OPERATING DATA REPORT 50-409 DOCKET NO.

DATE 05-05-82 COMPLETED BY G.R.GA00W TELEPilONE 3 8-689-2331 i

OPERATING STATUS La Crosse Boiling Water Reactor N'"e5

1. Unit Name:
2. Reporting Period: 0001. 04-01-82 to 2400. 04-30-82
3. Licensed Thermal Power (MWt):

165 65.3

4. Nameplate Rating (Gross MWe):

50

5. Design Electrical Rating (Net MWe):

50

6. Masimum Dependable Capacity (Gross MWe):

48

7. Masimum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Gise Reamns:

4 i

9. Power Lesel To which Restricted. If Any (Net MWe):
10. Reasons For Restrictions.lf Any:

4 This Month Yr..t o.Date Cumulatise 720 2880 109,539

11. Ilours in Reporting Period 197 9 1796.6

_73,070.2

12. Number Of flouri Reactor Was Critical 0

0 478

13. Reactor Rewne Shutdown flours l
14. Hours Generator On-Line 197.8 1706.2 67,393.4
15. Unit Resene Shutdown Hours

._ 0 0

79

16. Gruss Thermal Energy Generated (MWil) 23,639.8 212,692.4 9,208,481.1
17. Gross Electrical Energy Generated (MWH) 6601 59.143 3.749.001
18. Net Electrical Energy Generated (MWil) 5796 54.397 2,542,389 27.5 59.2 61.5
19. Unit Senice Factor 27.5 59.2 61.6
20. Unit AsailabWity Factor 16.8

_39.4 48.4

21. Unit Capacity Factor IUsing MDC Net,

_ 16.1 37.8 46.4

22. Unit Capacity Factor (Using 1)FR Net) 0 27.6 8.1
23. Unit Forced Outage Rate
24. Shutdowns Scheduled Oser Nest 6 Months IType. Date,and Duration of Each1:

Refueling in Progress - Commenced April 9, 1982.

Exoncted Duratinn is 12 wonke.

July 6, 1982

25. If Shut Down At End Of Report Period. Estimated Date of Startup.
26. Units in Test Status tPrior to Commercial Operation):

Forecast Achiesed INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCI \\L OPER ATION n -- >

l 8206010 I

50-409 UNlr slluloowNs Asp rower Rrnecisoss DOCKET No.

MN UNIT N AME DATE 05-05-62 b.K.bAUUW APRIL 198.?

COMPLET ED BY REPOR T MON 11:

TELEFilONE 6U0-669-44J1 W.r

.a e

1

{ ~t, Cauw A Curretine 33 1;

~ E4 Laa nset E

-h 3?

4 2s5 f.wns

?

E3 Assaun to I

Date

$5 5

ji=

Repois r 80 j ~*

Picsent Recurrente d

4 82-07 04-09-82 S

522.8 C

1 NA NA NA SCHEDULED REFUELING OUTAGE.

EXPECTED DURATION OF 11 WEEKS.

l l

I I

)

b l

i I

2

.I 4

i i 1.used Reason:

M et h.=l -

talubit G. Instrussi.wis s 5,heduled A faguspment Failurell.splain) 1 Manual to: Picparation.it' Dr.a B Maintenance or Test 2-Manual S s ain.

I.nti> Shet-is sor I.icemce C Refueling 4 Autoniaise Nrain.

I sent Report 11.1 R t I'de int.RI G-l D NrFulator) Ressiiction 4 Other il splaint O t til i l'4)perator Traming A Iisenv 1 umination l' Adnurmiraine 4

fe OntCrJf 604 JI I flol (I spIJin)

I slUlui 1 NJine Saulfte s'8 77) ll Other 11 splaus) l

.-mw,,,

- -, - -, ~.., -

e

AVERAGE DAILY UNIT POWER LEVEL

- 09 DOCKET NO.

LACBWR v3,7 DATE 05-05-82 COMPLETED ay G.R.GADOW TELEPHONE 608-689-2331 April, 1982

\\tDNDI DAY AVER AGE DAILY POWER LEVEL DAY AVER AGE DAILY POWER LEVEL (MWe Net)

(MWe-Neti 20 i

17 0

28 2

18 0

34 0

.t 19 34 4

20 0

34 0

5 21 35 0

6 22 34 7

23 0

34 8

24 0

3 0

9 25 0

to 26 0

0 11 27 0

0 a

12 28 0

0 0

13 29 0

0 14 30 0

15 38 0

16 INSTRUCTIONS On this format,hst the average daily unit power lesel in MWe Net for each day in the reportmg month. Compute to the nearest whole megawatt.

s 19/77)

5 I

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE APRIL 1982 i'

At the onset - of April 1982 reporting period, the reactor was at 28%

Rated Thermal Power (8 MWe-Net).

