Southern Nuclear Operating Company, Inc.
Post Off ice Box 1295 Birmingham, Alabama 35201-1295 Tel 205.992.5000 January 22, 2007 Docket Nos.:
50-424 50-425 Energy to Serve b u r WorldSY U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant Inservice Inspection Summary Report Ladies and Gentlemen:
Southern Nuclear Operating Company (SNC) submits herewith the Vogtle Electric Generating Plant Unit 1, Interval 2, Period 3, Outage 2 Inservice Inspection Summary Report (Enclosure). This report describes and summarizes the inservice inspection activities performed during the fall 2006 maintenancelrefueling outage. Paragraph IWA-6230 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, 1989 Edition requires submittal of the enclosed report.
The supporting inservice inspection documentation, e.g., examination plans and schedules, examination results and reports, examination methods and procedures, evaluation results, and corrective action and repairs, is available for review upon request at Vogtle Electric Generating Plant.
This letter contains no NRC commitments. If you have any questions, please advise.
Sincerely, T. E. Tynan Vice President - Vogtle Vogtle Electric Generating Plant 7821 River Road Waynesboro, GA 30830
Enclosure:
Vogtle Electric Generating Plant - Unit 1 Inservice Inspection Summary Report Refueling Outage (1R 13)
U. S. Nuclear Regulatory Commission NL-07-0 122 Page 2 cc:
Southern Nuclear Operating Comvany Mr. J. T. Gasser, Executive Vice President RType: CVC7000 U. S. Nuclear Regulatorv Commission Dr. W. D. Travers, Regional Administrator Mr. R. E. Martin, NRR Project Manager - Vogtle Mr. G. J. McCoy, Senior Resident Inspector - Vogtle
Enclosure Vogtle Electric Generating Plant - Unit 1 Inservice Inspection Summary Report Refueling Outage (1R13)
OWNER'S REPORT FOR INSERVICE INSPECTIONS for the THIRTEENTH MAINTENANCEIREFUELING OUTAGE VOGTLE ELECTRIC GENERATING PLANT, UNIT 1 (7821 River Road, P. 0. Box 1600, Waynesboro, Georgia 30830)
COMMERCIAL OPERATION DATE: May 31,1987 DOCUMENT COMPLETION DATE: January 2007 Prepared by SOUTHERN NUCLEAR OPERATING COMPANY (40 Inverness Center Parkway, P. 0. Box 1295, Birmingham, Alabama 35201) as LICENSEE AND OPERATING AGENT for GEORGIA POWER COMPANY (241 Ralph McGill Boulevard, N.E., P. 0. Box 4545, Atlanta, Georgia 30308-3374) as OWNER
Introduction ASME Form NIS-1 with Abstract - ASME Class 1 and 2 Class CC Containment Examinations and Tests (IWL)
Examination Summary Listings Class 1 and 2 Weld and Support Examinations System Pressure Tests Reportable Indication Summary Owner's Reports for Repairs or Replacements (Form NIS-2)
LIST OF ABBREVIATIONS ACC AD AF W A1 AN11 ASME ASNT ASTM BC ccss CCW CE CH CR CS cvcs DS ET EVAL FAC FB FNF FW FSAR GEO GPC HHSI HL HX HYD IEN IND INF IS1 IST ITS ID IR LB LD LD-I LD-0 LMT LU LU-I LU-0 MECH MS MT NCI NDE Acceptable AnchorDarling Auxiliary Feedwater System GPC Action Item (followed by unique no. denoting Action Item number)
Authorized Nuclear Inservice Inspector American Society of Mechanical Engineers American Society for Nondestructive Testing American Society for Testing and Materials Branch Connection Centrifugally Cast Stainless Steel Component Cooling Water Combustion Engineering Closure Head Condition Report Containment Spray Chemical and Volume Control System Downstream Eddy Current Examination Evaluation Flow-Accelerated Corrosion (may also be referred to as "erosion/corrosion")
Flange Bolting FAC Notification Report Feedwater System VEGP Final Safety Analysis Report (includes updates thereto)
Geometric Indications Georgia Power Company High Head Safety Injection Hanger Lug Heat Exchanger Hydraulic Snubber NRC Information Notice (may also be shown as "IN" followed by unique no. denoting notice number)
