NRC 2017-0021, Radiological Environmental Monitoring Program Report - January 1 Through December 31, 2016. Appendix 1
| ML17123A199 | |
| Person / Time | |
|---|---|
| Site: | Point Beach |
| Issue date: | 12/31/2016 |
| From: | Point Beach |
| To: | Office of Nuclear Material Safety and Safeguards, Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML17123A287 | List: |
| References | |
| NRC 2017-0021 | |
| Download: ML17123A199 (113) | |
Text
APPENDIX 1 Environmental, Inc. Midwest Laboratory Final Report for the Point Beach Nuclear Plant and Other Analyses Reporting Period: January - December 2016 112 pages follow
(
~fL A'TI Environmental, Inc.
'+~Ml Midwest Laboratory 700 Landwehr Road* Northbrook, IL 60062-2310
- phone (847) 564-0700 *fax (847) 564-4517 MONTHLY PROGRESS REPORT TO NextEra Energy RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP)
FOR THE POINT BEACH NUCLEAR PLANT TWO RIVERS, WISCONSIN PREPARED AND SUBMITTED BY ENVIRONMENTAL INCORPORATED MIDWEST LABORATORY Project Number: 8006 Reporting Period: January-December, 2016 Reviewed and Approved by ___
--+-~,..£...l,,.....i....;7,\\-~------
Date 02-03-2017 Distribution:
K. Johansen, 1 r copy, 1 e-mail S. Bartels, 1 hardcopy, 1 email
(
(
Section POINT BEACH NUCLEAR PLANT TABLE OF CONTENTS List of Tables...........,................................................................ iii
1.0 INTRODUCTION
...................................................................... iv 2.0 LISTING OF MISSED SAMPLES............................................. v 3
DATA TABLES........................................................................ vi Appendices A
lnterlaboratory Comparison Program Results.......................... A-1 B
Data Reporting Conventions..................................................... B-1 C
Sampling Program and Locations............................................ C-1 D
Graphs of Data Trends............................................................. D-1 E
Supplemental Analyses............................................................ E-1 F
Special Analyses...................................................................... F-1 ii
(
(
POINT BEACH NUCLEAR PLANT LIST OF TABLES Airborne Particulates and lodine-131 Location E-01, Meteorological Tower..............................................
1-1 Location E-02, Site Boundary Control Center..................................
1-2 Location E-03, West Boundary......................................................
1-3 Location E-04, North Boundary......................................................
1-4 Location E-08, G. J. Francar Residence.........................................
1-5 Location E-20, Silver Lake College.................................................
1-6 Airborne Particulates, Gamma Isotopic Analyses.......................................
2-1 Milk........................................................................................................
3-1 Well Water.............................................................................................
4-1 Lake Water.............................................................................................
5-1 Lake Water, Analyses on Quarterly Composites............................................... 6-1 Fish******************************************************************************************************************** 7-1 Shoreline Sediments ****************************************************************************************** 8-1 Soil*****************************************************************************************:*************************** 9-1 Vegetation (Grass).............................................................................................. 10-1 Aquatic Vegetation............................................................................................. 11-1 Gamma Radiation, as Measured by TLDs........................................................ 12-1 Groundwater Monitoring Program...................................................................... 13-1 Vegetation (Corn/Alfalfa).................................................................................... 14-1 iii Ii I:
(
POINT BEACH NUCLEAR PLANT
1.0 INTRODUCTION
The following constitutes the current Monthly Progress Report for the Environmental Radiological Monitoring Program conducted at the Point Beach Nuclear Plant, Two Rivers, Wisconsin.
Results of completed analyses are presented in the attached tables. Missing entries indicate analyses that are not completed. These results will appear in subseq.uent reports. Data tables reflect sample analysis results for both Technical Specification requirements and Special Interest locations and samples are randomly selected within the Program monitoring area to provide additional data for cross-comparisons.
For all gamma isotopic analyses, the spectrum is computer scanned from 80 to 2048 KeV.
Specifically included are Mn-54, Fe-69, Co-58, Co-60, zn.,.65, Zr-95, Nb-95, Ru-103, Ru-106, 1-131, Ba-La-140, Cs-134, Cs-137, Ce-141, and Ce-144. Naturally occurring gamma-emitters, such as K-40 and Ra daughters, are frequently detected in soil and s~diment samples. Specific isotopes listed are K-40, Tl-208, Pb-212, Bi-214, Ra-226 and Ac-228. Th~ results reported under "Other Gammas" may be Co-60, Ru-103 or any other radionuclide which is indicative of other gammas for the sample type. "Other Gammas" do not include naturally occuring radionuclides.
All concentrations, except gross beta, are decay corrected.
All samples were collected within the scheduled period unless noted otherwise in the Listing of Missed Samples.
iv
POINT BEACH NUCLEAR PLANT
{ *--..
2.0 LISTING OF MISSED SAMPLES 1.-
Expected Collection Sample Type Location Date Reason LW E-005 01-13-16 No sample due to icy conditions.
LW E-006 01-13-16 No sample due to icy conditions.
LW E-033 01-13-16 No sample due to icy conditions.
AP/Al E-02 02-04-16 GFI tripped.
LW E-033 02-11-16 No sample due to icy conditions.
AP/Al E-01 03-30-16 Pump failure.
Algae E-005 06-08-16 No algea available Algae E-012 06-08-16 No algea available AP/Al E-01 06-22-16 Loss of power <10 cubic meters.
(
AP/Al E-04 06-22-16 Loss of power <20 cubic meters.
AP/Al E-01 07-06-16 Electrical issues with sampler.
Algae E-005 08-10-16 No algea available Algae E-012 08-10-16 No algea available AP/Al E-01 07-27-16 Electrical issues wit,h sampler.
Pump tripped off due to storm on 8-20-16. Gross beta result=
AP/Al E-02 08-24-16 0.032+/-0.007 pCi/m3.
WW GW-17 09-28-16 Water not available.
Algae E-005 10-05-16 No algea available Algae E-012 10-05-16 No algea available LW E-001 12-31-16 No sample due to icy conditions.
LW E-005 12-31-16 No sample due to icy conditions.
LW E-006 12-31-16 No sample due to icy conditions.
' r \\.
LW E-033 12-31-16 No sample due to icy conditions.
v
POINT BEACH NUCLEAR PLANT 3.0 Data Table!?
vi
~ I r I r
/: c
POINT BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
L Location: E-01, Meteorological Tower Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vol.
Date Vol.
Collected (m3)
Gross Beta 1-131 Collected
{m3)
Gross Beta 1-131 Reguired LLD 0.010 0.030 Reguired LLD 0.010 0.030 01-06-16 308 0.038 +/- 0.004 < 0.008 07-06-16 NDa 01-14-16 344 0.029 +/- 0.004 < 0.010 07-13-16 303 0.023 +/- 0.003 < 0.008 01-20-16 271 0.021 +/- 0.004 < 0.012 07-20-16 304 0.017 +/- 0.003 < 0.008 01-27-16 295 0.030 +/- 0.004 < 0.008 07-27~16 NDa 08-03-16 288 0.021 +/- 0.003 < 0.009 02-04-16 339 0.022 +/- 0.003 < 0.008 02-10-16 255 0.029 +/- 0.004 < 0.011 08-11-16 333 0.033 +/- 0.004 < 0.008 02-17-16 303 0.023 +/- 0.004 < 0.007 08-17-16 253 0.031 +/- 0.004 < 0.007 02-24-16 298 0.023 +/- 0.004 < 0.008 08-24-16 289 0.026 +/- 0.004 < 0.013 03-02-16 305 0.026 +/- 0.004 < 0.009 08-31-16 300 0.026 +/- 0.004 < 0.007 03-10-16 341 0.021 +/- 0.003 < 0.007 09-07-16 310 0.025 +/- 0.003 < 0.007 03-16-16 240 0.014 +/- 0.004 < 0.009 09-14-16 302 0.022 +/- 0.003 < 0.010 03-23-16 312 0.017 +/- 0.003 < 0.007 09-21-16 298 0.031 +/- 0.004 < 0.009 03-30-16 NDa 09-28-16 299 0.020 +/- 0.003 < 0.010
(
1st Quarter 3rd Quarter Mean+/- s.d.
0.025 +/- 0.007 < 0.009 Mean+/- s.d.
0.025 +/- 0.005 < 0.009 04-06-16 299 0.018 +/- 0.003 < 0.008 10-05-16 0.022 +/- 0.003 < 0.009 04-13-16 307 0.015 +/- 0.003 < 0.008 10-12-16 0.030 +/- 0.004 < 0.009 04-20-16 295 0.021 +/- 0.003 < 0.007 10-19-16 0.026 +/- 0.004 < 0.012 04-27-16 303 0.019 +/- 0.003 < 0.009 10-26-16 0.014 +/- 0.003 < 0.011 11-02-16 0.019 +/- 0.003 < 0.008 05-04-16 300 0.016 +/- 0.003 < 0.010 05--'11-16 302 0.015 +/- 0.003 < 0.011 11-09-16 0.044 +/- 0.004 < 0.010 05-18-16 298 0.015 +/- 0.003 < 0.010 11-16-16 0.031 +/- 0.004 < 0.012 05-25-16 299 0.026 +/- 0.004 < 0.010 11-22-16 0.043 +/- 0.005 < 0.013 06-01-16 297 0.017 +/- 0.003 < 0.007 11-30-16 0.038 +/- 0.004 < 0.006 06-08-16 294 0.010 +/- 0.003 < 0.009 12-07-16 0.023 +/- 0.003 < 0.010 06-15-16 103 0.024 +/- 0.007 < 0.014 0
12-15-16 0.023 +/- 0.003 < 0.009 06-22-16 NDa 12-21-16 0.036 +/- 0.004 < 0.011 06-29-16 292 0.015 +/- 0.003 < 0.011 12-28-16 0.025 +/- 0.004 < 0.009 2nd Quarter 4th Quarter Mean+/- s.d.
0.018 +/- 0.005 < 0.010 Mean +/-s.d.
0.029 +/- 0.009 < 0.010 Cumulative Avera9e 0.024 +/- 0.008 < 0.009 a "ND" = No data; see Table 2.0, Listing of Missed Samples.
(
b Low volume due to tripped breaker.
r 1-1 t
POINT BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
(_
Location: E-02, Site Boundary Control Center Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vol.
Date Vol.
Collected (m3)
Gross Beta 1-131 Collected (m3)
Gross Beta 1-131 Required LLD 0.010 0.030 Required LLD 0.010 0.030 01-06-16
. 308 0.037 +/- 0.004 < 0.008 07-06-16 303 0.021 +/- 0.003 < 0.010 01-14-16 336 0.031 +/- 0.004 < 0.010 07-13-16 308 0.025 +/- 0.004 < 0.008 01-20-16 256 0.031 +/- 0.005 < 0.012 07-20-16 300 0.018 +/- 0.003 < 0.008 01-27-16.
295 0.034 +/- 0.004 < 0.008 07-27-16 292 0.028 +/- 0.004 < 0.006 08-03-16 304 0.019 +/- 0.003 < 0.009 02-04-16 NDa 02-10-16 240 0.028 +/- 0.004 < 0.011 08-11-16 342 0.032 +/- 0.004 < 0.008 02-17-16 284 0.021 +/- 0.004 < 0.008 08-17-16 262 0.026 +/- 0.004 < 0.006 02-24-16 287 0.021 +/- 0.004 < 0.008 08-24-16 NDa 03-02-16 293 0.026 +/- 0.004 < 0.009 08-31-16 302 0.022 +/- 0.003 < 0.007 03-10-16 333 0.021 +/- 0.003 < 0.007 09-07-16 312 0.022 +/- 0.003 < 0.007 03-16-16 242 0.015 +/- 0.004 < 0.009 09-14-16 294 0.019 +/- 0.003 < 0.010 03-23-16 308 0.014 +/- 0.003 < 0.007 09-21-16 301 0.033 +/- 0.004 < 0.009 03-30-16 296 0.024 +/- 0.004 < 0.010 09-28-16 299 0.020 +/- 0.003 < 0.010
/~-~
1st Quarter 3rd Quarter l
Mean+/- s.d.
0.025 +/- 0.007 < 0.009 Mean+/- s.d.
0.024 +/- 0.005 < 0.008 04-06-16 297 0.023 +/- 0.004 < 0.008 10-05-16 291 0.023 +/- 0.004 < 0.009 04-13-16 299 0.020 +/- 0.003 < 0.008 10-12-16 293 0.027 +/- 0.004 < 0.009 04-20-16 270 0.024 +/- 0.004 < 0.007 10-19-16 299 0.024 +/- 0.004 < 0.012 04-27-16 297 0.019 +/- 0.003 < 0.009 10-26-16 307 0.015 +/- 0.003 < 0.0.11 11-02-16 301 0.021 +/- 0.003 < 0.008 05-04-16 292 0.020 +/- 0.003 < 0.011 05-11-16 308 0.013 +/- 0.003 < 0.010 11-09-16 309 0.040 +/- 0.004 < 0.010 05-18-16 287 0.017 +/- 0.003 < 0.011 11-16-16 300 0.035 +/- 0.004 < 0.012 05-25-16 295 0.027 +/- 0.004 < 0.010 11-22-16 267 0.045 +/- 0~005 < 0.013 06-01-16 294 0.019 +/- 0.003 < 0.007 11-30-16 337 0.034 +/- 0.004 < 0.006 06-08-16 287 0.012 +/- 0.003 < 0.009 12-07-16 311 0.021 +/- 0.003 < 0.010 06-15-16 294 0.019 +/- 0.003 < 0.005 12-15-16 355 0.023 +/- 0.003 < 0.009 06-22-16 291 0.024 +/- 0.003 < 0.007 12-21-16 260 0.033 +/- 0.004 < 0.011 06-29-16 302 0.018 +/- 0.003 < 0.011 12-28-16 303 0.028 +/- 0.004 < 0.009 2nd Quarter 4th Quarter Mean +/-s.d.
0.020 +/- 0.004 < 0.009 Mean +/-s.d.
0.028 +/- 0.009 < 0.010 Cumulative Avera9e 0.024 +/- 0.007 < 0.009 a "ND"= No data; see Table 2.0, Listing of Missed Samples.
(
1-2
~
~
(
(
POINT. BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
Location: E-03, West Boundary Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vol.
Date Vol.
Collected cn13>
Gross Beta 1-131 Collected (m3).
Gross Beta Reguired LLD 0.010 0.030 Reguired LLD 0.010 01-06-16 308 0.035 +/- 0.004 < 0.008 07-06-16 300 0.021 +/- 0.003 01-14-16 346 0.033 +/- 0.004 < 0.010 07-13-16 305 0.023 +/- 0.003 01-20-16 264 0.029 +/- 0.004 < 0.012 07-20-16 301 0.015 +/- 0.003 01-27-16 302 0.031 +/- 0.004 < 0.008 07-27-16 296 0.022 +/- 0.003 08-03-16 306 0.018 +/- 0.003 02-04-16 344 0.020 +/- 0.003 < 0.008 02-10-16 265 0.028 +/- 0.004 < 0.010 08-11-16 344 0.026 +/- 0.003 02-17-16 288 0.020 +/- 0.004 < 0.007 08-17-16 260 0.024 +/- 0.004 02-24-16 290 0.021 +/- 0.004 < 0.008 08-24-16 297 0.022 +/- 0.003 03-02-16 301 0.027 +/- 0.004 < 0.009 08-31-16 301 0.022 +/- 0.003 03-10-16 340 0.022 +/- 0.003 < 0.007 09-07-16 307 0.021 +/- 0.003 03-16-16 249 0.013 +/- 0.004 < 0.009 09-14-16 302 0.019 +/- 0.003 03-23-16 311 0.016 +/- 0.003 < 0.007 09-21-16 299 0.027 +/- 0.004 03-30-16 297 0.021 +/- 0.004 < 0.010 09-28-16 298
. 0.018 +/- 0.003 1st Quarter 3rd Quarter Mean+/- s.d.
0.024 +/- 0.007 < 0.009 Mean +/-s.d.
0.022 +/- 0.003 04-06-16 293 0.020 +/- 0.003 <: 0.008 10-05-16 303 0.022 +/- 0.003 04-13-16 298 0.019 +/- 0.003 < 0.008*
10-12-16 303 0.027 +/- 0.004 04-20-16 302 0.021 +/- 0.003 < 0.007 10-19-16 300 0.024 +/- 0.004 04-27-16 301 0.017 +/- 0.003 < 0.009 10-26-16 302 0.014 +/- 0.003 11-02-16 298 0.019 +/- 0.003 05-04-16 303 0.019 +/- 0.003 < 0.010 05-11-16 312 0.012 +/- 0.003 < 0.010 11-09-16 311 0.039 +/- 0.004 05-18-16 294 0.014 +/- 0.003 < 0.010 11-16-16 301 0.029 +/- 0.004 05-25-16 299 0.029 +/- 0.004 < 0.010 11-22-16 264 0.042 +/- 0.005 06-01-16
. 292 0.018 +/- 0.003 < 0.007 11-30-16 337 0.033 +/- 0.004 06-08-16 296 0.013 +/- 0.003 < 0.009 12-07-16 305 0.024 +/- 0.003 06-15-16 297 0.021 +/- 0.003 < 0.005 12-15-16 357 0.025 +/- 0.003 06-22-16 291 0.019 +/- 0.003 < 0.007 12-21-16 259 0.027 +/- 0.004 06-29-16 301 0.016 +/- 0.003 < 0.011 12-28-16 299 0.028 +/- 0.004 2nd Quarter 4th Quarter Mean+/- s.d.
0.018 +/- 0.004 < 0.009 Mean +/-s.d.
0.027 +/- 0.008 Cumulative Avera9e 0.023 +/- 0.006
. 1-3 1-131 0.030
< 0.010
< 0.008
< 0.008
< 0.006
< 0.009
< 0.007
< 0.007
< 0.012
< 0.007
< 0.007
< 0.010
< 0.009
< 0.010
< 0.008
< 0.008
< 0.009
< 0.012
< 0.011
< 0.008
< 0.010
< 0.012.
< 0.013
< 0.006
< 0.010
< 0.009
< 0.011
< 0.009
< 0.010
< 0.009
POINT BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
f-Location: E-04, North Boundary Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vo.I.
Date Vol.
Collected
~m3)
Gross Beta 1-131 Collected (m3)
Gross Beta 1-131 Required LLD 0.010 0.030
- Required LLD 0.010 0.030 01-06-16 307 0.039 +/- 0.004 < 0.008 07-06-16 288 0.017 +/- 0.003 < 0.010 01-14-16 351 0.031 +/- 0.004 < 0.010 07-13-16 299 0.021 +/- 0.003 < 0.008 01-20-16 271 0.029 +/- 0.004 < 0.012 07-20-16 301 0.020 +/- 0.003 < 0.008 01-27-16 299 0.032 +/- 0.004 < 0.008 07-27-16 297 0.025 +/- 0.004 < 0.006 08-03-16 306 0.022 +/- 0.003 < 0.009 02-04-16 345 0.023 +/- 0.003 < 0.008 02-10-16 257 0.027 +/- 0.004 < 0.011 08-11-16 346 0.029 +/- 0.003 < 0.007 02-17-16 296 0~020 +/- 0.004 < 0.007 08-17-16 261 0.028 +/- 0.004 < 0.007 02-24-16 300 0.021 +/- 0.004 < 0.008 08-24-16 296 0.022 +/- 0.003 < 0.012 03-02-16 304 0.025 +/- 0.004 < 0.009 08-31-16
. 301
. 0.024 +/- 0.003 < 0.007 03-10-16 339 0.024 +/- 0.003 < 0.007 09-07-16 308 0.021 +/- 0.003 < 0.007 03-16-16 246 0.021 +/- 0.004 < 0.009 09-14-16 302 0.017 +/- 0.003 < 0.010 03-23-16 314 0.016 +/- 0.003 < 0.007 09-21-16 300 0.031 +/- 0.004 < 0.009 03-30-16 298 0.023 +/- 0.004 < 0.010 09-28-16 303 0.019 +/- 0.003 < 0.010 1st Quarter 3rd Quarter
(
Mean+/- s.d.
0.025 +/- 0.006 < 0.009 Mean+/- s.d.
0.023 +/- 0.004 < 0.008 04-06-16 300 0.024 +/- 0.004 < 0.008 10-05-16 309 0.020 +/- 0.003 < 0.008 04-13-16 300 0.015 +/- 0.003 < 0.008 10-12-16 310 0.027 +/- 0.004 < 0.009 04-20-16 299 0.019 +/--0.003 < 0.007 10-19-16 302 0.024 +/- 0.003 < 0.012 04-27-16 300 0.017 +/- 0.003 < 0.009 10-26-16
. 305 0.015 +/- 0.003 < 0.011 11-02-16 298 0.018 +/- 0.003 < 0.008 05-04-16 297 0.017 +/- 0.003 < 0.010 05-11-16 301 0.014 +/- 0.003 < 0.011 11-09-16 308 0.039 +/- 0.004 < 0.010 05-18-16 284 0.015 +/- 0.003 < 0.011 11-16-16 299
. 0.031 +/- 0.004 < 0.012 05-25-16 295 0.029 +/- 0.004 < 0.010 11-22-16 267 0.043 +/- 0.005 < 0.013 06-01-16 291 0.016 +/- 0.003 < 0.007 11-30-16 344 0.037 +/- 0.004 < 0.006 06-08-16 301 0.012 +/- 0.003 < 0.009 12-07-16 314 0.025 +/- 0.003 < 0.009 06-15-16 294 0.019 +/- 0.003 < 0.005 12-15-16 356 0.021 +/- 0.003 < 0.009 06-22-16 NDa 12-21-16 262 0.031 +/- 0.004 < 0.011 06-29-16 290 0.017 +/- 0.003 < 0.011 12-28-16 308 0.030 +/- 0.004 < 0.009 2nd Quarter 4th Quarter Mean +/-s.d.
0.018 +/- 0:005 < 0.009 Mean+/- s.d.
0.028 +/- 0.008 < 0.010 Cumulative Avera9e 0.024 +/- 0.007 < 0.009 a "ND" = No data; see Table 2.0, Listing of Missed Samples.
(
"~~-
1-4
POINT BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
(
Location: E-08, G.J. Francar Residence Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vol.
Date Vol.
Collected (m3)
Gross Beta 1-131 Collected (m3)
Gross Beta 1-131 Required LLD 0.010 0.030 Required LLD 0.010 0.030 01-06-16 306 0.043 +/- 0.005 < 0.008 07-06-16 301 0.019 +/- 0.003 < 0.010 01-14-16 344 0.031 +/- 0.004 < 0.010 07-13-16 311 0.021 +/- 0.003 < 0.008 01-20-16 262 0.027 +/- 0.004 < 0.012 07-20-16 306 0.020 +/- 0.003 < 0.008 01-27-16 296 0.030 +/- 0.004 < 0.008 07-27-16 300 0.026 +/- 0.004 < 0.006 08-03-16 306 0.018 +/- 0.003 < 0.009 02-04-16 339 0.021 +/- 0.003 < 0.008 02-10-16 263 0.029 +/- 0.004 < 0.010 08-11-16 347 0.029 +/- 0.003 < 0.007 02-17-16 294 0.022 +/- 0.004 < 0.007 08-17-16 264 0.024 +/- 0.004 < 0.006 02-24-16 286 0.021 +/- 0.004 < 0.008 08-24-16 296 0.022 +/- 0.003 < 0.012 03-02-16 309 0.023 +/- 0.004 < 0.009 08-31-16 300 0.025 +/- 0.003 < 0.007 03-10-16 338 0.021 +/- 0.003 < 0.007 09-07-16 312 0.019 +/- 0.003 < 0.007 03-16-16 242 0.017 +/- 0.004 < 0.009 09-14-16 309 0.022 +/- 0.003 < 0.009 03-23-16 315 0.013 +/- 0.003 < 0.007 09-21-16 302 0.028 +/- 0.004 < 0.009 03-30-16 296.
0.021 +/- 0.004 < 0.010 09-28-16 306 0.019 +/- 0.003 < 0.010
/'~'
1st Quarter 3rd Quarter
(_
Mean+/- s.d.
0.024 +/- 0.008 < 0.009 Mean +/-s.d.
0.022 +/- 0.004 < 0.008 04-06-16 307 0.024 +/- 0.003 < 0.008 10-05-16 321 0.014 +/- 0.003 < 0.008 04-13-16 309 0.015 +/- 0.003 < 0.008 10-12-16 314 0.027 +/- 0.004 < 0.009 04-20-16 294 0.019 +/- 0.003 < 0.007 10-19-16 303 0.025 +/- 0.004 < 0.012 04-27-16 304 0.019 +/- 0.003 < 0.009 10-26-16 306 0.015 +/- 0.003 < 0.011 11-02-16 296 0.019 +/- 0.003 < 0.008 05-04-16 301 0.016 +/- 0.003 < 0.010 05-11-16 307 0.012 +/- 0.003 < 0.010 11-09-16 310 0.043 +/- 0.004 < 0.010 05-18-16 291 0.014 +/- 0.003 < 0.011 11-16-16 302 0.033 +/- 0.004 < 0.011 05-25-16 299 0.026 +/- 0.004 < 0.010 11-22-16 265 0.037 +/- 0.004 < 0.013 06-01-16 293 0.016 +/- 0.003 < 0.007 11-30-16 336 0.035 +/- 0.004 < 0.006 06-08-16 307 0.013 +/- 0.003 < 0.009 12-07-16 317 0.025 +/- 0.003 < 0.009 06-15-16 294 0.021 +/- 0.003 < 0.005 12-15-16 356 0.021 +/- 0.003 < 0.00$
06-22-16 282 0.022 +/- 0.003 < 0.007 12-21-16 267 0.029 +/- 0.004 < 0.011 06-29-16 306 0.018 +/- 0.003 < 0.011 12-28-16 300 0.024 +/- 0.003 < 0.009 2nd Quarter 4th Quarter Mean+/- s.d.
0.018 +/- 0.004 < 0.009 Mean+/- s.d.
0.027 +/- 0.009 < 0.010 Cumulative Average 0.023 +/- 0.007 < 0.009 Indicator Locations Annual Mean +/- s.d.
0.023 +/- 0.007
< 0.009 c
11*
1-5
~
POINT BEACH NUCLEAR PLANT Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131.
(
Location: E-20, Silver Lake
- ~.-
Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Vol.
Date Vol.
Collected (ms)
Gross Beta 1-131 Collected (ms)
Gross Beta 1-131 Required LLD 0.010 0.030 Required LLD 0.010 0.030 01-06-16 303 0.041 +/- 0.004 < 0.008 07-06-16 298 0.021 +/- 0.003 < 0.010 01-14-16 346 0.047 +/- 0.004 < 0.010 07-13-16 308 0.020 +/- 0.003 < 0.008 01-20-16 272 0.026 +/- 0.004 < 0.012 07-2.0-16 302 0.020 +/- 0.003 < 0.008 01-27-16 298 0.027 +/- 0.004 < 0.008 07-27-16 295 0.024 +/- 0.003 < 0.006 08-03-16 300 0.021 +/- 0.003 < 0.009 02-04-16 341 0.024 +/- 0.003 < 0.008 02-10-16 259 0.028 +/- 0.004 < 0.011 08-11-16 346 0.027 +/- 0.003 < 0.007 02-17-16 297 0.020 +/- 0.004 < 0.007 08-17-16 262 0.025 +/- 0.004 <.0.006 02-24-16 294 0.022 +/- 0.004 < 0.008 08-24-16 295 0.025 +/- 0.003 < 0.012 03-02-16 307 0.021 +/- 0.003 < 0.009 08-31-16 301 0.023 +/- 0.003 -< 0.007 03-10-16 334 0.021 +/- 0.003 < 0.007 09-07-16 292 0.020 +/- 0.003 < 0.008 03-16-16 249 0.017 +/- 0.004 < 0.009 09-14-16 280 0.023 +/- 0.004 < 0.010 03-23-16 310 0.015 +/- 0.003 < 0.007.
09-21-16 301 0.028 +/- 0.004 < 0.009 03-30-16 293 0.023 +/- 0.004 < 0.010 09-28-16 300 0.022 +/- 0.003 < 0.010
~-
1st Quarter 3rd Quarter
(
Mean +/-s.d.
0.026 +/- 0.009 < 0.009 Mean+/- s.d.
0.. 023 +/- 0.003 < 0.008 04-06-16 306 0.020 +/- 0.003 < 0.008 10-05-16 301 0.021 +/- 0.003 < 0.008 04-13-16 308 0.017 +/- 0.003 < 0.008 10-12-16 305 0.027 +/- 0.004 < 0.009 04-20-16 291 0.023 +/- 0.004 < 0.007 10-19-16 301 0.024 +/- 0.003 < 0.012 04-27-16 301 0.017 +/- 0.003 < 0.009 10-26-16 311 0.015 +/- 0.003 < 0.011 11-02-16 302 0.022 +/- 0.003 < 0.008 05-04-16 299 0.016 +/- 0.003 < 0.010 05-11-16 305 0.012 +/- 0.003 < 0.010 11-09-16 311 0.039 +/- 0.004 < 0.010 05-18-16 290 0.016 +/- 0.003 < 0.011 11-16-16 301 0.029 +/- 0.004 < 0.012 I
05-25-16 294 0.030 +/- 0.004 < 0.010 11-22-16 264 0.044 +/- 0.005 < 0.013 06-01-16 294 0.018 +/- 0.003 < 0.007 11-30-16 339 0.037 +/- 0.004 < 0.006 06-08-16.
302 0.011 +/- 0.003 < 0.009 12-07-16.
313 0.021 +/- 0.003 < 0.009 06-15-16 294 0.020 +/- 0,003 < 0.005 12-15-16 355 0.026 +/- 0.003 < 0.009 06-22-16 286 0.021 +/- 0.003 < 0.007 12-21-16 268 0.031 +/- 0.004 < 0.011 06-29-16 300 0.017 +/- 0.003 < 0.011 12-28-16 307 0.026 +/- 0.004 < 0.009 2nd Quarter
- 4th Quarter Mean+/- s.d.
0.018 +/- 0.005 < 0.009 Mean +/-s.d.
0.028 +/- 0.008 < 0.010 Cumulative Average 0.024 +/- 0.007 < 0.009 Control Annual Mean +/- s.d.
0.024 +/- 0.007 < 0.009 f
1-6
POINT BEACH NUCLEAR PLANT Table 2. Gamma emitters in quarterly composites of air particulate filters
(
Units: pCi/m3 (Other)
(Other)
Location Lab Code Be-7 Be-7
.Cs-134 Cs-134 Cs-137 Cs~137 Co-60 (Co-60) Volume Req. LLD MDC 0.01 MDC 0.01 MDC
( 0.10)
MDC m3 1st Quarter E-01 EAP-1810 0.059 +/- 0.012
-0.0004 +/- 0.0004
< 0.0007 -0.0002 +/- 0.0004 < 0.0005
-0.0003 +/- 0.0006 < 0.0007 3609 E-02
- 1811 0.068 +/- 0.015
-0.0009 +/- 0.0006
< 0.0010 0.0004 +/- 0.0006 < 0.0010 0.0000 +/- 0.0009 < 0.0008 3477 E-03
- 1812 0.063 +/- 0.016
-0.0004 +/- 0.0005
< 0.0008 0.0001 +/- 0.0005 < 0.0006 0.0006 +/- 0.0005 < 0.0008 3904 E-04
- 1813 0.065 +/- 0.013 0.0003 +/- 0.0004
< 0.0008 -0.0003 +/- 0.0004 < 0.0005
-0.0002 +/- 0.0005 < 0.0006 3927 E-08
- 1814 0.061 +/- 0.011
-0.0005 +/- 0.0004
< 0.0007 -0.0001 +/- 0.0004 < 0.0005 0.0002 +/- 0.0003 < 0.0005 3889 E-20
- 1815 0.067 +/- 0.015
-0.0006 +/- 0.0005
< 0.0007 -0.0006 +/- 0.0005 < 0.0005
-0.0001 +/- 0.0006 < 0.0008 3903 2nd Quarter E-01 EAP-3825 0.071 +/- 0.013 0.0001 +/- 0.0004
< 0.0006 0.0000 +/- 0.0004. < 0.0006
-0.0001 +/- 0.0004 < 0.0006 3389 E-02
- 3826 0.083 +/- 0.018 0.0001 +/- 0.0004
< 0.0008 -0.0001 +/- 0.0005 < 0.0006 0.0002 +/- 0.0005 < 0.0003 3814 E-03
- 3827 0.093 +/- 0.015
-0.0002 +/- 0.0004
< 0.0009 -0.0003 +/- 0.0005 < 0.0005 0.0002 +/- 0.0005 < 0.0007 3879 E-04
- 3828 0.099 +/- 0.017 0.0004 +/- 0.0005'
< 0.0010 0.0001 +/- 0.0006 < 0.0008 0.0001 +/- 0.0007 < 0.0006 3550 E-08
- 3829 0.088 +/- 0.012
-0.0001 +/- 0.0003
< 0.0007 0.0000 +/- 0.0004 < 0.0007 0.0001 +/- 0.0004 < 0.0007 3894 E-20
- 3831 0.096 +/- 0.019
-0.0001 +/- 0.0004
< 0.0008 0.0004 +/- 0.0006 < 0.0009 0.0002 +/- 0.0007 < 0.0005 3868 3rd Quarter E-01 EAP-5685 0.085 +/- 0.016 0.0001 +/- 0.0006
< 0.0011 0.0000 +/- 0.0006 < 0.0008
-0.0001 +/- 0.0005 < 0.0005 3277 E-02
- 5686 0.070 +/- 0.014
-0.0004 +/- 0.0004
< 0.0009 0.0000 +/- 0.0005 < 0.0006 0.0003 +/- 0.0005 < 0.0005 3750 E-03
- 5687 0.068 +/- 0.015 0.0003 +/- 0.0004
< 0.0008 -0.0002 +/- 0.0005 < 0.0006 0.0003 +/- 0.0004 < 0.0005 3916 E-04
- 5688 0.076 +/- 0.015 0.0004 +/- 0.0005
< 0.0010 0.0003 +/- 0.0006 < 0.0008 0.0000 +/- 0.0006 < 0.0006 3906 E-08
- 5689 0.076 +/- 0.014 0.0001 +/- 0.0005
< 0.0009 0.0001 +/- 0.0006 < 0.0010 0.0002 +/- 0.0005 < 0.0007 3960 E-20
- 5690 0.075.+/- 0.018 0.0001 +/- 0.0005
< 0.0010 -0.0001 +/- 0.0006 < 0.0008
-0.0003 +/- 0.0005 < 0.0007 3879
- (~
4th Quarter E-01 EAP-7198 0.049 +/- 0.014
-0.0001 +/- 0.0005
< 0.0010 0.0002 +/- 0.0005 < 0.0008 0.0000 +/- 0.0005 < 0.0007 3895 E-02
- 7199 0.064 +/- 0.014 0.0001 +/- 0.0005
< 0.0009 0.0004 +/- 0.0005 < 0.0008
-0.0002 +/- 0.0005 < 0.0008 3933 E-03
- 7201 0.050 +/- 0.011
-0.0001 +/- 0.0004
< 0.0007 0.0000 +/- 0.0004 < 0.0007
-0.0005 +/- 0.0005 < 0.0004 3939 E-04
- 7202 0.065 +/- 0.014 0.0000 +/- 0.0005
< 0.0008 -0.0002 +/- 0.0006 < 0.0008 0.0001 +/- 0.0006 < 0.0009 3981 E-08
- 7203 0.051 +/- 0.011
-0.0007 +/- 0.0004
< 0.0006 0.0005 +/- 0.0006 < 0.0005
-0.0001 +/- 0.0005 < 0.0007 3993 E-20
- 7204 0.051 +/- 0.014
-0.0001 +/- 0.0003
< 0.0007 0.0003 +/- 0.0004 < 0.0008
-0.0002 +/- 0.0005 < 0.0005 3979 Annual Mean+/-s.d.
0.071 +/- 0.014
-0.0001 +/- 0.0003
< 0.0008 0.0000 +/- 0.0003 < 0.0007 0.0000 +/- 0.0002 < 0.0006
(
2-1
POINT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples Collection: Monthly Sample Description and Concentration (pCi/L)
E-11 Lambert Dai!Y Farm MDC MDC MDC Required Collection Date 01-13-16 02-10-16 03-09-16 LLD Lab Code EMI-195 EMI-566 EMI-1006 Sr-89
-0.5 +/- 0.8
< 0.7
-0.1 +/- 0.7
< 0.7
-0.4 +/- 0.9
< 0.8 5.0 Sr-90 0.8 +/- 0.3
< 0.5 0.6 +/- 0.3
< 0.5 0.9 +/- 0.4
< 0.6 1.0 1-131 0.02 +/- 0.16
< 0.29 Q.10+/-0.14
< 0.24
-0.11 +/- 0.17
< 0.35 O.q K-40 1299 +/- 101 1348 +/- 101 1302 +/- 96 Cs-134
-0.3 +/- 1.8
< 3.4 1.3 +/- 1.6
< 3.2
-0.4+/-1.7
< 3.0 5.0 Cs-137 0.3 +/- 2.3
< 4.3 0.3 +/- 1.7
< 3.2
-0.2+/-1.9
< 2.7 5.0 Ba-La-140 0.1 +/- 1.8
< 2.4
-0.4 +/- 1.8
< 1.8
-0.5 +/- 1.6
< 1.2 5.0 Other (Co-60)
-0.6 +/- 2.1
< 3.0 0.9 +/- 1.9
< 2.5
-1.1 +/- 1.8
< 1.9 15.0 Required Collection Date 04-13-16 05-11-16 06-08-16 LLD Lab Code EMI-1541
.. -- -~..J;Ml=..2295_
-EMl--288&-*-* -- -*-------- --
/'
Sr-89 0.1 +/- 0.8
< 0.8 0.4 +/- 0.7
< 0.7 0.8 +/- 0.8
< 1.0 5.0 f,
\\t,_
Sr-90 0.8 +/- 0.3
< 0.5 0,6 +/- 0.3
< 0.5 0.3 +/- 0.3
< 0.5 1.0 1-131 0.12 +/- 0.25
< 0.47
-0.03 +/- 0.18
< 0.39 0.06 +/- 0.15
< 0.26 0.5 K-40 1305 +/- 94 1351 +/- 97 1378 +/- 102 Cs-134
-1.2 +/- 1.7
< 3.0
-0.3 +/- 1.6
< 2.9 0.7 +/- 1.6
< 3.2 5.0 Cs-137 1.0 +/- 1.9
< 3.8 0.7 +/- 1.6
< 2.9 2.1 +/- 1.9
< 3.5 5.0 Ba-La-140 0.4 +/- 1.4
< 2.5
-1.7 +/- 1.5
< 3.8
-0.5 +/- 1.7
< 1.6 5:0 Other (Co-60) 1.5 +/- 2.0
< 2.5
-1.4 +/- 1.6
< 1.0
-1.6 +/- 2.1
< 2.4 15.0
(
3-1
POINT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples
~
'~.
Collection: Monthly Sample Description and Concentration (pCi/L)
E-11 Lambert Daiey Farm MDC MDC MDC Required Collection Date 07-13-16 08-10-16 09-14-16 LLD Lab Code EMI-3530 EMI-4253 EMI-4826 Sr-89 0.3 +/- 0.7
< 0.7 0.2 +/- 0.9
< 0.8
-0.4 +/- 0.8
< 0.7 5.0 Sr-90 0.5 +/- 0.3
< 0.5 0.7 +/- 0.4
< 0.6 0.9 +/- 0.4
< 0.6 1.0 1-131 0.08 +/- 0.10
< 0.14 0.08 +/- 0.23
< 0.45 0.03 +/- 0.13
< 0.23 0.5 K-40 1376 +/- 43 1414 +/- 120 1198 +/- 97 Cs-134 0.0 +/- 0.7
< 1.5 0.6 +/- 1.8
< 3.0 0.8 +/- 1.7
< 3.3 5.0 Cs-137 0.6 +/- 0.8
< 1.6 2.3 +/- 2.3
< 4.5 0.2 +/- 1.8
< 3.0 5.0 Ba-La-140
-0.6 +/- 0.7
< 2.4
-2.0 +/- 2.1
< 4.9
-0.3 +/- 1.6
< 3.4 5.0 Other (Co-60)
-0.1 +/- 0.9
< 1.9 1.3 +/- 2.4
< 4.6
-0.1 +/- 1.8
< 2.5 15.0 Required Collection Date 10-12-16 11-09-16 12-14-16 LLD Lab Code EMI-5455 EMI-6166 EMI-6822
(
Sr-89
-0.2 +/- 0.8
< 0.7
-0.3 +/- 0.7
< 0.6
-0.2 +/- 0.8
< 0.8 5.0 Sr-90 0.9 +/- 0.3
< 0.5 0.7 +/- 0.3
< 0.5 0.8 +/- 0.4
< 0.6 1.0 1-131 0.09 +/- 0.11
< 0.18 0.01 +/- 0.16
< 0.28 0.06 +/- 0.15
< 0.26 0.5 K-40 1370 +/- 107 1405 +/- 104 1383 +/- 98 Cs-134
-0.6 +/- 1.8
< 3.2
-0.3 +/- 2.0
< 4.0 0.1 +/- 1.7
< 3.~
5.0 Cs-137
-0.1 +/- 2.2
< 4.1 0.6 +/- 2.3
< 3.8 0.8 +/- 2.1
< 3.7 5.0 Ba-La-140
-0.3 +/- 1.9
< 4.2
-0.3 +/- 1.8
< 4.9
-0.7 +/- 1.3
< 2.6 5.0 Other (Co-60) 0.5 +/- 2.0
< 3.3 3.3 +/- 2.2
< 3.4
-0.6 +/- 2.1
< 2.8 15.0
(
3-2
POINT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples Collection: Monthly Sample Description and Concentration (pCi/L)
E-21 Strutz Dairy Farm MDC MDC MDC Required Collection Date 01-13:15 02-10-16 03-09-16 LLD Lab Code EMI-196 EMI-567 EMI-1007" Sr-89 0.1 +/- 0.8
< 0.9 0.0 +/- 0.7
< 0.9
-1.0 +/- 1.1
< 1.1 5.0 Sr-90 0.3 +/- 0.3
< 0.6 0.3 +/- 0.3
< 0.6 0.8 +/- 0.4
< 0.7 1.0 1-131
-0.01 +/- 0.16
< 0.29
-0.09 +/- 0.12
< 0.22 0.01 +/- 0.19
< 0.38 0.5 K-40 1442 +/- 111 1285 +/- 96 1436 +/- 105 Cs-134
-1.2 +/- 1.9
< 3.3
-1.7 +/- 1.5
< 2.8
-0.3 +/- 1.7
< 2.8 5.0 Cs-137 0.9 +/- 2.1
< 3.8 0.1 +/- 1.8
< 2.7 2.2 +/- 1.8
< 3.3 5.0 Ba-La-140 0.9 +/- 1.5
< 2.0
-2.2 +/- 1.7
< 2.6 0.2 +/- 1.8
< 2.7 5.0 Other (Co-60)
-0.3 +/- 2.3
< 3.3
-0.7 +/- 1.9
< 2.7 3.1 +/- 2.1
< 3.2 15.0 Required Collection Date 04-13-16 05-11-16 06-08-16 LLD Lab Code EMI-1542 EMI-2296 EMI-2887
~
Sr-89 0.6 +/- 0.7
< 0.8 0.5 +/- 0.6
< 0.8 0.3 +/- 0.7
< 0.8 5.0 Sr-90 0.5 +/- 0.3
< 0.5 0.1 +/- 0.3
< 0.6 0.3 +/- 0.3
< 0.5 1.0 1-131 0.09 +/- 0.16
< 0.29 0.06 +/- 0.21
< 0.43 0.09 +/- 0.12
< 0.17 0.5 K-40 1415 +/- 109 1310 +/- 79 1385 +/- 97 Cs-134
-0.4 +/- 1.6
< 2.9
-0.8 +/- 1.4
< 2.6
-0.6 +/- 1.5
< 2.8 5.0 Cs-137 0.8 +/- 2.3
< 3.4 0.5 +/- 1.5
< 2.4 0.9 +/- 1.9
< 3.3 5.0 Ba-La-140
-0.2 +/- 1.8
< 3.1 3.0 +/- 1.2
< 4.6
-1.3 +/- 1.6
< 1.7 5.0 Other (Co-60) 0.9 +/- 1.9
< 3.0
-0.7 +/- 1.7
< 2.0 1.3 +/- 1.7
< 2.5 15.0
(
f, 3-3
.PQINT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples Collection: Monthly Sample Description and Concentration (pCi/L)
E-21 Strutz Dai[ll Farm MDC MDC Collection Date 07-13-16 08-10-16 Lab Code EMI-3531 EMI-4254 Sr-89
-0.5 +/- 0.7
< 0.8 0.4 +/- 0.8
< 0.8 Sr-90 0.6 +/- 0.3
< 0.5 0.3 +/- 0.3
< 0.6 1-131.
