- ML20041F819 + (ML20041F819)
- 05000298/LER-1982-004, Forwards LER 82-004/03L-0.Detailed Event Analysis Submitted + (ML20041F820)
- ML20041F822 + (ML20041F822)
- 05000269/LER-1982-004, Forwards LER 82-004/01T-0.Detailed Event Analysis Encl + (ML20041F825)
- 05000298/LER-1982-004-03, /03L-0:on 820109,during Planned Power Reduction, Min Critical Power Ratio Was Below Operating Limit W/O Initiation of Corrective Actions Required by Tech Specs. Caused by Personnel Error.Procedures Will Be Revised + (ML20041F827)
- 05000269/LER-1982-004-01, /01T-0:on 820217,exam of Radiograph on Weld 85 on Isometric Drawing 11 Indicated Circumferential Void.Caused by Improper fit-up Weld & Insp During Initial Const.Section of Weld Replaced & Socket Welded to Coupling + (ML20041F828)
- ML20041F829 + (ML20041F829)
- ML20041F830 + (ML20041F830)
- 05000324/LER-1982-027, Forwards LER 82-027/03L-0 + (ML20041F832)
- ML20041F834 + (ML20041F834)
- ML20041F835 + (ML20041F835)
- ML20041F837 + (ML20041F837)
- 05000324/LER-1982-027-03, /03L-0:on 820202,main Steam Line Radiation High Channel D Would Not Actuate When Test Signal Was Applied to Channel Input Instrument D12-RM-K603D.Caused by Melted Insulation from Relay Coil of Channel Actuation Relay + (ML20041F838)
- ML20041F839 + (ML20041F839)
- ML20041F841 + (ML20041F841)
- ML20041F842 + (ML20041F842)
- IR 05000369/1982003 + (ML20041F843)
- 05000324/LER-1982-029, Forwards LER 82-029/03L-0.Detailed Event Analysis Encl + (ML20041F844)
- ML20041F846 + (ML20041F846)
- IR 05000518/1982002 + (ML20041F847)
- 05000324/LER-1982-029-03, /03L-0:on 820203,discovered Suction Header Low Pressure Lockout Rendering Divs I & II RHR Svc Water Subsystem Inoperable.Caused by Loss of Operating Fluid Level in Diaphragm Housing of Suction Header Pressure Switch + (ML20041F848)
- ML20041F849 + (ML20041F849)
- ML20041F850 + (ML20041F850)
- 05000325/LER-1982-012, Forwards LER 82-012/03L-0 + (ML20041F852)
- 05000269/LER-1982-001, Forwards LER 82-001/03L-0.Detailed Event Analysis Encl + (ML20041F854)
- ML20041F856 + (ML20041F856)
- ML20041F858 + (ML20041F858)
- 05000325/LER-1982-012-03, /03L-0:on 820203,primary Containment Atmospheric Oxygen Analyzer 1-CAC-AT-1259-2 Showed Unexpected Indications When Returned to Svc Following Routine Maint. Caused by Instrument Zero Ref Shift in Analyzer + (ML20041F859)
- ML20041F860 + (ML20041F860)
- 05000269/LER-1982-001-03, /03L-0:on 820203,motor Driven Emergency Feedwater Pump 1B Declared Inoperable Due to Bearing Vibration Exceeding Acceptable Limits.Caused by Misalignment Between Pump & Motor.Pump & Motor Realigned & Tested Satisfactorily + (ML20041F861)
- 05000320/LER-1982-009, Forwards LER 82-009/03L-0 + (ML20041F862)
- 05000325/LER-1982-006, Forwards LER 82-006/03L-0 + (ML20041F864)
- ML20041F866 + (ML20041F866)
- 05000327/LER-1982-018, Forwards LER 82-018/03L-0 + (ML20041F867)
- ML20041F869 + (ML20041F869)
- ML20041F871 + (ML20041F871)
- 05000325/LER-1982-006-03, /03L-0:on 820205,during Secondary Containment Integrity Verification,Flow Rate Could Not Be Achieved within Tech Specs Limit.Caused by Failure to Maintain Greater than 25-inch Vacuum Due to Penetration Air Leaks + (ML20041F872)
- 05000320/LER-1982-009-03, /03L-0:on 820201,auxiliary Bldg Ventilation Sys Declared Inoperable Due to Low Exhaust Flowrate.Caused by Failure to Readjust Flowrate to Be Greater than 65,000 Cfm Flowrate Limit.Exhaust Fan Vortex Dampers Adjusted + (ML20041F873)
- 05000327/LER-1982-018-03, /03L-0:on 820207,during Startup,Containment Lower Compartment Average Air Temp Discovered at 124.19 F.Two Lower Compartment Train a Coolers Temp Control Valves Had Wrong Settings.Cause Unknown + (ML20041F874)
- ML20041F875 + (ML20041F875)
- ML20041F876 + (ML20041F876)
- ML20041F878 + (ML20041F878)
- 05000296/LER-1982-004, Forwards LER 82-004/03L-0 + (ML20041F879)
- ML20041F881 + (ML20041F881)
- 05000296/LER-1982-004-03, /03L-0:on 820207,while Performing Surveillance Instruction,Temp Switches 3S-TS-73-2A & 3-TS-73-2B Operated Above Tech Specs Limit.Caused by Switches Being Out of Calibr.Switches Calibr + (ML20041F883)
- IR 05000324/1981025 + (ML20041F884)
- ML20041F886 + (ML20041F886)
- ML20041F887 + (ML20041F887)
- ML20041F888 + (ML20041F888)
- ML20041F890 + (ML20041F890)
- ML20041F891 + (ML20041F891)