Indication Indication Notification Form Inservice Inspection Inservice Testing VEGP Improved Technical Specification Inside Diameter Inside Radius Large Bore Longitudinal Seam Weld Extending Downstream Longitudinal Seam Weld Downstream Inside Radius of Elbow Longitudinal Seam Weld Downstream Outside Radius of Elbow Lambert, MacGill and Thomas Longitudinal Seam Weld Extending Upstream Longitudinal Seam Weld Upstream Inside Radius of Elbow Longitudinal Seam Weld Upstream Outside Radius of Elbow Mechanical Snubber Main Steam System Magnetic Particle Examination Nonconformance Item Nondestructive Examination
LIST OF ABBREVIATIONS - (continued)
NI NRC NRC-B NRI NSCW OR PL PM PR PROF PS PSA PSI PT RCS RCP RHR RI RLW RL RPV RR RWST SAT SB SCS SI SNC SUP T&C TDAF W UNSAT us UT VEGP No Indication United States Nuclear Regulatory Commission NRC Bulletin (followed by unique no. denoting Bulletin number)
No Recordable Indication Nuclear Service Cooling Water System Outside Radius Pipe Lug Paul-Munroe ENERTECH Pipe Restraint Profile Pipe Support Pacific Scientific Preservice Inspection Liquid Penetrant Examination Reactor Coolant System Reactor Coolant Pump Residual Heat Removal System Recordable Indication Refracted Longitudinal Wave Restraint Lug Reactor Pressure Vessel Relief Request (followed by unique no. denoting relief request number)
Refueling Water Storage Tank Satisfactory Examination Results Small Bore Southern Company Services Safety Injection System Southern Nuclear Operating Company Supplemental Data Thickness and Contour Turbine Driven Auxiliary Feedwater (Pump)
Unsatisfactory Examination Results Upstream Ultrasonic Examination Vogtle Electric Generating Plant (common unless followed by "-1" or "-2" to designate a specific plant unit)
Visual Examination Westinghouse iii
INTRODUCTION This report documents the examinations and tests performed at Vogtle Electric Generating Plant, Unit 1 (VEGP-I) between April 10,2005 (date of last examination performed during the twelfth maintenancelrefueling outage, 1 R12) and October 27,2006 (date of last examination performed during the thirteenth maintenancetrefueling outage, 1R13) to meet the requirements of Article IWA-6000 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, 1989 Edition (Code).
This report also addresses Code-applicable repairs andlor replacements, which were documented since the twelfth maintenancelrefueling outage at VEGP-I through the completion of the thirteenth maintenancelrefbeling outage in October 27,2006. The Owner's Reports for Repairs and Replacements (Form NIS-2) are included herein.
This report does not include a summary of the Steam Generator Tube Inspections which are required per VEGP Technical Specification 5.6.10. This will be provided in a separate report within one hundred eighty (1 80) days after the initial entry into MODE 4 following completion of an inspection performed in accordance with Technical Specification 5.5.9. The ASME Code requirements were met and the separate report will provide the details for these examinations.
FORM NIS-1 OWNER'S REPORT FOR MSERVICE INSPECTIONS As rewired bv the Provisions of the ASME Code Rules
- 1.
Owner:
Georgia Power Company, 241 Ralph McGill Blvd., N. E.
P. 0. Box 4545, Atlanta, Georgia 30308-3374
- 2.
Plant:
Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830
- 3. Plant Unit: One
- 4.
Owner Certification of Authorization: NIA
- 5.
Commercial Service Date: 0513 1/87
- 6. National Board Number for Unit: NIA
- 7.
Components Inspected:
National Board Number 22004 NIA Component or Appurtenance Reactor Pressure Vessel Selected Piping, Components, and Supports Manufacturer or Installer and Address Combustion Eng.
Inc.,
Chattanooga, TN Pullman Power
- Products, Williamsport, PA Manufacturer or Installer Serial Number 7372 System Numbers 1201,1204, 1205,1208,1301,1302 &
1305.