-0.02 +/- 0.12
< 0.22 0.16 +/- 0.24
< 0.47 K-40 1371 +/- 43 1348 +/- 79 Cs-134
-0.5 +/- 0.7
< 1.5
-0.2 +/- 1.2
< 2.3 Cs-137
-0.1 +/- 0.8
< 1.4 1.7 +/- 1.2
< 2.5 Ba-La-140
-1.1 +/- 0.7
< 3.0
-0.4 +/- 1.4
< 4.4 Other (Co-60) 0.1 +/- 0.8
< 1.3 0.5 +/- 1.5
< 2.6 Collection Date 10-12-16.
11-09-16 Lab Code EMI-5456 EMI-6167
(
Sr-89 0.4 +/- 0.8
< 0,9
-0.1 +/- 0.6
< 0.6
\\,
Sr-90 0.2 +/- 0.3
< 0.6 0.3 +/- 0.2
< 0.5 1-131 0.01 +/- 0.11
< 0.20 0.03 +/- 0.18
< 0.33 K-40 1469 +/- 94 1369 +/- 98 Cs-134
-0.7 +/- 1.7
< 3.4
-0.5 +/- 1.6
< 2.8 Cs-137
-1.1+/-1.8
< 1.9
-0.4 +/- 2.0
< 2.9 Ba-La-140
-1.6 +/- 1.4
< 4.5
-3.2+/-1.7
< 4.9 other (Co-60) 1.5 +/- 1.9
< 2.6
-0.7 +/- 1.9
< 2.9 3-4 09-14-16 EMI-4828
-0.7 +/- 0.7 0.7 +/- 0.3
-0.16 +/- 0.16 1445 +/- 90
-0.3 +/- 1.4
-0.2 +/- 1.7-
-1.1 +/- 1.6
-0.3 +/- 1.6 12-14-16 EMI-6823
-0.1 +/- 0.7 0.4 +/- 0.3
-0.06 +/- 0.12 1438 +/- 103
-1.0 +/- 1.7 1.8 +/- 2.0
-2.1 +/- 1.7 0.4 +/- 2.1 MDC Required LLD
< 0.7 5.0
< 0.6 1.0
< 0.39 0.5
< 2.6 5.0
< 3.5 5.0
< 3.5 5.0
< 2.7 15.0.
Required LLD
< 0.7 5.0
< 0.6 1.0
< 0.18 0.5
< 2.6 5.0
< 3.1 5.0
< 2.7 5.0
< 3.0 15.0 I I Ji r
~ L
POlbjT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples
(_
Collection: Monthly Sample Description and Concentration (pCi/L)
E-40 Barta MDC MDC Collection Date 01-03-16 02-10-16 Lab Code EMI-197 EMI-568 Sr-89 0.0 +/- 0.7
< 0.7
-0.1 +/- 0.7
< 0.7 Sr-90 0.4 +/- 0.3
< 0.5
.0.6 +/- 0.3
< 0.5.
1-131 0.02 +/- 0.17
< 0.31
-0.02 +/- 0.12
< 0.23 K-40 1333 +/- 112 1314 +/- 107 Cs-134
-1.0 +/- 1.9
< 3.4 0.3 +/- 1.9
< 3:7 Cs-137
-2.0 +/- 2.2
< 2.6 0.4 +/- 2.2
< 3.9 Ba-La-140 1.2 +/- 1;9
< 3.4
-0.1+/-2.0
< 3.1
.Other (Co-60) 3.2 +/- 2.2
< 3.3 1.4 +/- 1.8
< 2.2 Collection Date 04-13-16 05-11:15 Lab Code EMI-1543 EMI-2297
~-
Sr-89 0.4 +/- 0.6
<0.6
-0.1 +/- 0.7
< 0.6 Sr-90 0.3 +/- 0.3
< 0.5 0.5 +/- 0.3
< 0.5 1-131 0.08 +/- 0.?2
< 0.39 0.11 +/- 0.19
< 0.37 K-40 1305 +/- 104 1419.+/- 95 Cs-134 1.3 +/- 1.6
< 2.8 1.3 +/- 1.7
< 3.0 Cs-137 1.0 +/- 1.9.
< 3.5 1.3 +/- 1.8
< 3.5 Ba-La-140 2.3 +/- 1.6
< 3.8 3.0 +/- 1.3
< 4.1 Other (Co-60)
-1.1 +/- 2.0
< 1.6
-0.3 +/- 1.8
< 2.3
(_
3-5 03-09-16 EMI-1008 0.1 +/- 0.7 0.4 +/- 0.3
-0.05 +/- 0.18 1373 +/- 94 0.5 +/- 1.4 0.5 +/- 1.9
-0.7 +/- 1.7
-1.1 +/- 2.0 06-08-16 EMI-2888
-o:r 4 0.7 0.7 +/- 0.3 0.07 +/- 0.22 1448 +/- 98 0.7 +/- 1.4 2.2 +/- 1.9 0.3 +/- 1.2 0,7 +/- 2.0 MDC
< 0.7
< 0.5
< 0.37
< 2.6
< 2.2
< 1.8
< 1.6
< 0.7
< 0.5
< 0.42
< 2.8
< 3.4
< 2.7
< 3.2 Required LLD 5.0 1.0 0.5 5.0*
5.0 5.0 15.0
~
!I
POINT BEACH NUCLEAR PLANT Table 3. Radioactivity in milk samples
(_
Collection: Monthly Sample Description and Concentration (pCi/L)
E-40 Barta MDC MDC Collection Date 07-13-16 08-10-16 Lab Code EMI-3532 EMI-4255 Sr-89 0.1 +/- 0.6
< 0.6 0.6 +/- 0.7
< 0.6 Sr-90 0.5 +/- 0.3
< 0.4 0.4 +/- 0.3
< 0.5 1-131
-0.19 +/- 0.12
< 0.23 0.17 +/- 0.23
< 0.44 K-40 1448 +/- 43 1410 +/- 92 Cs-134 0.0 +/- 0.7
< 1.3 0.3 +/- 1.5
< 2.7 Cs-137 0.3 +/- 0.8
< 1.5
-0.5 +/- 1.6
< 2.5 Ba-La-140 0.8 +/- 0.7
< 3.4 0.4 +/- 1.3
< 4.8 Other (Co-60)
-1.0 +/- 0.8
< 1.0
-1.4 +/- 1.8
< 3.0 Collection Date 10-12-16 11-09-16 Lab Code EMI-5457 EMI-6168 Sr-89
-0.7 +/- 0.8
< 0.7 1.9 +/- 2.0
< 1.6 Sr-90 0.9 +/- 0.3
< 0.5 1.2 +/- 0.5
< 0.8 1-131 0.00 +/- 0.19
< 0.41
-0.08 +/- 0.18
< 0.32 K-40 1395 +/- 105 1322 +/- 109 Cs-134 0.5 +/- 1.8
< 3.2 0.6 +/- 1.9
< 4.5 Cs-137
-0.7 +/- 1.9
< 3.7
-1.1+/-2.4
< 3.1 Ba-La-140
-1.2 +/- 1.5
< 3.3
-5.1 +/- 1.7
< 3.8 Other (Co-60)
-1.1+/-1.8
< 2.3
-1.4 +/- 2.5
< 3.5 Sr-89 Annual Mean + s.d.
0.0 +/- 0.5 Sr-90 Annual Mean + s.d.
0.6 :!: 0.3 1-131 Annual Mean + s.d.
0.03 :!: 0.08 K-40 Annual Mean + s.d.
1370 :!: 60 Cs-134 Annual Mean + s.d.
-0.2 +/- 0.8 Cs-137 Annual Mean + s.d.
0.4 :!: 1.0 Ba-La Annual Mean+ s.d.
-1>.5 :!: 1.6 Co-60 Annual Mean+ s.d.
0.2 +/- 1.3
(
3-6 09-14-16 EMI-4829
-0.3 +/- 0.8 0.7 +/- 0.4 0.12 +/- 0.19 1295 +/- 106
-1.5 +/- 1.9
-0.5 +/- 2.0
-1.4 +/- 1.9 -
0.4 +/- 1.9 12-14-16 EMI-6824 0.5 +/- 0.6 0.3 +/- 0.3 0.06 +/- 0:12 1405 +/- 110
-0.9 +/- 1.7
-1.3 +/- 1.9
-2.6 +/- 1.5 0.4 +/- 2.1 MDC
< 0.7
< 0.6
.< 0.37
< 3.5
< 3.1
< 3.2
<.2.2
< 0.6
< 0.5
< 0.18
< 3.1
< 2.8
< 2.9
< 3.7 Required LLD 5.0 1.0 0.5 5.0 5.0 5.0 15.0 Required LLD 5.0 1.0 0.5 5.0 5.0 5.0 15.0
POINT BEACH NUCLEAR PLANT Table 4. Radioactivity in Well Water Samples, E-10 Collection: Quarterly Units: pCi/L 1st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Req.
Annual LLD Mean +/-s.d Collection Date 01-15-16 04-12-16 07-14-16 10-11-16 Lab Code EWW-240 EWW-1555 EWW-3556 EWW-5508 Gross Beta 3.9 +/-2.1 2.9 +/- 1.3 4.1 +/- 1.7 2.8 +/- 1.2 4.0 3.4 H-3
-3.4 +/- 71.9
-16.8 +/- 72.3 26.5 +/- 78.7 25.6 +/- 79.2 500 8.0 Sr-89
-0.3 +/- 0.4 0.3 +/- 0.5 0.1 +/- 0.4 0.1 +/- 0.4 5.0 0.1 Sr-90 0.2 +/- 0.2
-0.2 +/- 0.2 0.0 +/- 0.2 0.0 +/- 0.2 1.0 0.0 1-131 0.02 +/- 0.12
-0.02 +/-0.12 0.02 +/- 0.13
-0.16 +/- 0.23 0.5
-0.04 Mn-54 1.0 +/- 1.9
-0.4 +/- 1.3
-0.4 +/- 1.1 0.2 +/- 1.7 10 0.1 Fe-59
-2.1 +/- 3.3
-0.6 +/- 2.0
-1.9 +/- 2.0 4.2 +/- 3.5 30
-0.1 Co-58 0.3 +/- 1.6
-0.2 +/- 1.2
-1.2 +/- 1.0
-0.4 +/- 1.6 10
-0.4 Co-60 1.1 +/- 1.4
-0.6 +/- 1.3 0.0 +/- 1.1 0.6 +/- 1.8 10 0.3 Zn-65
-2.5 +/- 2.8 1.9 +/- 2.6 0.2 +/- 2.2
-4.3 +/- 4.5 30
-1.2 Zr-Nb-95
-4.9 +/- 2.2
-0.1 +/- 1.3
-2.1 +/- 1.4
-1.3 +/- 1.9 15
-2.1 Cs-134 0.3 +/- 1.6 0.3 +/- 1.3
-0.6 +/- 1.2 3.1 +/- 1.8 10 0.8 Cs-137 0.0 +/- 2.0 0.6 +/- 1.5
-1.1 +/- 1.3
-0.9 +/- 1.8 10
-0.4 Ba-La-140
-1.2 +/- 2.0
-0.3 +/- 1.4
-1.3 +/- 1.2
-0.8 +/- 2.3 15
-0.9
,/
Other (Ru-103)
-0.1 +/- 1.5.
0.7 +/- 1.2 0.2 +/- 0.9
-0.4 +/- 2.0 30 0.1
( *,,
MDC Data Collection Date 01-15-16 04-12-16 07-14-16 10-11-16 Lab Code EWW-240 EWW-1555 EWW-3556 EWW-5508 Gross Beta
< 3.8
< 2.0
< 2.8
< 2.0 4.0
< 2.7 H-3
< 145.5
< 147.8
< 146.9
< 150.9 500
< 147.8 Sr-89
< 0.5
< 0.7
< 0.5
< 0.6 5.0
< 0.6 Sr-90
< 0.5
< 0.5
< 0.4
< 0.4 1.0
< 0.5 1-131
< 0.22
< 0.21
< 0.23
< 0.44 0.5
< 0.28 Mn-54
< 3.2
< 1.7
< 1.7
< 3.0 10
< 2.4 Fe-59
< 5.1
< 4.2
< 2.8
< 6.2 30
<4.6 Co-58
< 3.0
< 2.1
< 1.4
< 2.3 10
< 2.2 Co-60
< 2.2
< 1.1
< 1.6
< 2.6 10
< 1.9 Zn-65
< 4.5
< 3.8
< 3.5
< 5.9 30
<4.4 Zr-Nb-95
< 4.1
< 2.1
< 2.7
< 2.7 15
<2.9 Cs-134
< 3.0
< 2.7
< 2.0
< 3.5 10
< 2.8 Cs-137
< 3.5
< 2.1
< 1.8
< 1.7 10
<2.3 Ba-La-140
< 3.2
< 3.9
< 1.6
< 2.6 15
< 2.8 Other (Ru-103)
< 2.4
< 3.2
< 1.8
< 2.2 30
<2.4
/
\\..
4-1
) r
(
\\
(
\\
POINT BEACH Table 5. Lake water, analyses for gross beta, iodine-131 and gamma emitting isotopes.
Location: E-01 (Meteorological Tower)
Collection: Monthly composites Units: pCi/L Lab Code Date Collected Gross beta 1-131 Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Other (Ru-103)
Lab Code Date Collected Gross beta 1-131 Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 MDC ELW-198 01-13-16 2.8 +/- 0.7
< 0.9 0.08 +/- 0.11
< 0.19 2.6 +/- 19.3
< 36.2
-0.3 +/- 1.8
< 3.1 2.5 +/- 3.4
< 5.8
-2.7 +/- 1.8
< 1.7 0.6 +/- 1.8
< 3.0
-2.4 +/- 4.3
< 5.1
-0.6 +/- 1.6
< 2.9
-0.6 +/- 1.9
< 3.8
-1.8 +/- 2.3
< 2.4
-0.3 +/- 1.9
< 2.4
-1.7+/-2.1
<3.5 ELW-2360 05-11-16 2.1 +/- 0.9
< 1.6
-0.12 +/- 0.22
< 0.4-1 7.9 +/- 12.1 1.6 +/- 1.3
-3.7 +/- 2.8 1.7 +/- 1.2
-1.8 +/- 1.3
-0.6 +/- 2.9
-1.5 +/- 1.3 0.8 +/- 1.3 0.2 +/- 1.6
< 31.3
< 2.5
< 4.8
< 2.5
< 1.3
< 3.7
< 2.6
< 2.8
< 2.7 Ba-La-140
-0.9 +/- 1.5
< 4.9 Other (Ru-103)
-0.6 +/- 1.5
< 2.7 Lab Code ELW-4901 Date Collected 09-14-16 MDC ELW-583 02-10-16 3.0 +/- 1.0
< 1.7 0.10 +/- 0.18
< 0.31 4.3 +/- 16.5
< 19.6
-0.3 +/- 1.6
< 2.3
-0.1 +/- 2.5
< 3.7 2.5 +/- 1.7
< 2.5 0.9 +/- 1.7
< 2.4 1.1 +/- 3.8
< 4.3
-0.7 +/- 1.7
< 2.5 0.0 +/- 1.6
< 3.1
-2.8 +/- 1.9
< 1.2
-0.3 +/- 1.5
< 2.0
-0.9 +/- 1.9
< 2.9 ELW-2929 06-08-16 3.1 +/- 0.7
< 0.9 0.01 +/-0.15
<0.27 2.7+/-11.1
-0:5 +/- 1.4
-2.1 +/- 2.6
-1.3+/-1.5 0.2 +/- 1.3 1.4 +/- 3.1 1.6 +/- 1.3 0.8 +/- 1.6 1.5 +/- 1.9 2.6 +/- 1.4
-0.6 +/- 1.4 ELW-5450 10-11-16
< 20.7
< 1.6
< 3.1
< 2.1
< 2.1
< 5:2
< 2.5
< 2.8
< 3.3
< 5.1
< 2.9 MDC ELW-1032 03-09-16 2.3 +/- 0.6
< 0.9 0.13+/-0.16
<0.27
-3.0 +/- 12.3
< 24.4 -
-0.5 +/- 1.5
< 2.2
-0.8 +/- 2.2
< 3.6 0.8 +/- 1.6
< 3.2 0.8 +/- 1.9
< 2.6 0.2 +/- 3.3
< 6.1
-0.5 +/- 1.6
< 2.5 0.3 +/- 1.8
< 3.1 0.7 +/- 1.7
< 3.0
-1.2 +/- 2.1
< 5. 1 0.5 +/- 1.5
< 3.2 ELW-3568 07-13-16 1.6 +/- 0.7
< 1.1 0.07 +/- 0.14
< 0.24
-1.7 +/- 6.2 0.3 +/- 0.6
-0.4 +/- 1.2 0.8 +/- 0.6 0.4 +/- 0.7 0.1 +/- 1.4 0.1 +/- 0.6
-0.2 +/- 0.6 0.1 +/- 0.7
-2.8 +/- 0.7
-1.3+/-0.7 ELW-6265 11-09-16
< 15.5
< 1.2
< 1.9
< 1.1*
< 1.0
< 2.6
< 1.8
< 1.4
< 1.3
< 5.4
< 1.2 Gross beta 1-131 1.3 +/- 0.6
< 0.9 1.6 +/- 0.7
< 0.43 -
-0.03 +/- 0.21
< 1.1 1.4 +/- 0.9
< 1.6
< 0.48 Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 other (Ru-103) 0.14 +/- 0.23 2.7 +/- 15.4 0.5 +/- 1.6 2.3 +/- 3.4 0.7 +/- 1.6
-0.9 +/- 1.7 1.4 +/- 2.9 0.0 +/- 1.5 0.5 +/- 1.6 1.6 +/- 1.7 7.0 +/- 1.4
-0.7 +/- 1.7
< 39.3
< 2.7
< 8.0
< 2.8
< 2.2
< 3.4
< 4.0
< 3.0
< 2.9
< 5.5
< 3.3 7.4 +/- 13.2 1.0 +/- 1.3 2.7 +/- 2.4 0.4 +/- 1.3
-1.5 +/- 1.6
-0.2 +/- 3.4
-1.5+/-1.4
-0.9 +/- 1.2
-0.3 +/- 1.6
-9.8 +/- 1.5
-1.0 +/- 1.4
- "NS"= No sample; see Table 2.0, Listing of Missed Samples.
< 0.46
-0.12 +/- 0.23
< 37.2
< 3.1
< 4.9
< 3.0
< 1.9
< 4.2
< 2.7
< 2.6
< 2.5
< 9.9
< 3.4 5-1
-1.9 +/- 7.5
-0.4 +/- 0.7 0.4 +/- 1.6-0.1 +/- 0.7
-0.6 +/- 0.8 0.4 +/- 1.6
-1.0 +/- 0.8
-0.8 +/- 0.8 0.7 +/- 0.9
-2.5 +/- 0.9
-0.2 +/- 0.9
< 19.2
< 1.1
< 3.6
< 1.8
< 1.4
< 2.9
< 1.7
< 1.6
< 1.5
< 3.5
< 2.5 MDC ELW-1544 04-12-16 1.6 +/- 0.6
< 0.9 0.13 +/- 0.16
< 0.28 5.4 +/- 15.6
< 28.7
-0.6 +/- 1.8
< 2.5 4.1 +/- 3.0
< 7.0
-1.2 +/- 1.5
< 1.9
-0.4 +/- 2.0
< 1.5
-1.4 +/- 4.0
< 3.5 0.5 +/- 1.7
< 4.3 0.6 +/- 1.8
< 3.6
-1.0 +/- 1.9
< 2.6 0.3 +/- 1.7
< 3.7 0.4 +/- 1.9
< 2.3 ELW-.4276 08-10-16 0.9 +/- 0.3
< 0.4 0.12 +/- 0.24
< 0.42
-7.0 +/- 8.0
-0.3 +/- 1.1 0.1 +/- 2.2 0.7 +/- 1.2 0.0 +/- 1.2 1.5 +/- 2.1
-0.6 +/- 1.2
-0.3 +/- 1.1 0.2 +/- 1.2
-4.6 +/- 1.2
-0.9 +/- 1.1 NS a 12-31-16
< 19.3
< 1.8
< 5.4
< 3.2
< 2.0
< 3.3
< 2.9
< 2.1
< 1.9
< 8.0
< 2.7 Req.LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30 Req.LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30 Req. LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30
/!
Ii r
I
(
(
POINT BEACH Table 5. Lake water, analyses for gross beta, iodine-131 and gamma emitting isotopes.
Location: E-05 (Two Creeks Park)
Collection: Monthly composites Units: pCi/L Lab Code Date Collected NS" 01-13-16 11/lDC ELW-584 02-11-16 MDC ELW-1033 03-09-16 MDC ELW-1545 04-12-16 MDC Gross beta 1-131 2.2 +/- 1.0
< 1.8 2.5 +/- 0.7
< 0.9 1.0 +/- 0.5
< 0.8 Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Other (Ru-103)
Lab Code Date Collected Gross beta 1-131 Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Other (Ru-103)
Lab Code Date Collected Gross beta 1-131 Be-7 Mn-54 Fe-59 Co-58 CQ--60 Zn-65 Zr-Nb-95 Cs-134 Cs-137
- Ba-La-140 Other (Ru-103)
ELW-2361 05-11-16 1.9 +/- 0.9
< 1.6
-0.11 +/- 0.19
< 0.35 16.5 +/- 11.2 0.7 +/- 1.2 1.2 +/- 1.9
-0.3 +/- 1.1 0.3 +/- 1.2 0.5 +/- 1.9 0.3 +/- 1.3
-0.3 +/- 1.1
-0.7 +/- 1.4
-1.6 +/- 1.4
-0.1 +/- 1.3 ELW-4902 09-15-16 0.6 +/- 0.5.
-0.05 +/- 0.18 26.7 +/- 15.0 0.3 +/- 1.7
-2.0 +/- 2.5 1.3 +/- 1.6 0.6 +/- 1.8 0.4 +/- 2.6
-0.5 +/- 1.5
-1.2 +/- 1.8
-1.8 +/- 1.7
-4.5 +/- 1.7
-0.4 +/- 1.8
< 27.7
< 2.4
< 3.6
< 1.9
< 1.4
< 3.0
< 2.1
< 2.1
< 1.4
< 3.0
< 2.4
< 0.8
< 0.37
< 37.8
< 2.9
< 2.8
< 2.0
< 2.3
< 4.4
< 3.3
< 3.3
< 1.7
< 10.3
< 4.6 0.08 +/- 0.13 5.5 +/- 18.3 0.2 +/- 1.5
-0.8 +/- 4.2 0.6 +/- 1.8 0.2 +/- 2.1 0.7 +/- 3.2
-0.2 +/- 1.6
-0.5 +/- 1.6 1.3 +/- 2.2
-1.7+/-1.7
-1.2 +/- 2.0
< 0.20
-0.04 +/- 0.13
< 34.1
-15.3 +/- 12.9
< 2.3 1.0 +/- 1.6
<6.7
-1.6+/-3.1
< 3.0
-0.7 +/- 1.6
< 2.3 2.7 +/- 1.3
< 3.9 0.1 +/- 3.1
< 2.1 0.5 +/- 1.8
< 3.2 0.0 +/- 1.6
< 3.9 1.1 +/- 1.9
< 1.3
-1.1 +/- 1.5.
< 2.0
-0.8 +/- 1.6
< 0.24
-0.07 +/- 0.17
< 17.6 0.4 +/- 13.7
< 2.6 0.2 +/- 1.9
< 6.9
. -0.2 +/- 2.6
< 1.3
-0.9 +/- 1.5
< 2.0 0.4 +/- 1.6
< 4.7
-1.6 +/- 2.8
< 4.2 3.2 +/- 1.7
< 3.2
-0.9 +/- 1.6
< 3.6
-0.7 +/- 1.6
< 2.3 3.6 +/- 2.3
< 4.1 1.2 +/- 1.8 ELW-2930 06-08-16 ELW-3569 07-13-16 ELW-4277 08-10-16 1.1 +/- 0.9
< 1.6 0.07 +/- 0.23
< 0.48
-0.9 +/- 14.0 0.0 +/- 1.4
-0.3 +/- 2.9
-1.5+/-1.6
-0.4 +/- 1.6
-5.2 +/- 3.8 0.7 +/- 1.6
-0.3 +/- 1.5 0.7 +/- 1.6 0.4 +/- 1.4 0.0 +/- 2.0 ELW-5451 10-11-16 1.6 +/- 0.7 0.04 +/- 0.23
-4.8 +/- 11.0
-0.3 +/- 1.4 0.4 +/- 2.2
-0.7 +/- 1.2 0.7 +/- 1.1 1.5 +/- 2.9
-1.4+/-1.4
-1.5 +/- 1.5 0.3 +/- 1.5
-4.2 +/- 1.3 0.3 +/- 1.3
< 25.0
< 2.0
< 4.9
< 2.4
< 1.7
< 3.2
< 3.0
< 3.0
< 2.4
< 2.1
< 4.0
< 1.2
< 0.49
< 29.2
< 2.3*
< 5.2
< 2.3
< 2.0.
< 4.9
< 3.0
< 2.3
< 2.3
< 4.7
< 4.0 1.9 +/- 0.8
< 1.2 0.12 +/- 0.13
< 0.21 4.1 +/- 5.7 0.3 +/- 0.5 0.2 +/- 1.0 0.1 +/- 0.6
-0.2 +/- 0.6 0.3 +/- 1.1
-0.1 +/- 0.6 0.1 +/- 0.6 0.2 +/- 0.7
-0.4 +/- 0.6
-0.1 +/- 0.7 ELW-6266 11-10-16 2.1 +/- 1.0 0.00 +/- 0.22
-1.6 +/- 14.0
-0.4 +/- 1.3*
-1.7 +/-2.7
-0.3 +/- 1.4 0.8 +/- 1.6
-1.7 +/- 3.5
-0.8 +/- 1.4 0.1 +/- 1.4
-0.4+/-1.7
-1.2 +/- 1.2
-0.5 +/- 1.5
< 15.6
< 1*.0
< 2.5
< 1.2
< 1.0
< 1.8
< 2.2
< 1.2
< 1.2
< 5.0
< 1.6
< 1.7
< 0.45
< 29.9
< 2.7
< 4.3
< 2.2
< 3.3
< 4.9
< 4.0
< 3.1
< 2.3
< 3.3
< 3.2 0.6 +/- 0.3 0.07 +/- 0.14 1.0 +/- 5.7 0.6 +/- 0.6
-0.2 +/- 1.1
-0.5 +/- 0.6 0.4 +/- 0.6
-0.6 +/- 1.1
-0.4 +/- 0.7
-0.8 +/- 0.6 0.2 +/- 0.7
-1.0 +/- 0.7
-0.3 +/- 0.7 NS" 12-31-16
- "NS"= No sample; see Table 2.0, Listing of Missed Samples.
< 0.32
< 20.0
< 2.9
< 4.1
< 2.0
< 2.2
< 1.6
< 4.2
< 2.8
< 1.8
< 7.9
< 3.3
< 0.4
< 0.24
< 15.2
< 1.2
< 3.2
< 1.3
< 1.0
< 2.2
< 2.5
< 1.2
< 1.3
< 6.8
< 1.2 Req. LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30 Req.LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30 Req. LLD 4.0 0.5 10 30 10 10 30 15 10 10 15 30
POINT BEACH Table 5. Lake water, analyses for gross beta, iodine-131 and gamma emitting isotopes.
Location: E-33 (Kewaunee)
Collection: Monthly composites Units: pCi/L f-MDC MDC MDC MDC NS" NS" Lab Code ELW-1035 ELW-1547 Date Collected 01-13-16 02-11-16 03-09-16 04-12-16 Req:LLD Gross beta 1.7 +/- 0.6
< 0.8 0.6 +/- 0.5
< 0.8 4.0 1-131
-0.05 +/- 0.12
< 0.23 0.00 +/- 0.18
< 0.32 0.5 Be-7 9.3 +/- 12.9
< 31.0 15.1 +/- 16.0
< 37.1 Mn-54
-0.3 +/- 1.7
< 2.0 0.1 +/- 1.5
< 1.5 10 Fe-59
-1.4 +/- 2.7
< 5.1 3.6 +/- 3.1
< 5.6 30 Co-58
-0.8 +/- 1.7
< 3.1 1.5 +/- 1.4
< 2.7 10 Co-60 1.9 +/- 1.5
< 1.6 1.5 +/- 1.4
< 0.9 10 Zn-65
- 1.2 +/- 2.6
< 3.6
-1.0+/-3.1
< 3.3 30 Zr-Nb-95
-0.6 +/- 1.7
< 2.9
-0.1 +/- 1.8
< 4.4 15 Cs-134 0.0 +/- 1.5
< 2.7
-0.1 +/- 1.8
< 3.1 10 Cs-137 1.4 +/- 1.7
< 3.1 1.6 +/- 1.8
< 3.1 10 Ba-La-140
~3.2 +/- 1.7
< 2.0 5.7 +/- 2.0
< 6.8 15 Other (Ru-103)
-0.5 +/- 1.4
< 2.6 0.2 +/- 2.0
< 3.8 30 Lab Code ELW-2363 ELW-2932 ELW-3571 ELW-4279 Date Collected 05-11-16 06-08-16 07-13-16 08-10-16 Req.LLD Gross beta 1.7+/-1.0
< 1.9 1.5 +/- 0.9
< 1.6 2.4 +/- 0.7
< 1.1 0.7 +/- 0.3
< 0.4 4.0 1-131
-0.08 +/- 0.16
< 0.30 0.11 +/- 0.16
< 0.27
-0.02 +/- 0.13
< 0.24 0.16 +/- 0.19
< 0.36 0.5 Be-7 3.9 +/- 11.0
< 27.8 5.8 +/- 10.2
< 23.6 4.4 +/- 4.4
< 11.3 7.3 +/- 4.3
< 12.8 Mn-54
-0.9 +/- 1.3
< 2.3
-0.7 +/- 1.2
< 2.3
-0.2 +/- 0.6
< 0.8 0.0 +/- 0.6
< 1.1 10 Fe-59
-0.2 +/- 2.6
< 3.3
-2.1 +/- 2.4
< 5.3 0.6 +/- 1.0
< 2.2 0.8 +/- 1.0
< 3.0 30 Co-58
-0.6 +/- 1.4
< 1.8 0.1 +/- 1.2
< 2.2 0.0 +/- 0.6
< 1.2
-0.6 +/- 0.5
< 0.8 10 Co-60 0.3 +/- 1.2
< 1.4 0.2 +/- 0.9
< 1.5
-0.2 +/- 0.6
< 0.8 0.1 +/- -0.6
< 1.2 10 Zn-65
-0.8 +/- 2.5
< 3.1
-0.7 +/- 2.2
< 2.7
-1.0 +/- 1.1
< 1.3
-0.4 +/- 1.1
< 2.4 30 c
Zr-Nb-95
-1.2 +/- 1.4
< 3.6
-0.3 +/- 1.1
< 2.2 0.0 +/- 0.6
< 2.0
-1.1 +/- 0.6
< 2.0 15 Cs-134
-0.7 +/- 1.4
< 2.7 0.7 +/- 1.2
< 2.2
-0.1 +/- 0.6
< 1.1 0.0 +/- 0.6
< 1.0 10 Cs-137
-0.7 +/- 1.6
< 2.7
-1.1 +/- 1.3
< 2.2 0.1 +/- 0.7
< 1.3
-0.1 +/- 0.7
< 1.1 10 Ba-La-140 0.2 +/- 1.3
< 4.2
-0.5+/-1.7
< 4.8 0.6 +/- 0.6
< 4.1
-0.4 +/- 0.6
< 5.9 15 Other (Ru-103)
-0.7 +/- 1.2
< 3.0 0.1 +/- 1.1
< 2.6
-0.4 +/- 0.5
< 1.1
-0.6 +/- 0.5
< 1.0 30 Lab Code ELW-4904 ELW-5453 ELW-6268 NS 8
Date Collected 09-15-16 10-11-16 11-10-16 12-31-16 Req.LLD Gross beta 1.0 +/- 0.5
< 0.8 1.4 +/- 0.7
< 1.2 1.9 +/- 0.9
< 1.6 4.0 1-131 0.12 +/- 0.14
< 0.23 0.22 +/- 0.23
< 0.43 0.16 +/- 0.21
< 0.39 0.5 Be-7
-13.5 +/- 11.5
< 27.4
-15.5 +/- 12.2
< 28.1
-10.5 +/- 9.1
< 29.1 Mn-54
-0.1 +/- 1.6
< 3.2 1.1 +/- 1.5
< 2.5
-0.4 +/- 1.2
< 1.6 10 Fe-59 0.8 +/- 3.0
< 5.8
-0.5 +/- 2.6
< 4.0 0.3 +/- 1.8
< 5.0 30 Co-58
-0.1 +/- 1.5
< 3.4 0.2 +/- 1.6
< 3.5 0.1 +/- 1.1
< 2.6 10 Co-60 0.4 +/- 1.5
< 1.5 0.6 +/- 1.7
< 2.6
-0.1 +/- 1.2
< 1.1 10 Zn-65 0.6 +/- 2.6
< 3.6 0.2 +/- 3.0
< 3.9
-1.7+/-2.1
< 2.6 30 Zr-Nb-95 0.5 +/- 1.4
< 4.2
-1.1 +/- 1.4
< 3.7 0.2 +/- 1.1
< 2.5 15 Cs-134
-0.3 +/- 1:5
< 2.8 0.7 +/- 1.5
< 2.9
-0.4 +/- 1.1
< 2.3 10 Cs-137 0.0 +/- 1.7
< 2.4 1.2 +/- 1.7
< 3.2 0.5 +/- 1.2
< 2.2 10 Ba-La-140
-6.9 +/- 1.8
< 8.0 0.5 +/- 1.5
< 10.0 1.1 +/- 1.4
< 12.5 15 Other (Ru-103) 1.0 +/- 1.5
< 4.5
-1.6 +/- 1.4
< 3.3
-2.2 +/- 0.9
< 2.2 30
- "NS"= No sample; see Table 2.0, Listing of Missed Samples.
Annual All locations Mean +/- s.d.
Mean +/- s.d.
Mean +/- s.d.
Gross Beta 1.7 +/- 0.7 1-131 0.03 +/- 0.10 Co-58 0.1 +/- 1.0 Cs-134
-0.1 +/- 0.8 Be-7 2.2 +/- 8.4 Co-60 0.1 +/- 1.0 Cs-137 0.1 +/- 1.1 Mn-54 0.0 +/- 0.7 Zn-65
-0.6 +/- 1.9 Ba-La-140
-1.0 +/- 4.0
(
Fe-59 0.0 +/- 1.9 Zr-Nb-95
-0.i +/- 1.0 Ru-103
-0.6 +/- 0.9
F-
-(
\\..
(
POINT BEACH NUCLEAR PLANT Table 6. Lake water, analyses for tritium, strontium-89 and strontium-90.
Collection: Quarterly composites of weekly grab samples Units: pCi/L Location E-01 (Meteorological Tower)
Period 1st Qtr.
MDC 4nd Qtr.
MDC 3rd Qtr.
Lab Code ELW-1077 ELW-3058 ELW-4920 H-3 80 +/-77
< 146 188 +/-81
< 148 43 +/-76 Sr-89 0.48 +/-0.69
< 0.71
-0.52 +/-0.90
< 0.97
-0.30 +/- 0.73 Sr-90 0.20 +/-0.29
< 0.56 0.38 +/-0.30
< 0.56 0.48 +/- 0.30 Location E-05 (Two Creeks Park)
Period 1st Qtr.
2nd Qtr.
3nd Qtr.
Lab Code ELW-1078 ELW-3059 ELW-4921 H-3 30 +/-74
< 143 102 +/-77
< 148 67 +/-78 Sr-89 0.27 +/-0.60
< 0.71
-0.88+/-1.12
< 1.29
-0.29 +/- 0.65 Sr-90
- 0.21 +/-0.24
< 0.45 0.36 +/-0.37
< 0.72 0.37 +/- 0.27 Location E-06 (Coast Guard Station)
Period 1st Qtr.
2nd Qtr..
3nd Qtr.
Lab Code ELW-1079 ELW-3060 ELW-4922 H-3 61 +/-76
< 146 206 +/-82
< 148 143 +/- 82 Sr-89 0.07 +/-0.61
< 0.82 0.21 +/-0.77
< 0.89
-0.10 +/- 0.67 Sr-90 0.11 +/- 0.23
< 0.48 0.14 +/-0.25
< 0.49 0.23 +/- 0.28 Location E-33 (Kewaunee)
Period 1st Qtr.
2nd Qtr.
3nd Qtr.
Lab Code.
ELW-1080 ELW-3061 ELW-4923 H-3 82 +/-77
< 146 72 +/-75
< 148 43 +/-76 Sr-89
-0.16 +/-0.64 < 0.87 0.51 +/-0.74
< 0.85 0.51 +/- 0.66 Sr-90 0.23 +/-0.25 < 0.49 0.09 +/-0.23
< 0.47
-0.05 +/- 0.25
- Tritium reanalyzed with a result of 224+/-89 pCi/L (<155).
- Tritium Annual Mean +/- s.d.
Sr-89 Annual Mean +/- s.d.
Sr-90 Annual Mean +/- s.d.
109 +/-69
-0.03 +/-0.43 0.24 +/-0.16 MDC
< 149
< 0.78
< 0.51
< 149
< 0.71
< 0.47
< 149
< 0.74
< 0.53
< 149
< 0.82
< 0.56 4th Qtr.
MDC ELW-6991 286 +/-87
< 145 a
-0.55+/-1.80
< 1.81 0.51 +/-0.43
< 0.81 4th Qtr.
- ELW-6992 109 +/-83
< 155 0.50+/-1.49
< 1.72 0.03 +/-0.35
< 0.75 4th Qtr.
ELW-6993 99 +/-77
< 145
-0.32+/-1.38
< 1.35 0.37 +/-0.35
< 0.65 4th Qtr.
ELW-6994 137 +/-79
< 145 0.11 +/- 1.34
< 1.45 0.25 +/-0.32
< 0.61
POINT BEACH NUCLEAR PLANT Table 7. Fish, analyses for gross beta and gamma emitting isotopes.
(_**~
Location: E-13
\\
Collection: 2x/ year Units: pCi/g wet Sample Description and Concentration Req.
MDC MDC MDC LLD Collection Date 01-11-16 01-04-16 01-04-16 Lab Code EF-312 EF-313 EF-314 Type Lake Herring Chinook Lake Trout Ratio (wet/dry wt.)
4.85 4.31 4.08 Gross Beta 3.56 +/- 0.07
< 0.052 3.30 +/- 0.07
< 0.087 3.71 +/- 0.07
< 0.240 0.5 K-40 3.36 +/- 0.41 3.08 +/- 0.42 3.11 +/- 0.44 Mn-54
-0.003 +/- 0.009
< 0.009
-0.006 +/- 0.010
< 0.011
-0.006 +/- 0.010
< 0.014 0.13 Fe-59
-0.004 +/- 0.020
< 0.057 0.038 +/- 0.020
< 0.075
-0.020 +/- 0.022
< 0.046 0.26 Co-58 0.011 +/- 0.009
< 0.021 0.009 +/- 0.009
< 0.023 0.007 +/- 0.010
< 0.029 0.13 Co-60 0.003 +/- 0.010
< 0.014 0.017 +/- 0.012
< 0.018 0.001 +/- 0.012
< 0.019 0.13 Zn-65
-0.022 +/- 0.026
< 0.029
-0.040 +/- 0.026
< 0.027
-0.027 +/- 0.030
< 0.043 0.26 Cs-134 0.001 +/- 0.010
< 0.020
-0.008 +/- 0.011
< 0.021
-0.029 +/- 0.013
< 0.021 0.13 Cs-137 0.004 +/- 0.012
< 0.021 0.013 +/- 0.012
< 0.022 0.028 +/- 0.012
< 0.019 0.15 Other (Ru-103) 0.028 +/- 0.011
< 0.048 0.002 +/- 0.011
< 0.047 0.001 +/- 0.011
< 0.041 0.5 Collection Date 01-15-16 01-16-16 01-16-16 Lab Code EF-315 EF-316 EF-317 Type Coho Whitefish Perch
(
Ratio (wet/dry wt.)
