- ST-HL-AE-5366, Forwards Response to NRC Bulletin 96-002, Movement of Heavy Loads Over Spent Fuel in Reactor Core or Over Safety-Related Equipment + (ML20111A912)
- ML20111A917 + (ML20111A917)
- 05000285/LER-1984-024, :on 841126,unplanned Ventilation Isolation Actuation Sys Actuation Occurred.Caused by Operator Changing Ventilation Discharge Duck Monitor RM-061 to High Alert/Alarm Setpoints During Temp Inversion + (ML20111A935)
- 05000251/LER-1984-025-01, :on 841124,reactor Trip Occurred.Caused by Ground in One Stab Connector of Reactor Coolant Pump 4a Breaker.Unit Brought to Refueling Shutdown Condition to Deenergized 4a 4-kV Bus for Insp & Repair + (ML20111A941)
- 05000389/LER-1984-010-03, :on 841119,inservice Insp Surveillance Requirements of Tech Spec 4.7.9 Performed & 19 Snubbers Declared Inoperable as Result.All Inoperable Snubbers Replaced or Repaired + (ML20111A943)
- ML20111A944 + (ML20111A944)
- PY-CEI-NRR-2049, Notifies of Completion of GL 89-10, Safety-Related Motor-Operated Valve Testing & Surveillance Activities + (ML20111A946)
- HL-5162, Forwards Rev 0 to Ei Hatch Nuclear Plant Unit 1,Cycle 17 Colr + (ML20111A948)
- ML20111A950 + (ML20111A950)
- 05000364/LER-1996-001-01, :on 960408,2B DG Experienced Reduction Followed by Resumption in Speed During Auto Start Surveillance Test. Caused by Procedural Inadequacy.Dg Test Procedures Revised to Ensure Relay Actuated/Reset W/Proper Delays + (ML20111A952)
- ML20111A953 + (ML20111A953)
- 05000413/LER-1984-027-01, :on 841126,RCS Boron Concentration Decreased to Less than 2,000 Parts Per Million.Cause Unknown.Boric Acid Added to Bring Level Above 2,000 Part Per Million + (ML20111A954)
- ML20111A955 + (ML20111A955)
- 05000389/LER-1984-011-03, :on 841121,reactor Tripped Due to Loss of Turbine Load & Auxiliary Feed Pump C Tripped on Overspeed. Caused by Generator Exciter Bearing Failure & Steam Leakage, Respectively.Bearing Replaced + (ML20111A956)
- ML20111A960 + (ML20111A960)
- 05000454/LER-1984-019-05, :on 841127,boron Dilution Protection Isolation Sys Actuated.Caused by Noise Spike on Source Range Channels. Westinghouse Requested to Investigate Means of Filtering Out Noise Spikes + (ML20111A965)
- ML20111A966 + (ML20111A966)
- HL-5153, Forwards Description of Util Insp Plan,Results of Initial & Expanded Scope Insps & Evaluation of Findings of Augmented ISI of Core Shroud Vertical Welds + (ML20111A968)
- 05000454/LER-1984-018-06, :on 841128,HVAC Outside Air Vent Fan Started During Filter Change.Caused by Monitor Tripping During Filter Change.Procedures Revised So Filter Changes Will Not Cause Radiation Monitors to Trip + (ML20111A971)
- ML20111A975 + (ML20111A975)
- 3F0596-07, Provides Interpretation of Status of Exemption from 10CFR70.24, Criticality Accident Requirements + (ML20111A984)
- AECM-85-0050, Special Rept 84-37/1:on 841129,loose Parts Detection Sys Declared Inoperable for 30 Days Reaching Time Limit of Tech Spec.Caused by Alarm Susceptibility to Changing Plant Conditions.Alarm Response Instruction Revised + (ML20111A988)
- BSEP-84-2766, LER 1-84-18 Re Support to Snubber 1-E11-84SS491 Found to Be Reportable Per 10CFR50.73.LER Number 1-84-18 May Be Reassigned + (ML20111A992)
