Semantic search

Jump to navigation Jump to search
 Issue dateSiteTitle
ML18009A70515 October 1990HarrisLER 90-019-00:on 900824,potential Loss of RHR Sys Noted Due to Loss of Ccw.Caused by Sys design.W/901015 Ltr
ML18009A66824 September 1990HarrisLER 90-018-00:on 900823,loss of Component Cooling Water Inventory Occurred.Caused by Lifted Reactor Coolant Drain Tank HX Valve Caused by Incorrect Relief Valve Setpoint. Inlet Isolation Valve Administratively closed.W/900924 Ltr
ML20081B8555 March 1984Diablo CanyonAffidavit of Jd Shiffer,R Patterson,Jm Gisclon,Kc Doss, JB Hoch,Rc Thornberry,Rd Etzler,Rk Rhodes & EM Burns Re J Cooper 840123 Affidavit & Joint Intervenor 840214 Motion on Design QA
ML20086N1635 October 1983Palo VerdeFinal Part 21 Rept Re Cable Separations in Control Room Panels.Separate Insps for Other Facilities Scheduled Prior to Fuel Load to Identify & Correct Cabling Separation Not in Compliance W/Spec 13-EM-306
ML20027B81322 September 1982Grand GulfLER 82-061/03L-0:on 820830,smoke Detector Zone Covering Standby Svc Water Pumphouse Alarmed & Would Not Clear.Caused by Dust Contamination of Ionization Smoke Detectors. Detectors Cleaned
ML20027B76022 September 1982Grand GulfLER 82-059/01T-0:on 820909,setpoints for RHR Injection Valve Differential Pressure Switches Found High.Caused by Erroneous Procedure Listing Setpoint as 58 Psig Vs 43 Psig. Change Issued to Correct Procedures
ML20054L3754 June 1982San OnofreInterim Deficiency Rept Re Atmospheric Dump Valves Failure to Close on Loss of Air Supply,Initially Reported on 820519. Also Reportable Per Part 21
ML20038C5653 December 1981San OnofreDeficiency Rept Re Improper Sized Wire Connections on Monitoring Devices,Initially Reported 811023.Will Advise Nuclear Measurements by Ltr That Component Contains Substantial Defect.Also Reportable Under Part 21
ML20038C5623 December 1981San OnofreDeficiency Rept Re Malfunction of Pressurizer Level Indicators,Initially Reported 811104.Bechtel Study Concludes Deficiency Also Reportable Under Part 21
ML20010F05626 August 1981San OnofreDeficiency Rept Re Improper Assembly of Coaxial Connectors in Electrical Containment Penetrations,Initially Reported on 810721.Westinghouse Notified of Condition on 810630.Also Reported Per Part 21
ML20010E17121 August 1981VogtlePart 21 Rept Re Load Transfer Design of Primary Loop Crohsover Leg Pipe Restraints,Initially Reported on 810706. Design Reanalyzed,Modified Restraints Installed & Review of NSSS Designs Initiated
ML20009E99017 July 1981San OnofreSuppl to 810619 Final Deficiency Rept Re Use of Incorrect Size Terminal Lugs for Thermon Heat Trace Sys Resistance Temp Detector.Condition Reportable Per Part 21