3.48 4.98 5.66 Gross Beta 3.04 +/- 0.06
< 0.059 3.66 +/- 0.07
< 0.026 2.53 +/- 0.06
< 0.026 0.5 K-40 2.93 +/- 0.44 3.50 +/- 0.49 2.68 +/- 0.47 Mn-54 0.008 +/- 0.012
< 0.027 0.003 +/- 0.011
< 0.021 0.006 +/- 0.011
< 0.024 0.13 Fe-59 0.003 +/- 0.024
< 0.055
-0.010 +/- 0.025
< 0.066 0.058 +/- 0.020
< 0.056 0.26 Co-58
-0.017 +/- 0.011
< 0.022
-0.013 +/- 0.010
< 0.019 0.002 +/- 0.012
< 0.030 0.13 Co-60
-0.003 +/- 0.014
< 0.023 0.006 +/- 0.015
< 0.022
-0.009 +/- 0.013
< 0.016 0.13 Zn-65
-0.220 +/- 0.039
< 0.050
-0.006 +/- 0.026
< 0.024
-0.007 +/- 0.020
< 0.033 0.26 Cs-134
-0.186 +/- 0.018
< 0.023
-0.003 +/- 0.013
< 0.026 0.003 +/- 0.011
< 0.019 0.13 Cs-137 0.015 +/- 0.015
< 0.029 0.012 +/- 0.014
< 0.023 0.077 +/- 0.031
< 0.031 0.15 Other (Ru-103) 0.010 +/- 0.011
< 0.041 0.007 +/- 0.013
< 0.037
-0.002 +/- 0.009
< 0.032 0.5 7-1
POINT BEACH NUCLEAR PLANT
(
Table 7. Fish, analyses for gross beta and gamma emitting isotopes.
Location: E-13 Collection: 2x/year Units: pCi/g wet Sample Description and Concentration (pCi/g wet)
Req.
MDC MDC MDC LLD Collection Date 01-19-16 03-07-16 03-07-16 Lab Code EF-319 EF-1302 EF-1304 Type Steelhead Trout Coho Lake Herring Ratio (wet/dry wt.)
4.20 3.45 4.89 Gross Beta 4.89 +/- 0.10
< 0.033 4.16 +/- 0.09
< 0.031 3.02 +/- 0.07
< 0.023 0.5 K-40 2.79 +/- 0.44 3.32 +/- 0.48 2.45 +/- 0.40 Mn-54 0.011 +/- 0.013
< 0.025 0.012 +/- 0.011
< 0.021 0.006 +/- 0.009
< 0.020 0.13 Fe-59
-0.024 +/- 0.022
< 0.025
-0.018 +/- 0.025
< 0.073 0.026 +/- 0.019
< 0.047 0.26 Co-58
-0.014 +/- 0.011
< 0.019 0.009 +/- 0.011
< 0.025 0.004 +/- 0.009
< 0.021 0.13 Co-60 0.004 +/- 0.012
< 0.011 0.009 +/- 0.011
< 0.015
-0.003 +/- 0.012
< 0.014 0.13 Zn-65
-0.011 +/- 0.032
< 0.042
-0.088 +/- 0.032
< 0.032 0.017 +/- 0.023
< 0.031 0.26 Cs-134
-0.008 +/- 0.011
< 0.022
-0.037 +/- 0.014
< 0.020
-0.014 +/- 0.010
< 0.020 0.13 Cs-137 0.023 +/- 0.015
< 0.029 0.013 +/- 0.013
< 0.019 0.007 +/- 0.012
< 0.021 0.15 Other (Ru-103) 0.004 +/- 0.012
< 0.042
-0.009 +/- 0.010
< 0.030 0.003 +/- 0.011
< 0.034 0.5 Collection Date 04-04-16 04-11-16 04-11-16 Lab Code EF-1946 EF-1947 EF-1948
-~-
Type Coho Whitefish Whitefish c-Ratio (wet/dry wt.)
4.89 4.80 5.06 Gross Beta 3.33 +/- 0.07
< 0.024 3.98 +/- 0.08
< 0.026 3.78 +/- 0.08
< 0.022 0.5 K-40 3.52 +/- 0.43 3.65 +/- 0.39 3.27 +/- 0.40 Mn-54 0.002 +/- 0.008
< 0.013 0.003 +/- 0.008
< 0.013 0.000 +/- 0.010
< 0.017 0.13 Fe-59
-0.025 +/- 0.017
< 0.031 0.003 +/- 0.017
< 0.029 0.009 +/- 0.020
< 0.056 0.26 Co-58
-0.002 +/- 0.006
< 0.010 0.005 +/- 0.008
< 0.016
-0.001 +/- 0.010
< 0.016 0.13 Co-60 0.007 +/- 0.010. < 0.015 0.007 +/- 0.009
< 0.012
-0.003 +/- 0.012
< 0.010 0.13 Zn-65
-0.008 +/- 0.021
< 0.022
-0.010 +/- 0.017
< 0.026 0.009 +/- 0.025
< 0.039 0.26 Cs-134 0.007 +/- 0.007
< 0.015 0.000 +/- 0.008
< 0.014
-0.009 +/- 0.009
< 0.019 0.13 Cs-137 0.027 +/- 0.013
< 0.021 0.012 +/- 0.010
< 0.018 0.008 +/- 0.012
< 0.016 0.15 Other (Ru-103) 0.003 +/- 0.008
< 0.021
-0.007 +/- 0.009
< 0.013 0.009 +/- 0.010
< 0.028 0.5
(
7-2
POINT BEACH NUCLEAR PLANT Table 7. Fish, analyses for gross beta and gamma emitting isotopes.
(
Location: E-13 Collection: 2x /year Units: pCi/g wet Sample Description and Concentration (pCi/g wet)
Req.
MDC MDC MDC LLD Collection Date 04-17-16 06-23-16 06-21-16 Lab Code EF-1949 EF-3306 EF-3307 Type Lake Trout Salmon Salmon Ratio (wet/dry wt.)
3.47 3.57 3.20 Gross Beta 3.70 +/- 0.09
< 0.040 4.23 +/- 0.06
< 0.017 3.35 +/- 0.05
< 0.014 0.5 K-40 3.66 +/- 0.40 3.21 +/- 0.40 2.70 +/- 0.38 Mn-54
-0.003 +/- 0.008
< 0.012
-0.007 +/- 0.009
< 0.011 0.004 +/- 0.007
< 0.013 0.13 Fe-59 0.003 +/- 0.020
< 0.042 0.005 +/- 0.017
< 0.051
-0.022 +/- 0.016
< 0.038 0.26 Co-58 0.009 +/- 0.008
< 0.018 0.005 +/- 0.008
< 0.020 0.010 +/- 0.008
< 0.021 0.13 Co-60
-0.005 +/- 0.009
< 0.007 0.003 +/- 0.008
< 0.013 0.001 +/- 0.008
< 0.010 0.13 Zn-65 0.015 +/- 0.020
< 0.032 0.002 +/- 0.019
< 0.029
-0.001 +/- 0.018
< 0.020 0.26 Cs-134
-0.002 +/- 0.008
< 0.015 0.007 +/- 0.008
< 0.012
-0.004 +/- 0.008
< 0.014 0.13 Cs-137 0.011 +/- 0.010
< 0.014 0.022 +/- 0.012
< 0.018 0.019 +/- 0.010
< 0.015 0.15 Other (Ru-103) 0.008 +/- 0.008
< 0.024 0.004 +/- 0.008
< 0.028
-0.002 +/- 0.007
< 0.025 0.5 Collection Date 06-07-16 07-27-16 08-02-16 Lab Code EF-3308 EF-4472 EF-4473
(
Type Lake Trout Rainbow Trout Brown Trout
\\
Ratio (wet/dry wt.)
4.33 3.74 3.73 Gross Beta 3.62 +/- 0.05
< 0.013 4.01 +/- 0.08
< 0.026 3.45 +/- 0.07
< 0.019 0.5 K-40 3.10 +/- 0.37 3.13 +/- 0.46 2.86 +/- 0.41 Mn-54 0.001 +/- 0.009
< 0.011 0.002 +/- 0.012
< 0.026
-0.001 +/- 0.010
< 0.020 0.13 Fe-59 0.003 +/- 0.016
< 0.034
-0.008 +/- 0.023
< 0.062 0.014 +/- 0.021
< 0.039 0.26 Co-58 0.010 +/- 0.008
< 0.017
-0.014 +/- 0.013
< 0.036
-0.005 +/- 0.010
< 0.013 0.13 Co-60
-0.002 +/- 0.010
< 0.013
-0.011 +/- 0.014
< 0.016 0.001 +/- 0.012
< 0.019 0.13 Zn-65 0.003 +/- 0.018
< 0.017
-0.065 +/- 0.040
< 0.071
-0.010 +/- 0.027
< 0.038 0.26 Cs-134
-0.003 +/- 0.008
< 0.013
-0.106 +/- 0.020
< 0.029
-0.010 +/- 0.011
< 0.021 0.13 Cs-137 0.002 +/- 0.011
< 0.015 0.006 +/- 0.017
< 0.031 0.018 +/- 0.013
< 0.027 0.15 Other (Ru-103) 0.004 +/- 0.006
< 0.030
-0.006 +/- 0.013
< 0.049 0.015 +/- 0.010
< 0.036 0.5 7-3
POINT BEACH NUCLEAR PLANT Table 7. Fish, analyses for gross beta and gamma emitting isotopes.
~
Location: E-13 Collection: 2x/year Units: pCi/g wet Sample Description and Concentration (pCi/g wet)
Req.
MDC MDC MDC LLD Collection Date 08-14-16 10-14-16 10-13-16 Lab Code EF-4474 EF-6209 EF-6210 Type Rainbow Trout Chinook Catfish Ratio (wet/dry wt.)
4.01 4.74 4.01 Gross Beta 3.43 +/- 0.07
< 0.024 3.78 +/- 0.07
< 0.022 3.36 +/- 0.06
< 0.019 0.5 K-40 2.98 +/- 0.41 3.11 +/- 0.41 2.75 +/- 0.36 Mn-54 0.011 +/- 0.009
< 0.021
-0.001 +/- 0.009
< 0.020 0.001 +/- 0.008
< 0.017 0.13 Fe-59
-0.011 +/- 0.019
< 0.040
-0.026 +/- 0.020
< 0.056
-0.021 +/- 0.017
< 0.032 0.26 Co-58 0.004 +/- 0.009
< 0.021 0.012 +/- 0.009
< 0.024
-0.007 +/- 0.009
< 0.015 0.13 Co-60
-0.006 +/- 0.010
< 0.016 0.008 +/- 0.012
< 0.012 0.009 +/- 0.008
< 0.014 0.13 Zn-65
-0.032 +/- 0.026
< 0.023
-0.023 +/- 0.025
< 0.039 0.013 +/- 0.015
< 0.026 0.26 Cs-134
-0.002 +/- 0.010
< 0.019
-0.013 +/- 0.010
< 0.020
-0.006 +/- 0.008
< 0.015 0.13 Cs-137 0.023 +/- 0.012
< 0.019 0.007 +/- 0.013
< 0.023 0.020 +/- 0.011
< 0.017 0.15 Other (Ru-103)
-0.001 +/- 0.010
< 0.028
-0.006 +/- 0.009
< 0.028 0.002 +/- 0.007
< 0.022 0.5 Collection Date 10-28-16 11-29-16 12-06-16 Lab Code EF-6211 EF-6743 EF-6744 Type Sturgeon Salmon Rainbow Trout
(
Ratio (wet/dry wt.)
3.97 5.94 5.25 Gross Beta 3.27 +/- 0.07
< 0.022 3.78 +/- 0.07
< 0.022 4.16 +/-0.08
< 0.028 0.5 K-40 2.49 +/- 0.37 2.93 +/- 0.36 3.53 +/- 0.40 Mn-54 0.005 +/- 0.009
< 0.017 0.007 +/- 0.009
< 0.016 0.001 +/- 0.011
< 0.020 0.13 Fe-59
-0.017 +/- 0.017
< 0.038
-0.011 +/- 0.016
< 0.025
-0.005 +/- 0.016
< 0.028 0.26 Co-58
-0.004 +/- 0.009
< 0.014
-0.006 +/- 0.008
< 0.013
-0.006 +/- 0.007
< 0.010 0.13 CQ-60
-0.013 +/- 0.010
< 0.006 0.005 +/- 0.008
< 0.013 0.000 +/- 0.008
< 0.013 0.13 Zn-65
-0.014 +/- 0.021
< 0.018
-0.012 +/- 0.018
< 0.022 0.003 +/- 0.020
< 0.030 0.26 Cs-134 0.003 +/- 0.008
< 0.016 0.005 +/- 0.007
< 0.014
-0.001 +/- 0.009
< 0.017 0.13 Cs-137 0.003 +/- 0.010
< 0.016 0.015 +/- 0.011
< 0.019 0.016 +/- 0.012
< 0.018 0.15 Other (Ru-103)
-0.008 +/- 0.009
< 0.022 0.006 +/- 0.006
< 0.015 0.006 +/- 0.007
< 0.019 0.5 7-4
( **-
(~-
POINT BEACH NUCLEAR PLANT Table 7. Fish, analyses.for gross beta and gamma emitting isotopes.
Location: E-13 Collection: 2x I year Units: pCi/g wet Sample Description and Concentration (pCi/g wet)
MDC MDC Collection Date 12-07-16 Lab Code EF-6745 Type Rainbow Trout Ratio (wet/dry wt.)
4.28 Gross Beta 4.28 +/- 0.09
< 0.034 K-40 3.12 +/- 0.37 Mn-54
-0.001 +/- 0.007
< 0.012 Fe-59
-0.010 +/- 0.013
< 0.018 Co-58 0.009 +/- ci.007
< 0.013 Co-60
-0.001 +/- 0.009
< 0.014 Zn-65
-0.010 +/- O.D15
< 0.010 Cs-134
-0.006 +/- 0.007
< 0.012 Cs-137 0.015 +/- 0.010
< 0.017 Other (Ru-103) 0.001 +/- 0.006
< 0.014 7-5 Req.
3.66 +/- 0.49 0.5 3.09 +/- 0.34 0.002 +/- 0.005 0.13
-0.003 +/- 0.020 0.26 0.001 +/- 0.009 0.13 0.001 +/- 0.007 0.13
-0.022 +/- 0.048 0.26
-0.017 +/- 0.042 0.13 0.017 +/- 0.015 0.15 0.003 +/- 0.008 0.5
POINT BEACH NUCLEAR PLANT Table 8. Radioactivity in shoreline sediment samples L
Collection: Semiannual Sample Description and Concentration (pCi/g dry)
MDC MDC MDC Collection Date 4112/2016 4/12/2016 4/12/2016 Lab Code ESS-1549 ESS-1550 ESS-1551 LLD Location E-01 E-05 E-06 Gross Beta 7.11 +/- 1.07
< 1.50 10.48 +/- 1.23
< 1.62 8.71 +/- 1.11
< 1.46 2.0 Be-7 0.011 +/- 0.056
< 0.12
-0.074 +/- 0.055
<: 0.09
-0.006 +/- 0.052
<: 0.12 K-40 5.45 +/- 0.38 7.47 +/- 0.42 6.73 +/- 0.41 Cs-134
-0.005 +/- 0.006
<: 0.009
-0.004 +/- 0.006
<: 0.009
-0.003 +/- 0.006
<: 0.008 0.15 Cs-137 0.021 +/- 0.012
<: 0.013 0.013 +/- 0.008
<: 0.014 0.012 +/- 0.008
<: 0.012 0.15 Tl-208 0.045 +/- 0.017 0.047 +/- 0.019 0.045 +/- 0.015 Pb-212 0.11 +/- 0.019 0.11 +/- 0.018 0.13 +/- 0.019 Bi-214 0.090 +/- 0.025 0.11 +/- 0.025 0.10 +/- 0.023 Ra-226 0.33 +/- 0.19 0.34 +/-0.15 0.35 +/- 0.17 Ac-228 0.15 +/- 0.050 0.15 +/- 0.049 0.16 +/- 0.053 Collection Date 4/12/2016 4112/2016 Lab Code ESS-1553 ESS-1554 Location E-12 E-33 Gross Beta 6.47 +/- 1.01
< 1.40 10.64 +/- 1.30
< 1.77 2.0 Be-7
-0.050 +/- 0.059
<: 0.12
-0.012 +/- 0.045
<: 0.09
(
K-40 3.82 +/- 0.34 6.12 +/-0.38
\\
Cs-134
-0.001 +/- 0.006
<: 0.011 0.004 +/- 0.006
<: 0.010 0.15 Cs-137 0.023 +/- 0.012
<: 0.012 0.008 +/- 0.008
< 0.015 0.15 Tl-208 0.049 +/- 0.015 0.037 +/- 0.014 Pb-212 0.15 +/- 0.021 0.10 +/- 0.017 Bi-214 0.12 +/- 0.026 0.11 +/- 0.023 Ra-226 0.51 +/- 0.15
< 0.34 0.45 +/- 0.13
< 0.26 Ac-228 0.15 +/- 0.041 0.11 +/- 0.041 8-1
POINT BEACH NUCLEAR PLANT
(
Table 8. Radioactivity in shoreline sediment samples Collection: Semiannual Sample Description and Concentration (pCi/g dry)
MDC MDC MDC Collection Date 10/11/2016 10/11/2016 10111/2016 Req.
Lab Code.
ESS-5546 ESS-5547 ESS-5549 LLD Location E-01 E-05 E-06 Gross Beta 9.02 +/- *1.12
< 1.49 9.47 +/- 1.20
< 1.61 11.60 +/- 1.29
< 1.67 2.0 Be-7
-0.068 +/- 0.069
< 0.17 0.012 +/- 0.049
< 0.14 0.12 +/- 0.12
< 0.39 K-40 6.05 +/- 0.46 7.23 +/- 0.46 4.40 +/- 0.53 Cs-134 0.009 +/- 0.007
< 0.013
-0.001 +/- 0.006
< 0.008
-0.090 +/- 0.019
< 0.028 0.15 Cs-137 0.003 +/- 0.009
< 0.014 0.009 +/- 0.008
< 0.013
-0.012 +/- 0.020
< 0.032 0.15 Tl-208 0.049 +/- 0.023 0.040 +/- 0.018 0.43 +/- 0.044 Pb-212 0.13 +/- 0.024.
0.11 +/- 0.019 1.01 +/- 0.051 Bi-214 0.17 +/- 0.030 0.12 +/- 0.027 0.97 +/- 0.072 Ra-226 0.28 +/- 0.18
< 0.35 0.40 +/- 0.14
< 0.26 1.74 +/- 0.38 Ac-228 0.15 +/- 0.078 0.16 +/- 0.050 1.14 +/- 0.11 Collection Date 10/11/2016 10/11/2016 Lab Code ESS-5550 ESS-5551 Annual Location E-12 E-33 Mean +/-s.d.
Gross Beta 7.76+/-1.10
< 1.51 8.57.-+/- 1.06
< 1.36 2.0 8.98+/-1.62
(~-
Be-7 0.015 +/- 0.055
< 0.14 0.071 +/- 0.077
< 0.25 0.002 +/- 0.060 K-40 4.67 +/- 0.39 6.19 +/- 0.46 5.81+/-1.22 Cs-134 0.003 +/- 0.006
< 0.012
-0.003 +/- 0.008
< 0.015 0.15
-0.01 +/-0.03 Cs-137 0.016 +/- 0.009
< 0.013 0.007 +/- 0.010
< 0.017 0.15 0.010 +/- 0.010 Tl-208 0.039 +/- 0.018 0.059 +/- 0.023 0.08 +/-0.12 Pb-212 0.12 +/- 0.020 0.11 +/- 0.027 0.21 +/- 0.28 Bi-214 0.10 +/- 0.025 0.099 +/- 0.029 0.20 +/-0.27 Ra-226 0.47 +/- 0.15
< 0.30 0:43 +/- 0.25 0.53 +/-0.43 Ac-228 0.11 +/- 0.064 0.18 +/- 0.086 0.25 +/-0.32 8-2
POINT BEACH NUCLEAR PLANT Table 9. Radioactivity in soil samples
(
Collection: Semiannual Sample Description and Concentration (pCi/g dry)
MDC MDC MDC Collection Date 5/26/2016 5/26/2016 5/26/2016 Req.
Lab Code ESQ-2663 ESQ-2665 ESQ-2666 LLD Location E-01 E-02 E-03 Gross Beta 24.35 +/- 1.00
< 0.92 28.04 +/- 1.16
< 1.02 31.59 +/- 1.29
< 1.16 2.0 Be-7 0.52 +/- 0.29 0.14 +/- 0.11
< 0.32 0.061 +/- 0.082
< 0.24 K-40 12.44 +/- 0.68 18.72 +/- 0.97 16.35 +/- 0.78 Cs-134
-0.004 +/- 0.012
< 0.017
-0.005 +/- 0.014
< 0.023
-0.007 +/- 0.011
< O.D16 0.15 Cs-137 0.077 +/- 0.031
< 0.029 0.079 +/- 0.040
< 0.036 0.10 +/- 0.024
< 0.024 0.15 Tl-208 0.13 +/- 0.024 0.18 +/- 0.043 0.17 +/- 0.030 Pb-212
. 0.43 +/- 0.037 0.49 +/- 0.038 0.42 +/- 0.034 Bi-214 0.32 +/- 0.045 0.39 +/- 0.049 0.31 +/- 0.043 Ra-226 1.19 +/- 0.34 1.17 +/-0.32 2.83 +/- 0.34 Ac-228 0.45 +/- 0.087 0.70 +/- 0.13 0.52 +/- 0.076 Collection Date 5/26/2016 5/26/2016 5/26/2016 Lab Code ESQ-2667 ESQ-2668 ESQ-2669 Location E-04 E-06 E-08 Gross Beta 16.74 +/- 0.95
< 0.97 17.73 +/- 0.91
< 0.86 21.34 +/- 1.11
< 1.13 2.0 r
Be-7
-0.048 +/- 0.069
< 0.18
-0.035 +/- 0.073
< 0.16
-0.051 +/- 0.055
< 0.12 K-40 10.43 +/- 0.52 9.67 +/- 0.51 12.15 +/- 0.54 Cs-134
-0.006 +/- 0.008
< 0.014
-0.013 +/- 0.008
< 0.012
-0.011 +/- 0.008
< 0.011 0.15 Cs-137 0.13 +/- 0.025
< 0.022 0.37 +/- 0.032
< 0.023 0.079 +/- 0.017
< 0.017 0.15 Tl-208 0.10 +/- 0.021 0.083 +/- 0.020 0.090 +/- 0.022 Pb-212 0.27 +/- 0.025 0.23 +/- 0.025 0.26 +/- *0.022 Bi-214 0.24 +/- 0.032 0.48 +/- 0.052 0.28 +/- 0.039 Ra-226 0.84 +/- 0.21 0.46 +/- 0.21 0.73 +/- 0.20 Ac-228 0.39 +/- 0.065 0.30 +/- 0.072 0.28 +/- 0.052 Collection Date 5/26/2016 5/26/2016 Lab Code ESQ-2670 ESQ-2671 Location E-09 E-20 Gross Beta 30.27 +/- 1.53
< 1.35 35.41 +/- 1.65
< 1.42 2.0 Be-7 0.056 +/- 0.081
< 0.20
-0.072 +/- 0.10
< 0.28 K-40 20.13 +/- 0.74 21.94 +/- 0.84 Cs-134
-0.003 +/- 0.011
< 0.016
-0.038 +/- 0.013
< 0.023 0.15 Cs-137 0.16 +/- 0.024
< 0.022 0.11 +/- 0.022
< 0.028 0.15 Tl-208 0.16 +/- 0.028 0.23 +/- 0.035 Pb-212 0.54 +/- 0.035 0.81 +/- 0.045 Bi-214 0.73 +/- 0.053 1.01 +/- 0.068 Ra-226 1.57 +/- 0.29 1.59 +/- 0.74 Ac-228 0.61 +/- 0.086 0.75 +/- 0.11
(
9-1
POINT BEACH NUCLEAR PLANT Table 9. Radioactivity in soil samples f=--
Collection: Semiannual Sample Description and Concentration (pCi/g dry)
MDC MDC MDC Collection Date 10/27/2016 10/27/2016 10/27/2016 Req.
Lab Code ESO-5900 ESO-5902 ESO-5903 LLD Location E-01 E-02 E-03 Gross Beta 17.71 +/- 1.03
< 1.06 22.82 +/- 1.14
< 1.11 29.63 +/- 1.20
< 1.50 2.0 Be-7 0.18 +/- 0.088
< 0.25 0.23 +/- 0.10
< 0.29 0.12 +/- 0.11
< 0.26 K-40 10.77 +/- 0.61 13.12 +/- 0.74 19.29 +/- 0.77 Cs-134
-0.001 +/- 0.010
< 0.020 0.002 +/- 0.011
< 0.020
-0.004 +/- 0.010
< 0.019 0.15 Cs-137 0.035 +/- 0.019
< 0.023 0.11 +/- 0.031
< 0.028 0.11 +/- 0.030
< 0.028 0.15 Tl~208 0.14 +/- 0.028 0.14 +/- 0.029 0.19 +/- 0.036 Pb-212 0.33 +/- 0.034 0.37 +/- 0.042 0.52 +/- 0.039 Bi-214 0.27 +/- 0.041 0.22 +/- 0.042 0.48 +/- 0.050 Ra-226 0.61 +/- 0.27 0.70 +/- 0.35 1.27 +/- 0.32 Ac-228 0.48 +/- 0.089 0.37 +/- 0.088 0.59 +/- 0.094 Collection Date 10/27/2016 10/27/2016 10/27/2016 Lab Code ESO-5904 ESO-5905 ESO-5906 Location E-04 E-06 E-08
(
Gross Beta 28.23 +/- 1.25
< 1.17 15.25 +/- 1.00
< 1.07 21.34 +/- 1.01
< 0.93 2.0 Be-7 0.099 +/- 0.072
< 0.18
-0.081 +/- 0.097
< 0.27
-0.024 +/- 0.091
< 0.17 K-40 17.96 +/- 0.74 9.49 +/- 0.59 13.82 +/- 0.73 Cs-134
-0.002 +/- 0.009
< 0.017
-0.002 +/- 0.009
< 0.014
-0.006 +/- 0.010
< 0.015 0.15 Cs-137 0.13 +/- 0.028
< 0.026 0.37 +/- 0.041
< 0.028 0.16 +/- 0.034
< 0.027 0.15 Tl-208 0.15 +/- 0.028 0.076 +/- 0.024 0.086 +/- 0.028 Pb-212 0.44 +/- 0.033 0.20 +/- 0.033 0.25 +/- 0.031 Bi-214 0.39 +/- 0.041 0.19 +/- 0.037 0.25 +/- 0.035
< 0.085 Ra-226 1.00 +/- 0.26 0.56 +/- 0.23
< 0.49 0.55 +/- 0.27 Ac-228 0.53 +/- 0.072 0.32 +/- 0.090 0.37 +/- 0.086 Collection Date 10/27/2016 10/27/2016 Lab Code ESO-5907 ESO-5908 Annual Location E-09 E-20 Mean +/- s.d.
Gross Beta 36.87 +/- 1.40
< 1.25 28.67 +/- 1.18
.< 1.06 25.37 +/- 6.70 2.0 Be-7 0.24 +/- 0.094
< 0.27 0.072 +/- 0.080
< 0.20 0.088 +/- 0.16 K-40 20.95 +/- 0.95 16.42 +/- 0.73 15.23 +/- 4.25 Cs-134
-0.002 +/- 0.013
< 0.020
-0.007 +/- 0.010
< 0.015 0.017 +/- 0.09 0.15 Cs-137 0.13 +/- 0.029
< 0.028 0.22 +/- 0.030
< 0.025 0.15 +/- 0.10 0.15 Tl-208 0.22 +/- 0.032 0.17 +/- 0.032 0.14 +/- 0.05 Pb-212 0.61 +/- 0.045 0.50 +/- 0.036 0.42 :!: 0.16 Bi-214 0.42 +/- 0.052 0.38 +/- 0.043 0.40 :!: 0.21 Ra-226 1.26 +/- 0.33 1.13 +/- 0.28 1.09 +/- 0.59 Ac-228 0.69 +/- 0.10 0.60 +/- 0.075 0.50 :!: 0.15 C.
9-2
POINT BEACH NUCLEAR PLANT Table 10. Radioactivity in vegetation samples Collection: Tri-annual
- ~'"
t I ~ Sample Description and Concentration (pCi/g wet)
MDC MDC MDC Location E-01 E-02 E-03 Collection Date 05-26-16 05-26-16 05-26-16 Lab Code EG-2642 EG-2644 EG-2645 Req. LLD Ratio (wet/dry) 6.77 7.00 6.05 Gross Beta 5.47 +/- 0.11
< 0.034 4.90 +/- 0.09
< 0.028 4.90 +/- 0.09
< 0.029 0.25 Be-7 0.44 +/- 0.18 0.63 +/- 0.14 0.32 +/- 0.11 K-40 4.89 +/- 0.43 5.20 +/- 0.36 5.41 +/- 0.37 1-131 0.004 +/- 0.007
< 0.023 0.003 +/- 0.006
< 0.018 0.006 +/- 0.006
< 0.021 0.060 Cs-134 0.005 +/- 0.008
< 0.015
-0.005 +/- 0.006
< 0.011 0.001 +/- 0.005
< 0.011 0.060 Cs-137 0.004 +/- 0.009
< 0.013
-0.002 +/- 0.006
< 0.007 0.001 +/- 0.006
< 0.009 0.080 Other (Co-60) 0.004 +/- 0.007
< 0.009.
-0.006 +/- 0.008
< 0.011 0.005 +/- 0.008
< 0.010 0.060 Location E-04 E-06 E-08 Collection Date 05-26-16 05-26-16 05-26-16 Lab Code EG-2646 EG-2647 EG-2648 Req. LLD Ratio (wet/dry) 7.00 5.36 8.15 Gross Beta 4.61 +/- 0.09
< 0.028 4.03 +/- 0.09
< 0.031 3.73 +/- 0.07
< 0.024 0.25 Be-7 0.30 +/- 0.09 2.54 +/- 0.21 0.68 +/-0.13 K-40 4.05 +/- 0.29 3.01 +/- 0.27 3.58 +/- 0.27 1-131 0.008 +/- 0.004
< 0.011 0.001 +/- 0.005
< 0.025 0.000 +/- 0.006
< 0.020 0.060 Cs-134 0.004 +/- 0.004
< 0.008 0.002 +/- 0.005
< 0.010 0.000 +/- 0.005
< 0.009 0.060 Cs-137
-0.003 +/- 0.006
< 0.008 0.007 +/- 0.006
< 0.012
-0.004 +/- 0.006
< 0.006 0.080
\\
Other (Co-60) 0.000 +/- 0.005
< 0.005
-0.004 +/- 0.006
< 0.005 0.001 +/- 0.006
< 0.006 0.060 Location E-09 E-20 Collection Date 05-26-16 05-26-16 Lab Code EG-2649 EG-2650 Req.LLD Ratio (wet/dry) 5.89 9.07 Gross Beta 5.34 +/- 0.11
< 0.033 4.01 +/- 0.08
< 0.026 0.25 Be-7 0.63 +/- 0.14 0.50 +/- 0.12 K-40 5.20 +/- 0.36 3.80 +/- 0.27 1-131 0.003 +/- 0.006
< 0.018 0.001 +/- 0.005
< 0.020 0.060 Cs-134
-0.005 +/- 0.006
< 0.011 0.002 +/- 0.005
< 0.008 0.060 Cs-137
-0.002 +/- 0.006
< 0.007
-0.004 +/- 0.005
< 0.007 0.080 Other (Co-60)
-0.006 +/- 0.008
< 0.011
-0.004 +/- 0.005
< 0.007 0.060
(
10-1
POINT BEACH NUCLEAR PLANT Table 10. Radioactivity in vegetation samples Collection: Tri-annual
(
Sample Description and Concentration (pCi/g wet)
MDC MDC Location E-01 E-02 Collection Date 07-28-16 07-28-16 Lab Code EG-3961 EG-3962 Ratio (wet/dry) 4.26 3.73 Gross Beta 4.28 +/- 0.10
< 0.036 7.64 +/- 0.17
< 0.053 Be-7 1.05+/-0.17 1.43 +/- 0.22 K-40 6.06 +/- 0.42 4.64 +/- 0.44 1-131 0.000 +/- 0.008
< 0.021 0.009 +/- 0.008
< 0.023 Cs-134 0.006 +/- 0.007
< 0.015
-0.004 +/- 0.008
< 0.017 Cs-137
-0.001 +/- 0.008
< 0.011 0.001 +/- 0.008
< 0.011 Other (Co-60)
-0.001 +/- 0.007
< 0.007
-0.006 +/- 0.009
< 0.008 Location E-04 E-06 Collection Date 07-28-16 07-28-16 Lab Code EG-3964 EG-3965 Ratio (weUdry) 3.77 3.07 Gross Beta 6.75 +/- 0.15*
< 0.053 2.98 +/- 0.07
< 0.028 Be-7 1.45+/-0.19 1.59 +/- 0.19 K-40 5.36 +/- 0.40 3.72 +/- 0.36 1-131
-0.001 +/- 0.006
< 0.017
-0.006 +/- 0.006
< 0.022 Cs-134
-0.002 +/- 0.006
< 0.012 0.001 +/- 0.007
< 0.013
-~
Cs-137 0.005 +/- 0.008
< 0.015 0.017 +/- 0.009
< 0.016 t
Other (Co-60)
-0.005 +/- 0.007
< 0.007
-0.005 +/- 0.007
< 0.006
\\.
Location E-09 E-20 Collection Date 07-28-16 07-28-16 Lab Code EG-3967 EG-3968 Ratio (wet/dry) 3.49 3.61 Gross Beta 7.42 +/-0.16
< 0.055 8.92 +/- 0.18
< 0.066 Be-7 2.00 +/- 0.23 2.31 +/- 0.20 K-40 6.58 +/- 0.52 5.65 +/- 0.39 1-131
-0.009 +/- 0.007
< 0.016
-0.007 +/- 0.005
< O.D15 Cs-134
-0.006 +/- 0.008
< O.D15 0.002 +/- 0.005
< 0.011 Cs-137
-0.005 +/- 0.009
< 0.011 0.000 +/- 0.007
< 0.013 Other (Co-60)
-0.001 +/- 0.009
< 0.009 0.005 +/- 0.006
< 0.009 10-2 E-03 07-28-16 EG-3963 5.92 7.51 +/- 0.14 0.93 +/- 0.15 6.46 +/- 0.38
-0.006 +/- 0.005 0.003 +/- 0.006 0.002 +/- 0.006 0.002 +/- 0.007 E-08 07-28-16 EG-3966 4.23 6.09 +/- 0.13 1.66 +/- 0.19 4.36 +/- 0.39
-0.001 +/- 0.006
-0.002 +/- 0.006
-0.003 +/- 0.007
-0.007 +/- 0.008 MDC
< 0.045
< 0.021
< 0.012
< 0.010
< 0.006
< 0.047
< 0.019
< 0.012
< 0.010
< 0.007 Req.LLD 0.25 0.060 0.060 0.080 0.060 Req.LLD 0.25 0.060 0.060 0.080 0.060 Req. LLD 0.25 0.060 0.060 0.080 0.060 Ii
~
I' fi:
E-(
(
POINT BEACH NUCLEAR PLANT Table 10. Radioactivity in vegetation samples Collection: Tri-annual Sample Description and Concentration (pCi/g wet)
MDC Location E-01 Collection Date 10-11-16 Lab Code EG-5466 Ratio (wet/dry) 2.57 Gross Beta 6.47 +/-0.16
< 0.058 Be-7 5.57 +/- 0.36 K-40 5.33 +/- 0.46 1-131 0.005 +/- 0.008
< 0.053 Cs-134
-0.008 +/- 0.008
< 0.015 Cs-137
-0.003 +/- 0.010
< 0.014 Other (Co-60)
-0.003 +/- 0.009
< 0.014 Location E-04 Collection Date 10-11-16 Lab Code EG-5469 Ratio (wet/dry) 2.33 Gross Beta 7.84 +/- 0.22
< 0.097 Be-7 4.71 +/- 0.33 K-40 5.55 +/- 0.43 1-131
-0.020 +/- 0.008
< 0.040 Cs-134
-0.006 +/- 0.007
< 0.012 Cs-137 0.007 +/- 0.008
< 0.009 Other (Co-60)
-0.001 +/- 0.009
< 0.013 Location E-09 Collection Date 10-11-16 Lab Code EG-5472 Ratio (wet/dry) 3.78 Gross Beta 6.77 +/- 0.16
< 0.066 Be-7 2.04 +/- 0.20 K-40 5.02 +/- 0.38 1-131
-0.010 +/- 0.006
< 0.044 Cs-134
-0.006 +/- 0.007
< 0.012 Cs-137
-0.002 +/- 0.008
< 0.014 Other (Co-60)
-0.001 +/- 0.008
< 0.012 Beta Annual Mean +/- s.d.
5.92 +/- 1.55 Be-7 Annual Mean +/- s.d.
2.08 +/- 1.62 K-40 Annual Mean +/- s.d.
5.00 +/- 1.00 1-131 Annual Mean +/- s.d. -0.001 +/- 0.007 Cs-134 Annual Mean +/- s.d. -0.001 +/- 0.004 Cs-137 Annual Mean +/- s.d. 0.001 +/- 0.005 Co-60 Annual Mean +/- s.d. 0.004 +/- 0.004 MDC E-02 10-11-16 EG-5467 3.54 7.95 +/- 0.18
< 0.068 3.11 +/- 0.28 5.69 +/- 0.43
-0.018 +/- 0.008
< 0.038 0.000 +/- 0.007
< 0.012
-0.001 +/- 0.008
< *0.013 0.001 +/- 0.008
< 0.011 E-06 10-11-16 EG-5470 3.68 5.34 +/- 0.13
< 0.049 3.03 +/- 0.26 3.20 +/- 0.32
-0.003 +/- 0.006
< 0.036 0.002 +/- 0.007
< 0.012
-0.002 +/- 0.007
< 0.008
-0.004 +/- 0.006
< 0.007 E-20 10-11-16 EG-5473 4.76 6.49 +/- 0.14
< 0.045 3.82 +/- 0.32 5.98 +/- 0.47 0.008 +/- 0.008
< 0.048 0.002 +/- 0.008
< 0.015 0.002 +/- 0.009
< 0.014 0.004 +/- 0.010
< 0.019 10-3 MDC E-03 10-11-16 EG-5468 Req.LLD 2.66 6.42 +/- 0.20
< 0.096 0.25 3.56 +/- 0.33 5.72 +/- 0.50 0.002 +/- 0.008
< 0.051 0.060
-0.009 +/- 0.008
< 0.014 0.060 0.001 +/- 0.008
< 0.012 0.080 0.001 +/- 0.008
< 0.011 0.060 E-08 10-11-16 EG-5471 Req. LLD 3.04 6.32 +/- 0.16
< 0.059 0.25 5.58 +/- 0.38 5.56 +/- 0.45
-0.001 +/- 0.008
< 0.042 0.060
-0.005 +/- 0.009
< 0.017 0.060 0.006 +/- 0.010
< 0.016 0.080
-0.004 +/- 0.010
< 0.009 0.060 Req.LLD 0.25 0.060 0.060 0.080 0.060
POINT BEACH NUCLEAR PLANT Table 12.
Ambient Gamma Radiation a
(
LLD/7days: < 1 mR/TLD 1st. Quarter, 2016 Date Annealed:
12-08-15 Days in the field 91 Date Placed:
01-05-16 Days from Annealing Date Removed:
04-05-16 to Readout:
121 Date Read:
04-07-16 Days in mR/Stnd Qtr Location Field Total mR NetmR (91 days)
Net mR per 7 days Indicator E-1 91 17.8 +/- 1.0 11.7 +/- 1.2 11.7 +/- 1.2 0.90 +/- 0.09 E-2 91 212 +/- 0.6 15.1 +/- 0.7 15.1+/-0.7 1.16 +/-0.06 E-3 91 21.1 +/- 2.0 15.1 +/-2.0 15.1 +/-2.0 1.16 +/- 0.16 E-4 91 17.8+/-1.5 11.7 +/- 1.6 11.7+/-1.6 0.90 +/- 0.12 E-5 91 19.9 +/- 1.1 13.8+/-1.1 13.8+/-1.1 1.06 +/- 0.09 E-6 91 17.4+/-1.0 11.3+/-1.0 11.3+/-1.0 0.87 +/- 0.08 E-7 91 16.6 +/- 0.8 10.6 +/- 0.9 10.6 +/- 0.9 0.81 +/- 0.07 E-8 91 18.5 +/- 1.1 12.4 +/- 1.2 12.4 +/- 1.2 0.95 +/- 0.09 E-9 91 22.1 +/- 0.7 16.0 +/- 0.8 16.0 +/- 0.8 1.23 +/- 0.06 E-12 91 15.7 +/- 0.8 9.6 +/-0.8 9.6 +/- 0.8 0.74 +/- 0.06 E-14 91 20.4 +/- 0.6 14.3 +/- 0.7 14.3 +/- 0.7 1.10 +/-0.06 E-15 91 18.7 +/- 0.4 12.7 +/- 0.5 12.7 +/- 0.5 0.98 +/- 0.04 E-168 91 21.6 +/- 0.3 15.5 +/- 0.5 15.5 +/- 0.5 1.19 +/-0.08 E-17 91 19.7 +/- 0.9 13.6 +/-1.0 13.6 +/-1.0 1.05 +/- 0.07 E-18 91 21.0 +/- 0.9 15.0 +/-1.0 15.0 +/-1.0 1.15 +/-0.07 E-22 91 21.1 +/- 1.5 15.0 +/-1.6 15.0 +/-1.6 1.15 +/- 0.12
(
E-23 91 19.7 +/- 0.5 13.6 +/- 0.6 13.6 +/- 0.6 1.05 +/- 0.05 E-24 91 19.6 +/- 0.5 13.5 +/- 0.6 13.5 +/- 0.6 1.04 +/- 0.04
\\
E-25 91 18.9 +/- 0.6 12.9 +/- 0.7 12.9 i 0.7 0.99 +/- 0.05 E-268 91 17.8 +/- 0.6 11.8+/-0.7 11.8 +/-0.7 0.91 +/- 0.06 E-27 91 20.7 +/- 0.3 14.7 +/- 0.5 14.7 +/- 0.5 1.13 +/- 0.04 E-28 91 15.4+/-1.0 9.4 +/- 1.1 9.4 +/- 1.1 0.72 +/- 0.08 E-29 91 15.3 +/- 0.8 9.3 +/- 0.9 9.3 +/-0.9 0.71 +/- 0.07 E-30 91 18.8+/-1.2 12.8 +/- 1.3 12.8+/-1.3 0.98 +/- 0.10 E-31 91 21.1 +/- 0.8 15.1+/-0.8 15.1 +/- 0.8 1.16 +/- 0.07 E-32 91 22.2 +/- 0.8 16.1 +/- 0.9 16.1 +/- 0.9 1.24 +/- 0.07 E-38 91 20.2+/-1.5 14.1 +/- 1.6 14.1+/-1.6 1.08 +/- 0.12 E-39 91 20.8 +/- 1.3 14.7 +/- 1.4 14.7+/-1.4 1.13 +/- 0.11 E-41 91 18.9 +/- 0.9 12.8+/-1.0 12.8+/-1.0 0.98 +/- 0.07 E-42 91 23.3+/-1.0 17.2+/-1.1 17.2+/-1.1 1.33 +/- 0.08 E-43 91 20.1 +/- 1.5 14.1 +/- 1.5 14.1 +/- 1.5 1.08 +/- 0.12 Control E-20 91 20.7 +/- 1.3 14.7+/-1.3 14.7 +/- 1.3 1.13 +/- 0.10 Mean+/-s.d.
