Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000366/LER-1982-001, Forwards LER 82-001/03L-0 + (03:02:05, 20 December 2024)
- ML20040C713 + (03:02:06, 20 December 2024)
- 05000278/LER-1981-021-03, /03L-0:on 811211,D Core Spray Pump Failed to Start During Surveillance Test Due to Failure of Pump Breaker to Close.Cause Not Determined.Failed Breaker Replaced & Checked Daily for 2 Wks to Verify Core Spray Sys Operability + (03:02:08, 20 December 2024)
- 05000327/LER-1981-157, Forwards LER 81-157/03L-0 + (03:02:09, 20 December 2024)
- ML20040C709 + (03:02:11, 20 December 2024)
- ML20040C708 + (03:02:11, 20 December 2024)
- ML20040C706 + (03:02:13, 20 December 2024)
- 05000321/LER-1981-143-03, /03L-0:on 811230,LPCI Reactor Level Switch, 1B21-N031A,contact on Switch 2,failed to Actuate at Tech Spec Levels.Caused by Bad Contact on Switch 2.Switch Replaced,Recalibr & Returned to Svc + (03:02:17, 20 December 2024)
- 05000309/LER-1982-001-03, /03L-0:on 811223,cracks Found in 0.5-inch Lines During Maint on Leaking Ball Valve.Caused by Frozen Lines Due to Failure of Heat Tracing on Recirculation Flow Transmitter Lines.Valve Parts & Heat Tracing Repaired + (03:02:19, 20 December 2024)
- ML20040C702 + (03:02:21, 20 December 2024)
- ML20040C703 + (03:02:21, 20 December 2024)
- ML20040C701 + (03:02:22, 20 December 2024)
- 05000321/LER-1981-143, Forwards LER 81-143/03L-0 + (03:02:24, 20 December 2024)
- ML20040C698 + (03:02:25, 20 December 2024)
- 05000271/LER-1981-036-03, /03L-0:on 811217,containment Isolation Valve CU-15 Failed to Seat Satisfactorily Per Tech Spec 4.7.D.1 During Quarterly Surveillance Testing.Caused by Failure of Closing Torque Switch.Torque Switch Will Be Replaced Next Shut + (03:02:27, 20 December 2024)
- 05000309/LER-1982-001, Forwards LER 82-001/03L-0 + (03:02:28, 20 December 2024)
- ML20040C694 + (03:02:30, 20 December 2024)
- 05000335/LER-1981-055-03, /03L-0:on 811219,during Normal Reactor Startup, Surveillance Requirement to Manually Trip Rx Trip Breakers Not Performed Per Tech Spec Limits.Caused by Personnel Error + (03:02:32, 20 December 2024)
- ML20040C692 + (03:02:33, 20 December 2024)
- ML20040C691 + (03:02:34, 20 December 2024)
- 05000320/LER-1981-037-03, /03L-0:on 811217,high Motor Bearing Temp Alarm Annunciated in Control Room for Nuclear Svc River Water Pump NR-P-1B.Caused by Failure of Lower Motor Bearing.Motor Replaced.Investigation Continuing + (03:02:35, 20 December 2024)
- 05000271/LER-1981-036, Forwards LER 81-036/03L-0 + (03:02:37, 20 December 2024)
- ML20040C687 + (03:02:39, 20 December 2024)
- PNO-II-82-012, on 820119,turbine & Reactor Tripped Due to High Water Level in Steam Generator 2 During Automatic Feed Control Sys Adjustment.Feedwater Isolation Resulted in Low Water Level in Steam Generator 1 Actuating Trip + (03:02:41, 20 December 2024)
- 05000311/LER-1981-131-03, /03L-0:on 811228,low Reading Noticed on 24 Reactor Coolant Loop Flow Channel 2.Channel Declared Inoperable. Caused by Failure of Flow Transmitter.Flow Transmitter Replaced & Calibr Satisfactorily + (03:02:42, 20 December 2024)
- 05000320/LER-1981-037, Forwards LER 81-037/03L-0 + (03:02:44, 20 December 2024)
- 05000335/LER-1981-055, Forwards LER 81-055/03L-0 + (03:02:46, 20 December 2024)
- 05000338/LER-1981-089-03, /03L-0:on 811217,during 99% Power,Turbine Driven Auxiliary Feedwater Pump Removed from Svc for Insp of Three Upsteam Check Valves.One Valve Found Missing Disc Nut,Washer & Retaining Pin.Parts Replaced on All Three Valves + (03:02:47, 20 December 2024)
- ML20040C679 + (03:02:49, 20 December 2024)
- 05000311/LER-1981-131, Forwards LER 81-131/03L-0.Detailed Event Analysis Encl + (03:02:53, 20 December 2024)
- ML20040C675 + (03:02:54, 20 December 2024)
- ML20040C674 + (03:02:55, 20 December 2024)
- ML20040C673 + (03:02:55, 20 December 2024)
- ML20040C671 + (03:02:56, 20 December 2024)
- ML20040C672 + (03:02:56, 20 December 2024)
- 05000338/LER-1981-089, Forwards LER 81-089/03L-0 + (03:03:00, 20 December 2024)
- ML20040C666 + (03:03:02, 20 December 2024)
- 05000327/LER-1981-159-03, /03L-0:on 811221,auxiliary Feedwater Pressure Control Valve 1-PCV-3-132 Failed to Respond During Performance of SI-166.1.Caused by Failure of Hydraulic Pump on Valve Operator to Deliver Discharge Pressure + (03:03:03, 20 December 2024)
- 05000302/LER-1981-078-03, /03L-0:on 811208,during Normal Operation,Emergency Feedwater Ultrasonic Flow indicator,FW-313-FI Exceeded Zero Check Low Limit.Caused by Inability of Instrument to Consistently Indicate Zero Flow.Instrument re-zeroed + (03:03:05, 20 December 2024)
- 05000219/LER-1981-068-03, /03L-0:on 811218,reactor Triple Low Water Level Indicator Switch RE18A Tripped at Monometer Reading Exceeding Tech Spec Limit.Caused by Instrument Drift.Switch Reset.Setpoint Sensors Will Be Replaced + (03:03:07, 20 December 2024)
- ML20040C661 + (03:03:08, 20 December 2024)
- ML20040C662 + (03:03:08, 20 December 2024)
- ML20040C659 + (03:03:10, 20 December 2024)
- 05000327/LER-1981-159, Forwards LER 81-159/03L-0 + (03:03:11, 20 December 2024)
- 05000366/LER-1981-134-03, /03L-0:on 811230,while Operator in Process of Synchronizing Diesel Generator w/4,160-volt G Emergency Bus, Diesel Tripped.Caused by Pressure Fluctuation in Jacket Coolant Subsystem.Affected Pressure Switch Checked + (03:03:12, 20 December 2024)
- 05000302/LER-1981-078, Forwards LER 81-078/03L-0.Detailed Analysis Encl + (03:03:14, 20 December 2024)
- IR 05000244/1981012 + (03:03:16, 20 December 2024)
- ML20040C652 + (03:03:17, 20 December 2024)
- 05000219/LER-1981-068, Forwards LER 81-068/03L-0.Detailed Event Analysis Encl + (03:03:18, 20 December 2024)
- 05000259/LER-1981-091-03, /03L-0:on 811220,FCO 31-152 Would Not Open During Performance of SI 4.2.G-2,rendering B Control Room Emergency Ventilation Inoperable.Caused by Failure of Modutrol Motor for Fco 31-152 Due to Open Windings.Motor Replaced + (03:03:20, 20 December 2024)
- ML20040C648 + (03:03:21, 20 December 2024)