A gradual escalation to 80% Rated Thermal Power (37 MWe-Net) was in progress due to an automatic shutdown in the preceding report period.

On April 8, -1982 at 2300, a de-escalation commenced for the scheduled refueling outage.

The turbine was manually tripped at 0550 4

on April 9,

1982 and the reactor was manually shut down immediately thereafter.

Significant maintenance iteiits performed during the reporting period a re indicated or the attached Mechanical Maintenance and Instrument and Electrical Maintenance listings.

1 i

i 3

4

APRIL 1982 Page 1 of 4 INSTRUMENT RND ELECTRICAL MAINTENANCE LER OR NATURE OF OUTAGE MALFUNCTION l

EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION SECURITY METAL DETECTOR CORRECTIVE OUTAGE UNKNOWN CONTINU0US ALIGNED AND BALANCED I

MR-0242 82-07 ALARM CIRCUIT SECURITY CRT READ 0UT #3 CORRECTIVE OUTAGE UNKNOWN IN0 PERATIVE REPLACED CAPACITOR 1

MR-0239 82-07 SECURITY E-FIELD CORRECTIVE OUTAGE UNKNOWN CONTINUOUS TIGHTENED WIRE LOOP 82-07 ALARM SECURITY E-FIELD CORRECTIVE OUTAGE UNKNOWN CONTINUOUS ALIGNED AND BALANCED 1

MR-0323 82-07 ALARM CIRCUIT I

SAFETY SYSTEM CH 1, 2 PREVENTIVE OUTAGE TEST DUE COMPLETED TESTS COMPLETED SAFETY AND H O #3 82-07 SYSTEM TESTS 2

NUCLEAR CH N-5 THROUGH PREVENTIVE OUTAGE TEST DUE COMPLETED TESTS COMPLETED TESTS N-5 I

N-8 82-07 THROUGH N-8 NUCLEAR CH N-1 PREVENTIVE OUTAGE NORMAL USAGE LOW COUNTS REPLACED NEUTRON MR-0276 82-07 DETECTOR QUALIFIED "J" B0X FACILITY OUTAGE ADDITIONAL COMPLETED COMPLETED INSTALLATION CHANGE 82-07 EQUIPMENT INSTALLATION INSTALLATION J.

74-82-11; MR-0214 RELOCATION OF TURBINE FACILITY OUTAGE RELOCATION RELOCATED COMPLETED BUILDING OILER COOLER CHANGE 82-07 REQUIRED EQUIPMENT RELOCATION CONTROL 06-81-14; MR-0270 METEOROLOGICAL FACILITY OUTAGE RELOCATION RELOCATED COMPLETED EQUIPMENT RELOCATION CHANGE 82-07 REQUIRED EQUIPMENT RELOCATION 48-81-2 MR-0103 WP6

i APRIL 1982 INSTRUMENT AND ELECTRICAL MAINTENANCE i

l LER OR NATURE OF OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION i

J HALON SYSTEM AUXILIARY FACILITY OUTAGE ADDITIONAL COMPLETED COMPLETED SHUTDOWN SWITCH CHANGE 82-07 EQUIPMENT INSTALLATION INSTALLATION 06-80-3A3; MR-0236 TENSIOMETER CORRECTIVE OUTAGE CALIBRATION COMPLETED COMPLETED CALIBRATION CALIBRATION MR-0209 82-07 REQUEST CALIBRATION i

MDS REGULATOR N2 CORRECTIVE OUTAGE REQUEST FOR REPLACED REPLACED GAUGES GAUGE MR-0157 82-07 CALIBRATION GAUGES FUEL GRAPPLE CORRECTIVE OUTAGE USAGE NO RED ADJUSTED STR0KE MR-0234 82-07 LIGHT 1B STATIC INVERTER FANS CORRECTIVE OUTAGE NORMAL USAGE INTERMITTENT REPLACED FAN MOTORS MR-0893 82-07 TROUBLE ALARMS 1B DIESEL BANK " A" PREVENTIVE OUTAGE CHANGE TIME REPLACED REPLACED START START BATTERIES MR-0288 82-07 BATTERY BATTERY FUEL GRAPPLE CORRECTIVE OUTAGE USAGE N0 GREEN LIGHT ADJUST LINKAGE MR-0296 82-07 l