19.5 +/- 2.0 13.4 +/- 2.0 13.4 +/- 2.0 1.03 +/- 0.16 Jn-Transit Exposure Date Annealed Date Read ITC-1 ITC-2 12-08-15 01-09-16 5.2 +/- 0.3 5.2 +/- 0.3 03-14-16 04-08-16 5.9 +/- 0.4 6.2 +/- 0.3 a The CaS04: Dy dosimeter cards provide four separate readout areas. Values listed represent the mean and standard deviation of the average of the four readings.
I \\
12-1
POINT BEACH NUCLEAR PLANT Table 12.
Ambient Gamma Radiation a
(
LLD/7days: < 1 mRfTLD 2nd Quarter, 2016 Date Annealed:
03-14-16 Days in the field 93 Date Placed:
04-05-16 Days from Annealing Date Removed:
07-07-16 to Readout:
116 Date Read:
07-08-16 Days in mR/Stnd Qtr Location Field Total mR NetmR (91 days)
Net mR per 7 days Indicator E-1 93 17.6+/-1.4 12.4 +/-1.5 12.1 +/- 1.5 0.93 +/- 0.11 E-2 93 22.8+/-1.4 17.5 +/-1.5 17.1 +/-1.5 1.32 +/- 0.11 E-3 93 23.9 +/-2.1 18.7 +/-2.2 18.3 +/- 2.2 1.41 +/- 0.17 E-4 93 20.7 +/- 0.6 15.5 +/- 0.8 15.2 +/- 0.8 1.17 +/- 0.06 E-5 93 20.7 +/- 0.4 15.5 +/- 0.8 15.2 +/- 0.7 1.17 +/-0.06 E-6 93 18.0 +/- 0.3 12.8 +/- 0.7 12.5 +/- 0.7 0.96 +/-0.05 E-7 93 19.9 +/- 0.4 14.7 +/- 0.7 14.4 +/- 0.7 1.10+/-0.06 E-8 93 20.0 +/- 0.9 14.8 +/- 1.1 14.5 +/- 1.1 1.11 +/-0.08 E-9 93 20.6 +/- 0.8 15.4+/-1.0 15.1 +/- 1.0 1.16 +/-0.07 E-12 93 15.3 +/- 0.5 10.1 +/- 0.8 9.8 +/- 0.8 0.76 +/- 0.06 E-14 93 22.0+/-1.6 16.8+/-1.7 16.4+/-1.7 1.26 +/- 0.13 E-15 93 22.4 +/- 0.9 17.2+/-1.1 16.8+/-1.1 1.29 +/- 0.08 E-168 93 21.2 +/- 0.5 15.9 +/- 0.8 15.6 +/- 0.8 1.20 +/- 0.06 E-17 93 24.0 +/- 0.6 18.8 +/- 0.8 18.4 +/- 0.8 1.41 +/- 0.06 E-18 93 24.0 +/- 0.7 18.8 +/- 0.9 18.4 +/- 0.9 1.41 +/- 0.07 E-22 93 22.1 +/- 0.8 16.9 +/- 1.0 16.6+/-1.0 1.27 +/- 0.07 E-23 93 23.8 +/- 0.4 18.6 +/- 0.8 18.2 +/- 0.7 1.40 +/- 0.06
~
E-24 93 21.1 +/- 0.8 15.9+/-1.0 15.6+/-1.0 1.20 +/- 0.08 E-25 93 21.6 +/- 0.8 16.4+/-1.0 16.0 +/- 1.0 1.23 +/- 0.07 E-268 93 20.7 +/- 0.4 15.5 +/- 0.7 15.1+/-0.7 1.16 +/-0.05 E-27 93 24.7 +/- 1.1 19.5 +/- 1.2 19.1+/-1.2 1.47 +/- 0.09 E-28 93 16.5 +/- 0.3 11.3+/-0.7 11.1 +/- 0.7 0.85 +/-0.05 E-29 93 15.9 +/- 0.5 10.7 +/- 0.8 10.5 +/- 0.8 0.80 +/- 0.06 E-30 93 18.9 +/- 0.8 13.7+/-1.0 13.4 +/- 1.0 1.03 +/- 0.08 E-31 93 21.5 +/- 1.6 16.3 +/- 1.7 15.9+/-1.7 1.22 +/- 0.13 E-32 93 25.2 +/- 0.9 20.0 +/- 1.1 19.5 +/- 1.0 1.50 +/- 0.08 E-38 93 20.9 +/- 0.5 15.6 +/- 0.8 15.3 +/- 0.8 1.18 +/- 0.06 E-39 93 20.6 +/- 0.6 15.4 +/- 0.8 15.1 +/- 0.8 1.16 +/-0.06 E-41 93 20.2 +/- 0.4 15.0 +/- 0.7 14.7 +/- 0.7 1.13 +/- 0.06 E-42 93 22.4+/-1.0 17.2 +/- 1.1 16.8+/-1.1 1.29 +/- 0.09 E-43 93 22.1 +/- 1.2 16.9+/-1.3 16.5 +/- 1.3 1.27 +/- 0.10 Control E-20 93 21.9+/-1.5 16.7+/-1.6 16.3 +/- 1.6 1.25 +/-0.12 Mean+/-s.d.
21.0 +/- 2.4 15.8 +/- 2.4 15.5 +/- 2.4 1.19 +/- 0.18 In-Transit Exposure Date Annealed Date Read ITC-1 ITC-2 03-14-16 04-08-16 5.9 +/- 0.4 6.2 +/-0.3 06-09-16 07-08-16 4.5 +/-0.3 4.3 +/- 0.2
- The CaS04:Dy dosimeter cards provide four separate readout areas. Values listed represent the mean and standard deviation of the average of the four readings.
I
(
I 12-2
POINT BEACH NUCLEAR PLANT Table 12.
Ambient Gamma Radiation a
- ' (
LLD/7days: < 1 mR/TLD 3rd Quarter, 2016 Date Annealed:
06-09-16 Days in the field 90 Date Placed:
07-07-16 Days from Annealing Date Removed:
10-05-16 to Readout:
125 Date Read:
10-12-16 Days in mR/Stnd Qtr Location Field Total mR NetmR (91 days)
Net mR per 7 days Indicator E-1 90 18.4 +/- 1.1 13.2+/-1.3 13.4 +/- 1.3 1.03 +/- 0.10 E-2 90 22.6 +/- 0.8 17.4+/-1.1 17.6+/-1.1 1.35 +/- 0.08 E-3 90 23.2 +/-2.0 18.0 +/- 2.1 18.2 +/- 2.1 1.40 +/-0.16 E-4 90 19.3 +/- 1.5 14.1 +/- 1.6 14.3+/-1.6 1.10 +/- 0.12 E-5 90 21.9+/-1.1 16.7+/-1.3 16.9+/-1.3 1.30 +/- 0.10 E-6 90 18.3 +/-1.0 13.1 +/- 1.2 13.3 +/- 1.2 1.02 +/- 0.09 E-7 90 18.2+/-1.0 13.0+/-1.2 13.2+/-1.2 1.01 +/- 0.09 E-8 90 19.1 +/- 1.1 13.9+/-1.3 14.1 +/- 1.3 1.08 +/- 0.10 E-9 90 24.0 +/- 0.8 18.8+/-1.0 19.1 +/- 1.0 1.47 +/- 0.08 E-12 90 15.6 +/- 0.8 10.4 +/- 1.0 10.5+/-1.1 0.81 +/- 0.08 E-14 90 21.2 +/-0.7 16.1+/-1.0 16.3+/-1.0 1.25 +/- 0.07 E-15 90 20.8 +/- 0.8 15.6+/-1.0 15.8+/-1.0 1.21 +/- 0.08 E-168 90 21.2 +/- 0.6 16.0 +/- 0.9 16.2 +/- 0.9 1.25 +/- 0.07 E-17 90 20.7+/-1.2 15.6 +/- 1.4 15.7 +/-1.4 1.21 +/-0.11 E-18 90 24.0+/-1.4 18.8+/-1.5 19.0 +/-1.6 1.47 +/-0.12 E-22 90 22.8+/-1.6 17.6 +/- 1.7 17.8+/-1.7 1.37 +/- 0.13 E-23 90 23.7 +/- 0.5 18.5 +/- 0.8 18.7 +/- 0.8 1.44 +/-0.07
(
E-24 90 20.2 +/- 0.9 15.0+/-1.1 15.2+/-1.1 1.17 +/- 0.09 E-25 90 20.6 +/- 0.6 15.4 +/- 0.9 15.6 +/- 0.9 1.20 +/- 0.07 E-268 90 19.6 +/- 0.8 14.4 +/- 1.0 14.6 +/- 1.0 1.12 +/-0.08 E-27 90 22.4 +/- 0.5 17.2 +/- 0.8 17.4 +/- 0.9 1.34 +/- 0.07 E-28 90 15.6 +/- 0.8 10.5+/-1.0 10.6 +/- 1.0 0.81 +/- 0.08 E-29 90 15.8+/-1.0 10.6+/-1.2 10.7+/-1.2 0.82 +/-0.09 E-30 90 19.3+/-1.1 14.1 +/- 1.3 14.3 +/- 1.3 1.10 +/- 0.10 E-31 90 22.7 +/- 0.6 17.5 +/- 0.9 17.7 +/- 0.9 1.36 +/- 0.07 E-32 90 25.5+/-1.0 20.3+/-1.2 20.5+/-1.2 1.58 +/- 0.09 E-38 90 21.7+/-1.7 16.6+/-1.8 16.7+/-1.8 1.29 +/- 0.14 E-39 90 23.3 +/- 1.4 18.2+/-1.6 18.4 +/- 1.6 1.41 +/- 0.12 E-41 90 22.6+/-1.7 17.4+/-1.8 17.6+/-1.9 1.36 +/-0.14 E-42 90 26.7 +/- 1.1' 21.6+/-1.3 21.8+/-1.3 1.68+/-0.10 E-43 90 24.0 +/- 1.3 18.8 +/- 1.5 19.1 +/- 1.5 1.47 +/- 0.11 Control E-20 90 22.0+/-1.4 16.8+/-1.5 17.0+/-1.6 1.31 +/- 0.12 Mean+/-s.d.
21.2 +/- 2.7 16.0 +/- 2.7 16.2 +/- 2.8 1.24 +/- 0.22 Jn-Transit Exposure Date Annealed Date Read ITC-1 JTC-2 06-09-16 07-08-16 4.5 +/- 0.3 4.3 +/- 0.2 09-08-16 10-12-16 5.7 +/- 0.2 6.2 +/- 0.5
- The CaS04:Dy dosimeter cards provide four separate readout areas. Values listed represent the mean and standard deviation of the average of the four readings.
{
1..,
12-3
POINT BEACH NUCLEAR PLANT
(~
Table 12.
Ambient Gamma Radiation a
\\
LLD/7days: < 1mR/TLD 4th Quarter, 2016 Date Annealed:
09-08-16 Days in the field 85 Date Placed:
10-05-16 Days from Annealing Date Removed:
12-29-16 to Readout:
118 Date Read:
01-04-17 Days in mR/Stnd Qtr Location Field Total mR NetmR (91 days)
Net mR per 7 days Indicator E-1 85 17.5+/-1.4 12.1 +/- 1.6 12.9+/-1.7 1.00 +/- 0.13 E-2 85 22.3+/-1.0 16.9+/-1.3 18.1 +/- 1.3 1.39 +/-0.10 E-3 85 23.0+/-1.4 17.6+/-1.5 18.9+/-1.7 1.45 +/- 0.13 E-4 85 20.3 +/- 0.6 14.9 +/- 0.9 15.9+/-1.0 1.23 +/- 0.08 E-5 85 20.3 +/- 0.5 14.9 +/- 0.8 16.0 +/- 0.9 1.23 +/- 0.07 E-6 85 17.8 +/- 0.5 12.4 +/- 0.8 13.2 +/- 0.9 1.02 +/- 0.07 E-7 85 19.3 +/- 0.9 13.9 +/- 1.1 14.9+/-1.2 1.14 +/-0.09 E-8 85 20.0 +/- 0.7 14.6+/-1.0 15.7+/-1.0 1.20 +/- 0.08 E-9 85 19.6 +/- 0.6 14.2 +/- 0.9 15.2+/-1.0 1.17 +/-0.08 E-12 85 15.6 +/- 0.6 10.2 +/- 0.9 10.9+/-1.0 0.84 +/- 0.07 E-14 85 22.4 +/- 1.2 17.0+/-1.4 18.1 +/- 1.5 1.40 +/- 0.12 E-15 85 21.9+/-1.2 16.5+/-1.3 17.7+/-1.4 1.36 +/- 0.11 E-168 85 21.1 +/-0.7 15.7 +/- 1.0 16.8 +/-1.0 1.29 +/- 0.08 E-17 85 22.9 +/- 0.4 17.5 +/- 0.8 18.8 +/- 0.9 1.44 +/- 0.07 E-18 85 22.6 +/- 0.6 17.2 +/- 0.9 18.5 +/- 1.0 1.42 +/- O.D7 E-22 85 22.0+/-1.2 16.6+/-1.4 17.7+/-1.5 1.36 +/- 0.11 E-23 85 23.2 +/- 0.5 17.8 +/- 0.9 19.1 +/- 0.9 1.47 +/- 0.07
{
E-24 85 20.5 +/- 0.4 15.1 +/- 0.8 16.2 +/- 0.9 1.25 +/- 0.07 I *.
/
E-25 85 21.8+/-1.2 16.4 +/- 1.4 17.5+/-1.5 1.35 +/- 0.11 E-268 85 21.1 +/- 0.2 15.7 +/- 0.7 16.8 +/- 0.8 1.29 +/- 0.06 E-27 85 25.4 +/- 0.9 20.0+/-1.2 21.4+/-1.2 1.64 +/- 0.10 E-28 85 17.6 +/- 0.4 12.2 +/- 0.8 13.1 +/- 0.9 1.01 +/- 0.07 E-29 85 16.2+/-1.6 b
10.8+/-1.7 11.6 +/- 1.9 0.89 +/- 0.14 E-30 85 19.3 +/- 0.7 13.9 +/- 1.0 14.9+/-1.0 1.14+/-0.08 E-31 85 22.3 +/- 2.0 16.9 +/- 2.1 18.1 +/- 2.2 1.39 +/- 0.17 E-32 85 25.7 +/- 1.3 20.3 +/- 1.4 21.7+/-1.5 1.67 +/- 0.12 E-38 85 21.2 +/- 0.4 15.8 +/- 0.8 16.9 +/- 0.9 1.30 +/- 0.07 E-39 85 2Q.9 +/- 0.8 15.5 +/- 1.1 16.6+/-1.1 1.28 +/- 0.09 E-41 85 21.1 +/- 1.1 15.7+/-1.3 16.8+/-1.3 1.29 +/-0.10 E-42 85 22.9 +/- 0.9 17.5+/-1.2 18.7+/-1.2 1.44 +/- 0.10 E-43 85 22.3+/-1.0 16.9+/-1.2 18.1 +/- 1.3 1.39 +/- 0.10 Control E-20 85 23.2 +/- 1.3 17.8+/-1.4 19.1 +/-1.5 1.47 +/-0.12 Mean+/-s.d.
20.1 +/- 1.5 15.6 +/- 2.3 19.7+/-1.5 1.29 +/- 0.19 In-Transit Exposure Date Annealed Date Read ITC-1 ITC-2 09-08-16 10-12-16 5.7 +/- 0.2 6.2 +/- 0.5 12-07-16 01-04-17 4.8 +/- 0.3 4.9 +/- 0.3 a The CaS04:Dy dosimeter cards provide four separate readout areas. Values listed represent the mean and standard deviation of the average of the four readings.
b Card corrupted; only one reading. No standard deviation; error calculated at 10%.
Annual Indicator Mean+/-s.d.
20.6 +/- 2.5 15.2 +/- 2.6 15.4 +/- 2.7 1.19 +/- 0.21 Annual Control Mean+/-s.d.
22.0 +/- 1.0 16.5 +/-1.3 16.8+/-1.8 1.29 +/-0.14
\\
Annual Indicator/Control Mean+/-s.d.
20.7 +/- 2.5 15.2 +/- 2.6 15.5 +/- 2.7 1.19 +/- 0.21 12-4
POINT BEACH NUCLEAR PLANT Table 13. Groundwater Tritium Monitoring Program (Monthly Collections)
(
Units= Ci/L Intermittent Streams Samele ID GW-01 GW-02 Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-27-16 NS" 01-27-16 NSa 02-24-16 EWW-764 27 +/- 79
< 155 02-24-16 EWW-765 186 +/- 87
< 155 03-31-16 EWW-1306 71 +/- 76
< 145 03-31-16 EWW-1307 190 +/- 82
< 145 04-27-16 EWW-1955
.83 +/- 82
< 147 04-27-16 EWW-1956 227 +/- 89
< 147 05-25-16 EWW"2686 71 +/- 79
< 151 05-25-16 EWW-2687 194 +/- 85
< 151 06-29-16 EWW-3297 148 +/- 80
< 150 06-29-16 EWW-3298 111 +/- 78
< 150 07-27-16 EWW-3976 166 +/- 81
< 145 07-27-16 EWW-3977 164 +/- 81
< 145 08-31-16 EWW-4630 105 +/- 80
< 155 08-31-16 EWW-4631 114 +/- 81
< 155 09-28-16 EWW-5138 115 +/- 82
< 157 09-28-16 c EWW-5139 689 +/- 106
< 148 10-19-16 EWW-5638 215 +/- 104
< 182 10-19-16 EWW-5639 52 +/- 98
< 182 11-30-16 EWW-6531 6 +/- 90
< 180 11-30-16 EWW-6532 116 +/- 94
< 180 12-28-16 EWW-6934 59 +/- 79
< 153 12-28-16 NS" Mean +/-s.d.
97 +/-62 Mean +/-s.d.
204+/-178 Samele ID GW-03 GW-17 Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-27-16 NS" 01-27-16 NS" 02-24-16 EWW-766 29 +/- 79
< 155 02-24-16 EWW-768 171 +/- 86
< 155 03-31-16 EWW-1308 42 +/- 74
< 145 03-31-16 EWW-1310 243 +/- 85
< 145 04-27-16 EWW-1958 64 +/- 81
< 147 04-27-16 EWW-1960 236 +/- 89
< 147 05-25-16 EWW-2688 65 +/- 78
< 151 05-25-16 EWW-2690 236 +/- 87
< 151 06-29-16 EWW-3300 27 +/- 74
< 150 06-29-16 EWW-3302 129 +/- 79
< 150 07-27-16 EWW-3978 52 +/- 75
< 145 07-27-16 EWW-3980 118 +/- 79
< 145 08-31-16 EWW-4632 16 +/- 75
< 155 08-31-16 EWW-4634 152 +/- 83
< 155 i
09-28-16 EWW-5140 57 +/- 78
< 157 09-28-16 NSb
\\,
10-19-16 EWW-5641 17 +/- 96
< 182 10-19-16 EWW-5643 199 +/- 103
< 182 11-30-16 EWW-6533
-12 +/- 89
< 180 11-30-16 EWW-6535 109 +/- 94
< 180 12-28-16 NS" 12-28-16 EWW-6936 207 +/- 87
< 153 Mean +/-s.d.
36 +/-25 Mean+/-s.d.
180 +/- 51 Wells Samele ID GW-04 (EiC Well)
Collection Date Lab Code Tritium MDC 01-27-16 EWW-384
-25 +/- 72
< 148 02-24-16 EWW-767
-30 +/- 75
< 155 03-31-16 EWW-1309 48 +/- 74
< 145 04-27-16 EWW-1959 3 +/- 77
< 147 05-25-16 EWW-2689
-4 +/- 75
< 151 06-29-16 EWW-3301
-17 +/- 71
< 150 07-27-16 EWW-3979 6 +/- 72
< 145 08-31-16 EWW-4633 69 +/- 78
< 155 09-2B-16 EWW-5141 47 +/- 76
< 148 10-19-16 EWW-5642 74 +/- 99
< 1B2 11-30-16 EWW-6534
-34 +/-BB
< 1BO 12-2B-16 EWW-6935 1.9 +/- 77
< 153 Mean +/-s.d.
13 +/-38
- "NS" = No sample; water frozen.
b "NS" = No sample; see Table 2.0, Listing of Missed Samples.
0 Sample reanalyzed with a result of 591+/-130 pCifL.
(
Ir 13-1
POINT BEACH NUCLEAR PLANT Table 13. Groundwater Tritium Monitoring Program (Monthly Collections)
(
Units= Ci/L
\\
Beach Drains Samele ID S-1 S-3 Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-10-16 NF" 01-10-16 NF" 02-10-16 NF" 02-10-16 NF" 03-09-16 EWW-1036 181*+/- 84
< 142 03-09-16 EWW-1037 244 +/- 87
< 142 04-21-16 EWW-1806 629 +/- 102
< 148 04-21-16 NF" 05-05-16 EWW-2195 187 +/- 84
< 149 05-05-16 NF" 06-09-16 EWW-2923 267 +/- 88
< 150 06-09-16 NF" 07-07-16 EWW-3435 228 +/- 89
< 148 07-07-16 NF" 08-10-16 EWW-4280 168 +/- 80
< 146 08-10-16 NF" 09-08-16 EWW-4771 176 +/- 90
< 155 09-08-16 NF" 10-06-16 EWW-5348 260 +/- 85
< 142 10-06-16 NF" 11-10-16 EWW-6269 211 +/- 93
< 176 11-10-16 NF" 12-07-16 EWW-6746 241 +/- 86
< 152 12-07-16 NF" Mean +/-s.d.
255 +/- 136 Mean +/-s.d.
Samele ID S-7 S-8 Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-10-16 NF" 01-10-16 NF" 02-10-16 NF" 02-10-16 NF" 03-09-16
- NF" 03-09-16 NF" 04-21-16 NF" 04-21-16 NF" 05-05-16 NF" 05-05-16 NF"
,e 06-09-16 NF" 06-09-16 NF" 07-07-16 NF" 07-07-16 NF"
\\
08-10-16 NF" 08-10-16 NF" 09-08-16 NF" 09-08-16 NF" 10-06-16 NF" 10-06-16 NF" 11-10-16 NF" 11-10-16 NF" 12-07-16 NF" 12-07-16 NF" Mean +/-s.d.
Mean +/-s.d.
Samele ID S-9 S-10 Collection Collection Date Lab Code*
Tritium MDC Date Lab Code Tritium MDC 01-10-16 NF" 01-10-16 NF" 02-10-16 NF" 02-10-16 NF" 03-09-16 NF" 03-09-16 NF" 04-21-16 NF" 04-21-16
.NF" 05-05-16 NF" 05-05-16 NF" 06-09-16 NF" 06-09-16 NF" 07-07-16 NF" 07-07-16 NF" 08-10-16 NF" 08-10-16 NF" 09-08-16 NF" 09-08-16 NF" 10-06-16 NF" 10-06-16 NF" 11-10-16 NF" 11-10-16 NF" 12-07-16 NF" 12-07-fa NF" Mean +/-s.d.
Mean +/-s.d.
""NF" = No flow.
( '...,
13-2
POINT BEACH NUCLEAR PLANT Table 13. Groundwater Tritium Monitoring Program
{Monthly Collections) f-Units= Ci/L Beach Drains (cont.)
Sam[!lelD S-11 S-12b Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-10-16 NF" 02-10-16 NF" 03-09-16 EWW-1038 140 +/- 82
< 142 04-21-16 NF" 05-05-16 NF" 06-09-16 NF" 07-07-16 NF" 08-10-16 NF" 09-08-16 NF" 09-08-16 EWW-4772 236 +/- 93
< 155 10-06-16 NF" 10-06-16 NF" 11-10-16 NF" 11-10-16 NF" 12-07-16 NF" 12-07-16 NF" Mean+/-s.d.
Sample ID U2 Fa~ade Subsurface Drain Sump Collection Collection Date Lab Code Date Lab Code Tritium MDC Tritium MDC 01-31-16 EW-1029 499 +/- 102
< 150 02-29-16 EW-1030 510. +/- 102
< 149 03-31-16 EW-2204 507 +/- 99
< 150 04-30-16 EW-2503 572 +/- 102
< 152 05-31-16 EW-2922 1018 +/- 133
< 157
(
06-30-16 EW-3615 1230 +/- 125
< 147 t '*
07-31-16 EW-4285 1333 +/- 128
< 146 08-31-16 EW-4908 929 +/- 116
< 149 09-30-16 EW-5524 615 +/- 104
< 151 10-31-16 EW-6393 966 +/- 119
< 177 11-30-16 EW-6753 1616 +/- 140
< 158 12-31-16 EW-7079 1523 +/- 136
< 155 Mean +/-s.d.
943 +/-410 a "NF" = No flow.
b New location as of 09-08-16.
13-3
POINT BEACH NUCLEAR PLANT Beach Drains
(
Units: = pCi/L Gamma isotopic analysis Location S-1 S-3 S-7 S-8 Collection Date 01-10-16 01-10-16 01-10-16 01-10-16 Lab Code NF" MDC NF" MDC NF" MDC NF" MDC Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-9 S-10 S-11 S-1 Collection Date 01-10-16 01-10-16 01-10-16 02-10-16 Lab Code NF" NF" NF" NF" Be-7 Mn-54 Fe-59 L_
Co-58 l
Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-3 S-7 S-8 S-9 Collection Date 02-10-16 02-10-16 02-10-16 02-10-16 Lab Code NF" NF" NF" NF" Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 a "NF" = No flow.
13-4
POINT BEACH NUCLEAR PLANT
(_
Beach Drains (cont.)
Units: = pCi\\L Gamma isotopic analysis Location S-10 S-11 S-1 S-3 Collection Date 02-10-16 02-10-16 03-09-16 03-09-16 Lab Code NF" MDC NF" MDC EW-1036 EW-1037 Be-7 8.6 +/- 12.1
< 24.4 4.4 +/- 12.1
< 28.2 Mn-54 0.3 +/- 1.7
< 3.1
-0.2 +/- 1.3
< 2.4 Fe-59 0.4 +/- 3.0
< 5.5 0.2 +/- 2.0
< 5.3 Co-58
-0.5 +/- 1.4
< 1.8 0.5 +/- 1.5
< 3.2 Co-60
-0.7 +/- 1.8
< 2.1
-0.8 +/- 1.6
< 0.9 Zn-65
-0.4 +/- 3.5
< 5.7
-0.5 +/- 2.6
< 2.6 Zr-Nb-95 0.6 +/- 1.5
< 3.4
-0.7 +/- 1.6
< 3.6 Cs-134
-0.1 +/- 1.5
< 2.7
-0.2 +/- 1.2
< 2.4 Cs-137 1.6 +/- 2.0
< 3.9
-0.6 +/- 1.7
< 2.6 Ba-La-140 0.2 +/- 1.7
< 2.6
-2.4 +/- 1.4
< 3.4 Location S-7 S-8 S-9 S-10 Collection Date 03-09-16 03-09-16 03-09-16 03-09-16 Lab Code NF" NF 8
NF" NF" Be-7 Mn-54 Fe-59
(
Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-11 S-1 S-3 S-7 Collection Date 03-09-16 04-21-16 04-21-16 04-21-16 Lab Code EW-1038 EW-1806 NF" NF" Be-7
-0.3 +/- 10.7
< 24.0 12.4 +/- 16.5
< 30.6 Mn-54 1.3 +/- 1.2
< 2.0
-0.9 +/- 1.8
< 2.6 Fe-59 0.7 +/- 2.6
< 5.2
-0.2 +/- 3.3
< 4.2 Co-58 1.8 +/- 1.2
< 2.3 1.5 +/- 1.4
< 2.6 Co-60
-1.3 +/- 1.5
< 1.7
-0.8 +/- 2.1
< 3.2 Zn-65 0.9 +/- 2.7
< 4.6 2.4 +/- 4.2
< 3.0 Zr-Nb-95
-1.4 +/- 1.7
< 3.8
-2.1 +/- 1.7
< 2.2 Cs-134
-0.6 +/- 1.5
< 2.7 0.9 +/- 1.8
< 4.2 Cs-137
-1.4 +/- 1.7
< 2.1
-0.9 +/- 2.0
< 2.8 Ba-La-140
-1.4 +/- 1.7
< 4.5
-2.5 +/- 1.8
< 2.3 a "NF" = No flow.
(
13-5
POINT BEACH NUCLEAR PLANT
(
Beach Drains (cont.)
Units: = pCi\\L Gamma isotopic analysis Location S-8 S-9 S-10 S-11 Collection Date 04-21-16 04-21-16 04-21-16 04-21-16 Lab Code NF 6
MDC NF 6
MDC NF 6
MDC MDC Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-1 S-3 S-7 S-8 Collection Date 05-05-16 05-05-16 05-05-16 05-05-16 Lab Code EW-2195 NF 6
NF 6
NFa Be-7 9.5 +/- 10.6
< 23.2 Mn-54
-0.7+/-1.2
< 1.5 Fe-59
-1.2 +/- 2.3
< 5.7 Co-58
-0.4 +/- 1.4
< 3.1
(-*-
-0.1 +/- 1.6
< 2.3 Zn-65 0.2 +/- 2.2
< 3.5 Zr-Nb-95 2.1 +/- 1.5
< 4.5 Cs-134 1.2 +/- 1.2
< 2.3 Cs-137
-0.1 +/- 1.4
< 1.8 Ba-La-140 6.4 +/- 1.5
< 10.1 Location S-9 S-10 S-11 S-1 Collection Date 05-05-16 05-05-16 05-05-16 06-09-16 Lab Code NF 6
NFa EW-2923 Be-7
-11.4 +/- 11.9
< 22.0 Mn-54
-0.9 +/- 1.5
< 2.0 Fe-59
-1.3 +/- 2.7
< 3.4 Co-58
-0.5 +/- 1.4
< 2.1 Co-60 0.5 +/- 1.5
< 1.9 Zn-65 2.8 +/- 3.1
< 4.8 Zr-Nb-95 0.9 +/- 1.6
< 3.9 Cs-134
-1.6 +/- 1.7
< 2.9 Cs-137 1.9 +/- 1.6
< 2.0 Ba-La-140
-2.3 +/- 1.6
< 2.1 a "NF" = No flow.
I
- I
/
I I * "
I\\
13-6 r
POINT BEACH NUCLEAR PLANT Beach Drains (cont.)
~-*
'(
Units: = pCi\\L Gamma isotopic analysis Location S-3 S-7 S-8 S-9 Collection Date 06-09-16 06-09-16 06-09-16 06-09-16 Lab Code NF 3
MDC NF 3
MDC NF 2
MDC NF 2
MDC Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-10 S-11 S-1 S-3 Collection Date 06-09-16 06-09-16 07-07-16 07-07-16 Lab Code NF 3
NFa EW-3435 NFa Be-7
-3.1 +/- 8.3
< 14.6 Mn-54
-0.3 +/- 1.0
< 1.5 Fe-59
-2.3 +/- 1.7
< 2.3
{
Co-58
-0.8 +/- 0.9
< 1.4 Co-60 0.5 +/- 1.0
< 0.8
\\.
Zn-65 1.1 +/- 1.8
< 2.3 Zr-Nb-95 0.5 +/- 1.0
< 2.0 Cs-134 0.5 +/- 1.0
< 1.9 Cs-137
-0.6 +/- 1.1
< 1.7 Ba-La-140
-0.1 +/- 1.1
< 4.0 Location S-7 S-8 S-9 S-10 Collection Date 07-07-16 07-07-16 07-07-16 07-07-16 Lab Code NFa NF*
NF 3
NFa Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 a "NF" = No flow.
(
\\
13-7
POINT BEACH NUCLEAR PLANT
{
Beach Drains (cont.)
\\;:-----
Units: = pCi\\L Gamma isotopic analysis Location S-11 S-1 S-3 S-7 Collection Date 07-07-16 08-10-16 08-10-16 08-10-16 Lab Code NF" MDC EW-4280 MDC NF" MDC NF" MDC Be-7 2.0 +/- 4.6
< 16.1 Mn-54 0.3 +/- 0.6
< 1.1 Fe-59
-0.8 +/- 1.0
< 2.9 Co-58 1.1 +/- 0.6
< 1.5 Co-60 0.6 +/- 0.6
< 1.3 Zn-65
-0.7 +/- 1.1
< 2.5 Zr-Nb-95
-0.4 +/- 0.6
< 1.8 Cs-134 0.0 +/- 0.6
< 1.1 Cs-137 0.7 +/- 0.7
< 1.4 Ba-La-140
-1.9 +/-0.7
< 4.4 Location S-8 S-9 S-10 S-11 Collection Date 08-10-16 08-10-16 08-10-16 08-10-16 Lab Code NF" NF" NF" NF" Be-7 Mn-54 Fe-59 Co-58
(
Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-1 S-3 S-7 S-8 Collection Date 09-08-16 09-08-16 09-08-16 09-08-16 Lab Code EW-4771 NF" NF" NF" Be-7
-10.4 +/- 9.6
< 17.1 Mn-54
-0.3 +/- 1.2
< 2.6 Fe-59 0.1 +/- 2.2
< 5.5 Co-58
-2.0 +/- 1.2
< 1.6 Co-60 0.7+/-1.2
< 2.4 Zn-65
-0.7 +/- 2.6
< 4.0 Zr-Nb-95
-0.4 +/- 1.2
< 2.5 Cs-134
-1.4+/-1.3
< 2.4 Cs-137 0.1 +/- 1.4
< 1.7 Ba-La-140
-0.6 +/- 1.3
< 7.7 a "NF" = No flow.
13-8
POINT BEACH NUCLEAR PLANT
(
Beach Drains (cont.)
Units: = pCi\\L Gamma isotopic analysis Location S-9 S-10 S-11 S-12 Collection Date 09-08-16 09-08-16*
09-08-16 09-08-16 Lab Code NF" MDC NF" MDC NF" MDC EW-4772 MDC Be-7
-4.5 +/- 10.3
< 29.4 Mn-54
-0.2 +/- 1.3
< 1.5 Fe-59
-0.8 +/- 2.7
< 7.0 Co-58 0.5 +/- 1.3
< 2.7 Co-60 0.5 +/- 1.2
< 2.0 Zn-65
-0.8 +/- 2.4
< 2.5 Zr-Nb-95
-0.9 +/- 1.5
< 3.7 Cs-134
-1.0+/-1.4
< 2.6 Cs-137 0.7 +/- 1.4
< 2.8 Ba-La-140
-5.5 +/- 1.4
< 7.2 Location S-1 S-3 S-7 S-8 Collection Date 10-06-16 10-06-16 10-06-16 10-06-16 Lab Code EW-5348 NF" NF" NF" Be-7
-0.4 +/- 10.5
< 25.5 Mn-54 0.4 +/- 1.4
< 1.9 Fe-59 2.2 +/- 2.0
< 4.2
{
Co-58
-0.2 +/- 1.3
< 1.7 Co-60
-0.1 +/- 1.1
< 1.3 Zn-65 2.6 +/- 2.9.
< 5.1 Zr-Nb-95 1.1 +/- 1.3
< 3.1 Cs-134 0.0 +/- 1.5
< 2.8 Cs-137 0.3 +/- 1.4
< 2.4 Ba-La-140
-1.4 +/- 1.8
< 6.0 Location S-9 S-10 S-11 S-12 Collection Date 10-06-16 10-06-16 10-06-16 10-06-16 Lab Code NF" NF" NF" NF" Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 13-9
POINT BEACH NUCLEAR PLANT
,FA
~
Beach Drains (cont.)
Units: = pCi\\L Gamma isotopic analysis Location S-1 S-3 S-7 S-8 Collection Date 11-10-16 11-10-16 11-10-16 11-10-16 Lab Code EW-6269 MDC NF" MDC NF 8
MDC NF" MDC Be-7 12.8 +/- 11.4
< 36.8 Mn-54 0.6 +/- 1.4
< 3.0 Fe-59
-1.3 +/- 2.6
< 4.6 Co-58
-0.9 +/- 1.4
< 2.1 Co-60
-0.3 +/- 1.4
< 1.8 Zn-65
-1.0+/-2.9
< 3.3 Zr-Nb-95 0.2 +/- 1.4
< 3.1 Cs-134
-0.1 +/- 1.2
< 2.3 Cs-137 1.0 +/- 1.5
< 2.5 Ba-La-140 2.6 +/- 1.6
< 7.7 Location S-9 S-10 S-11 S-12 Collection Date 11-10-16 11-10-16 11-10-16 11-10-16 Lab Code NF" NF" NF" NF" Be-7 Mn-54 Fe-59
(
Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location S-1 S-3 S-7 S-8 Collection Date 12-07-16 12-07-16 12-07-16 12-07-16 Lab Code EW-6746 NF" NF" NF" Be-7 6.7 +/- 4.6
< 12.0 Mn-54 0.0 +/- 0.6
< 1.0 Fe-59
-0.4 +/- 1.0
< 3.3 Co-58 0.5 +/- 0:5
< 1.0 Co-60 0.3 +/- 0.6
< 1.3 Zn-65 0.5 +/- 1.1
< 1.7 Zr-Nb-95
-0.1 +/- 0.6
< 1.3 Cs-134
-0.7 +/- 0.6
< 1.2 Cs-137 0.4 +/- 0.7
< 0.8*
Ba-La-140
-3.3 +/- 0.7
< 6.3 a "NF" = No flow.
(
13-10
(
(
Units: = pCi\\L Location Collection Date Lab Code Be-7 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Annual S-10 12-07-16 NFa All locations Mean +/- s.d.
Be-7 2.0 +/- 8.0 Mn-54 0.0 +/- 0.6 Fe-59
-0.4 +/- 1.1 POINT BEACH NUCLEAR PLANT Beach Drains (cont.)
S-11 12-07-16 NF" Mean +/- s.d.
Co-58 0.0 +/- 1.1 Co-60
-0.1 +/- 0.7 Zn-65 0.5 +/- 1A S-12 12-07-16 NF 8
Mean +/- s.d.
Zr/Nb-95 0.0 +/- 1.1 Cs-134
-0.2 +/- -0.8 Cs-137 0.2 +/- 1.0 13-11 Gamma isotopic analysis Mean +/- s.d.
Ba/La-140
-0.9 +/- 0.0
/!
I!
~
POINT BEACH NUCLEAR PLANT Table 13. Groundwater Tritium Monitoring Program (Quarterly Collections)
Units= Ci/L
~
Quarterly Wells Sample ID GW-05 (WH 6 Well)
GW-06 (SBCC Well)
Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-15-16 EWW-253 53 +/-73
< 141 01-15-16 EWW-254 15 +/- 71
< 141 04-12-16 EWW-1556 6 +/-74
< 148 04-12-16 EWW-1557
-106 +/- 91
< 158 a
07-14-16 EWW-3557 50 +/-80
< 147 07-14-16 EWW-3558
-1 +/- 77
< 147 10-12-16 EWW-5521
-21 +/- 74
< 151 10-12-16 EWW-5522
-62 +/- 71
< 151 Mean +/-s.d.
22 +/-36 Mean +/-s.d.
-38 +/-56 Sample ID GW-11 {MW-1)
GW-12 (MW-2)
Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-15-16 EWW-320 122 +/- 76
< 140 01-15-16 EWW-321 15 +/- 70
< 140 04-18-16 EWW-1899 93 +/-79
< 149 04-18-16 EWW-1900 1 +/- 74
< 149 07-20-16 EWW-3987 160 +/- 81
< 145 07-20-16 EWW-3988 58 +/- 75
< 145 10-20-16 EWW-5893 56 +/- 81
< 156 10-20-16 EWW-5894 6 +/- 78
< 156 Mean +/-s.d.
108 +/-44 Mean+/- s.d.
20 +/-26 Sample ID GW-13 (MW-6)
GW-14A (MW-05A)
Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-15-16 EWW-322 100 +/- 75
< 140 01-15-16 EWW-323 81+/-74
< 140
(
04-18-16 EWW-1901
-1 +/- 74
< 149 04-18-16 EWW-1902 103 +/- 79
< 149 07-20-16 EWW-3989 70 +/- 76
< 145 07-20-16 EWW-3990 236 +/- 85
< 145 10-20-16 EWW-5895 32 +/- 79
< 156 10-20-16 EWW-5896 21 +/- 79
< 156 Mean +/-s.d.
50 +/-44 Mean+/- s.d.
110 +/- 91 Sample ID GW-15A (MW-4)
GW-158 (MW-4)
Collection Collection Date Lab Code Tritium MDC Date Lab Code Tritium MDC 01-15-16 EWW-324 213 +/- 81
< 140 01-15-16 EWW-325 160 +/- 78
< 140 04-18-16 EWW-1903 143 +/- 86
< 149 04-18-16 EWW-1904 72 +/-78
< 149 07-20-16 EWW-3991 125 +/- 79
< 145 07-20-16 EWW-3992 167 +/- 81
< 145 10-20-16 EWW-5897 171 +/- 87
< 156 10-20-16 EWW-5898 67 +/- 81
< 156 Mean +/-s.d.
163 +/- 38 Mean +/-s.d.
116 +/-54 Sample ID GW-16 (MW-3)
Collection Date Lab Code Tritium MDC 01-15-16 EWW-327 201 +/- 80
< 140 04-18-16 EWW-1905 220 +/- 85
< 149 07-20-16 EWW-3993 181 +/- 82
< 145 10-20-16 EWW-5899 67 +/- 81
< 156 Mean +/-s.d.
