D II K E POWE H CO.WANY I'owru Brumiso 42 2 Sot:Tu Cni:ncir STurnT, CHAHIDTT E, N. C. 28242 w n.um o. ema n a sa.

January 31, 1979

%CF Pats > Cf MT I C L [ p** O N E. A S E A 704 S t r aae Pacouctios 373-4263 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Attention:

Mr. Robert L. Baer, Chief Light Water Reactors, Project Branch No. 2 Re: McGuire Nuclear Station Units 1 and 2 Docket Nos. 50-369, -370

Dear Mr. Denton:

Please find attached a copy of a revised table which summarizes the seismic qualification requirements of electrical equipment for McGuire Nuclear Station. Although only two pages of the table were revised, the entire table is included for completeness.

This table was originally submitted on May 2, 1977 in response to NRC staff concerns raised during the seismic qualification review team's visit to McGuire in January-February, 1977.

When this information was originally submitted, several tests were incomplete.

The attached table updates the original submittal to reflect the results of the testing.

Very truly yours, 2rk a PLp William O. Parker, Jr.

GAC:scs Attachment k

D( (

7902060cMl A

TABLE I McGUIRE NUCLEAR STATION - ELECTRICAL EQUIPMENT QUALIFICATION Sheet 1 of 6 Method of G Level G Level Natural Equipment Qualification Requ i reme nt Test Frequency Catego ry (Test or Analysis)

(ZPA)

(ZPA)

(HZ)

Electrical Penetration - Low Test - Single Axis 0.8 3.0 7.25, 21, 25 Voltage Random Multi-Frequency in Each Direction 125 VDC Distribution Centers Test - Biaxial 1.25 2.7 None Reporteci Multi-Frequency 120 VAC Vital Power Panel Test - Biaxial 1.25 2.7 None Reported Boards Mu l t i-Freque ncy Motor Control Centers Test - Blaxial 1.25 2.7 None Reported Multi-Frequency 125 VDC Battery Chargers Test - Biaxial Random 0.46 0.65 8.5, 13.5, 23 Multi-Frequency 125 VDC Batteries Test - Biaxial Random 0.5 1.1 None Found Multi-Frequency 600-120V Essential Transformer Test - Blaxial Random 2.5 7

None Reported Mu l t i-F req ue ncy 4160V Switchgear Test - Biaxial Random 0.8 1.0 FB/V 15, 19, 23, 27, Multi-Frequency 30, 42, SS/v 5, 13, 23, 27, 44 600V Load Centers Test - Biaxial 1.05 3

None Found Multi-Frequency 125 VDC/120 VAC Static Test - Biaxial Random 0.4 0.5 9, 10, 11, 12, 13,

.lnverters Multi-Frequency I4, 15

TABLE I McGUIRE NUCLEAR STATION - ELECTRICAL EQUIPMENT QUALIFICATION Sheet 2 of 6 Method of G Levei G Level Natural Equipment Qualification Requirement Test Frequency Ca tego ry (Test or Analysis)

(ZPA)

(ZPA)

(HZ)

Diesel Engine Analysis - Dynamic 0.48 N/A 22.1, 30.4 Diesel Engine Lube Oil Before Test - Biaxial Random 0.48 0.75 16, 25 and Af ter Pump Multi-Frequency Diesel Engine Generator Analysis - Dynamic 0.48 N/A 22.1, 30.4 D/G Surge Cubicle Test - Blaxial Random 0.48 1.0 8, 10, 12, 15, 18, 21, Multi-Fregiiency 29 D/G VR/ Exciter Panel Test - Biaxial Random 0.48 1.0 15, 21, 26, 30, 31 Multi-Frequency D/G Control Panel Test - Blaxial Random 0.48 0.9 5, 6, 18, 20, 24, Mutti-Frequency 31 D'G Starting Air Compressor Test - Biaxial Random 0.48 0.9 None Found ad Motor Multi-Frequency D/G Grounding Resistor Test - Biaxial Random 0.95 1.10 None Found Muiti-Frequency D/G Grounding Transformer Test - Biaxial Random 0.95 1.10 None Found Multi-Frequency D/G Instrument Air System Test - Blaxial Random 0.95 1.10 None Found Multi-Frequency D/G Fuel Oil Transfer Pump Test - Blaxial Random 0.95 1.10 None Found Back Pressure Relief Valve Multi-Frequency

TABLE I McGUlRE NUCLEAR STATION - ELECTRICAL EQUIPfiENT QUALIFICATION Sheet 3 of 6 Method of G Level G Level Natural Equipment Qualification Requ i reme nt Test Frequency Cate go ry (Test or Analysis)

(ZPA)

(ZPA)

(HZ)

D/G Fuel Oil Transfer Pump and Test - Biaxial Random 0.48 0.9 12, 15, 17, 18, 19, 22 Motor Mu l t i-Freq uency 25, 29, 30, 33 D/G Fuel Oil Booster Pump and Test - Blaxial Random 0.48 0.9 12, 13, 14, 15, 18, 19 Motor (AC)

