- 05000361/LER-1982-151-03, /03L-0:on 821128,while Performing Monthly Channel Check Surveillance,Temp Indication TI-0111BX for Reactor Coolant Hot Leg Read More than 48 F Lower than TI-0911X1. Caused by Setpoint Drift.Indicator Recalibr + (ML20064H936)
- ML20064H943 + (ML20064H943)
- PM-82-134, RO 50-366/1982-007:on 821230,while Performing Peak Shock Annunciator & Recorder Functional Test Procedure,Triaxial Response Spectrum Recorder Found Inoperable.Caused by Damaged Switches.Component Repaired by Manufacturer + (ML20064H944)
- 05000324/LER-1982-137-03, /03L-0:on 821206,during Operability Test of Remote Shutdown Panel,Rhrsw D/P Transmitter 2-E11-POT-N002BX Did Not Respond to Test Input Signal.Caused by Failed Transmitter Differential Pressure Unit.Transmitter Replaced + (ML20064H948)
- RC-94-0075, Application for Amend to License NPF-12,consisting of TS Change TSP 930012,deleting TS SR 4.8.4.1.a.3 Which Mandates Periodic Retesting of Penetration Protection Fuses & Bases B 3/4.8.4 Will Also Delete Refs to Subj Fuses + (ML20064H952)
- ML20064H959 + (ML20064H959)
- 05000333/LER-1982-056, Forwards LER 82-056/03L-0 + (ML20064H960)
- ML20064H964 + (ML20064H964)
- ML20064H970 + (ML20064H970)
- 05000324/LER-1982-006, Forwards Updated LER 82-006/03L-1 + (ML20064H976)
- 05000416/LER-1982-164, Forwards LER 82-164/03L-0 + (ML20064H982)
- 05000333/LER-1982-056-03, /03L-0:on 821215,LPCI Inverter a Tripped When Power Transferred to Maint Supply,Per Tech Spec 3.9.F. Redundant Sys Verified Operable.Caused by Failed Gate Timing Control Card.Card Returned to Vendor for Analysis & Repair + (ML20064H993)
- ML20064J001 + (ML20064J001)
- ML20064J002 + (ML20064J002)
- ML20064J005 + (ML20064J005)
- ML20064J008 + (ML20064J008)
- 05000387/LER-1982-067, Forwards LER 82-067/01T-0 + (ML20064J010)
- ML20064J012 + (ML20064J012)
- ML20064J018 + (ML20064J018)
- 05000416/LER-1982-164-03, /03L-0:on 821212 & 13,two Fire Doors in Auxiliary Bldg Blocked Open for Planned Maint Activities & to Support Plant Testing.Testing Completed,Hoses Removed & Doors Closed + (ML20064J021)
- ML20064J027 + (ML20064J027)
- ML20064J028 + (ML20064J028)
- 05000362/LER-1982-006, Ro:On 821217,incident Involving Emergency Safety Features Actuation Signal Occurred.Written Followup Rept W/Interim LER 82-006 Will Be Submitted by 821228 + (ML20064J029)
- 05000395/LER-1982-054, Forwards LER 82-054/03L-0.Detailed Event Analysis Encl + (ML20064J030)
- ML20064J034 + (ML20064J034)
- 05000324/LER-1982-006-03, RTGB Instrument 2-CAC-LR-2602 Indicated Level Exceeding Specified Upper Limit.Caused by Loss of Wet Ref Leg to Transmitters 2-CAC-LT-2602 & LT-2601.Trickle Flow re-established + (ML20064J037)
- ML20064J038 + (ML20064J038)
- ML20064J040 + (ML20064J040)
- 05000387/LER-1982-067-01, /01T-0:on 821224,grab Samples Not Taken Every 4 H While Main Condenser Offgas Hydrogen Monitor Inoperable. Caused by Lack of Communication Between Operations & Chemistry Group.Incident Reporting Procedure Changed + (ML20064J045)
- ML20064J046 + (ML20064J046)
- ML20064J048 + (ML20064J048)
- 05000395/LER-1982-054-03, /03L-0:on 821208,loose Part Detection Sys Failed Daily Channel Check.Caused by Microprocessor Failure. Microprocessor Replaced + (ML20064J049)
- LD-94-018, Suppls Submitted by Epri,Forwarding Rept on Technical Aspects of Emergency Planning for Alwrs + (ML20064J050)
- ML20064J051 + (ML20064J051)
- ML20064J053 + (ML20064J053)
- ML20064J054 + (ML20064J054)
- ML20064J056 + (ML20064J056)
- ML20064J061 + (ML20064J061)
- ML20064J068 + (ML20064J068)
- ML20064J069 + (ML20064J069)
- B14770, Proposed Tech Specs Supporting one-time Extension to 18- Month Surveillances + (ML20064J073)
- 05000361/LER-1982-158, Forwards LER 82-158/03L-0.Detailed Event Analysis Submitted + (ML20064J074)
- ML20064J078 + (ML20064J078)
- ML20064J079 + (ML20064J079)
- 05000338/LER-1982-076, Forwards LER 82-076/03L-0 + (ML20064J090)
- ML20064J091 + (ML20064J091)
- ML20064J102 + (ML20064J102)
- 05000338/LER-1982-076-03, /03L-0:on 821207,while in Mode 3,w/casing Cooling Pump 3A Removed from Svc to Perform Maint,Mode Change Made Due to Unscheduled Outage.Maint Completed in Mode 5 + (ML20064J103)
- ML20064J105 + (ML20064J105)
- 05000281/LER-1982-073-03, /03L-0:on 821207 & 24,FI-474 Drifted Low. Caused by Partial Loss of Fluid in Sensing Line to High Side of Transmitter.Valve Repaired & Sensing Line Filled + (ML20064J107)
- ML20064J112 + (ML20064J112)