167 +/-69 a corrected data; sample incorrectly identified as E-06 (LW) in April; resample EWW-2889 result= 4+/-74, <150 pCi/L.
(
1., -.
13-12
c r-Sample ID Collection Date 01-15-16 04-12-16 07-14-16 10-12-16 Mean+/- s.d.
Sam~Je ID Collection Date 01-22-16 04-19-16 05-02-16 07-16-16 10-15-16 Mean+/- s.d.
Sam~le ID Collection Date 01-22-16 04-19-16 05-02-16 07-16-16 10-15-16 Mean +/-s.d.
Sample JD Collection Date 05-05-16 POINT BEACH NUCLEAR PLANT Table 13. Groundwater Tritium Monitoring Program (Quarterly Collections)
Units= Ci/L Quarterly Wells (cont.)
GW-18 (WH 7 Well)
-1 +/- 70
< 141 EWW-1558 15 +/- 74
< 148 EWW-3559 41+/-79
< 147 EWW-5523 13 +/- 75
< 151 17+/-18 Fa~ade Wells GW-09 1Z-361A GW-091Z-361B MDC Collection Lab Code Tritium Date Lab Code Tritium EWW-334 242 +/- 82
< 140 01-22-16 EWW-335 146 +/- 78 EWW-2520 295 +/- 90
< 152 04-19-16 EWW-2521 153 +/- 83 EWW-2522 190 +/- 85
< 152 05-02-16 EWW-2523 45 +/-78 EWW-4018 138 +/- 80
< 150 07-16-16 EWW-4019 138 +/- 80 EWW-5889 211 +/- 87
< 156 10-15-16 EWW-5890 75 +/-79 215 +/-58 Mean+/- s.d.
112 +/- 48 GW-10 2Z-361A GW-10 2Z-3618 MDC Collection Lab Code Tritium Date Lab Code Tritium EWW-336 27 +/- 71
< 140 01-22-16 EWW-337
-25 +/- 72 EWW-2524
-11 +/- 75
< 152 04-20-16 EWW-2525 43 +/- 78 EWW-2526 10 +/- 76
< 152 07-16-16 EWW-4021 65 +/-76 EWW-4020 29 +/- 74
< 150 10-15-16 EWW-5892 47 +/- 78 EWW-5891
-50 +/- 72
< 156 1 +/-33 Mean +/-s.d.
32 +/-39 (Annual Collections)
Units= Ci/L Bogs GW-07 (North Bog)
GW-08 EiC Bog Collection Lab Code Tritium MDC Date Lab Code Tritium EWW-2197 120 +/- 81
< 149 05-05-16 EWW-2198 212 +/- 85 13-13 MDC
< 140
< 152
< 152
< 150
< 156 MDC
< 148
< 152
< 150
< 156 MDC
< 149
Table 13.
L Sample ID MH Z-065A Collection Lab Code Tritium Date 04-28-16 NS 8
10-28-16 NS 8
Mean +/-s.d.
Sample ID MH Z-065C Collection Lab Code Tritium Date 04-28-16 NSa 10-28-16 NS 8
Mean +/-s.d.
Sample ID MHZ-066A Collection Lab Code Tritium Date 04-29-16 EW-2350 234 +/- 83 10-28-16 EW-6383 227 +/- 94
(,_
Mean+/- s.d.
Sample ID MH Z-066C Collection Lab Code Tritium Date 04-28-16 EW-2353 222 +/- 82 10-28-16 EW-6385 166 +/- 92 Mean +/-s.d.
Sample ID MH Z-067A Collection Lab Code Tritium Date 04-29-16 EW-2355 226 +/- 83 10-28-16 EW-6388 246 +/- 95 Mean+/- s.d.
a "NS" = No sample; not sent.
(
POINT BEACH NUCLEAR PLANT Groundwater Tritium Monitoring Program Units = pCi/L Manholes MDC (pCi/L)
MDC (pCi/L)
MDC (pCi/L)
< 146
< 177 MDC (pCi/L)
< 146
< 177 MDC (pCi/L)
< 146
< 177 Collection Date 04-28-16 10-28-16 Mean+/- s.d.
Collection Date 04-28-16 10-28-16 Mean+/- s.d.
Collection Date 04-28-16 10-28-16 Mean+/- s.d.
Collection Date 04-28-16 10-28-16 Mean +/-s.d.
Collection Date 04-28-16 10-28-16 Mean+/- s.d.
13-14 Lab Code Lab Code Lab Code EW-2352 EW-6384 Lab Code EW-2354 EW-6387 Lab Code EW-2356 EW-6389 MH Z-0658 Tritium NSa NSa MH Z-065D Tritium NSa NS 8
MH Z-0668 Tritium 218 +/- 82 102 +/- 89 MH Z-066D Tritium 167 +/- 80 207 +/- 93 MH Z-0678 Tritium 230 +/- 83 180 +/- 92 MDC (pCi/L)
MDC (pCi/L)
MDC (pCi/L)
< 146
< 177 MDC (pCi/L)
< 146
< 177 MDC (pCi/L)
< 146
< 177
POINT BEACH NUCLEAR PLANT Manholes (cont.)
~ Samele ID MHZ-067C MH Z-067D Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-28-16 EW-2357 192 +/- 81
< 146 04-28-16 EW-2358 190 +/- 81
< 146 10-28-16 EW-6390 126 +/- 90
< 177 10-28-16 EW-6391 224 +/- 94
< 177 Mean+/- s.d.
Mean +/-s.d.
Sample ID MH Z-068 MH-1 Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-29-16 EW-2359 496 +/- 95
< 146 04-28-16 NS 8
10-28-16 EW-6392 187 +/- 93
< 177 10-28-16 NS 8
Mean+/- s.d.
Mean +/-s.d.
Sample ID MH-4 MH-6 Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-28-16 NS 8
04-28-16 NSa 10-28-16 NS 8
10-28-16 NS 8
(
Mean +/-s.d.
Mean+/- s.d.
Sample ID MH-7 MH-8 Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-28-16 NS 8
04-28-16 NSa 10-28-16 NS 8
10-28-16 NS 8
Mean+/- s.d.
Mean +/-s.d.
Sample ID MH-16 MH-2 Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-28-16 NS8 04-28-16 NS 8
10-28-16 NS 0
10-28-16 NS 8
Mean +/-s.d.
Mean+/- s.d.
Sample ID MH-5A MH-9 Collection Lab Code Tritium MDC Collection Lab Code Tritium MDC Date (pCi/L)
Date (pCi/L) 04-28-16 NS 8
04-28-16 NS 8
10-28-16 NS 8
10-28-16 NS 8
(
Mean +/-s.d.
Mean+/- s.d.
a "NS" = No sample; not sent.
13-15
POINT BEACH NUCLEAR PLANT Table 14. Radioactivity in vegetation samples Collection: Annual f '
\\,
Sample Description and Concentration (pCi/g wet)
MDC MDC MDC Location E-F1A E-F1B E-F2 Collection Date 09-15-16 09-15-16 09-15-16 Lab Code EVE-4861 EVE-4862 EVE-4863 Req. LLD Type Corn Corn Corn Ratio (wet/dry) 2.24 1.93 2.36 Gross Beta 2.82 +/- 0.06
< 0.021 2.82 +/- 0.06
< 0.018 2.61 +/- 0.05
< 0.017 0.25 Be-7 0.010 +/- 0.029
< 0.058
-0.006 +/- 0.024
< 0.065 0.039 +/- 0.029
< 0.064 K-40 2.15 +/- 0.15 1.77 +/- 0.14 2.00 +/- 0.17 1-131 0.015 +/- 0.003
< 0.031 0.002 +/- 0.003
< 0.030
-0.011 +/- 0.003
< 0.022 0.060 Cs-134
-0.003 +/- 0.003
< 0.006 0.001 +/- 0.002
< 0.005 0.000 +/- 0.003
< 0.006 0.060 Cs-137 0.002 +/- 0.003
< 0.005 0.001 +/- 0.003
< 0.005 0.000 +/- 0.003
< 0.004 0.080 Other (Co-60) 0.000 +/- 0.003
< 0.005 0.000 +/- 0.003
< 0.005 0.003 +/- 0.003
< 0.004 0.060 Location E-F3 E-F4 E-F5 Collection Date 09-15-16 09-15-16 09-15-16 Lab Code EVE-4864 EVE-4865 EVE-4866 Req. LLD Type Corn Corn Alfalfa Ratio (wet/dry) 2.27 1.75 6.37 Gross Beta 3.13 +/- 0.06
< 0.021 2.52 +/- 0.06
< 0.021 5.65 +/- 0.18
< 0.092 0.25 Be-7 0.018 +/- 0.017
< 0.043
-0.017 +/- 0.021
< 0.043 1.27 +/-0.15 c*
K-40 2.11 +/- 0.13 1.79 +/-0.14 6.02 +/- 0.41 1-131
-0.008 +/- 0.002
< 0.014
-0.002 +/- 0.003
< 0.023 0.015 +/- 0.006
< 0.033 0.060 Cs-134
-0.001 +/- 0.002
< 0.004 0.001 +/- 0.002
< 0.004 0.003 +/- 0.006
< 0.011 0.060 Cs-137 0.001 +/- 0.002
< 0.004 0.000 +/- 0.003
< 0.003 0.008 +/- 0.006
< 0.011 0.080 Other (Co-60) 0.001 +/- 0.002
< 0.004
-0.002 +/- 0.003
< 0.003 0.010 +/- 0.007
< 0.010 0.060 Location E-F6 E-F7 E-F8 Collection Date 09-15-16 09-15-16 09-15-16 Lab Code EVE-4867 EVE-4868 EVE-4870 Req. LLD Type Alfalfa Corn Corn Ratio (wet/dry) 7.38 2.40 1.76 Gross Beta 4.25 +/- 0.11
< 0.041 2.57 +/- 0.06
< 0.019 3.05 +/- 0.07
< 0.023 0.25 Be-7 1.17 +/- 0.17 0.066 +/- 0.029
< 0.061
-0.018 +/- 0.027
< 0.061 K-40 5.08 +/- 0.38 2.31 +/- 0.17 1.61+/-0.14 1-131
-0.005 +/- 0.006
< 0.030
-0.002 +/- 0.004
< 0.026
-0.010 +/- 0.003
< 0.023 0.060 Cs-134 0.000 +/- 0.007.
< 0.014 0.001 +/- 0.003
< 0.006
-0.015 +/- 0.003
< 0.006 0.060 Cs-137 0.002 +/- 0.007 *
< 0.012
-0.002 +/- 0.004
< 0.006 0.001 +/- 0.003
< 0.005 0.080 Other (Co-60) 0.000 +/- 0.008
< 0.012 0.001 +/- 0.003
< 0.005 0.002 +/- 0.003
< 0.005 0.060 14-1
POINT BEACH NUCLEAR PLANT Table 14. Radioactivity in vegetation samples Collection: Annual
(
Sample Description and Concentration (pCi/g wet)
MDC MDC Location E-F9 Collection Date 09-15-16 Lab Code EVE-4871 Type Corn Ratio (wet/dry) 1.87 Gross Beta 3.07 +/- 0.07
< 0.026 Be-7 0.007 +/- 0.026
< 0.062 K-40 1.77 +/- 0.14 1-131
-0.010 +/- 0.003
< 0.020 Cs-134 0.002 +/- 0.003
< 0.005 Cs-137 0.002 +/- 0.003
< 0.006 Other (Co-60) 0.002 +/- 0.003
< 0.004 Beta Annual Mean +/- s.d.
3.25 +/- 0.98 Be-7 Annual Mean +/- s.d.
0.25 +/- 0.51 K-40 Annual Mean +/- s.d.
2.66 +/- 1.55 1-131 Annual Mean+/- s.d. -0.001 +/- 0.010 Cs-134 Annual Mean+/- s.d. -0.001 +/- 0.005 Cs-137 Annual Mean+/- s.d. 0.002 +/- 0.003 Co-60 Annual Mean +/- s.d. 0.002 +/- 0.003
(
14-2 MDC Req. LLD 0.25 0.060 0.060 0.080 0.060
(-=---
All EnvironmentaHp Inc.
l"'\\I MuidlWest Laboratory 700 Landwehr Road* Northbrook, IL 60062-2310
-phone (847) 564-0700. fa)( (847) 564-4517 NOTE:
APPENDIX A INTERLABORATORY COMPARISON PROGRAM RESULTS Environmental Inc., Midwest Laboratory participates in intercomparison studies administered by Environmental Resources Associates, and serves as a replacement for studies conducted previously
,by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada. Results are reported in Appendix A. TLD lntercomparison results, in-house spikes, blanks, duplicates and mixed analyte performance evaluation program results are also reported. Appendix A is updated four times a year; the complete Appendix is included in March, June, September and December monthly progress reports only.
January, 2016 through December, 2016
c Appendix A lnterlaboratory-Gomparison Program Results Environmental, Inc., Midwest laboratory has participated in interlaboratory comparison (crosscheck) programs since the formulation of it's quality control program in December 1971. These programs are operated by agencies which supply environmental type samples containing concentrations of radfonuclides known to the issuing agency but not to participant laboratories. The purpose of such a program is to provide an independent check on a laboratory's analytical procedures and to alert it of any possible problems.
Participant laboratories measur~ the concentration of specified radionuclides and report them to the issuing agency. Several months later, the agency reports the known values to the participant laboratories and specifies control limits. Results consistently higher or lower than the known values or outside the control limits indicate a need to check the instruments or procedures used.
Results in Table A-1 were obtained through participation in the RAD PT Study Proficiency Testing Program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the U.S. EPA-Environmental Monitoring Systems Laboratory, Las Vegas, Nevada.
Table A-2 lists results for thermoluminescent dosimeters (TLDs), via irradiation and evaluation by the University of Wisconsin-Madison Radiation Calibration Laboratory at the University of Wisconsin Medical Radiation Research Center.
Table A-3 lists results of the analyses on in-house "spiked" samples for the past twelve months. All samples are prepared using NIST traceable sources. Data for previous years available upon request.
Table A-4 lists results of the analyses on in-house "blank" samples for the past twelve months. Data for previous years available upon request.
Table A-5 lists REMP specific analytical results from the in-house "duplicate" program for the past twelve months. Acceptance is based on the difference of the results being less than the sum of the errors..
Complete analytical data for duplicate analyses is available upon request.
The results in Table A-6 were obtained through participation in the Mixed Analyte Performance Evaluation Program.
Results in Table A-7 were obtained through participation in the MRAD PT Study Proficiency Testing Program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the Environmental Measurement Laboratory Quality Assessment Program (EML).
Attachment A lists the laboratory precision at the 1 sigma level for various analyses. The acceptance criteria in Table A-3 is set at +/- 2 sigma.
Out-of-limit results are explained directly below the result.
- A1
(
Attachment A ACCEPTANCE CRITERIA FOR "SPIKED" SAMPLES LABORATORY PRECISION: ONE STANDARD DEVIATION VALUES FOR VARIOUS ANALYSESa Analysis Gamma Emitters Strontium-89b Strontium-90b Potassium-40 Gross alpha Gross beta Tritium Radium-226,-228 Plutonium lodine-131, lodine-129b Uranium-238, Nickel-63b Technetium-99b lron-55b Other Analyses b Level 5 to 100 pCi/liter or kg
> 100 pCi/liter or kg 5 to 50 pCi/liter or kg
> 50 pCi/liter or kg 2 to 30 pCi/liter or kg
> 30 pCi/liter or kg
<!: 0.1 g/liter or kg
- 20 pCi/liter
> 20 pCi/liter
- 100 pCi/liter
> 100 pCi/liter
- 4,000 pCi/liter
> 4,000 pCi/liter
<!: 0.1 pCi/liter
<!: 0.1 pCi/liter, gram, or sample
- 55 pCi/liter
> 55 pCi/liter
- 35 pCi/liter
> 35 pCi/liter 50 to 100 pCi/liter
> 100 pCi/liter 8 From EPA publication, "Environmental Radioactivity Laboratory lntercomparison Studies Program", Fiscal Year, 19,81-1982, EPA-600/4-81-004.
b Laboratory limit.
A2 One standard deviation for single determination 5.0 pCi/liter 5% of known value 5.0 pCi/liter 10% of known value 5.0 pCi/liter 10% of known value 5% of known value 5.0 pCi/liter 25% of known value 5.0 pCi/liter 5% of known value
+/- 10" =
169.85 x {known)0*0933 10% of known value 15% of known value 10% of known value 6 pCi/liter 10% of known value 6 pCi/liter 15% of known value 1 O pCi/liter 10% of known value 20% of known v~lue
(
TABLE A-1. lnterlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.
RAD study Concentration (pCi/L)
Lab Code Date Analysis Laboratory ERA Control Result Result Limits Acceptance ERW-1392 4/4/2016 Sr-89 43.5 +/-4.3 48.2 37.8 -55.6 Pass ERW-1392 4/4/2016 Sr-90 27.5 +/- 1.9 28.5 20.7 -33.1 Pass ERW-1394b 4/4/2016 Ba-133 65.2 +/-3.8 58.8 48.7 - 64.9 Fail ERW-1394° 4/4/2016 Ba-133 57.8 +/-5.3 58.8 48.7 -64.9 Pass ERW-1394 4/4/2016 Cs-134 43.7 +/-3.0 43.3 34.6 -47.6 Pass ERW-1394 4/4/2016 Cs-137 86.1 +/-5.3 78.4 70.6 -88.9 Pass ERW-1394 4/4/2016 Co-60 108 +/- 44 102 91.8 -114 Pass ERW-1394 4/4/2016 Zn-65 240+/-13 214 193 -251 Pass ERW-1397 4/4/2016 Gr. Alpha 52.0 +/-2.2 62.7 32.9 -77.8 Pass ERW-1397 4/4/2016 Gr. Beta 33.9+/-1.2 39.2 26.0 -46.7 Pass ERW-1400 4/4/2016 1-131 24.7 +/-0.6 26.6 22.1 -31.3 Pass ERW-1402 4/4/2016 Ra-226 15.6 +/- 0.5 15.2 11.3 -17.4 Pass ERW-1402 4/4/2016 Ra-228 5.28 +/-0.76 5.19 3.12 -6.93 Pass ERW-1403 4/4/2016 Uranium 4.02 +/-0.42 4.64 3.39 -5.68 Pass ERW-1405 4/4/2016 H-3 8,150 +/- 270 7,840 6, 790 - 8,620 Pass SPW-2845 717/2015 Ba-133 60.3 +/-5.7 64.7 53.9 -71.2 Pass SPW-2845 717/2015 Cs-134 48.8 +/-9.3 50.1 40.3 -55.1 Pass
~
SPW-2845 71712015 Cs-137 101+/-8 89.8 80.8 -101 Pass c--
SPW-2845 717/2015 Co-60 65.1 +/-5.8 59.9 53.9 -68.4 Pass SPW-2845 717/2015 Zn-65 288 +/-29 265 238 -310 Pass ERW-3485 7/11/2016 Sr-89 43.3 +/-6.5 53.3 42.3 -60.9 Pass ERW-3485 7111/2016 Sr-90 39.0 +/-2.8 39.2 28.8 -45.1 Pass ERW-3487 7/11/2016 Ba-133 83.3 +/-4.9 82.9 69.7-91.2 Pass ERW-3487 7111/2016 Cs-134 62.5 +/-4.4 65.3 53.1 - 71.8 Pass ERW-3487 7/11/2016 Cs-137 98.1 +/- 5.6 95.2 85.7 -107 Pass ERW-3487 7111/2016 Co-60 122 +/-5 117 105 - 131 Pass ERW-3487 7/11/2016 Zn-65 124 +/-9 113 102 - 134 Pass ERW-3490 7111/2016 Gr.Alpha 46.6 +/-2.2 48.1 25.0 -60.5 Pass ERW-3490 7/11/2016 Gr. Beta 26.8+/-1.1 28.6 18.2 - 36.4 Pass ERW-3492 7/11/2016 1~131 23.7 +/- 1.0 24.9 20.7 -29.5 Pass ERW-3493 7/11/2016 Ra-226 12.9 +/- 0.4 12.3 9.2 -14.2 Pass ERW-3493 7/11/2016 Ra-228 5.8 +/-0.8 5.8 3.5 - 7.6 Pass
- ERW-3493 7111/2016 Uranium 32.B +/-0.B 25.2 28.4 -39.3 Pass ERW-3495 7111/2016 H-3 12,400 +/- 334 12,400 10,800 - 13,600 Pass
- Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resources Associates (ERA).
b No reason determineid for failure of Ba-133 result.
0 The result of reanalysis (Compare to original result, footnoted "b" above).
Al-1
(
TABLE A-2. Thermoluminescent Dosimetry, (TLD, CaS04: Dy Cards). ab mrem Lab Code Irradiation Delivered Reported Performance 0
Date Description Dose Dose Quotient (P)
Acceptance d Environmental. Inc.
Group 1 2016-1 1017/2016 Spike 1 135.0 148.3 0.10 2016-1 1017/2016 Spike 2 135.0 144.3 0.07 2016-1 1017/2016 Spike 3 135.0 133.2
-0.01 2016-1 1017/2016 Spike 4 135.0 139.6 0.03 2016-1 1017/2016 Spike 5 135.0 128.4
-0.05 2016-1 1017/2016 Spike 6 135.0
. 123.9
-0.08 2016-1 1017/2016 Spike 7 135.0 124.0
-0.08 2016-1 1017/2016 Spike 8 135.0 121.5
-0.10 2016-1 1017/2016 Spike 9 135.0 148.3 0.10 2016-1 1017/2016 Spike 10 135.0 126.8
-0.06 2016-1 1017/2016.
Spike 11 135.0 123.3
-0.09 2016-1 1017/2016 Spike 12 135.0 137.9 0.02 2016-1 1017/2016 Spike 13 135.0 126.0
-0.07 2016-1 1017/2016 Spike 14 135.0 127.2
-0.06 2016-1 1017/2016 Spike 15 135.0 144.5 0.07 2016-1 1017/2016 Spike 16 135.0 140.5 0.04 2016-1 1017/2016 Spike 17 135.0 146.0 0.08 2016-1 1017/2016 Spike 18 135.0 127.7
-0.05 2016-1 1017/2016 Spike 19 135.0 146.8 0.09
\\,
2016-1 1017/2016 Spike20 135.0
. 122.6
-0.09 2016-1 1017/2016 Spike 21 135.0 108.6
-0.20 2016-1 1017/2016 Spike22 135.0 119.6
-0.11 2016-1 1017/2016 Spike 23 135.0 135.1 0.00 2016-1 1017/2016 Spike 24 135.0 116.2
-0.14 2016-1 1017/2016 Spike25 135.0 118.9
-0.12 2016-1 1017/2016 Spike 26 135.0 128.5
-0.05 2016-1 1017/2016 Spike27 135.0 115.6
-0.14 2016-1 1017/2016 Spike 28 135.0
- 126.4
-0.06 2016-1 1017/2016 Spike 29 135.0 115.0
-0.15 2016-1 1017/2016 Spike 30 135.0 147.3 0;09 Mean (Spike 1-30) 130.4 0.03 Pass Standard Deviation (Spike 1-30) 11.5 0.09 Pass
- Table A~2 assumes 1 roentgen = 1 rem (NRC -Health Physics Questions and Answers 1 O CFR Part 20 - Question 96 - Page Last Reviewed/Updated Thursday, October 01, 2015).
b TLD's were irradiated by the University of Wisconsin-Madison Radiation Calibration Laboratory following ANSI N13.37 protocol from a known air kerma rate. TLD's were read and the results were submitted by Environmental Inc. to the University of Wisconsin-Madison Radiation Calibration Laboratory for comparison to the delivered dose.
0 Performance Quotient (P) is calculated as ((reported dose - conventially true value) + conventially true value) where the conventially true value is the delivered dose.
d Acceptance is achieved when neither the absolute value of mean of the P values, nor the standard deviation of the P values
(
exceed 0.15.
\\_
A2-1
.(
TABLE A-2 Thermoluminescent Dosimetry, (TLD, CaS04: Dy Cards): ab
- ~
mrem Lab Code
- Irradiation Delivered Reported Performance 0
Date Description Dose Dose Quotient (P)
Acceptan~ d Environmental, Inc.
Group 2 2016-2 1017/2016 Spike 31 87.0 83.0
-0.05 2016-2 1017/2016 Spike 32 87.0 88.3 0.01 2016-2 1017/2016 Spike 33 87.0 83.1
-0.04 2016-2 1017/2016 Spike 34 87.0 81.4
-0.06 2016-2 1017/2016 Spike 35 87.0 78.9
-0.09 2016-2 1017/2016 Spike36 87.0 80.3
-0.08 2016-2 1017/2016 Spike 37 87.0 101.1 0.16 2016-2 1017/2016 Spike 38 87.0 78.3
-0.10 2016-2 1017/2016 Spike 39 87.0 86.6 0.00 2016-2 1017/2016 Spike40 87.0 81.8
-0.06 2016-2 1017/2016 Spike 41 87.0 84.8
-0.03 2016-2 1017/2016 Spike42 87.0 79.9
-0.08 2016-2 1017/2016 Spike43 87.0 80.8
-0.07 2016-2 1017/2016 Spike44 87.0 80.2
-0.08 2016-2 1017/2016 Spike45 87.0 82.7
-0.05 2016-2 1017/2016 Spike46 87.0 104.0 0.20 2016-2 1017/2016 Spike47 87.0 86.1
-0.01 2016-2 1017/2016 Spike48 87.0 104.0 0.20
(
2016-2 1017/2016 Spike49 87.0 86.1
-0.01 2016-2 1017/2016 Spike 50 87.0 90.8 0.04 2016-2 1017/2016 Spike 51 87.0 85.7
-0.01 2016-2 1017/2016 Spike 52 87.0 86.5
-0.01 2016-2 1017/2016 Spike 53 87.0 86.4
-0.01 2016-2 101712016 Spike 54 87.0 92.6 0.06 2016-2 1017/2016 Spike 55 87.0 88.6 0.02 2016-2 1017/2016 Spike 56 87.0 78.9
-0.09 2016-2 1017/2016 Spike 57 87.0 82.6
-0.05 2016-2 1017/2016 Spike58 87.0 80.6
-0.07 2016-~
.1017/2016 Spike 59 87.0 89.9 0.03 2016-2 1017/2016 Spike 60 87.0 85.0
-0.02 Mean (Spike 31-60) 86.0 0.01 Pass Standard Deviation (Spike 31-60) 6.9 0.08 Pass
- Table A-2 assumes 1 roentgen = 1 rem (NRC -Health Physics Questions and Answers 1 O CFR Part 20 - Question 96 - Page Last Reviewed/Updated Thursday, October 01, 2015).
b TLD's were irradiated by the University of Wisconsin-Madison Radiation Calibration Laboratory following ANSI N13.37 protocol from a known air kerma rate. TLD's. were read and the results were submitted by Environmental Inc. to the University of Wisconsin-Madison Radiatiol'] Calibration Laboratory for comparison to the delivered dose.
- 0 Performance Quotient (P) is calculated as ((reported dose - conventially true value) + conventially true value) where the conventially true value is the delivered dose.
d Acceptance is achieved when neither the absolute value of mean of the P values, nor the standard deviation of the P values
(
exceed 0.15.
A2-2
(
\\**-..
TABLE A-3. In-House "Spiked" Samples
(..ab Code b SPW-290 SPW-292 SPW-294 SPW-414 W-020416 W-020416 W-021716 W-030716 W-030716 SPDW-70046 SPW-1163 SPW-1235 SPW-1235 SPW-1739 SPW-2052 W-042616 SPW-1823 SPW-1823 SPW-1998 SPW-1998 SPW-2097 SPW-2132 SPW-2229 SPW-2313 SPW-2341 SPW-2374 SPW-2411 SPW-2455 SPW-2455 SPW-2457 SPW-2504 SPW-2528 SPW-2566 SPW-2566 W-053116 W-053116 SPW-2704 SPW-2719 SPW-2749 SPW-2843 SPW-3227 W-061716 W-061716 SPW-3240 SPW-3240 Date 1/21/2016 1/21/2016 1/21/2016 2/1/2016 2/4/2016 2/4/2016 2117/2016 317/2016 317/2016 3/29/2016 3/22/2016 3/29/2016 3/29/2016 4/21/2016 4/21/2016 4/21/2016 4/23/2016 4/23/2016 4/29/2016 Analysis Sr-90 Sr-90 C-14 Ra-228 Gr. Alpha Gr. Beta Ra-226 Gr. Alpha Gr. Beta Ra-226 Ra-228 Gr.Alpha Gr. Beta Ra-228 Ra-226 Fe-55 Gr. Alpha Gr. Beta Cs-134 4/29/2016 Cs-137 5/3/2016 H-3 5/4/2016 H-3 5n/2016 H-3 5/13/2016 H-3 5/13/2016 H-3 5/14/2016 H-3 5/17/2016 Sr-90 5/19/2016 Gr. Alpha 5/19/2016 Gr. Beta 5/19/2016 U-238 5/20/2016 H-3 5/23/2016 H-3 5/24/2016 Gr. Alpha 5/24/2016 Gr. Beta 4/29/2016 Cs-134 4/29/2016
6/2/2016 Ra-228 6/3/2016 H-3 617/2016 H-3 6/17/2016 Ra-226 4/29/2016 Cs-134 4/29/2016 Cs-137 6/28/2016 Gr. Alpha 6/28/2016 Gr. Beta Concentration a Laboratory results 2s, n=1 ° 38.6+/-1.5 35.8+/-1.6 4,689 +/- 18 18.4 +/-2.2 20.8 +/-0.4 29.7 +/-0.3 17.9 +/-0.5 16.3 +/- 0.8 27.0 +/- 0.7 13.4 +/- 0.4 4.2 +/-0.7 21.0 +/- 0.4 29.4 +/- 0.3 16.2 +/- 2.0 16.0 +/- 0.5 1,519 +/- 61 21.0 +/- 0.4 26.6 +/-0.3 35.9 +/- 6.0 82.5 +/- 7.6 3,349+/-184 3,174 +/- 178 3,182 +/- 179 3,183 +/- 179 3,201 +/- 178 3,037 +/- 175 37.3 +/- 1.6 19.3 +/- 0.4 28.6 +/- 0.3 48.2 +/-2.4 3,181 +/- 178 2,998 +/- 175 19.8 +/- 0.5 30.4 +/- 0.3 34.0 +/-5.0 78.8 +/-7.0 38.0+/-1.6 18.1 +/-2.1 3,197+/-180 3,133+/-179 18.6 +/- 0.4 37.3 +/- 8.2 79.7+/-10.8 25.3 +/- 0.5 27.1 +/-0.3 A3-1 Known Activity 37.3 37.3 4,735 17.7 20.1 28.9 16.i 20.1 28.9 16.7 4.4 20.1 28.9 17.7 16.7 1,482 20.1 28.9 36.2 71.9 3,280 3,280 3,280 3,280 3,280 3,280 37.3 20.1 28.9 41.7 3,280 3,280 20.1 28.9 36.2 71.9 37.3 17.7 3,280 3,280 16.7 36.2 71.9 20.1 28.9 Control Limits d 22.4 - 52.2 22.4 - 52.2 2,841 - 6,629 10.6 -24.8 12.0 -28.1 17.3 -40.4 10.0 -23.4 12.0 - 28.1 17.3 -40.4 10.0 -23.4 2.6 -6.2 12.0 - 28.1 17.3 -40.4 10.6 - 24.8 10.0 -23.4 889 -2,075 12.0 - 28.1 17.3 -40.4 21.7 - 50.6 43.1 -100.6 1,968 - 4,592 1,968 - 4,592 1,968 - 4,592 1,968 - 4,592 1,968 - 4,592 1,968 - 4,592 22.4 '52.2 12.0 - 28.1 17.3 - 40.4 25.0 - 58.4 1,968 - 4,592 1,968 - 4,592 12.0 - 28.1 17.3 -40.4 21.7 - 50.6 43.1 -100.6 22.4 - 52.2 10.6 -24.8 1,968 - 4,592 1,968 - 4,592 10.0 - 23.4 21.7-50.6 43.1 -100.6 12.0 -28.1 17.3 -40.4 Acceptance Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
TABLE A-3. In-House "Spiked" Samples L
Concentration a Lab Code b Date Analysis Laboratory results Known Control 2s, n=1 c Activity Limitsd Acceptance SPW-3241 7/1/2016 H-3 8,821 +/- 283 8,650 5,190 -12,110 Pass SPW-3309 711/2016 H-3 8,619 +/- 278 8,650 5,190-12,110 Pass SPW-3313 7/1/2016 Ra-228 16.6 +/- 2.0 17.7 10.6 -24.8 Pass SPW-3328 71612016 Sr-89 13.4 +/- 9.2 14.8 8.9 -20.7 Pass SPW-3328 7/6/2016 Sr-90 12.3+/-1.3 11.4 6.8 -16.0 Pass SPAP-3365 71712016 Gr. Beta 39.7 +/- 0.1 42.2 25.3 -59.0 Pass SPAP-3367 71712016 Cs-134 1.2 +/- 0.7 1.2 0.7 -1.7 Pass SPAP-3367 71712016 Cs-137 94.4 +/-2.8 94.0 56.4 -131.6 Pass SPW-3370 71712016 C-14 4,444+/-17 4,735 2,841 - 6,629.
Pass SPW-3373 71712016 Ni-63 446 +/-5 401 241 -561 Pass SPW-3375 71712016 Tc-99 545 +/-9 539 324 - 755 Pass SPW-3519 7/14/2016 H-3 8,621 +/-279 8650 5,190 -12,110 Pass SPW-3688 6/29/2016 Ra-226 17.5 +/- 0.4 16.7 10.0 - 23.4 Pass SPW-3711 7/20/2016 H-3 44,368 +/-612 43,766 26,2.60 - 61,273 Pass SPW-3774 7/22/2016 H-3 45,259 +/- 619 43,766 26,260 - 61,273 Pass SPW-3776 7/22/2016 Gr. Alpha 23.3 +/- 0.5 20.1 12.0 -28.1 Pass SPW-3776 7/22/2016 Gr. Beta 27.5 +/- 0.3 28.9 17.3 -40.4 Pass SPW-3884 7/26/2016 H-3 45,850 +/-623 43,766 26,260 - 61,273 Pass SPW-3950 7/28/2016 Ra-228 17.8+/-1.8 16.7 10 -23 Pass SPW-3982 7/29/2016 H-3 45,273 +/- 619
.43,766 26,260 - 61,273 Pass W-073016 4/29/2016 Cs-134 36.5 +/- 6.1 36.2 21.7 -50.6 Pass
(
W-073016 4/29/2016 Cs-137 80.6 +/- 7.5 71.9 43.1 -100.6 Pass SPW-4134 8/4/2016 Ra-228 5.5 +/-0.8 6.7 4.0 - 9.3 Pass SPW-4340 8/17/2016 Ra-228 19.9 +/- 2.0 16.7 10.0 -23.4.
Pass SPW-4386 7/15/2016 Ra-226 18.0 +/- 0.4 16.7 10.0 - 23.4 Pass W-082716 4/29/2016 Ra-228 32.5 +/-5.2 36.2 21.7 - 50.6 Pass W-082716 4/29/2016 Ra-226 78.5 +/-8.3 71.9 43.1 -100.6 Pass SPW-4642 9/6/2016 U-238 45.8 +/-2.5 41.7 25.0 -58.4 Pass SPW-4999 9/26/2016 Sr-90 35.1 +/-2.2 36.8 22.1 - 51.5 Pass SPW-5091 9/12/2016 Ra-226 18.2 +/- 0.4 16.7 10.0 -23.4 Pass W-092716 4/29/2016 Cs-134 37.3+/-11.8 36.2 21.7 -50.6 Pass W-092716 4/29/2016 Cs-137 78.3+/-11.2 71.9 43.1 -100.6 Pass SPW-5165 9/30/2016.
Gr. Alpha 22.2 +/- 0.4 20.1 12.0 - 28.1 Pass SPW-5165 9/30/2016 Gr. Beta 27.2 +/- 0.3 28.9 17.3 - 40.4 Pass SPW-5426 9/28/2016 Ra-226 18.2 +/- 0.4 16.7 10.0 -23.4 Pass SPW-5510 10/18/2016 H-3 44,398 +/-618 43,766 26,260 - 61273 Pass SPW-5553 10/19/2016 U-238 50.0 +/-2.6 41.7 25.0 -58.4 Pass SPW-5555 10/19/2016 Ra-228 17.4+/-1.9 16.7 10.0 -23.4 Pass SPW-5612 10/20/2016 H-3 44,681 +/-622 43,766 26,260 - 61,273 Pass SPW-5741 10/25/2016 H-3 44,946 +/-624 43,766 26,260 - 61,273 Pass SPU-5833 10/26/2016 H-3 10,018 +/- 946 8,622
. 5,173 -12,071 Pass SPW-5862 10/28/2016 H-3 18,061 +/- 374 17,2'.44 10,346 -24,141 Pass W-103116 4/29/2016 Cs-134 36.0 +/-4.6 36.2 21.7 -50.6 Pass W-103116 4/29/2016 Cs-137 81.1 +/- 7.3 71.9 43.1 -100.6 Pass
(
A3-2
~.:-'
f'
/ c::::::::...
\\
~
(
TABLEA-3. In-House "Spiked" Samples Concentration a Lab Code b.
Date Analysis Laboratory results Known Control 2s, n=1 c Activity Limits d Acceptance SPW-5984 11/2/2016 H-3 17,727 +/-399 17,244 10,346 -24, 141 Pass SPW-6008 11/4/2016 H-3 17,854 +/-402 17,244 10,346 -24,141 Pass SPW-6124 11/8/2016 Ra-228 14.4+/-1.9 16.0 9.6 -22.4 Pass SPW-6132 11/9/2016 H-3 18,135 +/-374 17,243 10,346 -24,140 Pass SPW-6135 10/12/2016 Ra-226 18.9 +/- 0.4 16.7 10.0 -23.4 Pass SPW-6146 11/10/2016 H-3 17,488 +/-398 17,243 10,346 -24,140 Pass SPW-6222 11/12/2016 H-3 17,787 +/-408 17,243 10,346 -24,140 Pass SPW-6318 11/16/2016 H-3 17,379 +/-408 17,243 10,346 - 24, 140 Pass SPW-6349 11117/2016 H-3 17,893 +/- 371 17,243 10,346 -24,140 Pass SPW-6424 11/19/2016 H-3 18,258 +/-379 17,243 10,346 - 24, 140 Pass W-112616 4/29/2016 Cs-134 35.0 +/-6.0 36.2 21.7 - 50.6 Pass W-112616 4/29/2016 Cs-137 75.0 +/-7.1 71.9 43.1 -100.6 Pass SPW-6456 11/28/2016 Sr-90 41.9 +/-2.5 36.8 22.1 - 51.5 Pass SPW-6486 11/30/2016 Sr-90 35.6 +/-2.2 36.6 21.9 - 51.2 Pass SPW-6490 11/29/2016 Ra-226 18.8 +/- 0.4 16.7 10.0 -23.4 Pass SPW-6519 11/30/2016 Ni-63 438 +/-4 400 240 -560 Pass SPW-6527 12/1/2016 U-238 49.5 +/-2.5 41.7 25.0 - 58.4 Pass SPW-6616 12/3/2016 H-3 18,018 +/-374 17,243 10,346 - 24, 140 Pass SPW-6669 12/5/2016 H-3 18,237 +/-377 17,243 10,346 - 24,140 Pass SPW-6735 12/9/2016 H-3
. 17,939 +/- 396 17,243 10,346 -24,140 Pass SPW-6880 12/21/2016 H-3 17,835 +/- 396 17,243 10,346 -24,140 Pass SPW-6947 12/22/2016 Ni-63 450 +/-4 400 240 - 560 Pass W-122316 4/29/2016 Cs-134 36.0 +/-2.2 36.2 21.7 -50.6 Pass W-122316 4/29/2016 Cs-134 76.1 +/- 2.9 71.9 43.1 -100.6 Pass SPW-6948 12/30/2016 H-3 17,999 +/-398 17,243 10,346 - 24, 140 Pass SPW-6974 12/29/2016 Ra-226 17.6 +/- 0.4 16.7 10.0 -23.4 Pass a Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3), charcoal (pCi/charcoal canister), and solid samples (pCi/kg).
b Laboratory codes : W (Water), Ml (milk), AP (air filter), SO (soil), VE (vegetation), CH (charcoal canister), F (fish), U (urine).
c Results are based on single determinations.
d Control limits are established from the precision values listed in Attachment A of this report, adjusted to +/- 2s.
NOTE: For fish, gelatin is used for the spike matrix. For vegetation, cabbage is used for the spike matrix.