MSIV BYPASS CORRECTIVE OUTAGE WATER IN INCORRECT CLEARED WATER AND l

VALVE POSITION MR-0227 82-07 POSITIONING INDICATION-ADJUSTED INDICATOR UNIT MAIN STEAM BYPASS CORRECTIVE OUTAGE UNKNOWN INTERMITTENT CLEANED SET POINT-

)

VALVE WIDE RANGE MR-0228 82-07 OPERATION POTENTIOMETER CONTROLLER MSIV BYPASS VALVE CORRECTIVE OUTAGE USAGE INCORRECT VALVE READJUSTED FEED BACK POSITION MR-0260 82-07 POSITION UNIT FUEL GRAPPLE CORRECTIVE OUTAGE USAGE MOTOR SHAFT RETIGHTENED GEAR TO MR-0295 82-07 SLIPPAGE SHAFT WP6

6 APRIL 1982 Page 3 of 4 a

INSTRUMENT AND ELECTRICAL MAINTENANCE LER OR

[

NATURE OF OUTAGE MALFUNCTION 6

EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION FCP 1A FLOW TRANSMITTER CORRECTIVE OUTAGE UNKNOWN CAUSING RECORDER REPLACED CONTROL j

MR-0182 82-07 SPIKE AMPLIFIER FUEL GRAPPLE CORRECTIVE OUTAGE POOR DESIGN NO RED LIGHT REPLACED REED SWITCH I

MR-0296 82-07 AND RETURN SPRINGS I

i FCP 1B LEAK-0FF CORRECTIVE OUTAGE UNKNOWN INTERMITTENT REPLACED TEMPERATURE l

j TEMPERATURE ALARM MR-0160 82-07 ALARM ALARM UNIT REACTOR HEAD THERM 0 COUPLE CORRECTIVE OUTAGE ROUGH USAGE NO CONTACT TO REPLACED BROKEN BOLT MR-0298 82-07 REACTOR HEAD d

i FCP LEAK-0FF FLOW REPLACEMENT OUTAGE SUBSTITUTION INCREASE IN REPLACED FLOW TUBES j

METERS MR-0272 82-07 REQUEST RANGE AND CALIBRATED l

j l

CONDENSER VACUUM GAUGE CORRECTIVE OUTAGE MERCURY HARD TO READ INSTALLED CLEAN i

i MR-0229 82-07 CONTAMINATION GAUGE TUBE 1

REACTOR FEED PUMP PREVENTIVE OUTAGE CALIBRATION CALIBRATED CALIBRATED GAUGES PRESSURE INDICATOR MR-0302 82-07 REQUESTED GAUGES CCTV UNDERWATER CORRECTIVE OUTAGE LEAKAGE WATER INSIDE CLEANED AND SEALED INSPECTION CAMERA MR-0311 82-07 CAMERA CAMERA CCTV UNDERWATER CORRECTIVE OUTAGE SHORT INSIDE NO PICTURE REPLACED VIDICON INSPECTION CAMERA MR-0311 82-07 CAMERA PREAMP AND REPAIRED SHORT AND OPEN IN WIRING 1

1 LOCA QUALIFIED SOLEN 0ID PREVENTIVE OUTAGE UPGRADED COMPLETED COMPLETED j

VALVES MR-0280 &

82-07 EQUIPMENT INSTALLATION INSTALLATION MR-0328 i

SOLEN 0ID CLIP PREVENTIVE OUTAGE 10 CFR 21 COMPLETED COMPLETED INSPECTION i

i VERIFICATION MR-0325 82-07 REPORT INSPECTION i

i f

I WP6

l APRIL 1982 i

Page 4 of 4 j

f INSTRUMENT AND ELECTRICAL MAINTENANCE LER OR j

NATURE OF OUTAGE MALFUNCTION

]

EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION j

l l

LPSW PRESSURE TRANSMITTER CORRECTIVE OUTAGE LINE PLUGGED NO READ 0UT CLEARED LINE AND CALIBRATION MR-0294 82-07 CALIBRATED 7

DRY CLEANER CORRECTIVE OUTAGE USAGE N0 HEAT REPLACED HEATER MR-0324 82-07 ELEMENT FCP 17 DISCHARGE VALVE CORRECTIVE OUTAGE UNKNOWN NO INDICATION REPLACED WIRE ON l

