- 05000206/LER-1989-023, :on 890918,four Control Rods from Shutdown Bank 2 Dropped Into Core & Approx 23 Later,Remaining 12 Shutdown Bank Control Rods Dropped Into Core.Caused by Failure of Contactor Coil 2MS1.Coil Replaced + (06:00:07, 11 January 2025)
- 05000206/LER-1989-001-01, :on 890108,observed That Reactor Vessel Thermal Shield Support Block Bolts Out of Tolerance.Caused by high-cycle Flow Induced Vibration.Conceptual Design & Plan for Restoring Thermal Shield Support Initiated + (06:00:11, 11 January 2025)
- 05000206/LER-1989-020, :on 890723,both Fuse Blocks for Emergency Siren Transfer Switch Installed in Violation of Tech Specs. Caused by Failure to Document Manipulation of safety-related Equipment.Sign Installed on Fuse Blocks + (06:00:17, 11 January 2025)
- 05000206/LER-1989-019, :on 890724,unit Manually Tripped Due to Loss of Feedwater Flow to Steam Generator a & Hi Hi Level & Steam/ Feed Mismatch Alarm Received.Caused by Error in Incorporating Design Change Info + (06:00:20, 11 January 2025)
- 05000206/LER-1989-016, :on 890703,air Flow Test of Lube Oil Reservoir & Conditioner Fire Protection Sys Revealed That Approx 20 of 78 Nozzles Plugged.Caused by Accumulation of Piping Corrosion Matl Inside Fire Spray Header + (06:00:24, 11 January 2025)
- 05000206/LER-1989-014, :on 890405,determined That Unlimited Operation of Dc Buses on cross-train Chargers Unwarranted Condition. Caused by Failure to Develop Appropriate Tech Specs.Design Change Re Train Alignment Completed + (06:00:27, 11 January 2025)
- PNO-V-89-040, on 890703,shutdown for Greater than 48 H Occurred to Troubleshoot Reactor Coolant Pump Bearing Oil Problem.Oil Not Contaminated W/Metal or Water + (06:00:30, 11 January 2025)
- ML13331A334 + (06:00:32, 11 January 2025)
- 05000206/LER-1989-012, :on 890525,auxiliary Feedwater Sys Train a Actuation Occurred When wide-range Steam Generator Level Signals Decreased Below Actuation Setpoint.Caused by Effects of Internal Circulation Flow + (06:00:35, 11 January 2025)
- ML13331A332 + (06:00:37, 11 January 2025)
- ML13331A331 + (06:00:38, 11 January 2025)
- ML13331A330 + (06:00:40, 11 January 2025)
- 05000206/LER-1989-017, :on 890503,reactor Protection Sys Actuation Occurred While Withdrawing Control Bank II (Cbii).Caused by Spikes Generated by Sources Associated W/Cbii Due to Stored Energy Dissipation.Circuit Mods Installed + (06:00:43, 11 January 2025)
- ML13331A328 + (06:00:45, 11 January 2025)
- PNO-V-89-032, on 890525,auxiliary Feedwater Sys Actuation Occurred.Caused by Low Level Indication on Wide Range Instruments Modified as Part of Auxiliary Feedwater Sys Upgrades During Last Outage + (06:00:49, 11 January 2025)
- PNO-V-89-029, on 890517,startup Aborted Due to Unstable Intermediate Range Indications.Caused by Apparent Electronic Noise.Unit Remains in Mode 3,with Addl Troubleshooting of Nuclear Instrument Sys in Progress + (06:00:53, 11 January 2025)
- 05000206/LER-1989-013, :on 890404,discovered That Inservice Testing Program for Valves Did Not Include Open Response Time for Two RCS Porvs.Caused by Failure to Recognize Impact of Tech Spec Change.Porvs Included in Program + (06:00:57, 11 January 2025)
- PNO-V-89-023, on 890407,magnitude 4.6 Earthquake Occurred Near Newport Beach,Ca.Telephone Contact W/Univ of California Established That Reactor Shutdown Prior to Earthquake.Util Reported No Damage to Facility + (06:01:03, 11 January 2025)
- 05000206/LER-1989-008, :on 890303,determined That Possibility Exists That Containment Fire Suppression Sys Pneumatic Control Valve CV-92 Could Fail Open Due to Single Spurious Failure of Solenoid Valve.Training Program Initiated + (06:01:06, 11 January 2025)
- 05000206/LER-1989-004-01, :on 890302,identified Design Deficiency Associated W/Automatic Energization of safety-related 4 Kv Buses.Caused by Deficiencies W/Engineering Review & Design Basis Documentation.Training Program Initiated + (06:01:10, 11 January 2025)
- PNO-V-89-020, on 890329,33 Gpm Leak Identified from Seal Package for Reactor Coolant Oil Lift Pump A,Jogging Pump & Raising RCS Pressure.Rcs Pressure Lowered to Atmospheric Pressure.Methods for Correcting Problem Under Review + (06:01:14, 11 January 2025)
- 05000206/LER-1989-007, :on 890227,evaluation Determined That Design Provisions Intended to Trip Reactor in Event of Reactor Coolant Pump Locked Rotor Did Not Satisfy Single Failure Criterion.Caused by Absence of Documentation + (06:01:16, 11 January 2025)
