- 05000280/LER-1975-026-01, /01T:on 751130,auxiliary Feedwater Pump Discharge Valve MOV-FW-151A Failed to Automatically Open When Main Feed Pumps Locked Out.Caused by Failure of Switch.Adjustment of Lever Arm Corrected Problem +
- 05000280/LER-1975-025-01, /01T:on 751129,uncontrolled & Unplanned Release of Low Level Radioactive Matl Occurred.Caused by Primary Grade Water Tank 1-PG-TK-1B Overflow Due to Operator Error. Administrative Action Taken +