- B10546, Final Significant Deficiency Rept SD-23 Re Emergency Diesel Generator Shaft Spider Assembly.Initially Reported on 820628.Deficiency Resulted from Loose Stud & Nuts.S&W Will Retorque All Studs & Nuts + (18:14:21, 26 May 2025)
- 05000387/LER-1982-005-01, /01P-0:control Room Emergency Outside Air Supply Sys Failed to Automatically Start on Isolation Signal + (18:14:36, 26 May 2025)
- L-94-007, Forwards Revisions 10 & 11 to Security Plan for Point Beach Units 1 & 2.Withheld Per 10CFR1,50,70 & 73 + (18:15:09, 26 May 2025)
- 05000498/LER-1994-002, :on 940115,identified Centrifugal Charging Pump 1A Discharge Bypass Valve CV-MOV-8348 Opened.Caused by Hydropneumatic Transient.Mov Data Base Searched to Identify Other Valves Susceptible to Event + (18:15:27, 26 May 2025)
- TAC:M85515 + (18:15:31, 26 May 2025)
- ML20063J885 + (18:16:00, 26 May 2025)
- 05000280/LER-1982-045-03, /03L-0:on 820728,breaker for MOV-SW-202B Svc Water to CC HX Found Open W/Valve in Open Position.Cause Unknown. Breaker Closed & Returned to Svc + (18:17:17, 26 May 2025)
- ML20063H746 + (18:17:36, 26 May 2025)
- ML20063H691 + (18:17:47, 26 May 2025)
- ML20063H663 + (18:17:55, 26 May 2025)
- TAC:M85556 + (18:18:02, 26 May 2025)
- 05000272/LER-1981-009-01, /01X-2:on 810129,during Normal Operation, Containment Sump Pump Operation Indicated 4.3 Gpm of Unidentified Leakage.Caused by Magnetrol Level Indicator Operating Erratically + (18:18:16, 26 May 2025)
- 05000272/LER-1981-009, Forwards LER 81-009/01X-2.Detailed Event Analysis Encl + (18:18:20, 26 May 2025)
- L-94-004, Forwards Public & Central Files Versions of Revised Epips, Including Rev 15 to EPIP Form Index,Rev 1 to EPIP-1.3e & Rev 2 to EPIP-12.Central Files Version of Revised EPIPs Withheld + (18:18:23, 26 May 2025)
- ML20063H374 + (18:18:37, 26 May 2025)
- ML20063G878 + (18:19:30, 26 May 2025)
- L-94-005, Forwards Relief Request PTP-3-03 Associated W/Util Third Interval ASME Section XI Pressure Test Program + (18:19:48, 26 May 2025)
- 05000338/LER-1981-050-03, /03L-0:on 810615,individual Rod Position Indication for Rod J13 in Shutdown Bank a Deviated from Group Demand Position by Greater than 12 Steps.Caused by Instrument Drift.Channel for Rod J13 Properly Recalibr + (18:19:58, 26 May 2025)
- 05000338/LER-1981-050, Forwards LER 81-050/03L-0 + (18:20:03, 26 May 2025)
- 05000311/LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl + (18:20:34, 26 May 2025)
- ML20063F922 + (18:20:39, 26 May 2025)
- 05000249/LER-1982-018-03, /03X-1:on 820414,during Refueling Outage Quarterly Valve Timing Per Procedure DOS 1600-1,nitrogen Inerting Stop Valve 3-1601-55 Closure Time Exceeded Tech Specs.Caused by Hardening of Internal Seals.Valve Actuator Replaced + (18:21:24, 26 May 2025)
- 05000249/LER-1982-018, Forwards LER 82-018/03X-1 + (18:21:29, 26 May 2025)
- 05000346/LER-1982-006-03, /03L-1:on 820126,determination of Reportability Made Re 820113 Event.During Attempt to Start Component Cooling Water Pump 1-1,breaker AC113 Would Not Close.Caused by Worn Rack in Mechanism.Mechanism Replaced + (18:21:32, 26 May 2025)
- 05000346/LER-1982-006, Forwards LER 82-006/03L-1 + (18:21:36, 26 May 2025)
- 05000311/LER-1982-075, Forwards LER 82-075/01T-0.Detailed Event Analysis Encl + (18:21:57, 26 May 2025)
- ML20063F124 + (18:22:00, 26 May 2025)
- 05000263/LER-1981-017-03, While Removing Insulation,Cracks Discovered on 4-inch & 1-inch Reactor Water Cleanup HX Piping,Where Connected to Hx.Caused by Poor fit-up & Welding.Slag Line Removed & Weld Repaired + (18:22:17, 26 May 2025)
- 05000263/LER-1981-017, Forwards Updated LER 81-017/03L-1 + (18:22:20, 26 May 2025)
- 05000298/LER-1993-025, :on 930618,hydrogen/oxygen Monitoring Sys Operability Concerns Discovered Due to Moisture & Accumulation & Sample Pump Reliability.Design Change Implemented During 1993 Refueling Outage + (18:22:34, 26 May 2025)
