- 05000237/LER-1979-001-03, /03L-0 on 790103:torus Level Increased to -1 Inch, Due to Repetitive Starts of HPCI Turbine.Increase in Torus Level Determined to Be Result of Inadequate Procedure.Hpci Surveillance Procedures to Be Amended + (ML19270F298)
- ML19270F299 + (ML19270F299)
- 05000333/LER-1979-001, Forwards LER 79-001/03L-0 + (ML19270F300)
- ML19270F301 + (ML19270F301)
- ML19270F302 + (ML19270F302)
- 05000333/LER-1979-001-03, /03L-0 on 790105:failure to Perform Core Performance Surveillance on 781210 & 781223.Currently Developing Surveillance Test Checkoff List,To Ensure That Test Is Not Overlooked Again + (ML19270F303)
- 05000259/LER-1979-001, Forwards LER 79-001/01T-0 + (ML19270F304)
- ML19270F305 + (ML19270F305)
- 05000029/LER-1979-001, Forwards LER 79-001/03L-0 + (ML19270F306)
- ML19270F308 + (ML19270F308)
- 05000029/LER-1979-001-03, /03L-0 on 790103:during Normal Operation,Filter Alarm on Containment Main Coolant Sys Leakage Air Particulate Monitor Was Received.Caused by Running Out of Victoreen Type HV-70 Part 841-1-164 Filter Paper + (ML19270F309)
- 05000259/LER-1979-001-01, /01T-0 on 790118:reactor Scrammed Due to High Flux Actuating Intermediate Range Monitor high-high Neutron Monitoring Circuit;Reactor Neared Criticality.Caused by Withdrawal of High Reactivity Worth Rod + (ML19270F310)
- ML19270F311 + (ML19270F311)
- 05000346/LER-1979-007, Forwards LER 79-007/03L-0 + (ML19270F312)
- ML19270F313 + (ML19270F313)
- ML19270F314 + (ML19270F314)
- 05000346/LER-1979-007-03, /03L-0 on 790110:during Performance of Surveillance Test,Channel 2 of Containment Hydrogen Analyzer Was Found Inoperable.Caused by Defective Zener Diode in Millivolt Converter + (ML19270F315)
- 05000237/LER-1979-003-03, /03L-0 on 790105:PS 2-1430-1466D Tripped at 105 Psi.Caused by Instrument Drift + (ML19270F316)
- ML19270F317 + (ML19270F317)
- ML19270F319 + (ML19270F319)
- 05000321/LER-1979-002, Forwards LER 79-002/03L-0 + (ML19270F320)
- ML19270F322 + (ML19270F322)
- 05000409/LER-1979-003-01, /01T-0 on 790118:indicated Leakage Rate for Seal Injection Sys Makeup Valve Was 0.684 Std Cubic Ft/H.Cause Unknown.Valve Repaired,Now Complies W/Type C Test Criteria + (ML19270F323)
- 05000409/LER-1979-004-01, /01T-0 on 790119:indicated Leak Rate for Demineralized Water Isolation Valve Was 0.597 Std Cubic Ft/H.Caused by Normal Surface Wear.Valve Repaired & Now Complies W/Type C Test Criteria + (ML19270F324)
- 05000321/LER-1979-002-03, /03L-0 on 790111:during Normal Operation,Hpci Steam Supply valves,E41-F002 & E41-F003,automatically Isolated Due to Equipment Room High Differential Temp & Cold Outside Air Flowing Across Inlet Air Temp Elements + (ML19270F325)
- ML19270F326 + (ML19270F326)
- 05000325/LER-1979-005, Forwards LER 79-005/03L-0 + (ML19270F327)
- ML19270F328 + (ML19270F328)
- 05000346/LER-1979-006, Forwards LER 79-006/03L-0 + (ML19270F329)
- ML19270F330 + (ML19270F330)
- 05000325/LER-1979-005-03, /03L-0 on 790104:1A Recirculation Pump Tripped W/Reactor at 97% power.1B Pump Then Reduced to Approx 50% Speed.Caused by 1A Pump Motor Generator Set Low Lubrication Oil Pressure Signal & Missing Locknut.New Locknuts Put in + (ML19270F331)
- ML19270F332 + (ML19270F332)
- 05000346/LER-1979-006-03, /03L-0:on 790105,reviewer Noted 781228 Record of Continuous Alarm at Contact Data Record Point F018.Panel C4705 Not Reset.Caused by Failure of Indicator Lights on Panel C4705.Panel Reset,Clearing F018.Surveillance Modified + (ML19270F333)
- ML19270F334 + (ML19270F334)
- ML19270F335 + (ML19270F335)