ML20198K21530 November 1998NPDES Discharge Monitoring Rept for HCGS for Month of Nov 1998Grab sample
NJPDES
ML20065F98829 March 1994NPDES Noncompliance Notification:On 940324,daily Maximum Discharge of Low Volume & Oily Waste Sys Exceeded.Caused by Overload of Sys Trestment Capacity Due to Excessive Waste Oil.Sump & Downstream Lift Station CleanedNJPDES
ML20046B86930 July 1993NPDES Noncompliance 5 Day Rept Re Exceedance of Daily Max Limit for Total Residual Chlorine in Cooling Tower Blowdown Discharge to Delaware River.Caused by Rupture of Sodium Hypochlorite Injection Line.Injection Line IsolatedGrab sample
NJPDES
Temporary Modification
ML18096A90014 August 1992NPDES Noncompliance Notification:On 920715,20 Gallons of Diesel Fuel Discharged from 80-ton Crane Between Salem & Hope Creek Stations.Caused by Broken Fuel Line.Soil Around Discharge Excavated & Placed in Drums for Disposal
ML20099D44631 July 1992NPDES Noncompliance Notification:On 920702,discharge of Approx 20 Gallons of Sodium Hydroxide Solution to Ground West of Plant Cooling Tower Occurred.Chemistry Personnel Wrapped Pipe in Plastic to Prevent Addl DischargeTime of Discovery
ML20101S5518 July 1992NPDES Noncompliance Notification:On 920608,10 Gallons of Hydraulic Oil Discharged to Access Road West of Cooling Tower.Caused by Failure of Hydraulic Sys on 20-ton Mobile Crane.Broken Hydraulic Lines Replaced
ML20090L85419 March 1992Suppl to 920305 NPDES Noncompliance Notification:Approx 7.5 Cubic Feet of Soil & Gravel Removed from Discharge Area & Placed in 55 Gallon Drums.Drums Disposed of as Hazardous Waste at Licensed Disposal Facility
ML20094H12326 February 1992NPDES Noncompliance Notification:On 920127,approx 20 Gallons of Fuel Oil 2 Discharged from Auxiliary Boiler Fuel Oil Day Tank.Secondary Site Gauge Replaced & Operating Procedures Revised Re Draining of Water in Day Tank
ML18096A3683 December 1991Resubmitted NPDES Noncompliance Notification,Containing Notary Seal & Correcting Date to 911104.Certification Should Be Replaced W/Encl Certification
ML20091F44227 November 1991NPDES Noncompliance Notification:On 911029,3 Gallons of Fuel Oil Discharged from Main Fuel Oil Unloading Facility to Ground.Caused by Mishandling of Transfer Line.Fuel Oil Will Be Unloaded within Curbed Concrete Unloading Pad
ML18096A35914 November 1991NPDES Noncompliance Notification:On 911018,3 Gallons of Hydraulic Oil Discharged from Outrigger of Util 80-ton Crane to Ground.Caused by Ruptured Hydraulic Hose.New Hydraulic Hose InstalledNJPDES
ML20085F62815 October 1991NPDES Noncompliance Notification:On 910916,400 Gallons of 0.23 Ppm Chlorinated Stormwater Discharged from Sodium Hypochlorite Storage Tank Secondary Containment to Ground. Caused by Maint Personnel.Corrective Steps in ProgressNJPDES
ML20077L4932 August 1991Informs of 910726 Incident Re Suspected Release to Delaware River of Less than 1 Gallon of Fuel Oil Reported at Facility.Cause Not Determined.Personnel Reviewing Plant Operating RecordsNJPDES
ML18095A58213 November 1990NPDES Noncompliance Notification:On 900913,2 Gallons of Perchloroethylene Spilled at Bosco Cleaning Svcs Trailer on Artifical Island.Contractor Personnel Examined at Hosp. Cleaning Facility Will Be Removed from Island
ML19332C0177 November 1989NPDES Noncompliance Notification:On 890909,spill of Approx 1,000 Gallons of Ammonium Bisulfite Solution Occurred at Plant When Underground Pipeline Breached During Const Excavation.Corrective Action Taken to Stop Spill