Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20069P769 + (ML20069P769)
- ML20069P779 + (ML20069P779)
- ML20069P782 + (ML20069P782)
- 05000373/LER-1982-142-03, /03L-0:on 821102,radwaste Valve OWL067 Did Not Fully Close When Tripped W/Simulated Radwaste Discharge hi-hi Trip Signal.Caused by Fouling of Valve Internals W/ Foreign Matls.Valve Cleaned + (ML20069P794)
- 05000373/LER-1982-141, Forwards LER 82-141/03L-0 + (ML20069P798)
- 05000387/LER-1982-044, Forwards LER 82-044/03L-0 + (ML20069P801)
- 05000285/LER-1990-027, :on 901207,determined That Adequate Compensatory Fire Watch Insp of Door 971-1 in Room 23 Not Conducted & 3 Addl Doors Had step-off Pads Outside Doors. Remedial Training Conducted + (ML20069P804)
- ML20069P806 + (ML20069P806)
- ML20069P809 + (ML20069P809)
- ML20069P813 + (ML20069P813)
- ML20069P821 + (ML20069P821)
- ML20069P828 + (ML20069P828)
- ML20069P834 + (ML20069P834)
- 05000373/LER-1982-141-03, /03L-0:on 821102,RCIC Inboard Testable Check Valve IE51-F066 Failed to Indicate Closed.Cause Still Under Investigation W/Vendor.Alternative Limit Switch Configurations Being Evaluated + (ML20069P837)
- 05000387/LER-1982-047, Forwards LER 82-047/03L-0 + (ML20069P840)
- ML20069P868 + (ML20069P868)
- 05000387/LER-1982-042, Forwards LER 82-042/01T-0 + (ML20069P883)
- 05000272/LER-1982-090-01, /01T-0:on 821121,video Insp of Removed Fuel Assemblies Revealed Cladding Ruptures on Element in Fuel Assembly D-20.Cause Unknown.Vendor to Conduct More Detailed Investigation + (ML20069P888)
- 05000387/LER-1982-043, Forwards LER 82-043/01T-0 + (ML20069P894)
- 05000387/LER-1982-042-01, /01T-0:on 821116,review of Response to Internal Incident Rept Revealed That Grab Samples Not Taken at Required Frequency While RHR Svc Water Sys Monitor Out of Svc.Caused by Personnel Error + (ML20069P899)
- JAFP-82-1230, Responds to IE Bulletin 81-02,Suppl 1, Failure of Gate Type Valves to Close Against Differential Pressure. Valves Listed Are Not Installed at Facility + (ML20069P908)
- 05000249/LER-1982-008, Forwards Updated LER 82-008/03X-1 + (ML20069P911)
- 05000387/LER-1982-043-01, /01T-0:on 821116,engineering Review Revealed Failure of Single Component Could Defeat Overload Detection & Protection Devices for Containment Penetration Carrying Power Cables for Reactor Recirculation Pumps + (ML20069P922)
- ML20069P925 + (ML20069P925)
- 05000249/LER-1982-008-03, While Performing Refuel Surveillance Dis 2300-7,calibr Testing Discovered HPCI Temp Switches 2371A,2372A,2370C & 2370D Above Tech Spec Limit. Caused by Vibration Loosening Set Screws + (ML20069P927)
- 05000387/LER-1982-048, Forwards LER 82-048/03L-0 + (ML20069P932)
- 05000387/LER-1982-048-03, /03L-0:on 821101,control Rod Position Indication full-out Position Switch Inoperable for One Rod.Caused by Failed Subcomponent on Printed Circuit Board.Board Replaced + (ML20069P944)
- 05000219/LER-1982-054, Forwards LER 82-054/03L-0.Detailed Event Analysis Encl + (ML20069P952)
- 05000265/LER-1982-023, Forwards LER 82-023/03L-0 + (ML20069P962)
- LIC-94-0138, Forwards FCS Performance Indicators Rept for May 1994 + (ML20069P967)
- ML20069P972 + (ML20069P972)
- 05000333/LER-1982-050, Forwards LER 82-050/03L-0 + (ML20069P975)
- 05000219/LER-1982-054-03, /03L-0:on 821105,after Completing TIP Trace, Ball Valve on TIP Machine 3 Failed to Close.Caused by Moisture Buildup Around in-shield Limit Switch Operating Arm.Arm Cleaned & Switch Aligned + (ML20069P979)
- ML20069P982 + (ML20069P982)
- 05000382/LER-1990-018-03, :on 901206,discovered That Shutdown Cooling Sys Suction Line Relief Valves Not Demonstrated Operable Since Issuance of OL on 841218.Caused by Overlooking Configuration Since TS Written.Ts Change Will Be Sent + (ML20069P983)
- ML20069P994 + (ML20069P994)
- 05000373/LER-1982-140, Forwards LER 82-140/03L-0 + (ML20069Q000)
- ML20069Q004 + (ML20069Q004)
- 05000265/LER-1982-023-03, /03L-0:on 821104,turbine Stop Valve Could Not Be Reset During HPCI Testing,Preventing Turbine Operation. Caused by Corroded Contacts on Valve Hydraulic Oil Pressure Switch.Switch Replaced.Hpci Switches Cleaned + (ML20069Q016)
- ML20069Q019 + (ML20069Q019)
- 05000333/LER-1982-050-03, /03L-0:on 821109,scram Discharge Vol Rod Block Level Surveillance Test Not Performed within 7 Days of Reactor Startup,Per Tech Spec.Caused by Failure to Enter Frequency Statement in Procedure During Review of Amend 62 + (ML20069Q021)
- ML20069Q023 + (ML20069Q023)
- 05000373/LER-1982-140-03, /03L-0:on 821030,offgas Pretreatment Monitor Became Inoperative.Caused by Loss of Flow Due to Water in Sample Line.Sample Line Drained.Purge Valve Installed to Allow Proper Flow + (ML20069Q031)
- 05000373/LER-1982-139, Forwards LER 82-139/03L-0 + (ML20069Q036)
- ML20069Q038 + (ML20069Q038)
- 05000373/LER-1982-139-03, /03L-0:on 821030,Div 11 Oxygen Channel Was Reading Erratically.Caused by Moisture Buildup in Oxygen Sample Flowmeter.Moisture Removed & Instrumentation Recalibr + (ML20069Q039)
- ML20069Q042 + (ML20069Q042)
- 05000334/LER-1981-078, Forwards Updated LER 81-078/03X-1 + (ML20069Q054)
- 05000282/LER-1982-022, Forwards LER 82-022/03L-0 + (ML20069Q059)
- 05000282/LER-1982-022-03, /03L-0:on 821112,during Power Operation,Control Power Lost to Diesel Cooling Water Pump 22,rendering Pump Inoperable.Caused by Loose Fuse Clip.Clip Repaired & Pump Tested Satisfactorily + (ML20069Q067)
- 05000311/LER-1982-135, Forwards LER 82-135/01T-0.Detailed Event Analysis Encl + (ML20069Q075)