Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20083M314 + (ML20083M314)
- 05000265/LER-1983-001, Forwards LER 83-001/03L-0 + (ML20083M315)
- ML20083M317 + (ML20083M317)
- 05000247/LER-1982-049-99, /99X-0:on 821218,during Cycle 5/6 Refueling Outage,Ability of Central Control Room to Be Totally Isolated During Accidents Questioned Because Potential Air Leak Paths Identified.All Potential Paths Sealed + (ML20083M325)
- ML20083M326 + (ML20083M326)
- 05000361/LER-1982-150, Forwards LER 82-150/01T-0.Detailed Event Analysis Submitted + (ML20083M327)
- 05000395/LER-1982-063, Forwards LER 82-063/03L-0.Detailed Event Analysis Encl + (ML20083M333)
- ML20083M337 + (ML20083M337)
- 05000265/LER-1983-001-03, /03L-0:on 830102,offgas Radiation Monitor 1 Failed.Caused by Faulty Resistor in Power Supply to Monitor. Resistor Replaced + (ML20083M339)
- 05000296/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20083M343)
- ML20083M344 + (ML20083M344)
- 05000387/LER-1984-017, :on 840310,spray Pond Riser Networks A-1 & B-2 Found Frozen.Cause Not Stated.Networks Thawed by Ambient Temp & Guidelines Developed for Spray Pond Operation to Avoid Riser Freezing + (ML20083M346)
- ML20083M348 + (ML20083M348)
- 05000219/LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl + (ML20083M349)
- ML20083M350 + (ML20083M350)
- ML20083M352 + (ML20083M352)
- 05000237/LER-1983-001, Forwards LER 83-001/03L-0 + (ML20083M353)
- ML20083M356 + (ML20083M356)
- 05000361/LER-1982-150-01, /01T-0:on 821229,Kerotest Valve Incorrectly Installed Restricting Flow Through Liquid Radwaste Monitor RT-7813.Caused by Improper Installation.Valve Realigned & Liquid Effluent Releases Sampled + (ML20083M357)
- ML20083M358 + (ML20083M358)
- 05000387/LER-1983-001, Forwards LER 83-001/01T-0 + (ML20083M362)
- 05000237/LER-1983-001-03, /03L-0:on 830101,cracked Weld Discovered at Feedwater Heater 2D2 Emergency Spill to Normal Drain Line Connector.Caused by Excessive Movement of Drain Line.Weld Will Be Repaired During Upcoming Refueling Outage + (ML20083M365)
- ML20083M367 + (ML20083M367)
- ML20083M368 + (ML20083M368)
- 05000219/LER-1982-060-03, /03L-0:on 821210,reactor Mode Switch Repositioned from Shutdown to Refuel While Intermediate Range Monitor Channels 16 & 17 Out of Svc.Caused by Personnel Error.Strict Compliance W/Tech Specs Emphasized + (ML20083M371)
- 05000387/LER-1983-001-01, /01T-0:on 830105,main Condenser Offgas Monitor Train Declared Inoperable Precipitating Entry Into Action Statement Requiring Grab Sample Be Taken Every 4 H.Sample Not Taken Due to Technician Error + (ML20083M382)
- 05000361/LER-1982-167, Forwards LER 82-167/03L-0.Detailed Event Analysis Submitted + (ML20083M388)
- 05000387/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20083M392)
- 05000395/LER-1982-063-03, /03L-0:on 821220,isotopic Iodine Analysis Not Performed within 6 H After Plant Went from 5% to 21% Thermal Power within 1 H.Caused by Failure to Notify Chemistry Dept to Perform Analysis.Procedure Developed + (ML20083M397)
- 05000318/LER-1982-008, Forwards Updated LER 82-008/03X-1 + (ML20083M402)
- 05000395/LER-1982-066-03, /03L-0:on 821226,during Mode 1 Operation,Reactor Bldg Sump Leakage Detection Sys Declared Inoperable When High Level Alarm Remained in Alarm State.Caused by Failure of Capacitance Level Detection Sys.Sys Recalibr + (ML20083M407)
- NRC-95-0051, Monthly Operating Rept for Apr 1995 for Fermi 2 + (ML20083M409)
- 05000296/LER-1983-005-03, /03L-0:on 821222,while Performing Monthly Vibration Tests on 480-volt Reactor Motor Operator Valve Board Motor Generator Sets,High Vibration Readings Detected on 3DA Set Coupling.Caused by Excessive Seal Removal + (ML20083M413)
- 05000387/LER-1982-078-03, /03L-0:on 821218,during Startup Testing Program, Two Jet Pumps Did Not Indicate Flowrate.Caused by Air Trapped in Lines.Air Bled Off & Indicators Returned to Normal.Source of Air Could Not Be Determined + (ML20083M417)
- PY-CEI-NRR-1950, Monthly Operating Rept for Apr 1995 for Perry Nuclear Power Plant,Unit 1 + (ML20083M418)
- 05000361/LER-1982-167-03, /03L-0:on 821218,w/both Units in Mode 5,control Room Emergency Chiller E-336 Tripped on High Bearing Temp & Declared Inoperable.Caused by Faulty Solenoid Valve for Motor Oil Cooling Unit of Chiller.Valve Replaced + (ML20083M423)
- 1CAN059501, Monthly Operating Rept for Apr 1995 for ANO Unit 1 + (ML20083M429)
- 05000416/LER-1983-004, Forwards LER 83-004/01T-0 + (ML20083M432)
- 05000318/LER-1982-008-03, During Mode 3,inner Containment Door Would Not Latch,Preventing Outer Door from Opening.Caused by Failure of Air Mechanism Due to Broken Cam Follower.Overhaul Performed + (ML20083M441)
- 05000339/LER-1983-003, Forwards LER 83-003/03L-0 + (ML20083M446)
- JAFP-84-0384, Monthly Operating Rept for Mar 1984 + (ML20083M452)
- RC-95-0133, Monthly Operating Rept for Apr 1995 for VC Summer Nuclear Station + (ML20083M453)
- 05000416/LER-1982-180, Final LER 82-180/03L-0:on 821227,isolation Valve for Hose Station in Control Room Replaced Due to Leaking Which Pressurized Hose.Addl Hose Run to Supply Backup Fire Protection.Leaking Valve Replaced.Sys Returned to Svc + (ML20083M456)
- ML20083M460 + (ML20083M460)
- ML20083M468 + (ML20083M468)
- 2CAN059504, Monthly Operating Rept for Apr 1995 for ANO Unit 2 + (ML20083M469)
- 05000339/LER-1983-003-03, /03L-0:on 830104,middle Level Corner Support Temp for Steam Generator a Indicated Less than 225 F for 12 H. Caused by Condensation Due to High Secondary Steam Leakage from body-to-bonnet Leak of Blowdown Isolation Valve + (ML20083M470)
- 05000278/LER-1982-016-03, /03L-0:on 820831,while Operating at Power,Loss of Position Indication Observed on Motor Operated Steam Supply Valve MO-3-13-131 to RCIC Turbine.Caused by Grounded Relay Coil.Relay & Control Fuse Replaced + (ML20083M475)
- ML20083M479 + (ML20083M479)
- ML20083M480 + (ML20083M480)