State or Province Number N/A N/A
FORM NIS-1 (Back)
- 8. Examination Dates: A~ril 10.2005 to October 27.2006
- 9. Inspection Period Identifiation: Third Period
- 10. Inspection Interval Identification: Second Ins~ection Interval I I. Applicable Edition of Section XI =Addenda None
- 12. DatefRevision of Inspection Plan: Januaw 5.2007 / Revision 8
- 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)
- 14. Abstract of Results of Examinations and Tests. (See Abstract)
- 15. Abstract of Corrective Measures. (See Abstract)
We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable) _N/A Expiration Date N/A Date: 1 7 d L.
2 0
~
Signed:
Southern Nuclear Operating By:
Com~any. Inc. f p ~
Georgia Power Com~any Owner CERTIFICATE OF TNSERVICE TNSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler hs~ection and Insurance ComDanvof of Hartford. CT have inspected the components described in this Owner's Report during the period A~ril 10.2005 to -,
and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations, tests, and corrective measures described in this Owner's Report. Furthennore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commission: 6 A ?C6 National Board, State, Province, and Endorsements Date: / k T-20s
ABSTRACT - ASME CLASS 1 AND 2 Introductionf tatus The ASME Boiler and Pressure Vessel Code,Section XI, 1989 Edition (Code), is the applicable code for conducting inservice inspection activities during the second ten-year inspection interval at VEGP-1. Examinations and tests required by the Code are scheduled in accordance with "Inspection Program B" as defined in Code paragraphs IWB-2412 and IWC-2412. This "Owner's Report for Inservice Inspection" is for those third inspection period examinations and tests which were performed between April 10,2005 (date of last examination performed during the twelfth maintenancelreheling outage, 1 R12) and October 27,2006 (date of last examination performed during the thirteenth maintenancelrefueling outage, 1 R13).
The Risk Informed Program was approved by the NRC by letter dated September 30,2003 and implemented during the VEGP 1R11 reheling outage (ASME Class 1 and Class 2 piping only).
By Federal Register Notice 64 FR 5 1370 dated September 22, 1999, 10CFR 50.55a(g)(6)(ii)(C), lmplementation of Appendix VIII to Section XI, was incorporated into the rule to expedite implementation of Appendix VIII. The specific Supplements of Appendix VIII to Section XI, ASME Boiler and Pressure Vessel Code, 1995 Edition with the 1996 Addenda were implemented prior to the 1R12 rnaintenancelrefueling outage as required.
In addition to the summary of inservice inspection activities, this report addresses Code-applicable repairs and replacements documented at VEGP-1 since 1R12 through the end of 1R13. Class 1 and Class 2 Owner's Reports for Repairs or Replacements (Form N1S-2) are provided herein.
It should be noted that Authorized Nuclear lnservice Inspector (ANII) inspection services were provided for those examinations and tests required by the Code. ASME Section XI examinations and tests are itemized in the applicable sections by reference to Examination Category. Examinations which do not meet the Code-required coverage either reference request(s) for relief or indicate that additional relief is required.
Selected Class 1 and 3 examinations were not performed during the 1R13 outage. These examinations have been deferred until the 1R14 outage or at some other time which satisfies the requirement to perform the Second IS1 interval examinations within the one-year extension past the end of the interval (May 30,2007). Since the 1R14 outage will be in Spring 2008, examinations performed during that outage will satisfy ASME Code requirements.
The required examinations for Class 2 components were satisfied.
Class 1 Examinations Selected Class 1 components were examined by Southern Nuclear Operating Company (SNC) personnel utilizing ultrasonic testing (UT), magnetic particle testing (MT), liquid penetrant (PT), and visual testing (VT) methods, as applicable. Specific components and examination areas are itemized in the applicable portions of this document.
During the scope of VEGP-I examinations conducted, no Class 1 components were observed to have reportable UT. PT or MT indications.
In addition to components already identified in current requests for relief, five (5) reactor pressure vessel welds had limited volumetric coverage during UT examinations because of physical limitations due to the geometric configuration of the welded areas. In addition, two (2) reactor pressure vessel integrally welded attachments had limited surface coverage because of physical limitations due to the geometric configuration of the welded areas.