- 05000280/LER-1982-044-03, /03L-0:on 820720,operators Noted RWST Temp Indicators Reading 44 F & 46 F.Calibr of Channels Revealed 46 F Correct & Above Limit.Caused by One Inoperable Refrigeration Unit + (18:22:50, 26 May 2025)
- 05000254/LER-1994-002, Forwards LER 94-002,Rev 0 Re B CR HVAC Being Inoperable Due to Failure of Compressor Motor Contactor.Hot Gas Bypass Sys for Compressor Will Be Installed to Minimize Cycling by Inducing Larger Heat Load on Compressor + (18:22:58, 26 May 2025)
- 05000261/LER-1981-002, Updated LER 81-002/01T-2:on 810113,review of Svc Water Sys Revealed Potential Unmonitored Release Path on Svc Water Return Lines from Containment for Hydrogen Vent Header Motor Coolers.Caused by Design Error.Sys Will Be Modifie + (18:23:30, 26 May 2025)
- 05000249/LER-1981-017-03, 3B Motor Generator Set Undervoltage Relay Failed to Trip on Undervoltage Signal. Caused by Sticking Relay Tripping Device.Tripping Device Cleaned,Lubed & Placed Back in Svc + (18:24:11, 26 May 2025)
- 05000249/LER-1981-017, Forwards Updated LER 81-017/03X-1 + (18:24:15, 26 May 2025)
- 05000249/LER-1982-025, Forwards LER 82-025/03L-0 + (18:25:28, 26 May 2025)
- 05000334/LER-1982-013-99, During Containment Structural Integrity Insp,Discovered Missing Vent Plug in Mainstream Line Liner Test Channel & Five Previously Unreported Bulges.Affected Portion Removed + (18:25:51, 26 May 2025)
- 05000334/LER-1982-013, Forwards Updated LER 82-013/99X-1 + (18:25:54, 26 May 2025)
- 05000333/LER-1981-066-03, /03X-1:on 810816,during Routine Startup operations,100 F Heatup/Rate Found Below Limit.Caused by Personnel Error.Evaluation Performed.No Effect on Reactor Vessel Life.Personnel Counseled + (18:26:07, 26 May 2025)
- 05000333/LER-1981-066, Forwards LER 81-066/03X-1 + (18:26:12, 26 May 2025)
- 05000255/LER-1982-016, Forwards LER 82-016/03L-0 + (18:26:35, 26 May 2025)
- 05000325/LER-1982-088, Forwards LER 82-088/03L-0 + (18:27:01, 26 May 2025)
- 05000280/LER-1982-064-03, /03L-0:on 820530,w/unit at 100% Power,Charging Pump Svc Water Pump 1-SW-P-10B Failed to Develop Sufficient Discharge Pressure.Caused by Insufficient Npsh.Svc Water to Chillers Throttled + (18:27:18, 26 May 2025)
- 05000280/LER-1982-030-03, /03L-0:on 820526,during Cold Shutdown,Preparations for Filling Reactor Coolant Loop a Resulted in RCS Boron Dilution.Caused by Temporary Malfunction of Boric Acid Flow Controller.Controller Functioning Properly + (18:27:23, 26 May 2025)
- 05000334/LER-1980-027-03, During Maint of Diesel Generator Lube Oil Cooler,Internals of River Water Check Valve Discovered in Cooler.Caused by Flutter Due to High Flow Conditions Eroding Hinge Pin Guide.Valve Replaced + (18:27:25, 26 May 2025)
- 05000334/LER-1980-027, Forwards Updated LER 80-027/03L-1 + (18:27:28, 26 May 2025)
- TAC:42921 + (18:28:32, 26 May 2025)
- 05000348/LER-1982-038-03, /03L-0:on 820727,determined That FNP-0-STP-130 (Fire Hose stations-monthly) & FNP-0-STP-132 (Hydrant Hose House insp-monthly) Not Performed within Required Time Interval.Caused by Personnel Error + (18:29:18, 26 May 2025)
- 05000260/LER-1982-010, Corrected LER 82-010/03L-0 on 811021,during Full Power,Avg Power Range Monitor Output Signal Calibr Was Not Performed within Required Frequency During 811014-28.Caused by Personnel Error.Personnel Instructed to Be More Careful + (18:30:04, 26 May 2025)
- ML20063C266 + (18:30:19, 26 May 2025)
- GO2-82-830, Forwards Application for Ol,Consisting of Fsar,Environ Rept (Filed in PDR Category C),Emergency Preparedness Plan (Filed in Central Files),Fire Protection Sys Info (Filed in PDR Category F) & Antitrust Info (Filed in PDR Category M) + (18:31:05, 26 May 2025)