- 05000206/LER-1989-005-01, :on 890220 & 0317,emergency Diesel Generator 2 Automatically Started.Caused by Loss of Bus Signal from Sequencer 2.All Components & Wiring Associated W/Possible Root Causes Candidates Replaced & Tested + (06:01:19, 11 January 2025)
- ML13331A314 + (06:01:26, 11 January 2025)
- ML13331A313 + (06:01:27, 11 January 2025)
- ML13331A312 + (06:01:29, 11 January 2025)
- ML13331A311 + (06:01:30, 11 January 2025)
- 05000206/LER-1989-002-01, :on 890123,positive Reactivity Addition Occurred When Reactor Refueling Water Cavity Level Reduced & Cavity Surfaces Decontaminated.Caused by Misapplication of Positive Reactivity Guidance.Event Reviewed + (06:01:32, 11 January 2025)
- 05000206/LER-1989-001, :on 890108,reactor Vessel Thermal Shield Support Block Bolts Out of Tolerance.Caused by Support Sys Degradation.Monitoring Program Is Being Developed to Detect Changes in Thermal Vibration + (06:01:34, 11 January 2025)
- PNO-V-89-008, on 890118,magnitude 5 Earthquake Occurred 8 Miles South of Malibu,Ca.Earthquake Felt at Atomics Intl Facility But Not at Other Facilities + (06:01:37, 11 January 2025)
- 05000206/LER-1988-019-01, :on 881213,determined That Design Deficiencies Existed in Automatic Controls for Electrical Power Distribution Sys.Caused by Placing Excessive Reliance on Contractors.Training Program Initiated + (06:01:40, 11 January 2025)
- 05000206/LER-1988-018-01, :on 881212,structural Integrity of Steam Generator Sleeved Tubes Not in Accordance W/Design Requirements.Caused by Limitations of Eddy Current Test Technology Due to Misinterpretation of Data + (06:01:43, 11 January 2025)
- 05000206/LER-1988-021-01, :on 881212 & 13,containment Fire Protection Spray Inoperable Due to Plugged Nozzles.Caused by Piping Corrosion.Air Will Be Blown to Ensure Corrosion Products or Blockage Completely Removed + (06:01:46, 11 January 2025)
- 05000206/LER-1988-020-01, :on 881208,failure to Fully Implement Design Requirements of NUREG-0737 in Design of Steam Generator wide-range Level Indication Sys Occurred.Cause Under Inquiry.Corrective Actions Will Be Implemented + (06:01:48, 11 January 2025)
- ML13331A302 + (06:01:51, 11 January 2025)
- 05000206/LER-1988-017-01, :on 881202,discovered That Calculation Which Provides Basis for Min Tech Spec Vol Did Not Account for Pump G10S Bearing Cooling Water Flow.Caused by Personnel Error.Training Program Initiated + (06:01:53, 11 January 2025)
- ML13331A297 + (06:01:56, 11 January 2025)
- ML13331A295 + (06:01:58, 11 January 2025)
- TAC:67322 + (06:02:00, 11 January 2025)
- ML13331A293 + (06:02:01, 11 January 2025)
- 05000206/LER-1988-016-01, :on 881130,determined That Wiring Discrepancy, Associated W/South Refueling Water Pump,Could Adversely Affect Containment Spray Function.Caused by Not Removing Wire During Circuit Mods.Wire Removed + (06:02:04, 11 January 2025)
- 05000206/LER-1988-015-01, :on 881114,performance of Local Leakage Rate Tests (LLRT) on 880720 at Below Required Pressure Discovered.Caused by Cognitive Personnel Error.Assessment of LLRT Procedure Will Be Performed + (06:02:07, 11 January 2025)
- ML13331A288 + (06:02:10, 11 January 2025)
- 05000206/LER-1988-004-01, :on 880215,bonnet Bleed Off Solenoid Valve SV-3900,for Safety Injection Isolation Valve HV-851B,failed to Open.Caused by Crack in Sleeve in Which Valve Disc Moves on Opening + (06:02:12, 11 January 2025)
- 05000206/LER-1987-017, :on 871201,remotely Operated,Normally Closed, Containment Isolation Valves in Vent Line Did Not Close Upon Demand Upon Completion of Venting of Loop B Header.Seats of Valves Found Worn & Warped.Valves Replaced + (06:02:14, 11 January 2025)
- ML13331A285 + (06:02:16, 11 January 2025)
- 05000206/LER-1988-008-01, :on 880524,inadvertent Omission of Safety Injection Vent Valves from Local Leak Rate Testing Program. Caused by Valves Associated W/Penetration E15 Omitted from Local Leak Rate Testing Program + (06:02:19, 11 January 2025)
- PNO-V-88-062, on 881119,earthquake Occurred 30 Miles West of San Clemente,Ca.Earthquake Felt by Personnel in Unit 1 Control Room & No Seismic Instrumentation Alarms Received. Licensee Found No Damage After Visual Insp of Unit 1 + (06:02:22, 11 January 2025)
- ML13331A282 + (06:02:23, 11 January 2025)
- ML13331A281 + (06:02:24, 11 January 2025)
- 05000206/LER-1988-009, :on 880526,potential Diesel Loads in Excess of Regulatory Commitments.Caused by Calculation Errors & Inadequate Understanding of Loads on Diesel Generator. Personnel Trained in Proper Methodology + (06:02:27, 11 January 2025)