ML20040C673

From kanterella
Jump to navigation Jump to search
RO 219/82-01:on 820117,fire Diesels 1-1 & 1-2 Shut Down for Maint,Rendering Fire Suppression Water Sys Inoperable.Caused by Frozen Cooling Water Lines & Fuel Oil Due to Failure of Two Space Heaters.Heaters Replaced
ML20040C673
Person / Time
Site: Oyster Creek
Issue date: 01/18/1982
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
RO-219-82-01, RO-219-82-1, NUDOCS 8201290141
Download: ML20040C673 (3)


Text

f DESIGUATED ORIGI1?AL

' Certified By h8db b -

10: Ronald Haynes Directorate of Regulatory Operations Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 FRCI4: Jersey Central Power & Light Carpany Oyster Creek Nuclear Generating Station Docket No. 50-219 Forked River, New Jersey 08731 SUBJDCT: Special Report confirnung the telephone notification of Fire Protection Systen inoperability in accordance with g Technical Specifications 3.12.B.3

, m N

O REcy,VED 2.

g. ,
nef2Y19Q C Prelunnary Approval:

h /

e

.{<p J bb -

D

[ J.' T. Carroll, Jr.

Acting Director Oyster

/

/

/v Director (2)

Cffice of Marugment Inforrtation and j Program Control U.S. Nuclear Pegulatory Comnission Washington, D. C. 20555 NRC Resident Inc.pector (1) vister Creek Nuclear Generating S:c*. ion Forked River, N. J.

8201290141 820118 PDR ADOCK 05000219 S ppg qg

[/

OYSTER CREEK NUCLEAR GENERATING STATION Forked River, New Jersey 08731 i

Sp mini Report No. 82-1 i

Report Date January 18, 1982 Occurrence Date January 17, 1982 Telephone Report Date January 18, 1982 Time of Occurrence 1940 hours0.0225 days <br />0.539 hours <br />0.00321 weeks <br />7.3817e-4 months <br /> Identificationodoccurrence i

Fire suppression water syst s inoperable.

This event is considered to be reportable as defined in the Technical Specificatiana, paragraph 3.12.B.J(2) .

Conditions Prior to Occurrence Routine Shtitdown Operation Power: 0 Mht 0 bMe FlcN: Rocirculation: 5 x 410 p Feed: 0 lbs/hr.

Description of Occurrence On Sunday, January 17, 1982, the fire suppression water systen at Oyster Creek was declared inoperable. 1-2 fire diesel had started for no apparent reason and in the process overheated and was shutdown for maintenance. An operability.

Lest was perfprmed on 1-1 fire diesel to assure its availability. 1-1 fire diesel was subequently declared inoperable in light of the fact that it could not maintain proper engine speed and discharge pressure. A check of the electrically operated redtni?.nt fire suppression water systen revealed it too i was inoperable due to freezi:q of various instrumentation lines.

i e - r e.- 4e-_-_ -

s Special N port No. 82-1 Page 2 Apparent Cause of Occurrence Extremely low ambient taperature.

The cause of failure of the diesel fire pxps is attributed to extreely it.w ambient tmperatures. he low tenperatures caused frozen cooling water lines, one of which broke. In aMition, the fuel oil cooled below the cloud point which caused partial clogging of the fuel filters. Initiation of the 1-2 fire diesel pump was esased by ci frozen pressure sensing line. W e low ta peratures in the Fire Pmp livuse were the result of the malfunction of two of four installed:-

space heaters. The cause of failure of the electrically operated redundant fire protection systm was loss of pressure control due to frozen sensing lines.

Corrective Action l

me space heaters were repaired and returned to service. The cooling water line to 1-2 Diesel Fire Ptmp was repaired and operability tests on both diesels were .;

performed. Both diesel fire pumps were declared operable at 1310 hours0.0152 days <br />0.364 hours <br />0.00217 weeks <br />4.98455e-4 months <br /> on January 12, 1982. The redundant fire protection syste remains out of service at this tune.

Prepared by: w(([ /m,I Date: /// 7 2.'

D 4

s