A3-3
(
~-
(
'1<..__
(
TABLE A-4. In-House "Blank" Samples Concentration a Lab Code Sample Date Analysisb Laboratory results (4.6Scr)
Acceptance Type LLD Aclivity 0
Criteria (4.66 cr)
SPW-289 Water 1/21/2016 Sr-90 0.55 0.28 :1:0.29 SPW-291 Water 1/21/2016 Sr-90 0.61 0.15:1:0.30 SPW-293 Water 1/21/2016 C-14 147
-12 :I: 89 SPW-413 Water 2/1/2016 Ra-228 0.86 1.86 :I: 0.60 W-020416 Water 214/2016 Gr.Alpha 0.43
-0.17 :I: 0.28 W-020416 Water 2/4/2016 Gr. Beta 0.73 0.36 :1:0.53 W-020916 Water 2/9/2016 Ra-226 0.02 0.01 :I: 0.01 W-030716 Water 317/2016 Gr.Alpha 0.90
-0.36 :I: 0.32 W-030716 Water 317/2016 Gr. Beta 1.59
-0.62 :I: 0.71 SPDW-70045 Water 3/29/2016 Ra-226 0.03 0.01 :I: 0.02 SPDW-1234 Water 3/30/2016 Gr.Alpha 0.44
-0.05 :I: 0.30 SPDW-1234 Water 3/30/2016 Gr. Beta 0.79
-0.54 :I: 0.54 SPW-1738 Water 4/21/2016 Ra-228 1.05 0.13 :1:0.so SPW-1822 Water 4/23/2016 Gr. Alpha 0.50
-0.18 :I: 0.33 SPW-1822 Water 4/23/201°6 Gr. Beta 0.08
-0.35 :I: 0.51 SPW-2051 Water 4/1.2/2016 Ra-226 0.02 0.03 :1:0.02 SPW-2069 Water 5/3/2016 1-131 0.15 0.06 :1:0.09 SPW-2133 Water 5/4/2016 H-3 148 55 :1:76 SPW-2230 Water 517/2016 H-3 149
-11 :I: 73 SPW-2314 Water 5/13/2016 H-3 150
-29 :1:72 SPW-2342 Water 5/13/2016 H-3 143 50 :1:74 SPW-2364 Water 5/13/2016 1-131 0.22
-0.03 :1:*0.12 SPW-2375 Water 5/14/2016 H-3 146 1 :I: 70 SPW-2410 Water 5/17/2016 Sr-90 0.59 0.10 :1:0.29 SPW-2454 Water 5/19/2016 Gr.Alpha 0.47
-0.21 :I: 0.31 SPW-2454 Water 5/19/2016 Gr. Beta 0.77
-0.49 :I: 0.52 SPW-2456 Water 5/19/2016 U-238 0.15 0.00 :I: 0.09 SPW-2485 Water 5/20/2016 1-131 0.18
-0.01 :I: 0.10 SPW-2505 Water 5/20/2016 H-3 144 64 :1:75 SPW-2529 Water 5/23/2016 H-3 152
-3 :1:75 SPW-2530 Water 5/23/2016 Ra-228 0.96
-0.12 :I: 0.43 SPW-2565 Water 5/24/2016 Gr. Alpha 0.47 0.03 :I: 0.33 SPW-2565 Water 5/24/2016 Gr. Beta 0.77
-0.23 :I: 0.53 SPW-2703 Water 6/1/2016 Sr-89 0.68
-0.13:1:0.50 SPW-2703 Water 6/1/2016 Sr-90 0.55 0.11 :I: 0.27 SPW-2718 Water 6/2/2016 Ra-228 0.67 0.23 :1:0.34 SPW-2720 Water 6/2/2016 1-131 0.16 0,01 :I: 0.09 SPW-2750 Water 6/3/2016 H-3 151
-31 :I: 73 SPW-2844 Water 617/2016 H-3 148
-55 :I: 75
- sPMl-2959 Milk 6/14/2016 1-131 0.16 0.09 :I: 0.10 SPW-3137 Water 6/23/2016 1-131 0.15
-0.03 :I: 0.08 SPW-3226 Water 6/17/2016 Ra-226 0.02
-0.01 :I: 0.04 SPW-3239 Water 6/28/2016 Gr. Alplia 0.40
-0.15 :I: 0.26 SPW-3239 Water 6/28/2016 Gr. Beta 0.73 0.14 :I: 0.52 SPW-3687 Water 6/29/2016 Ra-226 0.04 0.03 :I: 0.03
- Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3). charcoal (pCi/charcoal canister). and solid samples (pCi/g).
0 l-131(G); iodine-131 as analyzed by gamma spectroscopy.
0 Activity reported is a net activity result.
A4-1 200 2
2 4
2 2
4 2
2 4
2 2
4 2
200 200 200 200 1
200 1
2 4
200 200 2
2 4
5 1
2 200 200 1
2 2
4 2
(
- ~.-
(
TABLE A-4. In-House "Blank" Samples Lab Code SPW-3312 SPW-3327 SPW-3327 SPAP-3364 SPW-3370 SPW-3372 SPW-3374 SPW-3710 SPW-3775 SPW-3775 SPW-3884 SPW-3949 SPW-3982 SPW-4133 SPW-4257 SPW-4339 SPW-4385 SPW-4641 SPW-4684 SPW-4872 SPW-4998 SPW-4998 SPW-5090 SPW-5164 SPW-5164 SPW-5425 Sample Type Water Water Water AP Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water Water SPW-5323 Water SPW-5552 Water SPW-5554 Water SPW-5611 Water SPW-5613 Water SPW-5613 Water SPW-5740 Water SPW-5743 Water SPW-5861 Water SPW-5983 Water SPW-6007 Water SPW-6131 Water SPW-6134 Water SPW-6145 Water SPW-6317 Water SPW-6348 Water SPW-6423 Water SPW-6455 Water SPW-6455 Water SPW-6489 Water Date 7/1/2016 7/6/2016 7/6/2016 717/2016 717/2016
- 717/2016 717/2016 7/20/2016 7/22/2016 7/2,2/2016 7/26/2016 7/28/2016 7/29/2016 8/4/2016 8/11/2016 8117/2016 7/15/2016 9/6/2016 9/8/2016 9/16/2016 9/26/2016 9/26/2016 8/19/2016 9/30/2016 9/30/2016 9/28/2016 1017/2016 10/19/2016 10/19/2016 10/20/2016 10/21/2016 10/21/2016 10/25/2016 10/25/2016 10/28/2016 11/2/2016 11/4/2016 11/9/2016 10/12/2016 11/10/2016 11/16/2016 11/17/2016 11/19/2016 11/28/2016 11/28/2016 11/29/2016 Analysisb Ra-228 Sr-89 Sr-90 Gr.Beta C-14 Ni-63 Tc-99 H-3 Gr. Alpha Gr. Beta H-3 Ra-228 H-3 Ra-228 1-131 Ra-228 Ra-226 U-238 H-3 1-131 Sr-89 Sr-90 Ra-226 Gr. Alpha Gr. Beta Ra-226 H-3 U-238 Ra-228 H-3 Gr. Alpha Gr. Beta H-3 Sr-90 H-3 H-3 H-3 H-3 Ra-226 H-3 H-3 H-3 H-3 Sr-89 Sr-90 Ra-226 Concentration a Laboratory results (4.66cr)
LLD Activity 0
0.67 0.67 0.60 0.002 115 122 6.07 147 0.73 0.45 151 0.76 145 0.80 0.17 0.73 0.09 0.21 151 0.21 0.54 0.53 0.03 0.46 0.74 0.02 157 0.18 0.72 153 0.76 0.42 154 1.26 179 156 156 180 0.05 171 180 182 181 0.58 0.67
.0.03 0.35 +/- 0.35 0.51 +/- 0.51
-0.14 +/- 0.26 0.005 +/- 0.001 49 +/- 71 115 +/- 76 1.00 +/- 3.70 35 +/-75 0.41 +/- 0.53
-0.14 +/- 0.30
-1+/-73 0.32 +/- 0.39 49 +/- 75 0.26 +/- 0.40
-0.01 +/- 0.10 0.36 +/- 0.39 0.75 +/- 0.09 o.oo +/- 0.13 48 +/-78 0.05 +/-' 0.11 0.06 +/- 0.39
-0.03 +/- 0.24 0.03 +/- 0.02
-0.05 +/- 0.32
-0.02 +/- 0.52 0.07 +/- 0.05
-12 +/- 75 0.00 +/-0.11 0.22 +/- 0.36 67 +/-.80
-0.55 +/- 0.51 0.02 +/- 0.29
-2 +/-72 0.72 +/- 0.67 129 +/- 91 8 +/- 78
-34 +/- 73 80 +/- 92
-0.02 +/- 0.12
-46 +/- 80
-43 +/- 82
-45 +/- 88 8 +/- 95
-0.15 +/- 0.46 0.09 +/- 0.32 0.03 +/- 0.02 Acceptance Criteria (4.66 cr) 2 5
0.01 200 200 10 200 2
4 200 2
200 2
2 2
200 1
5 2
2 4
2 200 1
2 200 2
4 200 200 200 200 200 2
200 200 200 200 5
1 2
- Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3), charcoal (pCi/charcoal canister), and solid samples (pCi/g).
b l-131(G); iodine-131 as analyzed by gamma spectroscopy.
c Activity reported is a net activity result.
A4-2
(
(
TABLE A-4. In-House "Blank" Samples Concentration a Lab Code Sample Date Analysisb
- Laboratory results (4.66cr)
Acceptance Type LLD Aclivity 0
Criteria "(4.66 cr)
SPW-6529 Water 12/1/2016 1-131 0.18
-0.03 +/- 0.10 1
SPW-6616 Water 12/3/2016 H-3 180 72 +/-92 200 SPW-6670 Water 12/5/2016 H-3 174 28 +/-92 200 SPW-6735 Water 12/9/2016 H-3 152 2 +/-73 200 SPW-6792 Water 12/15/2016 1-131 0.17 0.03 +/- 0.12 1
SPW-6819 Water 12/16/2016 H-3 158 14 +/-77 200 SPW-6879 Water
. 12/21/2016 H-3 147 80 +/-75 200 SPW-6947 Water 12/22/2016 Ni-63 93 26 +/-57 200 SPW-6973 Water 12/29/2016 Ra-226 0.03 0.03 +/- 0.02 2
- Liquid sample results are reported in pCi/Liter, air filters ( pCi!m3>, charcoal (pCi/charcoal canisterj, and solid samples (pCi/g).
b l-131(G); iodine-131 as analyzed by gamma spectroscopy.
0 Activity reported is a net activity result.
A4-3
(
(
\\.,
TABLE A-5. In-House "Duplicate" Samples Lab Code AP-010416 SPS-62, 63 WW-125, 126 SPS-199, 200 SPS-199, 200 AP-011116 AP-011216 WW-262,263 WW-346, 347 WW-283,284 AP-011916 AP-012016 AP-020116 SWU-472, 473 SG-493,494 SG-493, 494 SG-493, 494 AP-020816 AP-020916 SPS-619, 620 WW-640, 641 Date 1/4/2016 117/2016 117/2016 117/2016 117/2016 1/n/2016 1/12/2016 1/14/2016 1/14/2016 1/18/2016 1/19/2016 1/20/2016 211/2016 21212016 216/2016 216/2016 2/6/2016 218/2016 219/2016 2118/2016 2118/2016 Analysis Gr. Beta K-40 H-3 Cs-137 K-40 Gr. Beta Gr. Beta H-3 H-3 H-3 Gr. Beta Gr. Beta Gr. Beta Gr. Beta Ac-228 K-40 Pb-214 Gr. Beta Be-7 K-40 H-3
- AP-021916 2119/2016 Gr. Beta WW-822, 823 2126/2016 H-3 DW-70010, 70011 2129/2016.
Ra-226 DW-70010, 70011 2129/2016 Ra-228 SW-934, 935 SPS-913, 914 SPS-913, 914 SPS-913, 914 SPS-913, 914 AP-030716 F-1303,1304 SG-976, 977 SG-976, 977 PM-1094, 1095 Ml-1042, 1043 3/1/201.6 3/3/2016 3/3/2016 3/3/2016 3/3/2016 317/2016 317/2016 3/8/2016 3/8/2016 3/9/2016 317/2016 DW-70023, 70024 317/2016 DW-70023, 70024 317/2016 DW-70014, 70015 317/2016 DW-70026, 70027 317/2016 DW-70038, 70039 3/8/2016 DW-70035, 70036 3/8/2016 DW-70035, 70036 3/8/2016 AP-031516 AP-032116 AP-1218,1219 AP-1719,1720 AP-033016 SPS-1260, 1261 XW-1467, 1468 XWW-1530, 1531 AP-1827, 1828 AP-1323,1324 LW-1446, 1447 3/15/2016 3/21/2016 3/24/2016 3/28/2016 3/30/2016 3/30/2016 3/30/2016 3/30/2016 3/30/2016 3/31/2016 3/31/2016 Gr. Beta Cs-137 K-40 Ra-226 Ra-228 Gr. Beta K-40 Ra-226 Ra-228 K-40 K-40 Ra-226 Ra-228 Gr. Alpha Gr. Alpha Gr. Alpha Ra-226 Ra-228 Gr. Beta Gr. Beta Be-7 Be-7 Gr. Beta K-40 H-3 H-3 Be-7 Be-7 Gr. Beta First Result 0.044 +/- 0.006 21.1 +/- 1.9 659 +/- 102 0.09 +/- 0.02 7.60 +/- 0.60 0.024 +/- 0.005 0.030 +/- 0.004 153 +/- 78 1,036 +/- 117 437 +/- 92 0.042 +/- 0.005 0.023 +/- 0.003 0.023 +/- 0.005 4.37 +/- b.47 2.10 +/-0.20 5.79 +/- 0.57 1.84 +/- 0.11 0.020 +/- 0.004 0.032 +/- 0.005 20.0 +/- 1.8 90.1 +/- 75.0 0.021 +/- 0.003 2,770 +/- 173 4.88 +/- 0.29 3.00 +/- 0.77 0.94 +/- 0.52 0.08 +/- 0.03 17.45 +/- 0.94 1.02 +/- 0.08 1.09 +/- 0.15 O.D18 +/- 0.005 3.320 +/- 0.475 6.75 +/- 0.25 9.21 +/- 0.49 14.01 +/- 0.68 1,684 +/- 124 3.40 +/- 0.43 4.46 +/- 0.83 13.38+/-1.58 3.46 +/- 0.79 1.14+/-0.89 0.47 +/- 0.10 0.56 +/- 0.45 0.014 +/- 0.003 0.014 +/- 0.004 0.135 +/- 0.065 0.075 +/- 0.008 0.023 +/- 0.004 18.00+/-1.92 310 +/- 87 198 +/- 84 0.069 +/- 0.011 0.206 +/- 0.120 2.36 +/- 0.93 AS-1 Concentration a Second Result 0.051 +/- 0.006 21.2 +/- 2.1 748 +/- 106 0.08 +/-0.03 8.62 +/- 0.62 0.027 +/- 0.005 0.034 +/- 0.004 141 +/- 78 959+/-115 427 +/- 91 0.037 +/- 0.004 0.030 +/- 0.004 0.023 +/- 0.005 4.60 +/- 0.49 2.13 +/- 0.20 5.50 +/- 0.69 1.91 +/- 0.11 0.019 +/- 0.004 0.041 +/- 0.006 19.1 +/- 1.6 153.6 +/- 78.4 0.025 +/- 0.004 2,974+/-178 4.93 +/- 0.28 1.90 +/- 0.62 1.36 +/- 0.60 0.10 +/- 0.03.
16.83 +/- 0.95 1.13+/-0.17 1.13 +/-0.17 0.021 +/- 0.005 3.508 +/- 0.396 6.28 +/- 0.22 9.09 +/- 0.49 14.47 +/- 0.72 1,804+/-119 2.68 +/- 0.35 5.74 +/- 0.94 11.40 +/- 1.43 3.08 +/- 0.74 1.73 +/- 0.95 0.45 +/- 0.09 0.47 +/- 0.44 0.016 +/- 0.004 0.020 +/- 0.004 0.167 +/- 0.081 0.076 +/- 0.007 0.025 +/- 0.004 19.67+/-1.77 295 +/- 66 162 +/- 62 0.072 +/- 0.011 0.197 +/- 0.091 2.23+/-1.01 Averaged Result 0.047 +/- 0.004 21.2+/-1.4 703 +/- 74 0.08 +/- 0.02 8.11 +/- 0.43 0.026 +/- 0.003 0.032 +/- 0.003 147 +/- 55 997 +/- 82 432 +/- 65 0.040 +/- 0.003 0.027 +/- 0.002 0.023 +/- 0.004 4.49 +/- 0.34 2.12+/-0.14 5.65 +/- 0.45 1.86 +/- 0.06 0.020 +/- 0.003 0.036 +/- 0.004 19.5+/-1.2 121.6 +/- 54.2 0.023 +/- 0.002 2,672+/-124 4.91 +/- 0.20 2.45 +/- 0.49 1.15 +/- 0.40 0.09 +/- 0.02.
17.14 +/- 0.67 1.07 +/- 0.09 1.11+/-0.11 0.019 +/- 0.003 3.414 +/- 0.309 6.52 +/- 0.17 9.15 +/- 0.35 14.24 +/- 0.49 1,744 +/- 86 3.04 +/- 0.26 5.10 +/- 0.63 12.39 +/- 1.07 3.27 +/- 0.54 1.44 +/- 0.65 0.46 +/- 0.07 0.52 +/- 0.31 0.015 +/- 0.002 0.017 +/- 0.003 0.151 +/- 0.052 0.076 +/- 0.005 0.024 +/- 0.003 16.84+/-1.30 303 +/- 61 180 +/- 59 0.071 +/- 0.008 0.202 +/- 0.076 2.29 +/- 0.69 Acceptance Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass*
Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
- Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
(
,-*~*-
\\_
(
TABLE A-5. In-House "Duplicate" Samples Lab Code WW-1740, 1741 SPS-1344, 1345 SPS-1344, 1345 SPS-1344, 1345 SPS-1344, 1345 P-1509,1510 AP-041116 SS-1551, 1552 SS-1551, 1552 SS-1551,1552 SS-1551,1552 SS-1551, 1552 SS-1551, 1552 SS-1551, 1552 SS-1593, 1594 WW-1677, 1678 WW-1783,1784 BS-1804, 1805 WW-2021,2022 XWW-2240, 2241 XWW-2109, 2110 SPS-2130, 2131 AP-042516 BS-2065, 2066 AP-042716 SPS-1999, 2000 S0-2153,2154 S0-2153,2154 S0-2153,2154 S0-2153,2154 W-2394,2395 VE-2284,2285 AP-051016 SG-2261, 2262 SG-2261, 2262 BS-2439, 2440 WW-2534,2535 AP-051716 SPS-2945, 2946 SPS-2945, 2946 SPS-2578, 2579 AP-052516 G-2642,2643 S0-2663, 2664 S0-2663, 2664 S0-2663, 2664 S0-2663, 2664 S0-2663, 2664 S0-2663, 2664 SPS-2817, 2818 Date 4/2/2016 4/4/2016 4/4/2016 4/4/2016 4/4/2016 4/8/2016 4/11/2016 4/12/2016 4/12/2016 4/12/2016 4/12/2016 4/12/2016 4/12/2016 4/12/2016 4/12/2016 4/14/2016 4/14/20.16 4/18/2016 4/18/2016 4/18/2016 4/19/2016 4/25/2016 4/25/2016 4/25/2016 4/27/2016 4/28/2016 5/2/2016 5/2/2016 5/2/2016 5/2/2016 5/5/2016 5/9/2016 5/10/2016 5/10/2016 5/10/2016
. 5/12/2016 5/16/2016 5/17/2016 5/19/2016 5/19/2016 5/24/2016 5/25/2016 5/26/2016 5/26/2016 5/26/2016 5/26/2016 5/26/2016 5/26/2016 5/26/2016 5/~1/2016 DW-70091, 70092 6/1/2016 DW-70091, 70092 6/1/2016 BS-2925,2926 SPS~2796, 2797 SPS-2882, 2883 SPS-2882, 2883 6/3/2016 6/2/2016 617/2016 617/2016 DW-70102, 70103 6/13/2016 Analysis H-3 K-40 Pb-214 Ao-228 Cs-137 H-3 Gr. Beta Gr. Beta K-40 Tl-208 Bi-214 Pb-212 Ra-226 Ac-228 K-40 Ra-226 H-3 K-40 H-3 H-3 H-3 K-40 Gr. Beta K-40 Gr. Beta K-40 K-40 Cs-137 Ra-226 Pb-214 H-3 K-40 Gr. Beta Ac-228 Pb-214 K-40 H-3 Gr. Beta K-40 Be-7 Pb-214 Gr. Beta Be-7 Cs-137 K-40 Tl-208 Pb-212 Ra-226 Ac-228 K-40 Ra-226 Ra-228 K-40 K-40 K-40 Be-7 Ra-226 First Result 21,162 :I: 120 17.98 :I: 0.93 1.12 :1:0.09 1.23 :1:0.15 0.13 :I: 0,03 1,084 :I: 120 0.020 :I: 0.004 8.71 :I: 1.11 3.50 :I: 0.25 0.05 :I: 0.02 0.10 :I: 0.02 0.13 :I: 0.02 0.35 :I: 0.17 0.16 :I: 0.05 14.80 :I: 0.73 0.23 :1:0.13 768:I:111 0.79 :I: 0.02 5,548 :I: 221 638 :1:104 3461 :I: 185 7.80 :I: 0.84 0.020 :I: 0.004 14.40 :I: 1.50 0.023 :I: 0.003 19:84 :1:1.76 21.80 :I: 0.81 0.11 :I: 0.03 1.50 :I: 0.29 0.56 :I: 0.06 736 :I: 106
- 3.50 :I: 0.25 0.020 :I: 0.005 34.4:I:1.2 29.5 :I: 3.0 9.96 :I: 0.91 14,342 :I: 354 0.014 :I: 0.004 30.71 :I: 0.74 1.55 :I: 0.24 0.96 :I: 0.12 0.022 :I: 0.004 0.443 :I: 0.178 0.08 :I: 0.03 12.44 :I: 0.68 0.13 :I: 0.02 0.43 :I: 0.04 1.19 :1:0.34 0.45 :I: 0.09 12.10 :I: 0.70 5.61 :I: 0.29 1.45 :I: 0.58 7.74 +/-0.44 20.91 :I: 2.38 14.64 :I: 0.52 2.00 :I: 0.25 0.34 :I: 0.09 AS-i Concentration a Second Result 21,091 :I: 427 17.14 :I: 0.96 1.04 :I: 0.08 1.33 :I: 0.19 0.13+/-0.03 1,038+/-119 0.019 :I: 0.004 8.88:I:1.13 3.06 :I: 0.28 0.05 :1:0.02 0.09 :I: 0.02 0.11 :I: 0.02 0.30 :I: 0.17 0.17 :I: 0.05 14.89 :I: 0.78 0.35 :I: 0.15 632 :I: 107 0.87 :I: 0.19 5,707 :1:224 543 :I: 101 3250+/-180 6.80 :I: 0.60 0.023 :I: 0.004 14.72 :I: 1.19 0.019 :I: 0.003 18.963 :I: 2.42 21.17 :I: 0.85 0.11:1:0.07 1.22 :I: 0.29 0.57 :1: 0.06 631 :I: 102 3.06 :I: 0.28 0.018 :I: 0.005 34.4 :I: 1.4 31.9 :I: 3.3 10.27 :I: 0.76 14,613 :I: 357 0.015 :I: 0.004 31.75 :I: 0.78 1.90 :I: 0.35 0.80 :I: 0.14 0.022 :I: 0.004 0.247 :I: 0.247 0.07 :I: 0.03 11.64 :I: 0.63 0.14 :I: 0.03 0.41 :I: 0.04 0.87 :I: 0.28 0.53 :I: 0.10 11.05 :1:0.70 5.53 :1:0.30 (91:I:0.62 7.86 :I: 0.42 21.16:I:1.82 14.60 :I: 0.52 1.94 :I: 0.20 0.36 :I: 0.08*
Averaged Result 21,126 +/-222 17.56 :I: 0.67 1.08 :I: 0.06 1.28 :I: 0.12 0.13:f;0.02 1,061 :I: 85 0.019 :I: 0.003 8.80 :I: 0.79 3.28 :I: 0.19 0.05 :I: 0.01 0.10 :I: 0.02 0.12 :I: 0.01 0.32 :I: 0.12 0.17 :I: 0.04 14.85 :I: 0.53 0.29 :I: 0.10 700 :I: 77 0.83 :I: 0.10 5,627 :I: 157 591 :I: 72 3356 :I: 129 7.30 :I: 0.52 0.022 :I: 0.003 14.56 :I: 0.96 0.021 :I: 0.002 19.40 :I: 1.50 21.48 :I: 0.59 0.11 :I: 0.04 1.36 :I: 0.21 0.57 :I: 0.04 683 :I: 74 3.28 :I: 0.19 0.019 :I: 0.003 34.4 :I: 0.9 30.7 :1:2.2 10.11 :I: 0.59 14,477 :1:252 0.014 :I: 0.003 31.23 :I: 0.54 1.73 :I: 0.21 0.88 :I: 0.09 0.022 :I: 0.003 0.345 :I: 0.152 0.07 :I: 0.02 12.04 :I: 0.46 0.14 :I: 0.02 0.42 :I: 0.03 1.03 :I: 0.22 0.49 :I: 0.07 11.58 :I: 0.49 5.57 :I: 0.21 1.68 :I: 0.42 7.80 :I: 0.30 21.04 :I: 1.50 14.62 :I: 0.37 1.97 :I: 0.16 0.35 :I: 0.06 Acceptance Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass*
Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
(
\\
TABLE A-5. In-House "Duplicate" Samples Lab Code Date DW-70102, 70103 6/13/2016 AP-061416 SG-3144, 3145 SG-3144, 3145 SPS-3165, 3166 SPS-3323, 3324 WW-3231, 3232 AP-3830, 3831 AP-070516A AP-070516B XWW-3605,3606 DW-70135,70136 DW-70132,70133 DW-70132,70133 AP-071216 DW-70150,70151 SPS-3649,3650 SPS-3649,3650 SPS-3649,3650 SPS-3649,3650 AP-071816 DW-70163,70164 WW-3761,3762 SPS-4003,4004 AP-072516 VE-3936,3937 VE-3936,3937 VE-3936,3937 VE-3959,3960 VE-3959,3960 VE-3959,3960 DW-70169,70170 DW-70169,70170 AP-080116 SS-4131,4132 SS-4131,4132 SPS-4087,4088 WW-4976,4977 SPS-4266,4267 AP-081616 VE-4399,4400 VE-4399,4400 WW-5394,5395 SPS-4441,4442 AP-082216 VE-4462,4463 VE-4462,4463 WW-4594,4595 WW-4663,4664 SPS-4529,4530 AP-083016A AP-083016B VE-4615,4616 6/14/2016 6/17/2016 6/17/2016 6/22/2016 6/24/2016 6/27/2016 6/29/2016 7/5/2016 7/5/2016 717/2016 7/8/2016 7/fj/2016 7/8/2016 7/12/2016 7/14/2016 7/15/2016 7/15/2016 7/15/2016 7/15/2016 7/1 B/2016 7/19/2016 7/20/2016 7/23/2016 7/25/2016 7/25/2016 7/25/2016 7/25/2016 7/27/2016 7/27/2016 7/27/2016 7/28/2016 7/28/2016 8/1/2016 8/1/2016 8/1/2016 8/2/2016 8/4/2016 8/10/2016 B/16/2016 8/18/2016 8/18/2016 8/18/2016 8/22/2016 8/22/2016 8/22/2016 8/22/2016 8/26/2016 8/26/2016 8/26/2016 8/30/2016 8/30/2016 8/31/2016 Analysis Ra-228 Gr. Beta Be-7 K-40 K-40 K-40 H-3 Gr. Beta Gr. Beta Gr. Beta H-3 Gr.Alpha Ra-226 Ra-228 Gr. Beta Gr. Alpha Cs-137 K-40 Pb-214 Ac-228 Gr. Beta Gr. Alpha H-3 K-40 Gr. Beta Sr-90 Be-7 K-40 Sr-90 Be-7 K-40 Ra-226 Ra-228 Gr: B~ta K-40 Cs-137 K-40 H-3 K-40 Gr. Beta K-40 Be-7 H-3 K-40 Gr. Beta Be-7 K-40 H-3 H-3 K-40 Gr. Beta Gr. Beta K-40 First Result 0.93 +/- 0.47 0.026 +/- 0.004 2.23 +/- 0.12 7.57 +/- 0.25 21.14+/-2.27 18.67 +/- 1.57 414 +/- 104 0.088 +/- 0.012 O.Q18 +/- 0.002 0.025 +/- 0.005 3,316 +/- 186 3.66 +/- 1.01 1.32 +/- 0.14 3.92 +/- 0.94 0.014 +/- 0.004 5.00 +/- 1.06 0.12 +/- 0.03 16.68 +/- 0.79 1.20 +/- 0.06 1.28 +/-0.16 0.022 +/- 0.005 1.06 +/- 0.66 347 +/- 90 7.15+/-1.59 0.023 +/- 0.004 0.048 +/- 0.007 0.49 +/- 0.15 4.70 +/- 0.35 0.002 +/- 0.002 0.30 +/- 0.14 4.01 :I: 0.37 0.63 +/-0.11 1.85 +/- 0.63 0.029 :I: 0.003 12.47 :I: 0.71 0.10 :I: 0.03 17.06 +/- 1.56.
17,043 :I: 390 1.06 :I: 0.47 0.029 +/- 0.005 3.85 +/- 0.23 0.30 :I: 0.08 947+/-122 20.55 +/-2.23 0.021 +/- 0.005 0.91 +/- 0.09 7.48 +/- 0.26 675 +/- 107 607 +/- 104 21.98 +/- 2.52 0.030 +/- 0.003 0.032 :I: 0.009 2.96 +/- 0.16 AS-3 Concentration a Second Result 1.11 +/-0.53 0.023 +/- 0.004 2.24 +/- 0.12 7.09 +/- 0.23 22.66+/-1.60 21.53 +/- 1.65 498 +/- 108 0.093 +/- 0.015 0.014 :I: 0.002 0.026 :I: 0.005 3,316 :I: 181 2.76 +/-0.98 1.11 +/-0.15 2.94 +/- 0.90 0.018 :I: 0.004 4.43 +/- 1.04 0.12 +/- 0.03 16.52 :I: 0.86 1.17 +/- 0.08 1.28 +/-0.16 0.024 +/- 0.005 1.36 :I: 0.70 466 :I: 96 6.86 +/- 1.21 0.020 :I: 0.004 0.058 +/- 0.010 0.51 +/-0.15 4.86 +/- 0.37 0.003 +/- 0.001 0.25 :I: 0.12 4.16 +/- 0.34 0.69 +/- 0.11 1.31 +/- 0.84 0.033 +/- 0.003 13.24 +/- 0.81 0.13 +/- 0.04 19.5 +/- 1.97 16,821 :I: 388 1.69 +/- 0.52 0.025 :I: 0.004 3.27 +/- 0.41 0.45 +/- 0.20 846+/-119 19.69 +/- 1.74 0.015 +/- 0.005 0.89 +/- 0.11 7.60 +/- 0.23 788+/-111 501 +/- 100 21.85 :I: 1.56 0.035 :I: 0.004 0.026 +/- 0.004 3.11 +/- 0.17 Averaged Result 1.02 +/- 0.35 0.024 :I: 0.003 2.24 :I: 0.08 7.33 +/- 0.17 22.01 :I: 1.39 20.10+/-1.14 456 +/- 75 0.091 +/- 0.010 0.016 +/- 0.002 0.025 :I: 0.004 3,316 :I: 130 3.22 +/- 0.70 1.22 +/- 0.10 3.43 +/- 0.65 0.016 +/- 0.003 4.72 +/-0.74 0.12 +/- 0.02 16.6 :I: 0.58 1.19 :I: 0.06 1.28 +/- 0.11 0.023 +/- 0.003 1.22 :I: 0.48 407 +/- 66 7.00 +/- 1.00 0.022 :I: 0.003 0.053 +/- 0.006 0.50 :I: 0.10 4.78 +/- 0.25 0.003 +/- 0.001 0.27 :I: 0.09 4.08 :I: 0.25 0.76 +/- 0.08 1.58 +/- 0.53 0.031 +/- 0.002 12.86 +/- 0.54 0.12 +/- 0.02 18.28 +/- 1.26 16,932 +/-275 1.375 :I: 0.35 0.027 :I: 0.003 3.56 +/- 0.24 0.37 +/- 0.11 896 :I: 85 20.12:I:1.41 0.018 +/- 0.003 0.90 +/- 0.07 7.54+/-0.17 731 +/- 77 554 +/-72 21.92 :I: 1.48 0.033 :I: 0.002 0.029 +/- 0.005 3.03 +/-0.11 Acceptance Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
(
TABLE A-5. In-House "Duplicate" Samples Lab Code AP-090216 AP-090616 Ml-4751,4752 Ml-4751,4752 SW-4772,4773 WW-5285,5286 Ml-4826,4827 VE-4868,4869 VE-4868,4869 CF-4934,4935 CF-4934,4935 AP-092016 DW-70196,70197 F-4955,4956 VE-5044,5045 VE-5044,5045 WW-5219,5220 SPS-5087,5088 AP-092716 AP-5660,5661 AP-5681,5682 VE-5110,5111 AP-515~,5155 AP-5702,5703 Ml-5264,5265 Ml-5264,5265 SS-5547,5548 SS-5547,5548 SS-5547,5548 SS-5547,5548 SS-5547,5548 SS-5547,5548 AP-101116 WW-5526.5527 WW-5639,5640 WW-5723,5724 F-5811,5812 S0-5900,5901 S0-5900,5901 S0-5900,5901 S0-5900,5901 S0-5900,5901 S0-5900,5901 S0-5900,5901 S0-5900,5901 SS-5879,5880 SS-5879,5880 LW-6072,6073 BS-6009, 6010 BS-6009, 601 O F-6211,6212 F-6211,6212 DW-70230, 70231 DW-70230, 70231 F-6093,6094 Date 9/2/2016 9/6/2016 917/2016 917/2016 9/8/2016 9/13/2016 9/14/2016 9/15/2016 9/15/2016 9/19/2016 9/19/2016 9/20/2016 9/20/2016 9/20/2016 9/20/2016 9/20/2016 9/20/2016 9/23/2016
. 9/27/2016 9/28/2016 9/27/2016 9/28/2016 9/29/2016 9/30/2016 Analysis Gr. Beta Gr. Beta*
K-40 Sr-90 H-3 H-3 K-40 Gr. Bela K-40 K-40 Be-7 Gr. Bela Gr.Alpha K-40 Be-7 K-40 H-3 K-40 Gr. Beta Be-7 Be-7 K-40 Be-7 Be-7 10/4/2016 K-40 10/4/2016.
Sr-90 10/11/2016 Gr. Beta 10111/2016 K-40 10/11/2016 Tl-208 10/11/2016 Bi-214 10/11/2016 Pb-212 10/11/2016 Ac-228 10/11/2016 Gr. Beta 10/11 /2016 H-3 1 0119/2016 H-3 10/18/2016 H-3 10/20/2016 K-40 10/22/2016 1ci/2212016 10/2212016 10/22/2016 10/2212016 10/22/2016 10/2212016 10/22/2016 10/25/2016 10/25/2016 10/27/2016 10/27/2016 10/27/2016 10/28/2016 10/28/2016 10/28/2016 10/28/2016 10/31/2016 Cs-137 K-40 Tl-208 Pb-212 Bi-214 Ac-228 Ra-226 Gr. Beta K-40 Cs-137 Gr. Beta Cs-137 K-40 Gr. Beta K-40 Ra-226 Ra-228 K-40 First Result 0.022 +/- 0.004 0.023 +/- 0.005 1,693+/-112 1.23 +/- 0.38 196 +/- 91 18,010 +/-400 1 ;372.6 +/- 105 2.50 +/- 0.06 2.20 +/- 0.17 11.47 +/-0.82 0.43 +/-0.22 0.021 +/- 0.004 13.8+/-1.36 3.40 +/-0.44 0.46 +/- 0.05 4.37 +/- 0.12 63,744 +/- 743 21.04 +/-2.32 0.031 +/- 0.005 0.093 +/- 0.014 0.079 +/- 0.019 1.82 +/- 0.15 0.237 +/- 0.116 0.084 +/- 0.015 1,636 +/- 128 2.00 +/- 0.44 11.27+/-1.19 8.03 +/- 0.45 0.04 +/- 0.02 0.14 +/-0.03 0.12 +/-0.02 0.10 +/- 0.05 0.032 +/- 0.004 18,865 +/-408 192 +/- 103 36,012 +/- 560 0.91 +/- 0.30 0.05 +/- 0.02 9.82 +/- 0.60 0.10 +/- 0.02 0.32 +/- 0.03 0.20 +/- 0.04 0.41 +/- 0.08 0.45 +/- 0.23 16.49+/-1.01 14.94 +/- 0.83 0.06 +/- 0.03 0.88 +/- 0.49 0.14 +/- 0.08 17.04 +/- 1.58 3.25 +/-0.07 2.45 +/- 0.33 4.00 +/-020 5.30 +/- 0.80 3.77 +/- 0.50 AS-4 Concentration "
Second Result 0.027 +/- 0.004 0.023 +/- 0.005 1,760 +/- 99 1.00 +/- 0.33 236 +/-93 18,686 +/- 407 1,198.1 +/-97 2.57 +/- 0.06 2.30 +/- 0.17 11.76 +/- 0.50 0.46 +/- 0.13 0.017 +/- 0.004 15.28+/-1.36 2.86 +/-0.39 0.50 +/-0.11 4.68 +/-0.24 64,755 +/-749 18.84+/-1.88 0.032 +/- 0.005 0.086 +/- 0.019 0.071 +/- 0.015 2.14+/-0.18 0.195 +/- 0.096 f?.070 +/- 0.018 1,610 +/- 124 1.28 +/- 0.37 9.47+/-1.20 7.23 +/- 0.46 0.04 +/- 0.02 0.12 +/-0.03 0.11 +/- 0.02 0.16 +/- 0.05 0.028 +/- 0.004 18,904 +/-408 52 +/-98 36,207 +/- 561 0.75 +/-0.22 0.03 +/- 0.02 10.77 +/- 0.61 0.14 +/- 0.03 0.33 +/- 0.03.
0.27 +/- 0.04 0.48 +/- 0.09 0.61 +/- 0.27 17.71 +/- 1.03 15.26 +/- 0.84 0.09 +/- 0.04 1.53 +/- 0.56 0.13 +/- 0.06 18.30 +/- 1.42 3.27 +/- 0.07 2.49 +/- 0.37 4.10+/-0.30 5.20 +/-0.80 3.51 +/- 0.44 Averaged Result 0.024 +/- 0.003 0.023 +/- 0.003 1,726 +/- 75 1.11 +/-0.25 216 +/- 65 18,348 +/-286 1,285.4 +/- 71 2.53 +/- 0.04 2.25 +/- 0.12 11.61+/-0.48 0.45 +/-0.13 0.019 +/- 0.003 14.54 +/- 0.96 3.13 +/- 0.30 0.48 +/- 0.06 4.53 +/-0.13 64,250 +/-527 19.94 +/- 1.49 0.031 +/- 0.003 0.089 +/- 0.012 0.075 +/- 0.012 1.98 +/-0.12 0.216 +/- 0.075 0.077 +/- 0.012 1,623 +/-89 1.64 +/- 0.29 10.37 +/- 0.84 7.63 +/- 0.32 0.04 +/- 0.01 0.13 +/-0.02 0.11 +/-0.01 0.13 +/-0.04 0.030 +/- 0.003 18,884 +/-289 122 +/- 71 36,110 +/-396 0.83 +/- 0.19 0.04 +/-0.02 10.29 +/- 0.43 0.12 +/-0.02 0.32 +/- 0.02 0.23 +/- 0.03 0.44 +/- 0.06 0.53 +/- 0.18 17.10 +/-0.72 15.10 +/-0.59 0.08 +/- 0.02 1.21 +/- 0.37 0.13 +/-0.05 17.67+/-1.06 3.26 +/-0.05 2.47 +/-0.25 4.05 +/-0.18 5.25 +/- 0.57 3.64 +/- 0.33 Acceptance Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass*
Pass.
Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
- ' (
TABLE A-5. In-House "Duplicate" Samples
\\
Concentration ° Averaged Lab Code Date Analysis First Result Second Result Result Acceptance AP-110116 11/1/2016 Gr. Beta 0.021 +/- 0.004 0.024 +/- 0.004 0.023 +/- 0.003 Pass S-5963, 5964 11/1/2016 K-40 20.35 +/-2.29 18.59 +/- 1.90 19.47+/-1.49 Pass SG-6119,'6120 11/1/2016 Ac-228 5.70 +/- 0.44 6.28 +/- 0.57 5.99 +/- 0.36 Pass SG-6119, 6120 11/1/2016 Gr. Alpha 21.59+/-1.88 24.35 +/- 1.93 22.97 +/- 1.35 Pass SG-6119, 6120 11/1/2016 K-40 4.89 +/-1.10 5.90 +/- 1.08 5.40 +/- 0.77 Pass.
SG-6119, 6120 11/1/2016 Pb-214 3.99 +/- 0.21 4.35 +/- 0.32 4.17 +/- 0.19 Pass S-6051, 6052 11/4/2016 K-40 7.05 +/- 0.60 7.56 +/- 0.53 7.31 +/- 0.40 Pass WW-6297, 6298 11/8/2016 H-3 207 +/-98 165 +/- 97 186 +/- 69 Pass WW-6341,6342 11/8/2016 H-3 1,356+/-140 1,404 +/- 141 1,380 +/- 99 Pass S0-6406,6407 11/9/2016 Cs-137 0.36 +/- 0.04 0.43 +/- 0.05 0.40 +/- 0.03 Pass S0-6406,6407 11/9/2016 K-40 10.90 +/- 0.68 11.29 +/- 0.74 11.09, +/- 0.50 Pass AP-111416 11/14/2016 Gr. Beta 0.024 +/- 0.005 0.021 +/- 0.006 0.022 +/- 0.004 Pass WW-6829,6830 11/15/2016 H-3 39,982 +/- 589 40,315 +/-591 40,149 +/- 417 Pass DW-70239, 70240 11/17/2016 Gr. Alpha 7.99 +/-1.15 6.41 +/- 1.05 7.20 +/- 0.78 Pass AP-112216 11/22/2016 Gr. Beta 0.049 +/- 0.005 0.045 +/- 0.005 0.047 +/- 0.003 Pass S-6473, 6474 11/24/2016 K-40 19.37+/-1.97 23.80 +/-3.54 21.58 +/- 2.02 Pass SG-6938, 6939 11/28/2016 Ac-228 18.99 +/- 0.59 19.92 +/-0.79 19.46 +/- 0.49 Pass SG-6938, 6939 11/28/2016 Pb-214 15.28 +/- 0.34 14.96 +/- 0.43 15.12 +/-0.27 Pass AP-120116 1211/2016 Gr. Beta 0.029 +/- 0.003 0.030 +/- 0.003 0.030 +/- 0.002 Pass F-6567,6568 1211/2016 K-40 3.76 +/- 0.40 3.83 +/- 0.46 3.80 +/- 0.30' Pass S-6522, 6523 1211/2016 Ac-228 1.08 +/- 0.13 1.29 +/-0.16 1.19 +/-0.10 Pass S-6522, 6523 1211/2016 Pb-214 1.00 +/- 0.08 1.01 +/- 0.09 1.01 +/- 0.06 Pass S-6609, 661 o 12/1/2016 K-40 15.57+/-1.01 15.99 +/- 0.78 15.78 +/- 0.64 Pass S-6718, 6719 1217/2016 K-40 18.19 +/-2.13 18.76 +/- 1.80 18.48 +/- 1.39 Pass
(
WW-6784, 6785 1217/2016 H-3 922+/-117 905+/-116 914 +/-82 Pass AP-121216 12112/2016 Gr. Beta 0.026 +/- 0.005 0.028 +/- 0.005 0.027 +/- 0.003 Pass AP-7178,7179 1/3/2017 Be-7 0.047 +/- 0.015 0.062 +/- 0.017 0.054 +/- 0.012 Pass Note: Duplicate analyses are performed on every twentieth sample received in-house. Results are not listed for those analyses with activities that measure below the LLD.
