustion - internal to Confined to the object of origin None smoke before power removed component 50784 Relay Rack 2-PC 11/20/2005 Testing relay, started to smoke - fuses pulled and shot with Flaming combustion - external to Confined to the object of origin None extinguisher component (localized/single subcomponent) 50811 Control Cabinet 2-PC 1/9/2001 relay burning, found extinguisher and put out Flaming combustion - internal to Confined to the object of origin None component (localized/single subcomponent) 83-1 Wall Mounted 2-PC 4/4/1996 Smoke was discovered in the back boards area of the control room Flaming combustion - internal to Confined to the object of origin None by a security offer who was performing an hourly fire watch. component (localized/single subcomponent)

Smoke was emitting from the emergency lightning UPS. Damage limited to cabinet involved and adjoining cables 83-2 Wall Mounted 2-PC 4/4/1996 DC EQUP room fire - fire limited to transformer enclosure and Flaming combustion - internal to Confined to the object of origin None involved only internals. component (localized/single subcomponent) 4 Moving towards more Realistic Cabinet Damage

Example Flow controllers for Pump A and B are in Cabinet X.

Given a per panel ignition frequency of 1E-4, the conservative and more realistic results are:

Conservative full Cabinet Improved Cabinet Only Loss Modeling benefit is in Case Description Impact Frequency Frequency the Fire X1 Fire within Cabinet Both FC A and B Lost 7.00E-05 1.75E-05 within a X2 Fire within Cabinet FC A lost; FC B functional N/A 2.63E-05 cabinet X3 Fire within Cabinet FC B lost; FC A functional N/A 2.63E-05 region X4 Fire Damages cabinet and Target FCs A and B Lost and 1st Target 2.80E-05 2.80E-05 X5 Fire Damages whole room Whole Room Lost 2.00E-06 2.00E-06 Sum Check 1.00E-04 1.00E-04 5 Moving towards more Realistic Cabinet Damage

Industry Benefit Maximum site benefit is 20% CDF reduction. The average industry benefit is 2%.

6 Moving towards more Realistic Cabinet Damage

Questions 7 Moving towards more Realistic Cabinet Damage