INDICniOR MR-0287 82-07 P0TENTIOMETER l

FCP 1A BYPASS VALVE CORRECTIVE OUTAGE UNKNOWN INCORRECT REPAIRED AIR LEAK

}

POSITIONER MR-0332 82-07 POSITION

}

1A WASTE WATER PUMP CORRECTIVE OUTAGE PLUGGED GAUGE IN0 PERATIVE REPLACED GAUGE MR-0331 82-07 I

FUEL GRAPPLE CORRECTIVE OUTAGE USAGE IN0 PERATIVE REPAIRED OPEN WIRE j

MR-0335 82-07 AND ADJUSTED CLUTCH

[

t WASTE WATER MONITOR CORRECTIVE OUTAGE HIGH RADIATION SATURATED FLUSHED LINE AND MR-0336 82-07 DETECTOR ADJUSTED SET POINT i

i METEOROLOGICAL PREVENTIVE OUTAGE CALIBRATION NA CALIBRATED METEOROLOGICAL EQUIPMENT 82-07 DUE EQUIPMENT

)

i l

I i

i WP6

APRIL 1982 Page 1 of 2 MECHANICAL MAINTENANCE LER OR NATURE OF OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER.

CAUSE RESULT CORRECTIVE ACTION REACTOR VESSEL HEAD DISASSEMBLY OUTAGE REFUELING HEAD REMOVED HEAD REMOVED MR-0243 82-07 HIGH PRESSURE SERVICE CORRECTIVE OUTAGE SCALE BUILDUP PRESSURE LOSS CLEANED PIPING WITH WATER PUMP (HPSW)

MR-0274 82-07 WATER LANCE 1A CONTROL ROD DRIVE PREVENTIVE OUTAGE PREVENTIVE PREVENTIVE PERFORMED PREVENTIVE EFFLUENT PUMP MR-0281 82-07 MAINTENANCE MAINTENANCE MAINTENANCE ON PUMP 12 LOWER CONTROL R0D PREVENTIVE OUTAGE PREVENTIVE NA LOWERED AND PERFORMED DRIVE MECHANISMS MR-0247 82-07 MAINTENANCE /

PREVENTIVE MAINlENANCE ON ACCESS TO LOWER CONTROL R0D UPPER CONTROL DRIVE MECHANISMS R0D DRIVE MECHANISM (UCRDM) 1B FORCED CIRCULATION CORRECTIVE OUTAGE SEAL WEAR SEAL WATER REPLACED MECHANICAL, UPPER PUMP MR-0805, 0207 82-07 LEAKAGE AND LOWER SEALS EMERGENCY SERVICE WATER FACILITY OUTAGE NA NA INSTALLED AUTOMATIC BALL SYSTEM CHANGE 82-07 DRIP CHECK VALVE 83-82-2 MR-0271 1A REACTOR FEED PUMP CORRECTIVE OUTAGE WEAR WATER LEAKAGE FROM REMOVED PIPING, INSTALLED COUPLING MR-0177 82-07 COUPLING COOLER UNION AND SEALED OUTLET PIPING LUBE OIL COOLER CORRECTIVE OUTAGE WEAR WATER LEAKAGE CLEANED AND REPACKED TEMPERATURE CONTROL MR-0275 82-07 VALVE VALVE HIGH PRESSURE CORE SPRAY CORRECTIVE OUTAGE WEAR INCREASED STR0KE INSTALLED NEW PACKING PUMP DEMINERALIlED INLET MR-0243 82-07 TIME AND PACKING AND STROKED VALVE VALVE LEAK MP6

APRIL 1982 Page 2 of 2 l

MECHANICAL MAINTENANCE LER OR NATURE OF OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION i

REACTOR SIGHT GLASS CORRECTIVE OUTAGE AGE WATER / STEAM REBUILT UPPER SECTION MR-0076 82-07 LEAKAGE AND TORQUED EMERGENCY SERVICE WATER CORRECTIVE OUTAGE ORIGINAL LEAKING CONNEC-TIGHTENED GAS 4

SUPPLY SYSTEM PUMPS MR-0225 82-07 MANUFACTURE TIONS ON GAS CONNECTIONS LINES I

FORCED CIRCULATION PUMPS PREVENTIVE OUTAGE WEAR IN NA INSTALLED NEW CUP SEALS DISCHARGE VALVES MR-0267 82-07 SIMILAR I

DIAPHRAGMS TURBINE-GENERATOR PREVENTIVE OUTAGE 5 YEAR PM NA COMMENCED DISASSEMBLY OF MR-0244 82-07

. TURBINE-GENERATOR FOR O

MR-0245 OVERHAUL SEISMIC RESTRAINTS FACILITY OUTAGE NRC REQUIREMENT NA INSTALLING SEISMIC 1

CHANGES 82-07 RESTRAINTS 78-82-5, 74-82-12, 78-82-4, 74-81-7, 74-81-9 1

INSERVICE INSPECTION PREVENTIVE OUTAGE NA NA PERFORMING ISI MR-0282 82-07

{

MR-0283 MR-0240 l

l i

i

~

WP6 t

.-