- ML17317A931 + (22:02:08, 7 January 2025)
- 05000315/LER-1979-001-03, /03L-0 on 790122:during Mode 1,position of Rod F-6 Showed Deviation of Greater than 12 Steps from Demand Position.Caused by Drift in Signal Conditioning Module + (22:02:12, 7 January 2025)
- ML17317A929 + (22:02:14, 7 January 2025)
- 05000315/LER-1979-001, Forwards LER 79-001/03L-0 + (22:02:15, 7 January 2025)
- 05000316/LER-1979-003-03, /03L-0 on 790106:reactor Trip/Safety Injection Occurred.Caused by Freezing of Steam Generator/Main Steam Pressure Sensing Lines.Freezing Due to Failure to Close Off Steam Vent Openings in West Steam Encl + (22:02:17, 7 January 2025)
- 05000316/LER-1979-002-03, /03L-0 on 790106:during Startup,Auxiliary Feedwater Motor Operated Valve Would Not Close Due to Broken Wire in SMB-0-25 Operator.Caused by Vibration & Use of Solid Conductor + (22:02:19, 7 January 2025)
- ML17317A923 + (22:02:20, 7 January 2025)
- ML17317A922 + (22:02:21, 7 January 2025)
- ML17317A920 + (22:02:22, 7 January 2025)
- ML17317A918 + (22:02:22, 7 January 2025)
- ML17317A917 + (22:02:23, 7 January 2025)
- ML17317A915 + (22:02:24, 7 January 2025)
- ML17317A914 + (22:02:25, 7 January 2025)
- 05000316/LER-1979-001-03, /03L-0 on 790111:at 100% Power,Quadrant Power Tilt Ratio Alarm Per Tech Spec 4.2.4 Was in Error.Calculation of Tilt Ratio Is Required Every 12-h;first Survey Was Missed Because Alarm Instruments Were Being Calibr + (22:02:26, 7 January 2025)
- 05000316/LER-1979-001, Forwards LER 79-001/03L-0 + (22:02:28, 7 January 2025)
- ML17317A910 + (22:02:29, 7 January 2025)
- ML17317A909 + (22:02:30, 7 January 2025)
- ML17317A907 + (22:02:32, 7 January 2025)
- ML17317A906 + (22:02:32, 7 January 2025)
- 05000315/LER-1978-068-03, /03L-0 on 781221:during Rapid Power Reduction from 100% to 74% Axial Flux Difference Was Forced Outside Target Band Specified by Tech Specs.Inadvertent Feed Pump Turbine Trip Necessitated Load Reduction to Prevent Trip + (22:02:34, 7 January 2025)
- 05000315/LER-1978-067-03, /03L-0 on 781223:during Routine Surveillance Test on Solid State Protection Sys,Several Logic Functions in Train B Tested Unsatisfactorily.Test Card(Model 6056033G01) Had Failed & Was Replaced + (22:02:38, 7 January 2025)
- 05000315/LER-1978-067, Forwards LER 78-067/03L-0 & LER 78-068/03L-0 + (22:02:43, 7 January 2025)
- 05000316/LER-1978-031-03, /03X-1 on 780507:during Normal Operation Between 780507 & 780519 RPI Did Not Meet +/- 12 Step Limit of Tech Specs 22 Times.Caused by Recessed Pins in Connector + (22:02:47, 7 January 2025)
- ML17317A900 + (22:02:48, 7 January 2025)
- 05000316/LER-1978-022-03, /03X-1 on 780407:during Normal Operation,Position Indication for Rods D-12 & H-8 Exceeded +/- 12 Step Limit of Tech Specs.Outputs of Amplifiers That Feed Control Board Indicators Found to Be Incorrect + (22:02:50, 7 January 2025)
- 05000316/LER-1978-022, Forwards LER 78-022/03X-1, 78-031/03X-1 & 78-076/03X-1 + (22:02:52, 7 January 2025)
- ML17317A896 + (22:02:53, 7 January 2025)
- ML17317A891 + (22:02:55, 7 January 2025)
- ML17317A890 + (22:02:56, 7 January 2025)
- 05000315/LER-1978-066-03, /03L-0 on 781229:during Routine Startup,Rod Position Indication for Rods F-4,D-6 & K-6 Exceeded 12 Step Limit of Tech Specs.Caused by Drift of Signal Conditioning Modules + (22:02:58, 7 January 2025)
- 05000315/LER-1978-065-03, /03L-0 on 781229:indication for Pressurizer Level Channel 2 Deviated Approx 5% from Other 2 Channels.Caused by Gas Pocket in Sensing Line + (22:02:59, 7 January 2025)
- 05000315/LER-1978-042-03, /03X-1 on 780710:during Startup Testing,Flux Map Measurement Was Not Processed During Specified Time Limit. Though Flux Map Was Obtained,It Was Not Processed Due to Change in Manpower Requirements + (22:03:01, 7 January 2025)
- 05000315/LER-1978-038-03, /03X-1 on 780623:while in Mode 2,position of Rods C-3,C-13,N-13,H-6,F-8 & K-8 Indicated Deviation of Greater than 12 Steps from Demand Position.Caused by Signal Conditioning Modules + (22:03:03, 7 January 2025)
- 05000315/LER-1978-023-03, /03X-1 on 780312:during Containment Air Lock Leakage Test on 650 Foot Elevation Inner Door,Door Seal Leakage Rate Exceeded Tech Spec Limit,Caused by Paint Chips on Rubber Seal Which Obstructed Proper Seal on Door + (22:03:05, 7 January 2025)
- 05000315/LER-1978-023, Forwards LER 78-023/03X-1,LER 78-038/03X-1,LER 78-042/03X-1 LER 78-065/03L-0 & LER 78-066/03L-0 + (22:03:07, 7 January 2025)
- ML17317A878 + (22:03:09, 7 January 2025)
- ML17317A875 + (22:03:10, 7 January 2025)
- ML17317A877 + (22:03:10, 7 January 2025)
- ML17317A874 + (22:03:11, 7 January 2025)
- ML17317A872 + (22:03:12, 7 January 2025)
- 05000315/LER-1978-064-03, /03L-0 on 781214:during Surveillance Noted That Position of Rod M-8 Was Greater than Allowable 12 Step Limit.Caused by Maladjustment of Variable Shunt Resistor Contained in Control Board Indicator for Rod M-8 + (22:03:13, 7 January 2025)
- 05000315/LER-1978-064, Forwards LER 78-064/03L-0 + (22:03:15, 7 January 2025)
- 05000316/LER-1978-101-01, /01T-0 on 781223:both Control Room Pressurization Fans Were Inoperable.Caused by Water Seepage Into a Fire Protection Sys Switch,Resulting in Actuation of Fire Spray Sys & Lockout of the Fans + (22:03:17, 7 January 2025)
- ML17317A863 + (22:03:19, 7 January 2025)
- ML17317A862 + (22:03:20, 7 January 2025)
- 05000316/LER-1978-100-01, /01T-0 on 781217:containment APD(R-11)ran Out of Filter Paper & Caused High Flow Condition.Sample Pump Tripped,Rendered Containment Gaseous Monitoring Sys Inoperable.Caused by Need for Filter Paper in Sample Pump + (22:03:21, 7 January 2025)
- 05000316/LER-1978-100, Forwards LER 78-100/01T-0 + (22:03:23, 7 January 2025)
- IR 05000315/1978034 + (22:03:25, 7 January 2025)
- ML17317A855 + (22:03:26, 7 January 2025)
- IR 05000316/1978033 + (22:03:27, 7 January 2025)
- ML17317A847 + (22:03:29, 7 January 2025)