- ML20008F988 + (07:17:02, 23 December 2024)
- 05000366/LER-1981-030, Forwards LER 81-030/03L-0 + (07:17:04, 23 December 2024)
- ML20008F985 + (07:17:06, 23 December 2024)
- ML20008F984 + (07:17:06, 23 December 2024)
- ML20008F983 + (07:17:07, 23 December 2024)
- ML20008F982 + (07:17:08, 23 December 2024)
- ML20008F980 + (07:17:09, 23 December 2024)
- ML20008F979 + (07:17:11, 23 December 2024)
- ML20008F978 + (07:17:12, 23 December 2024)
- ML20008F976 + (07:17:13, 23 December 2024)
- ML20008F975 + (07:17:14, 23 December 2024)
- 05000366/LER-1981-032-03, /03L-0:on 810410,HPCI Auxiliary Oil Pump Tripped During Second HPCI Sys Manual Initiation.Caused by Coil Failure in Time Delay Relay Not Allowing Relay Contact.Coil Replaced,Pump Rerun & Design Change Initiated + (07:17:16, 23 December 2024)
- ML20008F973 + (07:17:17, 23 December 2024)
- 05000254/LER-1981-009-03, /03L-0:on 810407,while 1A RHR Svc Water Pump Being Run for Packing Adjustment,Pump Failed to Meet Flow Requirements of 3,500 Gpm at 198 Psig.Caused by 3 Pieces of Wood in Pump Suction.Packing Sleeve & Bearings Replaced + (07:17:19, 23 December 2024)
- 05000366/LER-1981-029-03, /03L-0:on 810408,during 100% Power,Rcic Inboard Steam Supply Isolation Valve Could Not Be Reopened After Closing on Isolation Signal.Caused by Excessive Activation & Tripped Breaker.Breaker Reset & Valve Tested + (07:17:21, 23 December 2024)
- 05000366/LER-1981-032, Forwards LER 81-032/03L-0 + (07:17:23, 23 December 2024)
- 05000254/LER-1981-009, Forwards LER 81-009/03L-0 + (07:17:25, 23 December 2024)
- ML20008F966 + (07:17:27, 23 December 2024)
- 05000366/LER-1981-029, Forwards LER 81-029/03L-0 + (07:17:28, 23 December 2024)
- 05000366/LER-1981-040-03, /03L-0:on 810423,hydraulic Control Unit Accumulator Low Pressure Alarm Annunciated for Rod 46-23. Caused by Accumulator Pressure Having Bled Down Below Tech Spec Level.Accumulator Recharged & Restored + (07:17:30, 23 December 2024)
- 05000366/LER-1981-028-03, /03L-0:on 810407,during Steady State Operation, Electrolyte Level in Some Cells of 2R42-S001A & B Station Batteries & 2R42-S002A Diesel Generator Battery Found Above High Level Mark.Caused by Personnel & Procedure Errors + (07:17:32, 23 December 2024)
- ML20008F961 + (07:17:34, 23 December 2024)
- ML20008F960 + (07:17:35, 23 December 2024)
- 05000366/LER-1981-040, Forwards LER 81-040/03L-0 + (07:17:37, 23 December 2024)
- ML20008F957 + (07:17:39, 23 December 2024)
- 05000366/LER-1981-028, Forwards LER 81-028/03L-0 + (07:17:41, 23 December 2024)
- 05000321/LER-1981-030-03, /03L-0:on 810413,during Refueling outage,1C71- K751B & D,Rps M-G Set Overvoltage Relays & 1C71-K752C,RPS M-G Set Undervoltage Relay Did Not Actuate.Caused by Setpoint Drift.Relays Recalibr & Returned to Svc + (07:17:43, 23 December 2024)
- ML20008F953 + (07:17:44, 23 December 2024)
- 05000321/LER-1981-030, Forwards LER 81-030/03L-0 + (07:17:46, 23 December 2024)
- 05000339/LER-1981-033-03, /03L-0:on 810414,during Mode 1 Operation at 100% Power,B Train Quench Spray Subsys Removed from Svc to Repair Leaking Drain Valve on Pump Discharge Line.Valve Repaired & Disc Replaced.Pump Returned to Svc + (07:17:48, 23 December 2024)
- ML20008F948 + (07:17:49, 23 December 2024)
- 05000366/LER-1981-035-03, /03L-0:on 810413,during Steady State Operation, Reactor Bldg to Torus Vacuum Breaker Isolation valve,2T48- F310,failed to Open Due to Failure of Differential Pressure switch,2T48-N210.Mechanism Cleaned.New Switch Ordered + (07:17:51, 23 December 2024)
- 05000339/LER-1981-033, Forwards LER 81-033/03L-0 + (07:17:52, 23 December 2024)
- 05000338/LER-1981-023-03, /03L-0:on 810411,individual Rod Position Indication for Rod B-08 in Control Bank D Deviated from Group Demand Position.Caused by Instrument Drift.Indicator Channel Recalibr + (07:17:54, 23 December 2024)
- 05000338/LER-1981-023, Forwards LER 81-023/03L-0 + (07:17:57, 23 December 2024)
- 05000315/LER-1981-010, Forwards LER 81-010/03L-0 + (07:18:00, 23 December 2024)
- ML20008F935 + (07:18:09, 23 December 2024)
- ML20008F929 + (07:18:16, 23 December 2024)
- ML20008F930 + (07:18:16, 23 December 2024)
- ML20008F928 + (07:18:17, 23 December 2024)
- ML20008F926 + (07:18:18, 23 December 2024)
- ML20008F925 + (07:18:19, 23 December 2024)
- ML20008F924 + (07:18:20, 23 December 2024)
- 05000245/LER-1981-006-03, /03L-0:on 810417,one of Two Ventilation Duct Radiation Monitors Was Found to Trip Outside Allowable Range.Caused by Setpoint Drift Due to Failed Sensor Converter.Converter Replaced + (07:18:22, 23 December 2024)
- ML20008F922 + (07:18:23, 23 December 2024)
- 05000245/LER-1981-006, Forwards LER 81-006/03L-0.Detailed Event Analysis Encl + (07:18:25, 23 December 2024)
- ML20008F919 + (07:18:26, 23 December 2024)
- ML20008F918 + (07:18:26, 23 December 2024)
- AECM-81-159, Final Deficiency Rept Re Reactor Pressure Vessel Level Sensing Lines,Initially Reported 800808.AE Has Completed Pipe Sleeve Extension to Recirculation Discharge Line Penetrations in Shield Wall.Corrections Completed 810601 + (07:18:27, 23 December 2024)
- ML20008F916 + (07:18:29, 23 December 2024)
- ML20008F915 + (07:18:29, 23 December 2024)