- HL-5164, Forwards MOR for April 1996 for Ei Hatch Nuclear Plant & Revised Rept for Mar 1996 + (ML20111A995)
- RBG-19389, Corrected Interim Deficiency Rept DR-182 Re Limitorque Motor Operator Failure on Feedwater Isolation Valve.Next Rept Will Be Provided by 850130 + (ML20111A996)
- ML20111B000 + (ML20111B000)
- RBG-19756, Interim Deficiency Rept DR-203 Re Arc Strikes on Interior Surface of Seven of Eight Air Start Receiver Tanks on Standby Diesel Generators Supplied by Tdi.Next Rept Will Be Submitted by 850110 + (ML20111B003)
- ML20111B006 + (ML20111B006)
- RBG-19736, Final Deficiency Rept DR-220 Re Tdi Standby Diesel Generator Cylinder Head Valve Seats.Initially Reported on 841119. Cylinder Heads Replaced + (ML20111B012)
- ML20111B013 + (ML20111B013)
- ML20111B014 + (ML20111B014)
- 05000352/LER-1984-017, :on 841127,improper Setpoint for Chlorine Analyzer Trip Switch Found.Caused by Personnel Error.Calibr Performed Immediately & Personnel Counseled Re Procedures + (ML20111B017)
- ML20111B019 + (ML20111B019)
- RBG-19758, Interim Deficiency Rept DR-243 Re Installation of Pacific Scientific Snubbers (PSA 10) & Bergen Paterson Clamps (PT 1001-15).Next Rept Will Be Provided by 850122 + (ML20111B021)
- ML20111B022 + (ML20111B022)
- ML20111B024 + (ML20111B024)
- RBG-19757, Interim Deficiency Rept DR-225 Re Motor Torque Specified for Motor Operated Valves Supplied by Velan Engineering,Ltd.Next Rept Will Be Provided by 850121 + (ML20111B027)
- RBG-19761, Interim Deficiency Rept DR-177 Re Installation,Design & Mfg of Coaxial & Instrumentation Cable for Neutron Monitoring Sys.Next Rept Will Be Provided by 850111 + (ML20111B028)
- 05000454/LER-1984-021-05, :Between 841127 & 1203,main Control Room Process Radiation Monitors Failed Automatic Check Source Tests,Causing Ventilation Sys to Switch to ESF Mode.Caused by Insufficient Tolerance in Setpoints + (ML20111B032)
- ML20111B033 + (ML20111B033)
- ML20111B036 + (ML20111B036)
- 05000362/LER-1984-041-01, :on 841126,containment Purge Isolation Sys Train Actuated.Caused by Grounding of Ac Power Cord Damaged by Drawer Removal from Plant Protection Sys.Personnel Cautioned + (ML20111B037)
- NSD-NRC-96-4704, Forwards Draft TSs 5.1,5.2 & 5.3 for Use in Preliminary Review of SSAR Section 18.7 + (ML20111B040)
- ML20111B046 + (ML20111B046)
- 05000311/LER-1984-025-01, :on 841126,audit Revealed That Weekly Plant Vent Particulate Sample for 840927 Not Analyzed within Time Required by Tech Specs.Caused by Personnel Error.Procedures Revised + (ML20111B047)
- 05000327/LER-1984-073, :on 841212,110 Fire Doors Failed to Meet Ul Stds.Caused by Maint & Mods Performed on Doors.Fire Watches Set Per Tech Specs & Mod/Repair Schedule & long-term Maint Being Addessed + (ML20111B049)
- ML20111B050 + (ML20111B050)
- ML20111B052 + (ML20111B052)
- 3F0596-04, Responds to NRC Bulletin 96-002, Movement of Heavy Loads Over Spent Fuel,Over Fuel in Reactor Vessel or Over Safety-Related Equipment + (ML20111B056)
- RBG-42888, Forwards Summary of Startup Physics Testing Conducted on Cycle 7 Core Reload + (ML20111B063)
- ML20111B064 + (ML20111B064)