More than ninety percent (90%) of the required volume must be examined as addressed in ASME Section XI Code Case N-460 for adequate ASME Section XI Code-required examination coverage to be attained. As noted herein, the subject code case has been approved by the NRC for use as documented in NRC Regulatory Guide 1.147. It is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.
Class 1 Pressure Test Table IWB-2500-1, Examination Category B-P, of ASME Section XI requires the performance of a system leakage test (IWB-5221) each maintenance/refueling outage. This system leakage test (LT-1) was performed prior to plant startup following the refueling outage. These visual examinations revealed minor leakage and boron residue at mechanical connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.
Table IWB-2500- 1, Examination Category B-P, of ASME Section XI also requires the performance of a system hydrostatic test (IWB-5222) once at or near the end of each inspection interval. This test is identified as the Class 1 hydrostatic test (HT-1) and it extends to the Class 1 pressure boundary extremity (i.e., second isolation valve) and also includes selected adjacent Class 2 components which are typically isolated from the Class 1 boundary by check valves. As an alternative to ASME Section XI requirements, Code Case N-498-4, which was conditionally accepted for use in Revision 14 of Regulatory Guide 1.I47 dated August 2005, was used. Code Case N-498-4 deleted the elevated pressure requirement for the hydrostatic test and reduced the holding time requirement but retained the requirement to extend the boundary subject to test pressurization to include each of the Class 1 pressure-retaining components. To assure that all Class 1 pressure retaining components and selected adjacent Class 2 pressure retaining components are pressurized requires for some isolated boundaries that valves be aligned to positions other than their normal alignment and for some isolated boundaries the use of a hydrostatic test pump. Portions of this test were not completed during the 1 R13 maintenance / refueling outage nor are they planned to be completed by the end of the second inspection interval which ends May 30,2007. However, as allowed by IWB-2412 the remaining portions are scheduled to be performed in maintenance /refueling outage 1R14 which is scheduled in the Spring of 2008. The visual examinations performed in the 1R13 maintenance / refueling outage revealed minor leakage and boron residue at mechanical connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.
ASME Section XI, Subparagraph IWA-5242(a) requires removal of insulation from pressure-retaining bolted connections for VT-2 examination during system pressure testing for systems borated for the purposes of controlling reactivity. ASME Section XI Code Cases N-533-1 and N-616 were utilized during the refueling outage. These Code Cases were approved for use in Revision 13 of Regulatory Guide 1.147 dated June 2003. Case N-533-1 allows insulation to be removed while the connections are at atmospheric or static pressures. With the insulation removed a direct visual examination is performed to detect previously occurring leakage through the presence of boric acid crystals. Case N-616 allows the VT-2 examination to occur without insulation removal provided the bolting material is resistant to boric acid degradation.
The test boundary of the system leakage test includes both Class 1 and Class 2 components. The frequency for removal of insulation and direct visual examination for Class 1 pressure-retaining bolted connections is once each refueling outage (refer to Table IWB-2500-1, Examination Category B-P) and as such those activities occurred during the refueling outage. The Class 2 components comprise part of the reactor coolant pressure boundary but are not required to be classified as Class 1 per 10 CFR 50.55a(c)(2). The frequency for removal of insulation and direct visual examination for Class 2 pressure-retaining bolted connections is once each inspection period (refer to Table IWC-2500-1, Examination Category C-H). Those applicable Class 2 activities were completed also during the refueling outage.
Class 2 Examinations Selected Class 2 Piping welds were examined utilizing UT. Specific components and examination areas are itemized in the applicable portions of this report document.
During the scope of VEGP-1 examinations conducted, no Class 2 components were observed to have reportable indications.
Two (2) piping weld examinations had limited coverage due to the geometric configuration of the welded areas.
More than ninety percent (90%) of the required volume must be examined as addressed in ASME Section XI Code Case N-460 for adequate ASME Section XI Code-required examination coverage to be attained. As noted herein, the subject code case has been approved by the NRC for use as documented in NRC Regulatory Guide 1.147. It is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.