- Results are reported in units of pCi/L, except for air filters (pCi/Filter or pCi/m3), food products, vegetation, soil and sediment {pCi/g).
(
AS-5
(____
TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP).
Concentration a Reference Known Control Lab Code b Date Analysis Laboratory result Activity Limits 0
Acceptance MAS0-1053 2/1/2016 Ni-63 1,206 +/- 20 1250 875 -1625 Pass MAS0-1053 2/1/2016 Si'-90 0.65 +/- 1.27 0.00 NA 0
Pass MAS0-1053 2/1/2016 Tc-99 0.1 +/- 5.5 0.0 NA c Pass MAS0-1053 2/1/2016 Cs-134 908 +/- 26 1030 721 -1339 Pass MAS0-1053 2/1/2016 Cs-137 0.10 +/-6.20 0.00 NA c Pass MAS0-1053 2/1/2016 Co-57 1058 +/- 26 992 694 - 1290 Pass MAS0-1053 2/1/2016 Co-60 1229 +/- 28 1190 833 - 1547 Pass MAS0-1053 2/1/2016 Mn-54 1235 +/- 43 1160 812-1508 Pass MAS0-1053 2/1/2016 Zn-65 753 +/- 64 692 484 - 900 Pass MAS0-1053 2/1/2016 K-40 753+/-140 607 425 - 789 Pass MAS0-1053 211/2016 Am-241 79 +/-6 103 72 - 134 Pass MAS0-1053 2/1/2016 Pu-238 73.9 +/-9.2 63.6 44.5 - 82.7 Pass MAS0-1053 2/1/2016 Pu-239/240 0.76 +/- 1.34 0.21 NAd Pass MAS0-1053 211/2016 U-234/233 45.0 +/- 5.1 45.9 32.1 -59.7 Pass MAS0-1053 2/1/2016 U-238 129 +/- 9 146 102 - 190 Pass MAW-989 2/1/2016 Am-241 0.018 +/- 0.015 0.00 NA 0
Pass MAW-989 2/1/2016 H-3 0.2 +/-2.8 0.0 NA 0
Pass MAW-989 2/1/2016 Ni-63 12.8 +/- 2.7 12.3 8.6 -16.0 Pass MAW-989 2/1/2016 Sr-90 8.70 +/- 1.20 8.74 6.12 -11.36 Pass 1
MAW-989 2/1/2016 Tc-99
-1.1 +/- 0.6 0.0 NA 0
Pass MAW-989 2/1/2016 Cs-134 15.5 +/- 0.3 16.1 11.3 +/- 20.9 Pass MAW-989 2/1/2016 Cs-137 23.7 +/- 0.5 21.2 14.8 -27.6 Pass MAW-989e 2/1/2016 Co-57 1.38 +/- 0.12 0.00 NA 0
Fail MAW-989 2/1/2016 Co-60 12.5 +/- 0.3 11.8 8.3 -15.3 Pass MAW-989 211/2016 Mn-54 12.2 +/- 0.4 11.1 7.8 -14.4 Pass MAW-989 211/2016 Zn-65 15.7 +/- 0.7 13.6 9.5 -17.7 Pass MAW-989
. 2/1/2016 K-40 288 +/-5 251 176 - 326 Pass MAW-989 2/1/2016 Fe-55 17.3 +/- 7.0 16.2 11.3 - 21.1 Pass MAW-989 2/1/2016 Ra-226 0.710 +/- 0.070 0.718 0.503 - 0.933 Pass MAW-989 2/1/2016 Pu-238 1.280 +/- 0.110 1.244 0.871 +/- 1.617 Pass MAW-989 2/1/2016 Pu-239/240 0.640 +/- 0.080 0.641 0.449 - 0.833 Pass MAW-989 2/1/2016 U-234/233 1.39+/-0.12 1.48 1.04 -1.92 Pass
- MAW-989 2/1/2016 U-238 1.43+/-0.12 1.53 1.07 - 1.99 Pass MAW-893 2/1/2016 Gross Alpha 0.600 +/- 0.050 0.673 0.202 - 1.144 Pass MAW-893 2/1/2016 Gross Beta 2.10 +/- 0.06 2.15 1.08 - 3.23 Pass MAW-896 2/1/2016 1-129 3.67 +/- 0.20 3.85 2.70 -5.01 Pass MAAP-1056 2/1/2016 Gross Alpha 0.39 +/- 0.05 1.20 0.36 -2.04 Pass MAAP-1056 2/1/2016 Gross Beta 1.03 +/- 0.07 0.79 0.40-1.19 Pass AG-1
/~*
(_,
TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP).
Concentration a Reference Known Control Lab Code b Date Analysis Laboratory result Activity Limits c Acceptance MAAP-1057
- 2/1/2016 Sr-90 1.34 +/-0.15 1.38 0.97 +/- 1.79 Pass MAAP-1057 2/1/2016 Cs-134
-0.01 +/- 0.03 0.00 NAC Pass MAAP-1057 2/1/2016 Cs-137 2.57 +/- 0.10 2.30 1.61 -2.99 Pass MAAP-1057 2/1/2016 Co-57 3.01 +/- 0.06 2.94 2.06 -3.82 Pass MAAP-1057 2/1/2016 Co-60 4.28 +/- 0.10 4.02 2.81 -5.23 Pass MAAP-1057 2/1/2016 Mn-54 4.90 +/- 0.13 4.53 3.17 -5.89 Pass MAAP-1057 2/1/2016 Zn-65 4.09 +/- 0.18 3.57 2.50 -4.64 Pass MAAP-1057 2/1/2016.
Am-241 0.059 +/- 0.015 0.0805 0.0564 - 0.1047 Pass MAAP-1057 2/1/2016 Pu-238 0.066 +/- 0.020 0.0637 0.0446 - 0.0828 Pass MAAP-1057 2/1/2016 Pu-239/240 0.074 +/- 0.020 0.099 NAd Pass MAAP~1057 2/1/2016 U-234/233 0.151 +/- 0.026 0.165 0.116-0.215 Pass MAAP-1057 2/1/2016 U-238 0.160 +/- 0.026 0.172 0.120 -0.224 Pass MAVE-1050 211/2016 Cs-134 9.83 +/- 0.19 10.62 7.43 - 13.81 Pass MAVE-1050 2/1/2016 Cs-137 6.06 +/-0.19 5.62 3.93 -7.31 Pass MAVE-1050 2/1/2016 Co-57 13.8 +/- 0.2 11.8 8.3 - 15.3 Pass MAVE-1050 2/1/2016 Co-60 0.022 +/- 0.040 0.00 NA c Pass MAVE-1050 2/1/2016 Mn-54 0.009 +/- 0.044 0.000 NA c Pass MAVE-1050 2/1/2016 Zn-65 10.67 +/- 0.39 9.60 6.70 -12.50 Pass
(
MAS0-4780f 8/1/2016 Ni-63 648 +/- 14 990 693 -1287 Fail
. MAS0-47809 8/1/2016 Ni-63 902 +/-46 990 693 - 1287 Pass MAS0-4780 8/1/2016 Sr-90 757+/-16 894
. 626 -1162 Pass MAS0-4780 8/1/2016 Tc-99 559 +/- 12 556 389 -723 Pass MAS0-4780 8/1/2016 Cs-134 0.93 +/-2.92 0.00 NA c Pass MAS0-4780 8/1/2016 Cs-137 1061 +/- 12 1067 747 -1387 Pass MAS0-4780 8/1/2016 Co-57 1178 +/- 8 1190 833 - 1547 Pass MAS0-4780 8/1/2016 Co-60 841+/-9 851 596 -1106 Pass MAS0-4780 811/2016 Mn-54 0.69 +/-2.53 0.00 NAC Pass MAS0-4780 8/1/2016 Zn-65 724+/-19 695 487 -904 Pass MAS0-4780 8/1/2016 K-40 566 +/- 52 588 412 - 764 Pass MAS0-4780 8/1/2016 Am-241 0.494 +/- 0.698 0.000 NA c Pass MAS0-4780 8/1/2016 Pu-238 69.7 +/- 7.4 70.4 49.3 -91.5 Pass MAS0-4780 8/1/2016 Pu-239/240 53.9 +/-6.3 53.8 37.7 -69.9 Pass MAS0-4780h 8/1/2016 U-233/234 46.8 +/- 3.9 122 85 -159 Fail MAS0-4780h 8/1/2016 U-238 46.6 +/- 3.9 121 85 -157 Fail MAW-4776 8/1/2016 1-129 4.40 +/- 0.20 4.54 3.18 -5.90 Pass MAVE-4782 8/1/2016 Cs-134
-0.01 +/- 0.05 0.00 NAC Pass MAVE-4782 8/1/2016 Cs-137 6.18 +/- 0.20 5.54 3.88 - 7.20 Pass MAVE-4782 8/1/2016 Co-57 8.13 +/- 0.16 6.81 4.77 -8.85 Pass MAVE-4782 8/1/2016 Co-60 5.30 +/- 0.15 4.86 3.40 -6.32 Pass MAVE-4782 8/1/2016 Mn-54 8.08 +/- 0.24 7.27 5.09 - 9.45 Pass MAVE-4782 8/1/2016 Zn-65 6.24 +/- 0.36 5.40 3.78 -7.02 Pass
{
I AG-2
(
TABLEA-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP).
Concentration "
Reference Known NAC Lab Code b Date Analysis Laboratory result Activity Limits c Acceptance MAAP-4784 8/1/2016 Sr-90 1.18 +/- 0.10 1.03 0.72 -1.34 Pass MAAP-4784 8/1/2016 Cs-134 1.58 +/- 0.08 2.04 1.43 - 2.65*
Pass MAAP-4784 8/1/2016 Cs-137 1.85 +/- 0.09 1.78 1.25 -2.31 Pass MAAP-4784 811/2016 Co-57 2.39 +/-0.52 2.48 1.74 -3.22 Pass MAAP-4784 8/1/2016 Co-60 3.22 +/- 0.08 3.26 2.28 -4.24 Pass MAAP-4784 8/1/2016 Mn-54 2.82 :i: 0.12 2.75 1.93 - 3.58 Pass MAAP-4784 8/1/2016 Zn-65
-0.015 +/- 0.06~
0.00 NAC Pass MAAP-4784 8/1/2016 Am-241
-0.001 +/- 0.006 0.00 NAC Pass MAAP-4784 8/1/2016 Pu-238 0.075 +/- 0.022 0.069 0.049 - 0.090 Pass MAAP-4784 8/1/2016 Pu-239/240 0.048 +/- 0.015 0.054 0.038 - 0.070 Pass MAAP-4784 8/1/2016 U-234/233 0.151 +/- 0.036 0.150 0.105 -0.195 Pass MAAP-4784 8/1/2016 U-238 0.147 +/- 0.034 0.156 0.109 -0.203 Pass MAW-4778 8/1/2016 H-3 365 +/- 11 334 234 -434 Pass MAW-4778 811/2016 Fe-55 23.6+/-16.3 21.5 15.1 +/-28.0 Pass MAW-4778 8/1/2016 Ni-63 17.0 +/- 2.8 17.2 12.0 +/-22.4 Pass MAW-4778 8/1/2016 Sr-90 0.17 +/- 0.28 0.00 NA c Pass MAW-4778 811/2016 Tc-99 9.50 +/- 0.41 11.60 8.10 -15.10 Pass MAW-4778 811/2016 Cs-f34 22.6 +/- 0.4 23.9 16.7 -31.1 Pass
(
MAW-4778 8/1/2016 Cs-137 0.018 +/-0.117 0.00 NAC Pass
\\...
MAW-4Tl8 8/1/2016 Co-57 27.6 +/- 0.2 27.3 19.1 +/-35.5 Pass MAW-4778 8/1/2016 Co-60 0.018 +/- 0.090 0.00 NAC Pass MAW-4778 8/1/2016 Mn-54 16.2 +/- 0.4 14.8 10.4-19.2 Pass MAW-4778 8/1/2016 Zn-65 19.3 +/- 0.7 17.4 12.2 -22.6 Pass MAW-4778 8/1/2016 K-40 286 +/-6 252 176 -328 Pass MAW-4778 8/1/2016 Ra-226 1.48 +/- 0.09 1.33 0.93 -1.73 Pass MAW.-4778 8/1/2016 Pu-238 1.09 +/-0.13 1.13 0.79 -1.47 Pass MAW-4778 8/1/2016 Pu-239/240 0.003 +/- 0.011 0.016 NA d Pass MAW-4778*
8/1/2016 U-234/233 1.80 +/-0.13 1.86 1.30 -2.42 Pass MAW-4778 8/1/2016 U-238 1.77+/-0.13 1.92 1.34 -2.50 Pass MAW-4778 8/1/2016 Am-241 0.678 +/- 0.086 0.814 0.570 +/- 1.058 Pass
- Results are reported in units of Bq/kg (soil), Bq/L (water) or Bq/total sample (filters, vegetation).
b Laboratory codes as follows: MAW (water), MAAP (air filter), MASO (soil), MAVE (vegetation).
0 MAPEP results are presented as the known values and expected laboratory precision (1 sigma, 1 determination) and control limits as defined by the MAPEP. A known value of "zero" indicates an analysis was included in the testing series as a "false positive". MAPEP does not provide control limits.
d Provided in the series for "sensitivity evaluation". MAPEP does not provide control limits.
- The laboratory properly identified ~e Sn-75 interfering peak in the vicinity of Co-57 and stated so in the comment field. MAPEP requires results to be reported as an activity with an uncertainty. Since the calculated uncertainty was less than the activity MAPEP interpreted the submitted result as a "false positive" resulting in a failure.
1 Original analysis for l'Ji-63 failed.
9 Reanalysis with a smaller aliquot resulted in acceptable results. An investigation ls in process to identify better techniques for analyzing samples with complex matrices.
h MAPEP states that samples contain two fractions of Uranium; one that is soluble in concentrated HN03 and HCI acid and.one that is "fundamentally insoluble in these acids". They also state that HF treatment can not assure complete dissolution.
(
Results are consistent with measuring the soluble form.
AG-3
(
TABLEA-7. lnterlaboratory Comparison Crosscheck Program, Environmental Resource Associates (ERA)8 *
~
MRADStudy Concentration a Lab Code b Date Analysis Laboratory ERA Control Result Result Limits Acceptance ERAP-1101 3/14/2016 Am-241 37.3 45.9 28.3 - 62.1 Pass ERAP-1101 3/14/2016 Co-60 637 623 482 -778 Pass ERAP-1101 3114/2016 Cs-134 251 304 193 - 377 Pass ERAP-1101 3/14/2016 Cs-137 1,273 1,150 864 -1,510 Pass ERAP-1101 3/14/2016 Fe-55
< 162 126 39.1 -246 Pass ERAP-1101 3/14/2016 Mn-54
<2.64
<50.0 0.00 -50.0 Pass ERAP-1101 3/14/2016 Pu-238 68.0 70.5 48.3 -92.7 Pass ERAP-1101 3114/2016 Pu-239/240 54.1 54.8
- 39. 70 - 71.60 Pass ERAP-1101 3/14/2016 Sr-90 139 150 73.3 -225.0 Pass ERAP-1101 3/14/2016 U-233/234 59.3 64.8 40.2 -97.7 Pass ERAP-1101 3114/2016 U-238 55.5 64.2 41.5 - 88.8 Pass ERAP-1101 3/14/2016 Zn-65 428 356 255 -492 Pass ERAP-1101 3/14/2016 Gr. Alpha 98.0 70.1 23.5.-109 Pass ERAP-1101 3/14/2016 Gr. Beta 78.6 54.4 34.4 -79.3 Pass ERS0~1105 3/14/2016 Am-241 1,030 1,360 796 -1,770 Pass ERS0-1105 3/14/2016 Ac-228 1,540 1,240 795 -1,720 Pass
~
(
ERS0-1105 3/14/2016 Bi-212 1,550 1,240 330 -1,820 Pass ERS0-1105 3/14/2016 Bi-214 3,100 3,530 2, 130 - 5,080 Pass ERS0-1105 3/14/2016 Co-60 5,600 5,490 3,710 - 7,560 Pass ERS0-1105 3/14/2016 Cs-134 3,030 3,450 2,260 - 4, 140 Pass ERS0-1105 3/14/2016 Cs-137 4,440 4,310 3,300 - 5,550 Pass ERS0-1105 3/14/2016 K-40 10,300 10,600 7,740 - 14,200 Pass ERS0-1105 3/14/2016 Mn-54
< 50.8
< 1000 0.0 -1,000 Pass ERS0-1105 3/14/2016 Pb-212 1,140 1,240 812 -1,730 Pass ERS0-1105 3/14/2016 Pb-214 3,190 3,710 2, 170 - 5,530 Pass ERS0-1105 3/14/2016 Pu-238 680 658 396 -908 Pass ERS0-1105 3/14/2016 Pu-239/240 460 496 324 - 0,685 Pass ERS0-1105 3/14/2016 Sr-90 7,740 8,560 3,260 - 13,500 Pass ERS0-1105 3/14/2016 Th-234 3,630 3,430 1,080 - 6,450 Pass ERS0-1105 3/14/2016 U-233/234 3,090 3,460 2, 110 - 4,430 Pass ERS0-1105 3/14/2016 U-238 3,280 3,430 2, 120 - 4,350 Pass ERS0-1105 3/14/2016 Zn-65 2,940 2,450 1,950 - 3,260 Pass ERW-1115 3/14/2016 Gr. Alpha 105.0 117.0 41.5 -181.0 Pass ERW-1115 3/14/2016 Gr. Beta 76.2 75.5 43.2 -112.0 Pass ERW-1117 3/14/2016 H-3 8,870 8,650 5,800 -12,300 Pass A7-1
(
£___
\\.
TABLEA-7. lnterlaboratory Comparison Crosscheck Program, Environmental Resource Associates (ERA) 2*
MRADStudy Concentration a Lab Code b Date Analysis Laboratory ERA Control Result Result Limits Acceptance ERVE-1108 3/14/2016 Am-241 1,930 2,120 1,300 - 2,820 Pass ERVE-1108 3/14/2016 Cm-244 1,294 1,560 764 -2,430 Pass ERVE-1108 3/14/2016 Co-60 1,164 1,100 759 -1,540 Pass ERVE-1108 3/14/2016 Cs-134 1,056 1,070 687 -1,390 Pass ERVE-1108 3/14/2016 Cs-137 930 838 608 -1,170 Pass ERVE-1108 3/14/2016 K-40 32,200 31,000 22,400 - 43,500 Pass ERVE-1108 3/14/2016 Mn-54
<24.5
<300 0.00 -300 Pass ERVE-1108 3/14/2016 Zn-65 3,320 2,820 2,030 - 3,960 Pass ERVE-1108 3/14/2016 Pu-238 3,410 2,810 1,680 - 3,850 Pass ERVE-1108 3/14/2016 Pu-239/240 4,120 3,640 2,230 - 5,010 Pass ERVE-1108 3/14/2016 Sr-90 8,120 8,7,10 4,960 - 11,500 Pass ERVE-1108 3/14/2016 U-233/234 4,350 4,160 2,740 - 5,340 Pass ERVE-1108 3/14/2016 U-238 4,220 4,120 2, 750 - 5,230 Pass ERW-1111 3/14/2016 Am-241 113 121 81.5 -162 Pass ERW-1111 3/14/2016 Co-60 1,120 1,050 912 -1,230 Pass ERW-1111 3/14/2016 Cs-134 806 842 618 - 968 Pass ERW-1111 3/14/2016 Cs-137 1,190 1,100 934 -1,320 Pass ERW-1111 3/14/2016 Mn-54
<5.89
< 100 0.00 -100 Pass ERW-1111 3114/2016 Pu-238 159 138 102 -172 Pass ERW-1111 3/14/2016 Pu-239/240 113 98.7 76.6 -124 Pass ERW-1111 3/14/2016 U-233/234 46.9 52.7 39.6 - 68.0 Pass ERW-1111 3/14/2016 U-238 50.4 52.3 39.9 -64.2 Pass ERW-1111 3114/2016 Zn-65 1,160 1,010 842 -1,270 Pass ERW-1111 3/14/2016 Fe-55 1,600 1,650 984 -2,240 Pass ERW-1111 3/14/2016 Sr-90 430 434 283 -574 Pass a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing administered by Environmental Resources Associates, seNing as a replacement for studies conducted previously by the Environmental Measurements Laboratory Quality Assessment Program (EML).
b Laboratory codes as follows: ERW (water), ERAP (air filter), ERSO (soil), ERVE (vegetation). Results are reported in units of pCi/L, except for air filters (pCi/Filter), vegetation and soil (pCi/kg).
c Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.
A7-2
. l
(
APPENDIX B
\\
DATA REPORTING CONVENTIONS.
B-1
/
i Data Reporting Conv~ntions 1.0. All activities, except gross alpha and gross bet<!, are decay corrected to collection time or the end of the collection period.
2.0. Single Measurements Each single measurement is reported as follows:
x :l: s wher~:
x ;; value of the me~surememt; s = 21J co1.mting uncertainty (corresponding ti;i thc;:J. 9P.% q9nfid~nee leY~I).
In cases where the activity 1$ less than the lower limit pf detection L, it ii? reported ias:..: I.,,
where I,. :;:: the lower limit Qf detection based on 4.66cr uncertainty for a packground sample.
3.0. Duplicat~ analyses If duplicate analyses <ilr~ r1;1ported, the convention is as follows. :
3.1 Individual results: For two analysis results; x1 ;1:: s1 and ~ ;t s~
Reported result
- x +/- s; where x = (1/2) (x1 + ~) ancl s = (1/2) J s: +
s~
3.2.
Individual results:
< ~1, < L2 ReRo.rted result < L"' where L = lower of L1 and L2 3,3.
Individual results:
x ;:ts, < L
~~P.orted resu.lt:
?< ;1: s if x ii!: L; < L otheiwise.
4.0. Comgutation of AV(3rag0s and.. Standard Deviations 4.1 Averages and staf!dard deviations listed in the tables are computed from all of the individual meal'}urements qver the period ave.raged; for example, lln annual stand~rd qevi;ition would not be the average of qui;irterly
- >tandard deviatiQns. Th~ ;:iverage x and st;;indafq devii::lti9n ::i" of a set of n m,1mbers ~1
- x2.** ~n ~re defined a~ follows:
_1 x.,. ri l: x 4.2 Values below the highest lower limit of detection are not included in the average.
4.3 If all values in the averaging group aft; lei;is than the highest LL.P. the highest LLD is reported.
4.4 If ci!I but one of the values are less than the highest LLD, the single value ~ and associat~d two sigma error is reported.
4.5 In roune;ng off, the f9f1Qwing rules are followE1d:
4.5.1. If the number following those to be retained is less thal') 5, the number ls qropped, ~nd the retained numbers 1;1re kept unchangect. As an example, 11.443 is ro1.md!.':!d off to 11.44.
4.5.2.
If the number following those to Qe retained is equal to or gr~ater than 5, the number is dropped and the last ret;:iined numb~r is raised oy 1. As an example, 11.445 is rounded off to 11,45.
13-2
\\.
(
i POINT BEACH NUCLEAR PLANT APPENDIXC Sampling Program and l..ocgtion$
C-1 I !
- ' l t POINT BEACH NUCLEAR PLANT Locations Collection Type Analysis Sample Type No.
codes (and Type)a (and Frequency)b (and Frequency)b Airborne Filters 6
E-1-4. 8, 20 Weekly GB, G$, on QC for each locatiqn Airborne Iodine 6
E-1-4, ~. 20 Weekly 1-131 Ambient Radiation 22
!:H-9, 12, 14-18, 20, Quarterly Ambient Gamma (l'LD's) 22-32, 34-36, 38,39 Lake Water 5
E-1, 5, 6, 33 Monthly GB, GS, 1-131 on MC H-3, Sr-89*90 on QC Well Water E-10 Quarterly GB, GS, H-3, Sr-89-90, 1-131 Vegetation 8
E-1-4, 6, 9, 20 3x/ year GB,GS as available Shoreline Silt 5
E-1, 5, 6, 12, 33 2x/year GB,GS Soil 8
E-1-4, 6, 8, 9, 20 2x/year GB,GS Milk 3
E-11, 40, 21 Monthly GS, 1-131, Sr-89-90 Algae 2
E~5, 12 3x/y~ar GB.GS as available Fish E-13 2x/y~ar GB, GS (in edible portions) as av;:iili;ible a Locations codes are defined in Table 2. Control Stations are indicated by (C). All other staUons are inoicators.
b Analysis type is coded as follows: GS. = gross beta, GA = gross alpha, GS = gamma spectroscopy, H-3 = tritium, Sr-89 = strontium-89, Sr-90 = strontium-90, 1-131 = iodine-131. Analysis frequency is coded as follows:
MC = monthly composite, QC = quarterly c;omposite.
C-2
POINT BEACH NUCLEAR PLANT APPENDIX D Graphs of Data Trends D-1
POINT BEACH Air Particulates - Gross Beta
(
Location E-1, monthly averages 2012-2016 0.050 f\\
'I, (t) 0:030 -h.-~--+-+----+---\\-----+--;..µ.------<!'>-!-+-----!,"'-,
-+~ --~--++
E
~ \\.r i )j
~ 0.020' -t--~-+-----w-t----+---¥----_,,_---,,-"<-++--+---<>/ ---+---e--
oo 0.010 _, ___________________ _
- 0. 000 +++++++++++++++++++++++++++-H-+-1-+-Hl-+-Hl-+-HH-+-IH-+-IH-+-lf-++-jH-+-l-f-H~
2012 2013 2014 2015
. 2016 2017 Year Location E-2, monthly averages 2012-2016 0.050
\\-. -
0.040 0.030
("I)
- ~
~I E
f ~
C3 0.020 i
- a.
~~
0.010 0.000 2012 2013 2014 2015 2016 2017 Year D-2
(
("')
E
~
(..) c.
(-
("')
E
~
(..) c.
(
POINT BEACH Air Particulates - Gross Beta Location E-3, monthly averages 2012-2016 0.050 0.040 0.030 0.020 0~
0.010 0.000 2012 2013 2014
. 2015 2016 0.050 0.040 0.030 0.020 0.010 Year Location E-4, monthly averages 2012-2016
\\\\
I
\\*
2017 0.000 +++++-+++-+++-+++-+++-+++-++++++++++++++++++++++++++++++++++++++++~
2012 2013 2014 2015 2016 2017 Year D-3
l...
\\
('t)
E
-. u c..
POINT BEACH Air Particulates - Gross Beta Location E-8, monthly averages 2012-2016 0.050 0.040 f ~
0.030 I
~
~,~
0.020
~
0.0*10 0.000 ++-t-+++-~H-H-+-+++++-~H-H-+-++++-t-+++-H-+-t-+-H-++t-+-++++++++-H-H-+HI 2012 2013 2014 2015 2016 2017 Year Location E-20, monthly averages 2012-2016 0.050 fa.
0.040 -<-------rl-->..---------------
\\
\\
C') 0.030 ----r-~----;-t-7";--:---r-----,,..-<e-----;-----t>
E
~.J \\
~. 0.020 +--~~-~14--~~~~"'-+t--;..--f-__.o'.._~~.!p--"--
~
0.010 -!-------------------
- 0. 0 0 0 1-+++-+-+++-1-+-+-t-+++++-+-+-+-+-<l-+-+-t-+-t-+++-+-+++-t-++-i-++-+-+-+-1-+-+-+--<t-++-l-+-+-t-++-+-t-t-H 2012 2013 2014 2015 2016 2017 Year D-4
POINT BEACH NUCLEAR PLANT APPENDIX E Supplemental Analyses c*
POINT BEACH NUCLEAR PLANT
(
Facade Wells Units:== pCi\\L Gamma isotopic analysis Location GW-09 1Z-361A GW-09 1Z-361B GW-10 2Z-361A GW-10 2Z-361B Collection Date 01-22-16 01-22-16 01-22-16 01-22-16 Lab Code EWW-334 MDC EWW-335 MDC EWW-336 MDC EWW-337 MDC Be-7 5.1 +/- 10.2
< 28.8
-9.1 +/- 12.3
< 26.4 6.4 +/- 11.1
< 33.5
-3.2 +/- 10.0
< 23.6 Mn-54
-0.4 +/- 1.2
< 2.1
-0.6 +/- 1.2
< 1.9 0.0 +/- 1.4
< 2.3 0.8 +/- 1.3
< 2.7 Fe-59 2.8 +/- 2.2
< 6.5
-1.1 +/- 2.5
< 4.6
-0.6 +/- 2.4
< 5.9
-2.2 +/- 2.3
< 4.8 Co-58
-0.2 +/- 1.3
< 2.8 0.4+/-1.2
< 2.3 0.5 +/-1.3
< 3.0 1.2+/-1.3
< 3.0 Co-60 0.2 +/- 1.3
< 1.7 0.7 +/- 1.2
< 2.0 0.5 +/- 1.4
< 2.7
-0.2 +/- 1.4
< 1.9 Zn-65 1.6 +/- 2.4
< 4.7
-5.6 +/- 3.1
< 4.2
-1.9 +/- 2.7
< 4.9 1.5 +/- 2.6
< 4.8 Zr-Nb-95
-0.3 +/- 1.3
< 2.9
-0.6 +/- 1.3
< 3.3
-4.3 +/- 1.5
< 4.2
-2.2 +/- 1.4
< 2.8 Cs-134
-0.6 +/- 1.2
< 2.4
-0.5 +/- 1.3
< 2.6
-2.7+/-1.5
< 2.6
-0.8 +/- 1.3
< 2.5 Cs-137 0.3 +/- 1.5
< 2.7 0.2 +/- 1.5
< 2.7
-0.9 +/- 1.5
< 2.5 2.6 +/- 1.5
< 2.9 Ba-La-140 2.1 +/- 1.4
< 5.9 0.1 +/- 1.4
< 6.2
-1.9 +/- 1.7
< 6.0
-5.3 +/- 1.5
< 6.2 Location GW-09 1Z-361A GW-09 1Z-361B GW-10 2Z-361A GW-10 2Z-361B Collection Date 04-19-16 04-19-16 04-19-16 04-20-16 Lab Code EWW-2520 EWW-2521 EWW-2524 EWW-2525 Be-7
-9.7 +/- 11.1
< 28.5 0.4 +/- 10.8
< 39.0
-6.3 +/- 11.2
< 34.7
-0.7 +/- 13.3
< 36.2 Mn-54
-1.8+/-1.4
< 2.3
-0.2 +/- 1.4
< 2.0 0.8 +/- 1.4
< 3.2 1.1 +/- 1.7
< 3.6 Fe-59
-1.0 +/- 2.5
< 6.0
-0.9 +/- 2.6
< 7.6 7.0 +/- 2.7
< 11.0 1.2 +/-3.0
< 10.0 Co-58 0.2 +/- 1.4
< 2.5 0.1 +/- 1.4
< 3.8
-0.1 +/- 1.4
< 3.7 1.7 +/- 1.6
< 5.0 Co-60
-0.4 +/- 1.5
< 2.7
-0.8 +/- 1.5
< 2.6 1.0+/-1.6
< 3.3 1.9 +/- 1.8
< 3.3 f--
Zn-65 0.0 +/- 2.7
< 5.9 0.9 +/- 2.4
< 4.5 1.5 +/- 2.7
< 5.2 1.1 +/- 3.3
< 7.4 Zr-Nb-95
-1.1 +/- 1.5
< 5.9
-0.1 +/- 1.4
< 5.5
-2.3 +/- 1.5
< 4.8 2.3 +/- 1.7
< 6.1
-\\--
Cs-134 0.0+/-1.5
< 2.8
-0.2 +/- 1.4
< 2.6 0.0 +/- 1.4
< 2.6 0.6 +/- 1.7
< 3.2 Cs-137 2.2 +/- 1.5
< 2.9 0.9 +/- 1.6
< 3.0 1.2 +/- 1.6
< 3.1
-0.3 +/- 1.9
< 2.9 Ba-La-140
-6.2 +/- 1.6
< 15.1
-4.4 +/- 1.6
< 19.0 a
-5.0 +/- 1.6
< 20.6 a
-0.7 +/- 2.0
< 31.7 a
Location GW-09 1Z-361A GW-09 1Z-361 B GW-10 2Z-361A GW-09 1Z-361A Collection Date 05-02-16 05-02-16 05-02-16 07-16-16 Lab Code EWW-2522 EWW-2523 EWW-2526 EWW-4018 Be-7 16.5 +/- 13.5
< 36.3 9.5 +/- 12.1
< 26.3 4.1 +/- 10.8
< 29.5 3.4 +/- 13.6
< 33.5 Mn-54
-0.4 +/- 1.4
< 2.2 0.6+/-1.3
< 2.3
-0.6 +/- 1.3
< 1.8
-1.1 +/- 1.5
< 1.8 Fe-59
-2.5 +/- 3.0
< 7.0 0.1 +/- 2.5
< 6.9
-3.0 +/- 2.4
< 7.1 1.8 +/- 2.8
< 5.3 Co-58 0.1 +/- 1.4
< 3.4
-0.3 +/- 1.2
< 3.1 1.7 +/- 1.3
< 3.7
-0.4 +/- 1.4
< 2.8 Co-60 1.0 +/- 1.4
< 2.3
-0.7 +/- 1.5
< 1.8 0.9 +/- 1.4
< 2.7
-0.8 +/- 1.4
< 2.8 Zn-65
-2.2 +/- 3.1
< 6.0
-1.1+/-2.3
< 4.1
-1.1 +/- 2.6
< 4.4 0.6 +/- 3.0
< 5.4 Zr-Nb-95
-2.6 +/- 1.5
< 3.1 0.7+/-1.4
< 4.8
-0.5 +/- 1.4
< 4.6 0.1 +/- 1.5
< 3.6 Cs-134
-0.3 +/- 1.5
< 3.1
-0.7 +/- 1.3
< 2.6
-0.7+/-1.4
< 2.5 0.1 +/- 1.5
< 3.2 Cs-137 1.4 +/- 1.6
< 3.1 1.6 +/- 1.5
< 2.8 0.1 +/- 1.5
< 3.1 0.7 +/- 1.6
< 3.0 Ba-La-140
-1.5 +/- 1.5
< 6.4 5.4 +/- 1.6
< 12.6
-3.4 +/- 1.4
< 8.2
-3.9 +/- 1.6
< 6.1 LLD for La-140 nor reached due to age of sample and smaller sample size; samples counted for 60,000 seconds.
r-
\\..
E-2
POINT BEACH NUCLEAR PLANT
/f" Facade Wells L
Units: = pCi\\L Gamma isotopic analysis Location GW-09 1Z-361B GW-102Z-361A GW-10 2Z-361B GW-091Z-361A Collection Date 07-16-16 07-16-16 07-16-16 10-15-16 Lab Code EWW-4019 MDC EWW-4020 MDC EWW-4021 MDC EWW-5889 MDC Be-7 10.3 +/- 10.5
< 24.9 10.8 +/- 12.1
< 34.0 0.1 +/- 10.2
< 24.5 8.0 +/- 10.5
< 24.7 Mn-54 0.6 +/- 1.3
< 2.9 0.4 +/- 1.3
< 2.8 0.7 +/- 1.2
< 2.3 0.5 +/- 1.4
< 2.7 Fe-59
-1.7 +/- 2.4
< 5.9
-1.0 +/- 2.3
< 5.2
-2.3 +/- 2.2
< 4.2
-1.9 +/- 2.3
< 6.1 Co-58
-1.1 +/- 1.3
< 1.8 0.6 +/- 1.2
< 2.7
-0.5 +/- 1.2
< 1.9 0.3 +/- 1.3
< 1.7 Co-60 0.7 +/- 1.4
< 2.8
-0.7 +/- 1.3
< 1.8
-0.5 +/- 1.4
< 1.6 0.4 +/- 1.4
< 2.1 Zn-65 0.9 +/- 2.5
< 5.0 1.6 +/- 2.5
< 5.3 1.4 +/- 2.3
< 3.9
-0.1 +/- 2.7
< 5.5 Zr-Nb-95 0.0 +/- 1.5
< 3.7
-0.3 +/- 1.3
< 3.1 0.3+/-1.3
< 3.4 0.8 +/- 1.4
< 3.1 Cs-134
-0.3 +/- 1.4
< 2.6 0.7 +/- 1.4
< 2.6
-0.9 +/- 1.3
< 2.4
-0.5 +/- 1.3
< 2.4 Cs-137 0.2 +/- 1.5
< 3.0
-0.6 +/- 1.4
< 2.4
-0.5 +/- 1.5
< 2.6 0.8 +/- 1.5
< 2.8 Ba-La-140
-2.8 +/- 1.6
< 7.3
-2.3 +/- 1.6
< 8.2
-5.4 +/- 1.3
< 4.1
-2.7 +/- 1.5
< 4.5 Location GW-091Z-3618 GW-10 2Z-361A GW-102Z-3618 Collection Date 10-15-16 10-15-16 10-15-16 Lab Code EWW-5890 EWW-5891 EWW-5892 Be-7
-4.9 +/- 13.1
< 20.5
-3.8 +/- 11.7
< 26.5 10.6 +/- 10.0
< 22.6 Mn-54 0.0 +/- 1.4
< 2.9 1.2 +/- 1.1
< 2.1 0.3+/-1.3
< 2.5 Fe-59
-0.7 +/- 2.7
< 6.2
-0.1 +/- 2.2
< 5.5
-0.8 +/- 2.2
< 6.1 Co-58
-0.1 +/- 1.3
< 3.3 0.1 +/- 1.2
< 2.6 0.4 +/- 1.2
< 3.2 Co-60 3.1 +/- 1.4
< 2.4
-0.2 +/- 1.4
< 2.2
-1.5 +/- 1.4
< 2.0 Zn-65
-0.8 +/- 2.9
< 4.9
-2.0 +/- 2.4
< 3.5
-0.4 +/- 2.7
< 5.3 t
Zr-Nb-95 0.3 +/- 1.4
< 4.5
-0.8 +/- 1.3
< 3.7 1.8+/-1.3
< 4.0 Cs-134 1.3 +/- 1.4
< 3.0 0.4 +/- 1.3
< 2.4
-0.7 +/- 1.2
< 2.3 Cs-137 0.6 +/- 1.6
< 2.8 0.0 +/- 1.5
< 2.5 0.5 +/- 1.4
< 2.9 Ba-La-140
-1.9 +/- 1.5
< 7.6 1.6 +/- 1.4
< 6.6
-3.1 +/- 1.4
< 5.2
(
E-3
POINT BEACH NUCLEAR PLANT L
Supplemental Analyses Units: = pCi\\L Gamma isotopic analysis Location U2FSSDS U2FSSDS U2FSSDS Collection Date 01-31-16 02~29-16 04-01-16 Lab Code EW-1029 MDC EW-1030 MDC EW-2204 MDC Be-7
-12.2 +/- 11.8
< 26.8 13.6 +/- 13.9
< 35.0
-3.3 +/- 9.8
< 34.4 Mn-54 0.8 +/- 1.3
< 2.5 0.6 +/- 1.3
< 2.9 0.0 +/- 1.3
< 2.8 Fe-59 0.6 +/- 2.2
< 6.2
-2.2 +/- 2.8
< 4.5
-0.1 +/- 2.2
< 8.8 Co-58 0.6 +/- 1.2
< 2.8 0.4 +/- 1.3
< 2.7
-0.1 +/- 1.2
< 2.3 Co-60 0.3 +/- 1.4
< 2.3 0.3 +/- 1.4
< 3.3 0.7 +/- 1.4
< 3.1 Zn-65
-0.8 +/- 2.5
< 4.8 2.0 +/- 2.9
< 5.7 1.0 +/- 2.5
< 4.5 Zr-Nb-95
-0.5 +/- 1.3
< 5.8 0.0 +/- 1.4
< 3.0 1.8 +/- 1.3
< 5.8 Cs-134
-1.1 +/- 1.3
< 2.6 0.4 +/- 1.4
< 2.9 0.2 +/- 1.3
< 2.4 Cs-137 0.1 +/- 1.4
< 2.7 0.6 +/- 1.5
< 2.6
-0.7 +/- 1.5
< 2.4 Ba-La-140 7.4+/-1.4
< 26.0 a
-1.1 +/- 1.5
< 2.7 0.6 +/- 1.6
< 17.2 Location U2FSSDS U2FSSDS U2FSSDS Collection Date 04-25-16 05-31-16 06-30-16 Lab Code EW-2503 EW-2922 EW-3615 Be-7
-7.1 +/- 13.3
< 19.0
-1.3 +/- 13.6
< 28.9 0.3 +/- 11.0
< 21.6 Mn-54 0.6 +/- 1.4
< 2.8
-1.2 +/- 1.3
< 1.8 1.0 +/- 1.3
< 2.5 Fe-59
-0.3 +/- 2.7
< 4.7
-1.3+/-2.8
< 5.5 0.6 +/- 2.4
< 4.8 Co-58
-1.7 +/- 1.4
< 1.8 1.6 +/- 1.3
< 2*.5
-0.2 +/- 1.3
< 1.9
(
(
-1.0 +/- 1.5
< 1.8 0.6 +/- 1.4
< 2.8 0.9 +/- 1.4
< 2.7 Zn-65 2.3 +/- 3.0
< 5.7 1.3 +/- 3.0
< 4.7
-1.1+/-2.7
< 4.3 Zr-Nb-95
-1.5 +/- 1.5
< 2.6
-0.6 +/- 1.5
< 3.5
-1.6 +/- 1.4
< 3.4 Cs-134
-0.7 +/- 1.5
< 3.1
-0.3 +/- 1.4
< 3.0
-1.4 +/- 1.4
< 2.6 Cs-137 1.1 +/- 1.5
< 2.6 1.6 +/- 1.5
< 3.o*
0.4 +/- 1.5
< 3.1 Ba-La-140
-3.5 +/-.1.6
< 5.1
-1.4 +/- 1.5
< 2.4
-2.7 +/- 1.5
< 4.7 Location U2FSSDS U2FSSDS U2FSSDS Collection Date 07-31-16 08-31-16 09-30-16 Lab Code EW-4285 EW-4908 EWW-5524 Be-7
-7.5 +/- 9.9
< 21.9
-0.9 +/- 10.2
< 27.8 2.6 +/- 10.0
< 27.7 Mn-54
-0.4 +/- 1.3
< 1.9 0.3 +/- 1.3
< 3.0 0.5 +/- 1.2
< 2.4 Fe-59
-0.3 +/- 2.1
< 4.7
-1.4 +/-2.2
< 4.9
-2.2 +/-2.1
< 3.1 Co-58 0.2 +/- 1.2
< 2.9 0.2 +/- 1.2
< 2.8 0.1 +/- 1.3
< 2.3 Co-60 0.5 +/- 1.3
< 2.3 0.1 +/- 1.3
< 2.0 0.5 +/- 1.4
< 2.7 Zn-65 1.3 +/- 2.5
< 5.2
-0.6 +/- 2.5
< 4.7 0.2 +/- 2.3
< 3.7 Zr-Nb-95 0.4 +/- 1.3
< 3.3 0.9 +/- 1.3
< 4.4
-0.6 +/- 1.3
< 3.5 Cs-134
-1.0 +/- 1.3
< 2.4 0.4 +/- 1.3
< 2.5
-0.5 +/- 1.3
< 2.3 Cs-137 1.8 +/- 1.5
< 3.1 0.7 +/- 1.5
< 2.8 1.9 +/- 1.5
< 3.1 Ba-La-140 3.8 +/- 1.4
< 6.3
-9.0 +/- 1.6
< 11.5
-0.7 +/- 1.5
< 6.2
- LLD not reached due to age of sample; sample received 03-11-16.
f
(
ji r
1:,
E-4 L
POINT BEACH NUCLEAR PLANT
(
Supplemental Analyses Units: = pCi\\L Gamma isotopic analysis Location U2FSSDS U2FSSDS U2FSSDS Collection Date 10-31-16 11-30-16 12-31-16 Lab Code EW-6393 MDC EW-6753 MDC EW-7079 MDC Be-7
-5.2 +/- 10.6
< 27.2 1.4 +/- 10.3
< 29.2 7.8 +/- 14.2
< 28.8 Mn-54
-0.2 +/- 1.4
< 3.1 0.7 +/- 1.2
< 2.6 0.3 +/- 1.5
< 2.3 Fe-59
-2.1 +/- 2.3
< 2.9 2.2 +/- 2.1
< 5.0 0.6 +/- 3.0
< 6.0 Co-58
-0.2 +/- 1.2
< 2.3 0.5 +/- 1.3
< 2.9 0.5 +/- 1.4
< 2.5 Co-60
-0.6 +/- 1.4
< 2.8
-1.1 +/- 1.4
< 2.0 0.9 +/- 1.5
< 2.1 Zn-65
-0.9 +/- 2.6
< 3.5 0.5 +/- 2.3
< 3.5
-2.1 +/- 3.2
< 5.0 Zr-Nb-95 0.7 +/- 1.4
< 2.8 0.7 +/- 1.3
< 3.4 1.2 +/- 1.5
< 4.1 Cs-134
-0.6 +/- 1.4
< 2.8
-0.7 +/- 1.3
< 2.3 0.4 +/- 1.4
< 3.0 Cs-137 1.0 +/- 1.5
< 2.1 0.2 +/- 1.5
< 2.5
-1.0 +/- 1.7
< 3.6 Ba-La-140 3.1+/-1.5
< 8.6
-5.8 +/- 1.5 *,
< 3.9
-2.0 +/- 1.4
< 3.7 Annual Mean +/-
s.d.