Mul t i-F req uency 21, 25, 30, 33 D/G Lube Oil Filter Pump and Test - Biaxial Random 0.48 0.75 10, 11, 12, 13, 14, 15 Motor Mu I t i-F req uen cy 17 D/G Jacket Water /Intercooler Test - Blaxial Random 0.48 0.75 17, 27, 29, 30 Pumps and Motor Mu l t i-F reque ncy D/G Crankcase Vacuum Blower Test - Biaxial Random 1.0 1.5 1.8, 2.8, 33 Mu l t i-Freq uency D/G Jacket Water Surge Tank Analysis Dynamic 0.48 N/A Mne Found D/G Fuel Oil Day Tank Analysis - Dynamic 0.48 N/A None Found D/G Fuel Oil Drip Tank Ana lysis - Dynamic 0.48 N/A None Found D/G Fuel Starting Air Tank Analysis - Dynamic 0.48 N/A None Found D/G Fuel Oil Booster Pump Analysis - Equivalent 0.28 N/A Above 33 Motor (DC)

Static (Note 1)

Auvillary Feedwater Pump Analysis - Equivalent 0.12 N/A 23 (axial)

Motor Static (Note 2) 27 (late.al)

Component Cooling Pump Motor Analysis - Equivalent 0.2 N/A 26 (axial)

Static (Note 2) 28 (lateral)

' Fuel Pool Cooling Pump Motor Analysis - Equivalent 0.2 N/A 52 (axial)

Static (Note 2) 54 (lateral)

TABLE I McGUIRE NUCLEAR STATION - ELECTRICAL EQUIPMENT QUALIFICATION Sheet 4 of 6 Method of G Level G Level Natu ra l Equipment Qualification Requirement Test Frequency Catego ry (Test or Analysis)

(ZPA)

(ZPA)

(HZ)

Engineered Safeguards Air Handling Unit Fan Motors for:

-a.

Boric Acid Transfer Analysis - Equivalent 0.45 N/A Above 33 Pump Motors Static (Note 1)

-b.

Containment Spray and Analysis - Equivalent 0.45 N/A Above 33 RHR Sump Pump Motors Static (Note I) c.

Fuel Pool Cooling Pump Analysis - Equivalent 0.845 N/A Above ?3 Motors Static (Note 1) d.

Containment Spray Pump Analysis - Equivalent 0.45 N/A Above 33 Static (Note 1) e.

RHR Pump Motors Analysis - Equivalen 0.45 N/A Above 33 Static (Note 1)

Switchgear Room Air Handling Analysis - Equivalent 0.845 N/A Above 33 Unit Fan Motors Static (Note 1)

Control Room Area Air Handling Analysis - Equivalent 0.94 N/A Above 33.

Unit Fan Motors Static (Note 1)

Control Room Air Handling Unit Analysis - Equivalent 0.94 N/A Abova 33 Fan Motors Static (Note 1)

Control Room and Control Room Analysis - Equivalent 0.94 N/A Above 33 Area Outside Air Pressurizing Static (Note 1)

Fan Motors Chilled Water Pump Motor Analysis - Equivalent 0.94 N/A Above 33 Static (Note 1)

RCP Voltage / Frequency Monitor Test - Blaxial Random 0.95

..o 11, 13, 20, 27, 30, Panel Multi-Frequency 32, 34

TABLE I McGUIRE NUCLEAR STATION - ELECTRICAL EQUIPMENT QUALIFICATION Sheet 5 of 6 Method of G Level G Level Natural Equipment Qualification Requ i reme nt Test Frequency Category (Test or Anal ysis)

(ZPA)

(ZPA)

(HZ)

Hoffman Cabinets Test - Biaxial Random 1.0 2.0 5, 6.5, 10, 15, 16, Multi-Frequency 17, 19, 20, 23, 26, 29 30, 31 Auxiliary Feedwater Panel Test - Biaxial Random 0.48 0.8 12, 16, 23, 25, 27, Multi-Frequency 34 Auxiliary Feedwater Turbine Test - Biaxial Random 0.48 0.8 13, 16, 20, 22, 26, Panel Multi-Frequency 33 Auxiliary Shutdown Panel Test - Biaxial Random 0.48 0.8 10, 14, 18, 20, 23, Multi-Frequency 25, 30, 33.

600-120/15KVA Transforrer Test - Biaxial Random 1.5 2.0 None Found Multi-Frequency D/G Load Sequencer Test - Biaxial Random 0.9 1.1 13, 14, 15, 17, 23, Multi-Frequency 25, 29, 30, 31, 33 HVAC Auxiliary Relay Panel Test - Biaxial Random 0.95 1.3 7.5, 13, 15, 17, 20, Mu l t i-F req uency 24, 27, 29, 32 HVAC Control Panel Test - Biaxial Random 0.95 1.3 15, 23, 30, 36 Multi-Frequency Main Control Board Dynamic Analysis & Test See Note 3 Mechanical Valve Operators Test - Biaxial Random 0.95 3.0 None Found Multi-Frequency Mechanical Division Fluid Test - Biaxial Random 0.95 95 21, 29, 30 System Transmitters Multi-Frequency

TABLE I McGUIRE NUCLEAR STATION - ELECTRICAL EQUIPMENT QUAllFICATION Sheet 6 of 6 NOTE 1 - Natural frequencies determined by computer analysis; verified by prototype testing.

NOTE 2 - Natural frequencies determined by prototype tests.

NOTE 3 - A seismic qualification program was conducted to verify the structural integrity of Main Control Boards and define typical required response spectra (RRS) for Class E devices contained therein.

Finite element models comprised of beam and plate elements were developed to mathematically simulate the structure.

The results of in place field testing were used to verify the mathematical model.

The results of this seismic qualification program demonstrated that the main control l

boards have the structural integrity to survive the specified seismic excitations.

.