List of results
- PY-CEI-NRR-1774, Responds to NRC Re Violations Noted in Insp Rept 50-440/93-23 on 931219-940129.Corrective Actions:Restored Continuous Reactor Water Conductivity Measurement on 940116 & Human Performance Enhancement Sys Evaluation Initiated + (ML20064L085)
- LG-83-049, Forwards Response to 821210 Request for Addl Info on IE Bulletin 81-03, Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel). Monitoring Program for Clams to Be Established + (ML20064L089)
- ML20064L092 + (ML20064L092)
- 05000416/LER-1982-187, Forwards LER 82-187/99X-0 + (ML20064L094)
- 05000254/LER-1983-001, Forwards LER 83-001/03L-0 + (ML20064L107)
- 05000416/LER-1982-187-99, /99X-0:on 821229,smoke Detection Zone Covering Auxiliary Bldg Corridors at 166-ft Elevation Alarmed & Would Not Reset.Caused by Accumulation of Dust in Detector. Detector Cleaned,Functionally Tested & Returned to Svc + (ML20064L110)
- 1CAN028306, Submits Updated Info Re Status of Ongoing Steam Generator Tube Inservice insps.Once-through Steam Generator Tube Sheet Maps,Defective Tube Summary & Summary of Operational History of Previous Cycle Encl + (ML20064L113)
- ML20064L117 + (ML20064L117)
- 05000324/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20064L118)
- ML20064L123 + (ML20064L123)
- 05000366/LER-1980-150, Forwards Updated LER 80-150/03X-1 + (ML20064L124)
- ML20064L125 + (ML20064L125)
- 05000254/LER-1983-001-03, /03L-0:on 830104,diesel Generator 1/2 Tripped on High Crankcase Pressure Signal.Caused by Lubricating Oil Splashing on Pressure Sensor Upon Startup.Sensor Replaced + (ML20064L127)
- ML20064L128 + (ML20064L128)
- ML20064L131 + (ML20064L131)
- 05000440/LER-1994-007, :on 940217,passive Seismic Instrument Failure Occurred Due to Intrusion of Water.Affected Instrument, Peak Acceleration Recorder Replaced + (ML20064L132)
- ML20064L134 + (ML20064L134)
- ML20064L137 + (ML20064L137)
- 05000324/LER-1983-004-03, /03L-0:on 830105,during Jumper Installation, Reactor Protection Sys Relay C72-K6C Found Melted Around Coil.Caused by Overheating of Relay.Relays to Be Inspected Monthly Until Replaced W/Improved Components + (ML20064L142)
- L-94-009, Forwards Revised ASME Section XI Pressure Test Program Relief Request PTP-3-03.Relief Request Revised to Include 100% Volmetric Exam of Welded Joints Associated W/Repair as Part of Proposed Alternate Requirement + (ML20064L145)
- NRC-94-4079, Advises That Review of Proprietary Matl NRC RAI on AP600 Received in ,Indicates That RAI Contains No Info Westinghouse Considers Proprietary + (ML20064L147)
- ML20064L148 + (ML20064L148)
- ML20064L151 + (ML20064L151)
- 05000366/LER-1980-147, Forwards Updated LER 80-147/03X-1 + (ML20064L154)
- 05000336/LER-1994-003-02, :on 940218,degration of Sychronizing Capability Between Inverters Potential to Invalidate Assumption for Main Stream Line Break.Adjustments Made to Underfrequency Frequency Limiter Circuit + (ML20064L160)
- 05000366/LER-1980-150-03, HPCI Steamline Pressure a Logic Did Not Auto Isolate Until 89 Psig.Possibly Caused by Switches Not Environmentally Qualified.Switches to Be Replaced by Analog Transmitter Sys + (ML20064L164)
- ML20064L166 + (ML20064L166)
- ML20064L167 + (ML20064L167)
- ML20064L168 + (ML20064L168)
- ML20064L172 + (ML20064L172)
- ML20064L178 + (ML20064L178)
- 05000333/LER-1993-027-01, :on 931221,determined That Heat Detectors Located in SBGT Sys Filter Trains Not Being Functionally Tested.Caused by Inadequate Test Procedure Development, Review & Approval.Test Procedures Revised + (ML20064L181)
- ML20064L182 + (ML20064L182)
- 05000366/LER-1980-147-03, A & B post-accident Monitoring Drywell Hydrogen Peroxide Analyzers Found Inoperable.Caused by Combination of Failures of Related Equipment.Components Associated W/Analyzers Repaired + (ML20064L185)
- ML20064L186 + (ML20064L186)
- ML20064L190 + (ML20064L190)
- ML20064L200 + (ML20064L200)
- ML20064L201 + (ML20064L201)
- ML20064L202 + (ML20064L202)
- 05000362/LER-1982-011, Forwards LER 82-011/03L-0.Detailed Event Analysis Submitted + (ML20064L204)
- ML20064L206 + (ML20064L206)
- AECM-83-0062, Final Deficiency Rept Re Corroded Terminal Boards on Rosemount Pressure,Flow & Level Transmitters in safety- Related Applications.Initially Reported on 820421.Maint Work Orders Issued to Restore Transmitters to Design Specs + (ML20064L209)
- ML20064L210 + (ML20064L210)
- 05000305/LER-1983-001-03, /03L-0:on 830105,during Full Power Operation, Electrician Performing Maint Pulled Fuse to de-energize SV33379 Which Allowed Caustic Additive to Drain from Tank to Suction of Containment Spray Pumps + (ML20064L213)
- ML20064L214 + (ML20064L214)
- ML20064L217 + (ML20064L217)
- 05000321/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20064L218)
- ML20064L222 + (ML20064L222)
- 05000362/LER-1982-011-03, /03L-0:on 821217,during Mode 5,Zone 41 (Cable Spreading Room) Fire Detectors Removed from Svc to Permit Repair of Cables.Caused by Minor Cable Damage During Const Activities.Cable Replaced + (ML20064L228)
- LIC-94-0056, Generator Eddy Current Test Rept 1993 Refueling Outage + (ML20064L229)
- ML20064L233 + (ML20064L233)