Class 2 Pressure Tests Table IWC-2500-1, Examination Category C-H, of ASME Section XI requires system pressure testing each inspection period. The specific system pressure tests performed are itemized in the "Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests found only minor leakage or residue at mechanical joints such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation.
ASME Section XI, Subparagraph IWA-5242(a) requires removal of insulation from pressure-retaining bolted connections for VT-2 examination during system pressure testing for systems borated for the purposes of controlling reactivity. ASME Section XI Code Cases N-533-1 and N-616 were utilized. These Code Cases were approved for use in Revision 13 of Regulatory Guide 1.147 dated June 2003. Case N-533-1 allows insulation to be removed while the connections are at atmospheric or static pressures. With the insulation removed a direct visual examination is performed to detect previously occurring leakage through the presence of boric acid crystals. Case N-616 allows the VT-2 examination to occur without insulation removal provided the bolting material is resistant to boric acid degradation.
Class 1 and 2 Component Su~ports No Class 1 or 2 Component Supports were examined this outage.
Cate~ory L-A. Concrete The Containment concrete surface examination (including grease cans) was performed during the summer of 2005 to satisfy the requirements of 10 CFR 50.55a and the 1992 Edition of ASME Section XI Subsection IWL with the 1992 Addenda. The concrete examinations were performed by a qualified vendor per criteria specified by the 1992 Edition and the 1992 Addenda of ASME Section XI and under the guidance of a Registered Professional Engineer.
Request for Engineering Review 1052234101 was initiated to provide and document technical assistance. Optical aids and flashlights were used when performing the examination that included both direct and indirect visual examination methods. This VT3C concrete surface examination required no VT-1C examinations of areas that had not been previously identified during the last concrete visual examination and zero grease leakage was detected on the Containment concrete surface.
Based on the results of the Containment concrete surface visual examination the Containment concrete has no evidence of degradation that warrants further evaluation and repair and remains in an acceptable structural condition and satisfies acceptance by examination criteria per IWL-3211.
Category L-B, Unbonded Post-Tensioning Svstem The Containment unbonded post-tensioning system examination was performed during the summer of 2005 to satisfy the requirements of 10 CFR 50.55a and the 1992 Edition of ASME Section XI Subsection IWL with the 1992 Addenda. The examinations were performed by a qualified vendor per criteria specified by the 1992 Edition and the 1992 Addenda of ASME Section XI. Request for Engineering Review 1052234101 was initiated to provide and document technical assistance. All requirements, including tendon anchorage areas and corrosion protection medium, to satisfy acceptance by examination criteria, per IWL-3221.3 and IWL-3221.4. were met.
