Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20053B735 + (ML20053B735)
- ML20053B736 + (ML20053B736)
- ML20053B737 + (ML20053B737)
- 05000260/LER-1982-014, Forwards LER 82-014/03L-0 + (ML20053B738)
- ML20053B740 + (ML20053B740)
- ML20053B743 + (ML20053B743)
- 05000260/LER-1982-014-03, /03L-0:on 820420,HPCI Sys Made Inoperable for Calibr of Speed Sensing & Control Circuits W/O Performing Surveillance Tests.Caused by Personnel Error in Failing to Determine Inoperability + (ML20053B744)
- AECM-82-226, Interim Deficiency Rept 1 Re Corroded Terminal Boards on Pressure,Flow & Level Transmitters Utilized in safety- Related Applications,Initially Reported 820421.Definite Corrective Actions Not Formulated.Final Rept by 820806 + (ML20053B745)
- AECM-82-223, Final Deficiency Rept for Unit 1 & Interim Deficiency Rept for Unit 2 Re O Ring Seals on Rosemount Transmitters, Initially Reported 820421.Lubrication Procedure Written. Unit 2 Final Rept by 821029.Also Reported Per Part 21 + (ML20053B750)
- ML20053B751 + (ML20053B751)
- 05000325/LER-1982-038-03, /03L-0:on 820419,reactor Scrammed Due to Opening of 125-volt Battery Charger Output Breaker While Removing Electrical Clearance on Div II Battery.Caused by Operator Error.Breaker Reclosed & Power Restored to 1B-1 Bus + (ML20053B753)
- ML20053B754 + (ML20053B754)
- ML20053B755 + (ML20053B755)
- 05000348/LER-1982-016, Forwards LER 82-016/03L-0 + (ML20053B756)
- 05000348/LER-1982-016-03, /03L-0:on 820403,pressurizer Level Indicator LI- 459Z on Hot Shutdown Panel Declared Inoperable.Caused by Faulty Transmitter Amplifier Card.Card Replaced & Instrumentation Channel Returned to Svc + (ML20053B759)
- ML20053B760 + (ML20053B760)
- ML20053B762 + (ML20053B762)
- ML20053B765 + (ML20053B765)
- ML20053B766 + (ML20053B766)
- 05000325/LER-1982-030, Forwards LER 82-030/03L-0 + (ML20053B767)
- AECM-82-217, Forwards Summary of Environ Protection Program Re Const of Facilities for 6 Months Ending 820430 + (ML20053B770)
- 05000325/LER-1982-030-03, /03L-0:on 820419,HPCI Steam Line Area High Differential Temp Switch 1-E51-DTS-N604D Would Not Respond to Applied Test Signal.Caused by Electronic Failure of Switch Module.Module 86DT Replaced + (ML20053B772)
- ML20053B773 + (ML20053B773)
- 05000369/LER-1982-026, Forwards LER 82-026/03L-0 + (ML20053B774)
- ML20053B776 + (ML20053B776)
- ML20053B779 + (ML20053B779)
- 05000369/LER-1982-026-03, /03L-0:on 820326,while in Mode 1,EMF Monitors 35, 36 & 37 Declared Inoperable Due to Loss of Alarm Received in Control Room.Caused by Seized Air Pump Due to Worn Pump Vanes.New Vanes Installed & Pump Returned to Svc + (ML20053B781)
- ML20053B782 + (ML20053B782)
- 05000296/LER-1982-007, Forwards LER 82-007/03X-1 + (ML20053B783)
- AECM-82-182, Interim Deficiency Rept Re Supports Installed & Accepted by Reactor Controls,Inc Not in Accordance W/Approved Design Requirements,Initially Reported 820317.QC Holds Still Being Evaluated.Next Rept by 820601 + (ML20053B785)
- 05000296/LER-1982-007-03, /03X-1:on 820318,ice Storm Caused Loss of Offsite Power to 4-kV bus-tie Board.Caused by Interruption of Power to Cooling Tower Transformers & 4-kV Switchgear Feeding bus-tie Board Due to Loss of 161-kV Lines + (ML20053B789)
- ML20053B793 + (ML20053B793)
- ML20053B794 + (ML20053B794)
- ML20053B797 + (ML20053B797)
- AECM-82-164, Final Deficiency Rept Re Seismically Unsupported Sensing Line Between Standby Diesel Generator Starting Air Receiver Tank & Starting Air Compressor,Originally Reported on 820205.Nonseismic Line Rerouted.Also Reported Per Part 21 + (ML20053B798)
- ML20053B799 + (ML20053B799)
- 05000280/LER-1982-022, Forwards Updated LER 82-022/03X-1 & LER 82-047/01T-0 + (ML20053B801)
- ML20053B803 + (ML20053B803)
- ML20053B805 + (ML20053B805)
- ML20053B806 + (ML20053B806)
- ML20053B807 + (ML20053B807)
- ML20053B808 + (ML20053B808)
- 05000321/LER-1982-031, Forwards LER 82-031/03L-0 + (ML20053B810)
- ML20053B813 + (ML20053B813)
- ML20053B814 + (ML20053B814)
- 2CAN058205, Forwards Monthly Operating Rept for Apr 1982 + (ML20053B816)
- ML20053B818 + (ML20053B818)
- ML20053B819 + (ML20053B819)
- 05000321/LER-1982-031-03, /03L-0:on 820422,particulate Sample Pump & Noble Gas Panel Monitors 1D11-K631,623 & 633 Declared Inoperative. Caused by Component Failure & Inleakage of Air to Monitors. Pump Repaired & Air Leaks Stopped + (ML20053B821)
- ML20053B822 + (ML20053B822)
- 05000280/LER-1982-047-01, /01T-0:on 820418,transfer of Gaseous Waste Between Gas Stripper Surge Tank & Waste Gas Surge Tank Resulted in Lifting of RV-GW-107 & Unplanned Release.Caused by Premature Lifting of RV-GW-107.Relief Valve Cleaned & Reset + (ML20053B823)