Be-7
-1.0 +/- 7.0 Mn-54 0.3 +/- 0.6 Fe-59
-0.5 +/- 1.4 c-Co-58.
0.2 +/- 0.8 Co-60 0.2 +/- 0.7 Zn-65 0.3 +/- 1.4 Zr-Nb-95 0.0 +/- 1.1 Cs-134
-0.4 +/- 0.6 Cs-137
-0.2 +/- 3.1 Ba-La-140
-0.8 +/- 4.4
(
E-5
POINT BEACH NUCLEAR PLANT APPENDIX F Special Analyses f--
(
F-1
I \\
/
1,
\\
Dr. Kjell Jotian~n Point Beach Nuclear Plant
~10 Nuqlear.Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1178 DATE:
03-31-16 SAMPLE$. RECEiVED:---._,0'"""3--1""""1---16"'---
Analyses for tritium and gamma emitling isotopes.
lab Code EXW-1031 Date Collected 01.0.7-16 location We,st Digester
.Isotope MOC I Corice~tratibn (pCi/L)
Required LLb H-3
< 15Q.
6S+/- 82 200 K-40 81.. 2. +/- 18.5 Mn-5.4
< {2
-0.4 +/- 0.6 10 Co-58
< 2.0 0.4 +/- b.6 10
.co.So
~-.
1.9 +/- 0.9 ~
10 Fe-59
< 4.1
.:Q.6 +/- 1 :1 30 Zn-6.5
< 2.2
-0.4 +/- 1.2 Zf*Nb-95
< 3.6 0.2 +/- O.~
15 Ri.1-103
< 3A.
0.. 1 +/- 0.5 1-1 ~1
< 277.0
-66.7 :+/- 0.6 Cs'-134
< 0.9.
0,1 :!: Q,6 10 os-131
<LO 0.? +/- 0.7 10 Ba-La*140
< 24,3a
-12.9 +/- 0.6 15 Ce-141
< 7.9
-2.9 +/- 4.6 Ce-144
< 10.2
-1.7 +/- 1.0
'Tl~208
< 1.7 2.2 +/- 0.7 Si-212
< 18.7
-4.2 +/- 8.3 01.214
< 3.1 7.5 +/- 1.5 Pbc212
< 2.4 3.7 +/- f o Pb-214
< 3.4 5.0 +/- 1.4 Ra-226
< 29.8 87.3+/- 14.0 Ac.228
< 5.2 8.3 +/- 2.4 U-235
< 1.5
-4..2 +/- 0.8 Less than (<}, value is based on a 4.66 sigma countln_g error for the background sample and it's the MDC value for this measurement The err9r given is* the probabie coui)ting error at 95% confidence level.
0 Required LLD not met due to the sample age. The sanipl.e was counted on the pay receiveq for 60,000 sec.
D recCOUr'Jt On the diffferenl detecto~: 3, 7 +/- 1.3 ppifl.
Appr9ved:
i l I i I l
i r
1' f
/
[; \\ __ -
/~
I,
\\
Dr. Kjell Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1176 DATE: ---=03=-_=08=--..,..,16~
SAMPLES RECEIVED:
02-26-16 Analyses for tritium and re-analysis for gamma emitting isotopes.
Lab Code EXW-763 Date Collected 02-17-16.
Location Sewage Digester East Isotope MDC I Concentration (pCi/L)
< 172 99 +/- 87 200 K-40
< 69.6 286.8 +/- 28.7 Mn-54
< 3.2
-0.4 +/- 1.6 10 Co-58
< 2.4
-1.9 +/- 1.6 10 Co-60
< 4.3 1.1 +/- 2.0 10 Fe-59
< 8.2 0.9 +/- 3.0 30 Zn-65
< 5.2
-1.5 +/- 3.2 30 Zr-Nb-95
< 5.2
-1.3 +/- 1.8 15 Ru-103
< 4.7 1.6 +/- 1.4 1-131
< 20.0 1.2 +/- 1.6 Cs-134
< 2.4
. -0.8 +/- 1.6 10 Cs-137
< 3.2 1.2 +/- 1.9 10 Ba-La-140
< 10.8
-4.9 +/- 1.9 15 Ce-141
< 7.2
-4.4 +/- 2.4 Ce-144
< 17.5 0.9 +/- 1.1 Tl-208
< 4.2 5.0 +/- 2.1 Bi-212
< 6.5 19.7 +/- 23.2 Bi-214 14.0 +/- 5.2 Pb-212
< 6.5 11.6+/-3.0 Pb-214 14.2 +/- 8.0 Ra-226
< 79.9 224.9 +/- 36.0 Ac-228
< 12.0 7.9 +/- 6.6 U-235
< 4,1
-11.8+/- 2.1 Less than (<), value is based on a 4.66 sigma counting error for the background sample and it's the MDC value for this measurement. The error given is the probable counting error at 95% confidence level.
Approved:
(
(
Dr. Kjell Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two*Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -11'77 DATE:
04-.12-.16 SAMPLES RECEIVED: ----=o"'"3--,:,28"'"'-..,.,16=--
CORRECTED REPORT Analyses for tr1ti1.,1m and gamma emittihg isotopes.
LabCo(le EXW-1214 Date Collected 03-22-16 Loqation Sewage Digester West a Isotope MOC i Concentration.(pCi/L)
Required.LLD.
< 145 107 +/- 78 200 K~40 104.4 +/- 49.1 Mn-?.4
< 3.5 0.2 +/- 1.6 10 co~58
< 2.2
-1.6 +/- 1.9 10 CO-SQ
< 2:9 0.6 +/- 2.2 10 Fe-59.
< 3.5 0.4 +/- 3.5 30 Zn-65
<4.7
-o.e +/- 3.. 3 30 Zr-Nb-95
<3A o.*1 +/- 2.0 15 Ru-103
< 3.9 0.1 +/- 2:1 J.::131
.,, 7.6
-0.7 +/- 1:8 os-134
< 3.t1 0.7 +/- 1.8 10 ds-137
< 3.~
0.3 +/- 2.. 0 10 Ba-La~140
< 1-.8
-4.? +/- 2.1 15 Ce-141
< 8.0 0.9 +/- 3.2 Ce-144
< 26.1
-1.5 +/- 14.6 Tl-208
< 4.4 3.1 +/- 2.3 Bi-212
< 3.4 7:0 +/- 19.8 Bi*~14
< 10.8 8.Q +/- 5.:0 Pb-212
<: 8.2 9.1 +/- 3.f;)
Pb-214.
< 11.3 8.~ t 4.~.
<:: 100.6 14.7 +/- 42.9 Ac-228
< 14.6 4.9 +/- 6.0 U-23$
< 4.8 0.0 +/- 2.8 Less than(<), value is based on a 4.66 sigma counting error for the background sample and it's the MDC value for this measurement. The error given is the probable c~>Unting error at 95% confidence level.
Approved:
QA Manager I
I l
f f I t I J
I I
I t r;
j:
v i:
I'.
1 1;
1!
!i
(~
(
Dr. Kjell Johanse.n Point Beach Nucle.ar'Plant 661 O Nuclear Road Two Ri11ei-s, Wisconsin 54241 LABOR/ffORY REPORT NO.:
8008*100 -1179 DATE: -----;;U;.;4*.,.,:,1~3~-;.16~
SAMPLES RECf::IVEO: __
__;0;...:4...;;~0;.,:.1--"1.;:,.6 _
Analyses for tritium and.gC!miTia emitting isotop!'!S.
labCooe EXW-1305 Date Collected 03c2{1-16 LocatiOn Equalization Tank.
Isotope MDC/ Concentration {pCi/L)
< 152 223 +/- 87 200
.K-40
< 77.6 213.7 +/- 38:5 Mn-,54
< 4.1
-0.4 +/- 2.1 10 Co,:Pa
< 3,5
-0.2 ;I: 1.8 10 Co-6.0.
< 3.0
-0.6 +/- 2:3 10 Fe-59
< 8.4 1.6 +/- 3.6 30 Zn-65
< 6.1 0.2 +/- 4.. 0 zr~Nb-95
<4.9 1.8 +/- 2.2 15 Ru*.103
< 4.4 0.4 +/- 1.9 l".'131
< 8.2
.* o.7 +/- 1.9 Cs-134
< 2:6.
-2.1 +/- 2.1 10 Cs-137
< 3.6
--0.6 +/- 2.4.
10 Ba-ta-140
< 4.s
-1.4 +/- 2.2 15 Ce-141
< 7.9
-3.5 +/- 3.3
,Ce~144
< 27.4
-1:a :1: 1.5 Tl-208
< 5.3 2.6 ;I: 2.3 Bi-212
< 52.2' 41.8 ;I: 2£.8 Bi-214
< 11.9 2~.2 +/- 5:6 PJr212
< 8.5 1:0.6 ;I: 3.8 Pt;.;214
< 12.s 19.4 +/- 5.4
'Ra*226
< 109.4 1~1.1 ;I: 49.7 Air228
< 17.7 7.1 +/- 8.1 U.2;3l)
< 5.6
-11.6 +/- 3.2 Less than(<}, value is b<1sed on a 4.6..6 sigma counting er,ror for the background sample and i.t's the MDC value for this measurement. The error given is the probable counting error at 95% confidence level.
Appi:9ved:
I I
I
.\\
- l. ;
I I
(
f
\\.
(
Dr. Kjell Johansen Point B~~ch Nu~~,ar plant 6610 Nuciear ~Oad Two Rivers; Wl~corisin 54241 LA~~TORY REPORT NO.:
aoo~tO:Q. *118-0.
DATE:
- .04.-,22-16 SAMPLES Rl=CEIVED:*-. _
_...__,-04"-i'..Q~*."'7-.-.16,;;o.. -
Analyses for tritium and gamma emittirlg isotopes.
Lab Code l;XW-'1467 P~te Collected 03-30-16.
Location Equali~~tJ(>n Basin Isotope MOC l Concentration {pCi/L)
R$QUire!1 LlO H-3
< 1.42 29Q +/- 86 200 K-40
< 111.0 155.3 '* 55.9 Mn-54
<4.7 b.8+/- 2.6 m
Co"5$
<**4.5.
-0.2 ;f;..2..6 10 co,60
<2,6
-2.1 :I: 2.9.
1.0 Fe:.:59
<:a.9 0.5 :I: 5.2 30 Zil-65
~ 10.2 6.2 *:1: 5,9 Zr-Nb:-95
< 6.2
.o.~ t: 3,£!
15 Ru-1D3
<4.9
-1:5 ! 2,4 1~131-
< 16.2 9,9 ~ 2,9 CS-134
,.;4.9 t.o :1: *a.2 10 Cs-1:37
< 5.,&
3.6 t $:3 10 Ba-J..a-140
<6.8
-4,6 +/- 4,o 15 Ce-.141
< 1Jl.~
2.3 t *4.8 Ge-144
< 31.5
-9.4 :t 22.7 Tl:-208
< 7<.8 5:2 +/-, 3.4 Bi-212
< *ao.4 19.8 :t 41.1 l:li-214
< 18.3
.29.9 :t; RO fi,p:.212 it:: *12.8
- 12.4 +/- *5:9 P-6~214
- < 19;1
_2~.Q ~ 8,6 Ra-226
< 161.1 215:2.f 73.2 Aq,.2~8
< 24.1 14.;i +/- 11-4 U-2~*
< 7.6
-.11.5 +/-. 4.6 Less than (<), vah.le is ba~d on a 4:66. sigma eo.~nting error for the badkground sample and it's the MDC value for this measurement. The error given is ih~ pr~baP.Je coµntirig e.frQr at 9$% CQnfi~ri~ level.
E-mail: Kjell.Johansen@nee.com E-majl: $ophia.Ba~el~@riee.corri Approved:
I I
I I ' i l
(
.~
(
I \\,
Dr, K.iell.Johansen PO,iryf 13,e.ac!J NlicJ~ar Planf.
6610 Nuclear Roap TwQ Rlvers;Wisconsin 54241 l.A!;IORATORY REPOR)" N:O.:
aooe~100 *1.181 DATE;.
Q4:.22~16
$Af\\/iPi.E$ RECEIVE;D:.;.....o..-.-.....;;0;.;,4-""'0""1~~16;:;.._ -
AOaly~es for tritium and gamm.a emitting isotopes.
Lab Code Pate Coilected Lotion
~sote>pe H*S K-40 i\\/ln-54
- co~sa Co;QO Fe:.59 Z""'65
- Zr-Nb-95 RiM03" Ha1..
Cs-1;34 Cs~137 Ba*la-140 c~1-41
- qe-..144 ri-20.e s;.212 Bi-214.
p~~12 Pb*214 Ra-226 A-c-228 U-235 EXW-14o9 04*01-16 Etjiia!~~tipn ~f!Sjh
.MDC I Concentration (pCill)
< 112.1
< -6:2
~*a.4
< 4.7
-< 5.6
- -;::: 10.0
< 4.6
<.6.*2
< 16, 1
- 4,0*
< 6,2
- i:; 7.2
< 1.0.5
<31:3
< 7.~
< 13,o
< 1-8.6
< 11.s
< 17.5
< 163.8
< ~5.{l
< 7:0 21e +/- ()~
1$q,o :1: 5.1.6
-1.0 :I: 2.:9 4.:1 ;!; ~,9.
1.2 +/- 3.3
-1.:2 +/- 6.0 1.9 +/- 6.6
-1..6 :!; 3.0
~{).. 2 :1: 2.0 0.. 3 ;i: 2:~
1.7 +/- 2.'7 2.8 :I: 3.3
-4.9 +/- 3:6
-1.2 +/- 5.0
-5.5 +/- 21.2
.5.2*:1: \\Hi 21.9.+/- 38.6 2~.7.+/- 8.1.
14:9 +/- 5:9 9.2 +/- 7.9 264.7 +/- 68.B 9.2 :t 11.2
-11.2 t 4.5 10
~()
10 30 15 10 10 15 Less. th~o (<), v;;ilue is based Qi'J ? 4.66 sigma coun~ing erroi:- for the bapkground sample <;1nd ifs ~he MDC v:;;iiue
- fot this measurement. The error given is the probable countin~ error.at.Q5% confidenpe lever E-mail; KJeii.J.ohansen@nee.cpm E-meiil: ~cip!1ia.~rt~ls@nf1!e.ci:>n°'
t I
f I' I/ i
fr-
\\"*
{
- t.
Dr. Kjell johansen LABORATORY REPORT NO.:
aoas;-100 -1183 Point Betich Nucli3ar Plant 6610 Nuclear Road DATE:
.04-26-16.
SAMPLES RECEIVED: --..... -..1'4-.,...
...,...16,,..,.,-
Two Rivers, Wis(;()nsin ?4241 Analyses tot tritium and for g~mma emitting isotop*es.
~P C:ode E;XW-1548 Date Collected 04-12-16 J._ocation Sew~ge [)igester East Isotope
'MDC /Concentration (pCill)
~ 147 2aa +/-ea
- 200 K-40
< 1.22.t 240.7 :I; 67.4 Mi'1"54
< 7.2 3.5 +/- ~.1 10 Co-5B
< 4.:9
.5.2
- 3,1:
1D Co-SO
<: 5;3
-1;0 +/- 4,2 10 fe-:59
< 4.9
-14.5 +/- 6.3 30 Zn-65
< 8,2
-0.4 +/- 5.5 30 Zr-Nb-95
- c 6.8 0,2 +/- 3.8.
15 Ru-103
<; 4.1
-0.2 :I: 2:9 1-131
'< 5.7
-3;3 ;!; 3,0 Cs-134
< 4:5 "0.~ +/- 3.3 10 Cs-137
< 6.3
.0.3 ;I: $.8.
10 ea~L~-140
< 3.5
-3.4 +/- 3.3 15 Ce*141*
< 1o.o 3.0 :I: 5.2 Ce-144
< 30.7 2.7+/- 2.2 Tl,208
< 7.5*
4,3 +/- 3,6 Bi-212
< 76.1 44.3.+/- 40.8 ai,2:14
< 18.2
.25.7 +/- 9:2 Pb~212
< 13.5 11.3 :I: 6.3 Pb-2f4
< 18.7 19:a *::1:. a.7 Ra-226
< 157.3 198.5 :I: 75.4 Ac-228
<'27.8
'16.1 :I: 13.8 u.235
< 6.7
-11.3 +/- 4,7 Less than(<), vah,ie is based pn a 4.613 sigma counti!'li:J etrc;ir for the baCkground sample a.nd it's the MDC value for this measurement. The error given is the probable counting error at 95% confidence level.
E-mail: Kjell.Johanseri@nee.com
- E*mail: Sophia.Bartels@nee.com Forrest G. Shaw Ill Quality Ass1Jrance Approved:
I I
f l l I
I. I
- f I!
~
/,
~
ll t
1"'~~~-
t..
(
Ot. Kjell Johansen Point Beciqh Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241
- LABORATORY REPORT NO.:
- 8006-100 -1169 DATE:.
05-31-16 SAIViP!-ES REC.ENED: ----=o"'"s-=20-,,...* """16,.--
Analyses for tritium and gamma emitting isotopes.
Lab Code S<Jl\\/-2491 Date Collected.
os.-06-16 Location Eq4ali~.atiori Tank Isotope Moc I CQncentraticm (pCill.)
Required Lt,D.
< 14$
87 +/- 77
- 200 K-40
< 52.2 1.63.1 :!; 22.8 1111.n~~
< 2,4
'"'0.6-+/- 1.2 10 Co-58
< 2.8
-2.4 '* 1.2 10 Co-60
< 2.2
-0.7 :t 1.3 10 F~-59
< 5.4
-'0.5 +/- 2.3 30 Zn-65
< 4.3
-1.5 +/- 2.5 i:r-Nb-95
< 3:2 1.1 +/- 1.3 1?
Ru-103
< 3.2 0.2 +/- 1 :1 1-131
< 9~6
~1,9 +/- 1.2 C$~134
<::.2.1 0.1 +/- 1.2 10 os-137
< ~
.* 5 1.3 +/- 1.4 10*
Ba-La-140
< 6:0
-1.5 +/- 1.5 15 CE!-141
< 5.6
-0.2 +/- 2.1 ce:-144
< 15.2
.11.7 :t 8.8 11-208
< 3.5 3.* 3 ii: 1.5 Bi-212
< 38.9 13.8 :t 18.4 Bi-214
< 7-fj 12.0 ~ 3:1 Pb.212
< 5.5 8.3 +/- 2.3 Pb~21.4
<: 7.4 11;9 +/- ~-1 Ra-221:1
< 70.7 220.6 +/- 30.9 Ac-228
<. 10.3 14.9 +/- 4:7 U~235
< 3.8
-10.1 +/- 2.0 less than.(<), val1,1e is based on a 4.66 sigma counting error for the *background sample and it's the MDC value for this measurement. The error given is the probable counting err-0r at 95% confidence l~vel.
E-mail: Kjell.Johanseli@nee.com E-mail: Sophia. Bartels@riee.'t:pm Approved:
.Forrest G. Shaw 111 Quality Assuranee I
1 I I I
I
(
(
~
(
\\
Dr. Kjell Jotiansen LABORATORY REPORT NO.:
8006-100 -1192 Point Beach Nuclear Plant 6610 Nuciear'Road DATE:
,06-15-16 SAMPLES RECEIVED:--~0~6--1~0-~16-Two Rivet~, Wisconsin 54241.
Analyses for tritium.and gamma emitting isotopes.
lab Code EXW-2~21 Date ~ollected 05-18.16 L6c~tion west Digester Isotope MDC I C.oncentrati.on (pCill)
Regulred LLO H-3
< 157 W2 +/- 10.3 200 K-40 83.9 +/- 39.0 Mn-54
< 2.8 1.7 +/- 1.3 10 cq.;5s
< 3.6 2.1 +/- 1.4 10 Co'60
< 2.9 U.6 +/- 1.6 10 Fe*59
< 5.7
-f6 +/- 2.4
.30 Zn-65
< 5.1 1.5 +/- 2.6 Zr-Nb-95
< 4.4
-0.5 +/- 1:4 15 Ru-103
< 2.3
-1.1 +/- 1.2 1-131
< 16.3
-4.5 +/- 1.3' Cs~134
<1]
-1.B +/- 1.4 10 Cs,-1~7
<: 2.3 0.6 +/- 1.4 10 Sa~La-140
< 10.3 0.9 +/- 1.. 6 15 Ce-141
< 7.1
~1.7 +/- 2.1 Ce.-~44*
< 15.0 0.8 :!: 9.$
Tl-2()8
<: 3.4 6,9 +/- 1.9 Bi-212
<: 44.0 13.6 +/- 19.4 Bi-214
- 12.5 +/- 4.5 Pb-212
<: 6.2 11.. 8 +/- 2.5 Pb-214
<£.3 21.7 % 3.9 Ra-226
< 72A 205:8 +/- 32.9 Ac-228
< 13.$
11.0 +/-* 5.7 U-235
< 3.5
-8.3 +/- 2.0 Less than (<), value is base(:! ~:m a 4.66 sigma counting eri:or for the background sample and it's the MOC value for t.his measurement.. The error given is the probable counting error at 95% confidence level.
Approved:
l I I I I 1 i I I I
1 I f
i f
I* i r
I*
\\,
- t t~
~,
\\,
)l}~ ATn Environmental, Dnc.
~J'='\\U li Midwest Laboratory 700 LamJWP..'u Ro.'!Jd.. NGl?hbrPoh tL 600P2*::?310 Phone (647.i 554-0700
- foY f847.J 51.J.4517 Dr. Kjell Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1194 DATE:
07-27-16 SAMPLES RECEIVED: ---0~7::-_:;:.,15::-_.;-,16:--
Analyses for tritium and for gamma emitting isotopes.
Lab Code EXW-3614 Date Collected 06-20-16 Location Sewage Digester East Isotope MDC f Concentration (pCi/L)
< 144 151 +/- 80 200 K-40 166.5 +/- 39.1 Mn-54
< 2.6
-0.3 +/- 1.4 10 Co-58
< 3.5 0.0 +/- 1.4 10 Co-60
< 2.5 0.0 +/- 1.4 10 Fe-59
< 5.6
-0.3 +/- 2.4 30 Zn-65
< 4.1 1.1 +/- 2.4 30 Zr-Nb-95
< 3.9
-2.6+/-1.4 15 Ru-103
< 4.2
-0.3 +/- 1.2 1-131
< 30.0 7.3 +/- 1.3 Cs-134
< 1.8
-0.6 +/- 1.4 10 Cs-137
< 2.8 0.2 +/- 1.6 10 Ba-La-140
< 6.9 1.9 +/- 1.4 15 Ce-141
< 6.8
-2.7 +/- 2.1 Ce-144
< 20.7 6.3 +/- 9.4 Tl-208
< 3.5 4.4 +/- 1.7 Bi-212
< 38.3 20.8 +/- 18.3 Bi-214
< 12.8 31.9 +/- 3.8 Pb-212
< 5.9 15.1 +/- 2.6 Pb-214
< 13.2 30.9 +/- 3.7 Ra-226
< 69.1 193.7 +/- 31.0 Ac-228
< 13.1 13.1 +/- 5.7 U-235
< 4.3
-8.5 +/- 2.0 Less than (<), value is based on a 4.66 sigma counting error for the background sample and it's the MDC value for this measurement. The error given is the probable counting error at 95% confidence level.
E-mail: Kjell.Johansen@nee.com E-mail: Sophia.Bartels@nee.com Approved:
(
(
Dr. Kjelf Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1200 DATE:
09-07-16 SAMPLES RECEIVED: ---0.:..:9~-0.:..:1'--1..:...:6::..__
Analyses for tritium and gamma emitting isotopes.
Lab Code EXW-4539 Date Collected 08-25-16 Location West Digester Isotope MDC I Concentration (pCiJL)
< 192 64 +/- 118 200 K-40
< 123.5 223.6 +/- 62.6 Mn-54
< 7.0 1.3 +/- 3.2 10 Co-58
< 6.5 3.2 +/- 3.1 10 Co-60
< 4.6 0.9 +/- 4.3 10 Fe-59
< 12.0 7.1 +/- 6.2 30 Zn-65
< 10.9 0.8 +/- 6.1 Zr-Nb-95
< 4.9 1.6 +/- 3.3 15 Ru-103
< 3.4
-4.2 +/- 2.4 1-131
< 7.5 0.8 +/- 3.0 Cs-134
< 4.8 1.6 +/- 3.2 10 Cs-137
< 6.2
-3.9 +/- 3.9 10 Ba-La-140
< 4.7 0.7 +/- 3.8 15 Ce-141
< 11.0
-4.5 +/- 5.4 Ce-144
< 43.8 3.6 +/- 22.8 Tl-208
< 7.8 4.0 +/- 3.8 Bi-212
< 74.2 16.5 +/- 42.5 Bi-214
< 17.7 17.0 +/- 8.2 Pb-212
< 11.4 11.1 +/- 6.2 Pb-214
< 19.4 20.8 +/-.. 8.3 Ra-226
< 168.0 185.4 +/- 81.6 Ac-228
< 25.7 16.7 +/- 14.0 U-235
< 10.2
-8.2 +/- 5.4 Less than ( <}, value is based on a 4,66 sigma counting error for the background sample and it's the MDC value for this measurement. The error given.is the probable counting error at 95% confidence level.
Approved:
c_*
I
\\.
Dr. Kjell Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1201 DATE: ---..,...1 o=--2=0=--..,...16-SAMPLES RECEIVED:
09-22-16 Analyses for tritium and for gamma emitting isotopes.
Lab Code EXW-4953 Date Collected 09-20-16 Location Sewage Digester East Isotope MDC I Concentration (pCi/L)
< 183 143 +/- 92 200 K-40 193.5 +/- 93.7 Mn-54
< 4.9
-0.4 +/- 3.5 10 Co-58
< 6.4 1.6+/-3.2 10 Co-60
< 5.8 1.7 +/- 3.8 10 Fe-59
< 6.0
-1.2 +/- 5.7 30 Zn-65
< 12.8.
-5.9 +/- 7.2 30 Zr-Nb-95
< 5.1
-1.1 +/- 2.9 15 Ru-103
< 5.5
-1.6 +/- 3.2 1-131
< 13.2 2.0 +/- 3.3 Cs-134
< 5.3 1.0 +/- 3.0 10 Cs-137
< 7.3 4.5 +/- 4.1 10 Ba-La-140
< 5.4
-3.2 +/- 4.9 15 Ce-141
< 11.6
-4.7 +/- 5.1 Ce-144
< 41.8
-1.4 +/- 2.4 Tl-208
< 8.3 4.0 +/- 4.3 Bi-212
< 79.1 13.5 +/- 45.6 Bi-214
< 19.3 6.1 +/- 8.1 Pb-212
< 12.2 14.8 +/- 6.5 Pb-214
< 20.6 15.6 +/- 8.8 Ra-226
< 186.3 208.0 +/- 83.2 Ac-228
< 22.7 9.9 +/- 14.4 U-235
< 9.2
-11.0 +/- 5.5 Less than (<), value is based on a 4.66 sigma counting error for the background sample and it's the MDC value for this measurement. The error given is the probable counting error at 95% confidence level.
E-mail: Kjell.Johansen@nee.com E-mail: Sophia.Bartels@nee.com Forrest G. Shaw Ill Quality Assurance Approved:
f
/. 'I
(
/~
c)
(
Dr. Kjell Johansen Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
8006-100 -1213 DATE:
01~03-17 SAMPLES RECEIVED: ----1-2--2-9--1 -------
Analyses for tritium and gamma emitting isotopes.
Lab Code EXW-6937 Date Collected 12-15-16 Location West Digester Isotope MDC I Concentration (pCi/L)
< 154 89 +/- 81 200 K-40 83.8 +/- 45.7 Mn-54
< 2.5 0.2 +/- 1.3 10 Co-58
< 2.3
-1.0 +/- 1.2 10 Co-60
< 2.6 0.9 +/- 1.5 10 Fe-59
< 3.0
-1.9 +/- 2.4 30 Zn-65
< 5.2 0.8 +/- 6.1 Zr*Nb-95
< 3.7 0.1 +/- 1.4 15 Ru-103
< 2.7
-1.1 +/- 1.2 1-131
< 9.3
-3.3 +/- 1.3 Cs-134
< 1.8 0.2 +/- 1.4 10 Cs-137
< 2.4 0.3 +/- 1.5 10 Ba-La-140
< 4.7 0.2 +/- 1.5 15 Ce-141
< 6.1 0.1 +/- 2.2 Ce-144
< 15.5
-1.7 +/- 9.3 Tl-208
< 3.9 3.9 +/- 1.6 Bi-212
< 39.4 17.9 +/- 18.3 Bi-214
< 9.3 17.5 +/- 3.5 Pb-212
< 5.6 10.9 +/- 2.4 Pb-214
< 8.6 16.2 +/- 3.2 Ra-226
< 69.7 222.7 +/- 31.2 Ac-228
< 12.8 20.6 +/- 5.3 U-235
< 3.6
-8.5 +/- 2.0 Less than (<), value is based on a 4.66 sigma counting error for the background sample and it's the MDC valµe for this measurement. The error given is the probable counting error at 95% confidence level.
E-mail: sophia.bartels@nee.com Email: kjell.johansen@nee.com Approved:
(_
(~
(
A'"T'I Envill"@li1lry~gm10 Unc.
- G""'\\D I Madlwest orabWw 700 Landwohr Rood* Northbrook, IL 60062-fi!310 phone (847} 1564-D7DO *fax (347} 564-4517 Mr. Richard Welty Radiation Protection Mgr.
Point Beach Nuclear Plant NextEraEnergy 6610 Nuclear Road Two Rivers, WI 54241 LABORATORY REPORT NO.:
DATE:
SAMPLES RECEIVED:
PURCHASE ORDER NO.:
8006-100-1188 06-10-16 04-07-16 Below are the corrected results of the readout of supplemental TLDs deployed during the first quarter, 2016.
Period:
1st Quarter, 2016 Date Annealed:
12/08/15 Date Placed:
See note below Date Removed:
04/05/16 Date Read:
04/07/16 Days in the Field:
See note below Days from Annealing to Readout:
121 In-transit exposure:
6.37 +/- 0.53 NetmR 8
Net mR 8
Location Total mR NetmR 8
Std Qtr per 7 day!?
SGSF-North 90 days in field 19.8 +/- 0.8 13.5 +/- 0.9 13.6 +/- 1.0 1.05 +/- 0.07 SGSF-East 90 days in field 16.8 +/- 0.7 10.5 +/- 0.9 10.6 +/- 0.9 0.81 +/- 0.07 SGSF-South 90 days in field 18.4 +/- 0.6 12.0 +/- 0.8 12.2 +/- 0.8 0.94 +/- 0.06 SGSF-West 90 days in field 18.0 +/- 0.4 11.7+/-0.7 11.8+/-0.7 0.91 +/- 0.05 ISFSl-North 91 days in field 38.4 +/- 0.9 32.0 +/- 1.0 32.0 +/- 1.0 2.46 +/- 0.08 ISFSl-East 91 days in field 47.3 +/- 0.8 40.9 +/-0.9 40.9 +/-0.9 3.15 +/- 0.07 ISFSl-South 91 days in field 20.5 +/- 0.6 14.1 +/- 0.8 14.1 +/- 0.8 1.09 +/- 0.06 ISFSl-West 91 days in field 59.9 +/-2.9 53.6 +/-2.9 53.6 +/-2.9 4.12 +/- 0.22 Control 91 days in field 25.4+/-1.0 19.0+/-1.1 19.0 +/- 1.1 1.46 +/- 0.09 Note: SGSF locations placed 1/6/16 (90 days in field) IFSFI and control locations placed 1/5/16 (91 days in field)
~~~~
Quality Assurance APPROVED
( ___
(.
(
A-rl Environment:a.8, Hnc.
- l""'\\I Midwest Laboraton-y 700 Landwehr Road* Northbrook, IL 60082-2310 phone (847) 564-0700
- rax (847) 564-4517 Mr. Richard Welty Radiation Protection Mgr_
Point Beach Nuclear Plant NextEraEnergy 6610 Nuclear Road Two Rivers, WI 54241 LABO.RATORY REPORT NO.:
DATE:
SAMPLES RECEIVED:
PURCHASE ORDER NO.:
8006-1 00-1198 08-04-16 07-08-16 Below are the results of the readout of supplemental TLDs deployed during the second quarter, 2016.
Period:
2nd Quarter, 2016 Date Annealed:
03/14/16 Date Placed:
04/05/16 Date Removed:
07/05/16 Date Read:
07/08/16 Days in the Field:
91 Days from Annealing to Readout:
116 In-transit exposure:
5.09 +/- 0.40 NetmR NetmR Location Total mR NetmR Std Qtr per7 days SGSF-North 18.6 +/- 0.6 13.5 +/- 0_7 13.5 +/- 0.7 1.04 +/- 0.06 SGSF-East 18.9 +/- 0.9 13.8+/-1.0 13.8+/-1.0 1.06 +/- 0.08 SGSF-South 18.4 +/- 0.6 13.3 +/- 0.7 13.3 +/- 0.7 1.03 +/- 0.05 SGSF-West 19.5+/-1.1 14.4+/-1.2 14.4+/-1.2 1.11 +/- 0.09 ISFSl-North 31.7+/-1.4 26.6+/-1.5 26.6+/-1.5 2.05 +/- 0.11 ISFSl-East 44.3 +/- 0.2 39.2 +/- 0.5 39.2 +/- 0.5 3.02 +/- 0.04 ISFSl-South 23.0+/-1.0 17.9+/-1.1 17.9+/-1.1 1.38 +/- 0.08 ISFSl-West 63.3 +/-2.8 58.2 +/-2.8 58.2 +/- 2.8 4.48 +/- 0.22 Control 22.8 +/- 0.6 17.7 +/- 0.7 17.7 +/- 0.7 1.36 +/- 0.05
?eG~*
Quality Assurance APPROVED
(
t A'll En"ironmentatt~ Air"Dc.
- r"\\I I M5~
Labcl1'Ci!lt<0>irw 700 Lendwehr Road* Nwthbrook, IL 60062-2:410 phone (847) 564-0700. '"" (847) 564-4517 Mr. Richard Welty Radiation Protection Mgr.
Point Beach Nuclear Plant NextEraEnergy 6610 Nuclear Road Two Rivers, WI 54241 LABORATORY REPORT NO.:
DATE:
SAMPLES RECEIVED:
PURCHASE ORDER NO.:
8006-100-1207 11-07-16 10-06-16 Below are the results of the readout of supplemental TLDs deployed during the third quarter, 2016.
Period:
3rd Quarter, 2016 Date Annealed:
06/09/16 Date Placed:
07/05/16 Date Removed:
10/05/16 Date Read:
10/12/16 Days in the Field:
92 Days from Annealing to Readout:
125 In-transit exposure:
5.27 +/- 0.32 NetmR NetmR Location Total mR NetmR Std Qtr per? days SGSF-North 19.7+/-1.0 14.4+/-1.0 14.3 +/- 1.0 1.10 +/- 0.08 SGSF-East 17.8 +/- 0.8 12.5 +/- 0.8 12.4 +/- 0.8 0.95 +/- 0.06 SGSF-South 19.4 +/- 0.5 14.1 +/- 0.6 13.9 +/- 0.6 1.07 +/- 0.05 SGSF-West 18.0 +/- 1.0 12.7 +/- 1.0 12.6 +/- 1.0 0.97 +/- 0.08 ISFSl-North 38.8 +/- 1.2 33.5 +/- 1.3 33.1 +/- 1.3 2.55 +/- 0.10 ISFSl-East 51.3+/-1.9 46.1 +/- 1.9 45.6+/-1.9 3.50 +/- 0.14 ISFSl-South 22.4 +/- 1.2 17.1 +/- 1.3 17.0 +/- 1.3 1.30 +/- 0.10 ISFSl-West 62.8 +/- 3.0 57.5 +/- 3.1 56.9 +/- 3.0 4.38 +/- 0.23 Control 25.4 +/-0.9 20.1 +/- 0.9 19.9 +/- 0.9 1.53 +/- 0.07
~~
Quality Assurance APPROVED
~
(
AT'I Envirol!'llment:a!, ln1t:.
J""'\\I
- Midwest Laboll'a~
7110 Landwehr Road* Norlhbrodt, IL 6006~2310 phone (847) 564-0700 * "' (841) 564-4817 Mr. Richard Welty Radiation Protection Mgr.
Point Beach Nuclear Plant NextEraEnergy 16610 Nuclear Road Two Rivers, WI 54241 LABORATORY REPORT NO.:
DATE:
SAMPLES RECEIVED:
PURCHASE ORDER NO.:
8006-100-1218 02-15-17 12-30-16 Below are the results of the readout of supplemental TLDs deployed during the fourth quarter, 2016.
Period:
4th Quarter, 2016 Date Annealed:
09/08/16 Date Placed:
10/05/16 pate Removed:
12/29/16 Date Read:
01/05/17 Days in the Field:
85 Days from Annealing to Readout:
119 In-transit exposure:
5.31+/-0.36 NetmR NetmR Location Total mR NetmR Std Qtr per7 days SGSF-North 18.1 +/- 0.9 12.8 +/- 1.0 13.7 +/- 1.1 1.05 +/- 0.08 SGSF-East 18.8 +/- 0.8 13.5 +/- 0.8 14.5 +/- 0.9 1.11 +/- 0.07 SGSF-South 18.4 +/- 0.8 13.0 +/- 0.9 14.0+/-1.0 1.07 +/- 0.07 SGSF-West 18.8 +/- 0.9 13.5 +/- 1.0 14.5+/-1.1 1.11 +/- 0.08 ISFSl-North 31.3 +/- 2.2 26.0 +/- 2.2 27.9 +/- 2.4 2.14 +/- 0.18 ISFSl-East 50.3 +/- 1.7 45.0 +/- 1.7 48.1 +/- 1.8 3.70 +/- 0.14 ISFSl-South 23.8 +/- 1.7 18.5+/-1.7 19.9 +/- 1.8 1.53 +/- 0.14 ISFSl-West 58.8 +/- 3.8 53.5 +/- 3.8 57.2 +/- 4.0 4.40 +/- 0.31 Control 20.6 +/- 1.1 15.3+/-1.1 16.3 +/- 1.2 1.26 +/- 0.09 Quality Assurance APPROVED
(
i ATH Env:ironmentml, Inc.
RU U Mlidlwest labpratpg-y 700 Landwehr Road* Northbtaok. IL 60062-2310 phone (847) 864-b'ZOO *fax (847) 564-4517 Dr. Kjell Johansen NextEra Energy Point Beach Nuclear Plant 6610 Nuclear Road Two Rivers, Wisconsin 54241 LABORATORY REPORT NO.:
DATE:
SAMPLES RECEIVED:
PURCHASE ORDER NO.:
Below are the results of the analyses for tritium in four AC condensate samples.
Sample Collection Lab Concentration I MDC (Q,Gi/L)
Location Date Code H-3 Training Building 10-10-16 EW-5517 21+/-76/<.151 South Service Building 10-10-16 EW-5518 2,911+/-174/<151 U2 TB Control Room-AC 10-10-16 EW-5519 6,096 +/- 240 I< 151 South Gate 10-16-16 EW-5520 171 +/- 85 I < 153 8006-100-1206 11-03-2016 10-17-2016
(
- \\
\\'":~ 1 The error given is the probable counting error at the 95% confidence level. The less than (<) value, is based on 4.66 sigma counting error for the background sample.
E-mail: kjell.johansen@NextERAEnergy.com APPROVED BY:
~~
11r§jl&