Based on the results of the Containment unbonded post-tensioning examination the Containment post-tensioning system has experienced no abnormal degradation and remains in an acceptable condition.
VEGP Unit 1 Thirteenth Refueling Outage Inservice Inspection Report Interval 2, Period 3, 1VR13 Exam
~omponent ID Component Description Procedure Report No Results Comments Category B-G-1 11201-V6-001-B01 CLOSURE HEAD STUDS NMP-ES-024-504 S06V1 U059 NRI THROUGH B54 B-N-3 1 1201 -V6-001-CSS-01 CORE SUPPORT STRUCTURE VENDOR-VT SAT B-N-I 11201-V6-001-101 VESSEL INTERIOR VENDOR-VT SAT B-N-1 B-D B-D B-D B-D B-D B-D B-D B-D B-G-1 B-G-I B-G-I VESSEL CLOSURE HEAD INTERIOR (FSAR 5.3.3.7)
SAT N I NI NI N I NI N I N I N I NI SAT SAT OUTLET NOZZLE N1 INNER RADIUS AT 22" VENDOR ENHANCED VT INLET NOZZLE N2 INNER RADIUS AT 67" VENDOR ENHANCED VT INLET NOZZLE N3 INNER RADIUS AT 113" VENDOR ENHANCED VT OUTLET NOZZLE N4 INNER RADIUS AT 158" VENDOR ENHANCED VT OUTLET NOZZLE N5 INNER RADIUS AT 202" VENDOR ENHANCED VT INLET NOZZLE N6 INNER RADIUS AT 247" VENDOR ENHANCED VT INLET NOZZLE N7 INNER RADIUS AT 293" VENDOR ENHANCEDVT VENDOR ENHANCED VT OUTLET NOZZLE N8 INNER RADIUS AT 338" 11201-V6-001-LO1 THROUGH L54 THREADS IN FLANGE VENDOR-UT 1 1201 -V6-001-NO1 THROUGH N54 CLOSURE HEAD NUTS 11201-V6-001-SO1 THROUGH S54 CLOSURE WASHERS
VEGP Unit 1 Thirteenth Refueling Outage Inservice Inspection Report Interval 2, Period 3, lVR13 Exam Component ID Component Description Procedure Report No Results Comments Category B-A 11 201-V6-001-W03 (0-180) 0 TO 180 DEG VESSEL SHELL TO VENDOR-UT RI CODE ACCEPTABLE FLANGE WELD 6-A 11201-V6-001-W03 (180-180 TO 360 DEG VESSEL SHELL TO VENDOR-UT 360)
FLANGE WELD B-A 1 120 1 -V6-00 1 -W04 UPPER SHELL TO INTERMEDIATE VENDOR-UT SHELL WELD 6-A 1 120 1 -V6-00 1 -W05 INTERMEDIATE SHELL TO LOWER VENDOR-UT SHELL WELD B A 1 120 1 -V6-00 1 -W06 LOWER SHELL TO BOTTOM HEAD VENDOR-UT TORUS WELD B-A 1 120 1 46-00 1 -W07 B-A 11201-V6-001-W12 6-A 11201-V6-001-W13 B-A 1 1201 -V6-00 1-W14 6-A 1 1201 -V6-00 1-W 1 5 B-A 1 1201 -V6-001-W 16 6-A 11201-V6-001-W17 B A 1 1201 -V6-001-W 18 B-A 1 1201 -V6-001-W19 B-A 1 1201-V6-001-W20 BOTTOM HEAD TORUS TO BOTTOM HEAD DOME WELD UPPER SHELL LONGITUDINAL WELD AT 42" UPPER SHELL LONGITUDINAL WELD AT 162" UPPER SHELL LONGITUDINAL WELD AT 282" INTERMEDIATE SHELL LONGITUDINAL WELD AT 0" INTERMEDIATE SHELL LONGITUDINAL WELD AT 120" INTERMEDIATE SHELL LONGITUDINAL WELD AT 240" LOWER SHELL LONGITUDINAL WELD AT 60" LOWER SHELL LONGITUDINAL WELD AT 180" LOWER SHELL LONGITUDINAL WELD AT 300" VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT VENDOR-UT RI CODE ACCEPTABLE RI CODE ACCEPTABLE RI CODE ACCEPTABLE - 78.43%
CODE COVERAGE NI 74.15% CODE COVERAGE N I N I NI RI CODE ACCEPTABLE NI RI CODE ACCEPTABLE NI 79.03% CODE COVERAGE NI 79.03% CODE COVERAGE NI 79.03% CODE COVERAGE
VEGP Unit 1 Thirteenth Refueling Outage lnservice Inspection Report Interval 2, Period 3,1VR13 Exam Component ID Component Description Procedure Report No Results Comments Category B-H 11 201 -V6-001-W204 LIFTING LUG 0" NMP-ES-024-401 S06VlM001 NRI 59.2% CODE COVERAGE B-H 11201-V6-001-W205 LIFTING LUG 120" NMP-ES-024-401 S06V1 MOO2 NRI 59.2% CODE COVERAGE B-A 11201-V6-001-W21 BOTTOM HEAD TORUS MERlDlONAL VENDOR-UT WELD AT 0" B-A 11 201 -V6-001-W22 BOTTOM HEAD TORUS MERlDlONAL VENDOR-UT WELD AT 90" B-A 11 201 -V6-001 -W23 BOTTOM