- 05000293/LER-1980-036, Forwards LER 80-036/01T-0 + (ML19344D937)
- ML19344D938 + (ML19344D938)
- 05000293/LER-1980-036-01, /01T-0:on 800806,found Hourly Fire Check of Auxiliary Offgas Bldg Not Performed on Continuous Basis Since 800707 While Fire Detection Units Were Inoperable. Caused by Communications Lapse Between Personnel + (ML19344D939)
- ML19344D940 + (ML19344D940)
- ML19344D941 + (ML19344D941)
- ML19344D942 + (ML19344D942)
- 05000321/LER-1980-093, Forwards LER 80-093/03L-0 + (ML19344D943)
- ML19344D944 + (ML19344D944)
- ML19344D945 + (ML19344D945)
- ML19344D946 + (ML19344D946)
- ML19344D947 + (ML19344D947)
- ML19344D948 + (ML19344D948)
- 05000321/LER-1980-093-03, /03L-0:on 800731,during Normal Operation,One Torus Water Level Recorder Was Found Inoperative.Caused by Defective Recorder Amplifier.Amplifier Replaced & Recorder Returned to Normal Operation + (ML19344D949)
- 05000321/LER-1980-094, Forwards LER 80-094/03L-0 + (ML19344D950)
- ML19344D951 + (ML19344D951)
- ML19344D952 + (ML19344D952)
- 05000321/LER-1980-094-03, /03L-0:on 800731,during Normal Operation,Offgas Dihydrogen Analyzer N62-N009B Sample Pump Tripped.Caused by Setpoint Drift of Flame Check Water Flow.Water Flow Readjusted & Sample Pump Restarted + (ML19344D953)
- ML19344D954 + (ML19344D954)
- 05000366/LER-1980-111, Forwards LER 80-111/03L-0 + (ML19344D955)
- ML19344D956 + (ML19344D956)
- 05000366/LER-1980-111-03, /03L-0:on 800724,while Operating at Steady State, HPCI Steam Line Inboard Isolation Valve 2E41-F002 Isolated, Making Hcpi Inoperable.Probably Caused by Personnel Bumping HPCI Steam Leak Detection Relay + (ML19344D957)
- 05000325/LER-1980-034-03, /03L-0:on 800804,during Insp of Snubbers on Safety Sys,Pt 19.6.0.1,Bergen Paterson snubber,1B21-70155184,found Overextended.Caused by Loose Pipe Clamp.Clamp Repositioned & Tightened + (ML19344D961)
- ML19344D962 + (ML19344D962)
- 05000312/LER-1980-037, Forwards LER 80-037/04L-0 + (ML19344D963)
- 05000312/LER-1980-037-04, /04L-0:on 800728,monthly Review of Plant Effluent Recorder Charts Indicated Total Dissolved Solids Discharged Exceeded Tech Specs.Caused by Higher than Normal Flow Rate & High Conductivity + (ML19344D965)
- ML19344D966 + (ML19344D966)
- 05000366/LER-1980-112, Forwards LER 80-112/03L-0 + (ML19344D968)
- ML19344D969 + (ML19344D969)
- ML19344D970 + (ML19344D970)
- 05000366/LER-1980-112-03, /03L-0:on 800723,during Steady State Operation, While Performing on HPCI Steam Line Delta P Flow Switch 2E41-N004,high Side micro-switch Found Inoperative.Caused by micro-switch Subcomponent Failure + (ML19344D971)
- ML19344D972 + (ML19344D972)
- ML19344D973 + (ML19344D973)
- 05000366/LER-1980-114, Forwards LER 80-114/03L-0 + (ML19344D974)
- ML19344D975 + (ML19344D975)
- ML19344D976 + (ML19344D976)
- 05000366/LER-1980-114-03, /03L-0:on 800726,while Taking Unit to Cold Shutdown,Hpci Sys Failed to Isolate at Greater than or Equal to 100 Psig.Caused by Corrosion of B Isolation Logic Pressure Switch 2E41-N001D.Instrument Replaced + (ML19344D977)
- ML19344D978 + (ML19344D978)
- ML19344D979 + (ML19344D979)
- ML19344D980 + (ML19344D980)
- ML19344D981 + (ML19344D981)
- 05000344/LER-1980-016, Forwards LER 80-016/03L-0 + (ML19344D982)
- ML19344D985 + (ML19344D985)
- 05000344/LER-1980-016-03, /03L-0:on 800719,during Low Power Physics Testing, South Boric Acid Tank Boron Concentration & North Boric Acid Tank Level Exceeded Tech Specs.Caused by Personnel Error + (ML19344D986)