HEAD TORUS MERlDlONAL VENDOR-UT WELD AT 180" B-A 1 1201 -V6-001 -W24 BOTTOM HEAD TORUS MERlDlONAL VENDOR-UT WELD AT 270" B-D 1 1201 -V6-00 1 -W25 VESSEL TO OUTLET NOZZLE N1 VENDOR-UT WELD AT 22" B-D 1 1201 -V6-001 -W26 VESSEL TO INLET NOZZLE N2 WELD VENDOR-UT AT 67" B-D 1 1201-V6-001-W27 VESSEL TO INLET NOZZLE N3 WELD VENDOR-UT AT 113" B-D 1 1201 -V6-001 -W28 VESSEL TO OUTLET NOZZLE N4 VENDOR-UT WELD AT 158" B-D 1 1201 -V6-001 -W29 VESSEL TO OUTLET NOZZLE N5 VENDOR-UT WELD AT 202" B-D 1 1201 -V6-001-W30 VESSEL TO INLET NOZZLE N6 WELD VENDOR-UT AT 247" 0-D 11201-V6-001-W31 VESSEL TO INLET NOZZLE N7 WELD VENDOR-UT AT 293" B-D 11 201 -V6-001-W32 VESSEL TO OUTLET NOZZLE N8 VENDOR-UT WELD AT 338" R-A 11201 -V6-001-W33-RI OUTLET NOZZLE TO SAFE END VENDOR-UT WELD AT 22" N I RI CODE ACCEPTABLE RI CODE ACCEPTABLE RI CODE ACCEPTABLE RI CODE ACCEPTABLE
Exam Component ID Category R-A 1 1201 -V6-001 -W34-RI R-A 11201 -V6-001 -W35-RI R-A 1 1 201 -V6-001 -W36-RI R-A 11201 -V6-001-W37-RI R-A 11201 -V6-001-W38-RI R-A 1 1201 -V6-001-W39-RI R-A 11 201 -V6-001-W40-RI B-N-2 1 1201 -V6-001 -W41 B-N-2 1 1 20 1 -V6-00 1 -W42 B-N-2 1 1201 -V6-00 1 -W43 B-N-2 1 1201-V6-001-W44 B-N-2 1 1201 -V6-001 -W45 B-N-2 1 1201 -V6-00 1 -W46 R-A 1 1208-005-CV11O-RI VEGP Unit 1 Thirteenth Refueling Outage Inservice Inspection Report Interval 2, Period 3,1VR13 Component Description Procedure Report No Results Comments INLET NOZZLE TO SAFE END WELD VENDOR-UT N I AT 67" INLET NOZZLE TO SAFE END WELD VENDOR-UT AT 113" OUTLET NOZZLE TO SAFE END VENDOR-UT WELD AT 158" OUTLET NOZZLE TO SAFE END VENDOR-UT WELD AT 202" INLET NOZZLE TO SAFE END WELD VENDOR-UT AT 247" INLET NOZZLE TO SAFE END WELD VENDOR-UT AT 293" OUTLET NOZZLE TO SAFE END VENDOR-UT WELD AT 338" RI CODE ACCEPTABLE CORE SUPPORT LUG AT 0" VENDOR-VT N I CORE SUPPORT LUG AT 60" VENDOR-VT N I CORE SUPPORT LUG AT 120" VENDOR-VT N I CORE SUPPORT LUG AT 180" VENDOR-VT N I CORE SUPPORT LUG AT 240" VENDOR-VT N I CORE SUPPORT LUG AT 300" VEN DOR-VT N I 3" PIPE DS (FO-0200,201,202)
NMP-ES-024-510 SAT
VEGP Unit 1 Thirteenth Refueling Outage lnsewice Inspection Report lntewal 2, Period 3, 1VR13 Exam Component ID Component Description Procedure Report No Results Comments Category R-A 1 1301-002-1 1-Rl 6 OUTLET TO FLANGE NMP-ES-024-502 S06V1 U070 NRI 78.4% CODE COVERAGE S06V1 U072 NRI SOW1 U071 NRI R-A 11 301 -003-1 5-RI 6" OUTLET TO FLANGE R-A 11301-015-1-RI 10" OUTLET TO PIPE NMP-ES-024-502 S06V1 U051 NRI 81 % CODE COVERAGE S06V1 U052 NRI S06V1 U073 NRI NMP-ES-024-502 S06V1 U054 NRI S06VlU053 NRI
SYSTEM PRESSURE TESTS The following pressure tests on Class 1 and Class 2 components were included in the scope of the maintenancelrefueling outage. These pressure tests included system hydrostatic tests, system inservice tests, and system leakage tests. It should be noted that the hydrostatic test identified was performed to satisfy the "once per ten year" requirements described in ASME Section XI, Code Case N-498-4. Boundaries for the pressure tests are described in the VEGP-1 Inservice Inspection Plan - Second 10-Year Interval document. Examination results are discussed in the applicable sections of this report document. The examination data for these pressure tests is available at the plant site for review upon request.
Svstem Hvdrostatic Test Schedule (HTs)
Svstem Inservice Test Schedule (ITS)
HT -
-Cat, 1
11 12 Svstem Leakage Test Schedule (LT)
Exam.
B-P C-H C-H C-H IT -
Number I I 12 LT - -
Exam. -
Test Number Cat.
Description 1
B-P Class 1 System Leakage Test Test Description Class 1 Hydrostatic Test (Partially performed)
Containment Spray Train A Open Flow Path Test Containment Spray Train A Open Flow Path Test Exam.
Cat.
C-H C-H Test Description Centrifugal Charging Pump 1208-P6-002 (Train "A") Discharge Inservice Test Centrifugal Charging Pump 1208-P6-003 (Train "B") Discharge Inservice Test
REPORTABLE INDICATION
SUMMARY
The following indication identified on the Condition Report was issued due to reportable indications or conditions being observed during the examination of either Class 1 or 2 components during the thirteenth (1 3")
maintenancelrefueling outage at VEGP-I (referenced attachments are available at the VEGP plant site for review upon request):
The Indication Notification Form(s) constitute only those reportable indications or conditions observed during the SNC M & IS Department scope of work. Any reportable indications or conditions observed by VEGP Site personnel or outside contractors during their scope of work should be identified bylto the VEGP site in report docurnent(s) which are referenced herein.
INF No.
None Affected ComponentIArea 11201-V6-001-CSS-01 INF Disposition Condition Report 20061 11 159 was written when the vendor (Westinghouse) observed an anomaly on the "RPV Core Support Structure" during the 10 year reactor pressure vessel examination. The anomaly is believed to be raised metal located on the comer of the 90 degree upper core plate insert (counter clockwise side of keyway).
In conclusion, the indications observed on the bottom surface of the upper core plate clevis inserts will not affect the form, fit, or function of the reactor pressure vessel intemals. Therefore, the upper intemals can be reinstalled without any adverse consequences on their continued operability.
OWNER'S REPORTS FOR REPAIRS OR REPLACEMENTS (FORM NIS-2)
The following Owner's Reports for Repairs or Replacements (Form NIS-2) are provided for work activities documented at VEGP-I since the last maintenance/refueling outage (1R12) through the completion of the thirteenth maintenancelrefueling outage (1R13). Reports are identified by their respective traveler number which is denoted on each of the NIS-2 reports. The originals of the NIS-2 reports are filed with their respective traveler packages at the plant site. Only those NIS-2 reports applicable to VEGP-1 are included in this report document. Any attachments, e.g., code data reports, etc.,
referenced in the NIS-2 reports will be made available for review upon request at the plant site.
The NIS-2s for the following travelers are included herein:
FORM NIS-2 OWNER'S R QBJ E'BA b~
REPUCEMEN, As Required By The Provisions Of T he ASME Code Section XI Traveler#
04118
, y.
- 1.
Owner Southem Nuclear Operating Company Dale Apd 25,2005 e
Name 40 lnvemess Center Perkway, Birmingham. AL S heel 1
of 1
Address
- 2.
Plant Vogtte Electtic Generating Rent Unit 1
Name Waynesbwo. GA 30830 10402305 Address Repair Organization P.O. No., Job No.. etc.
- 3.
Work Performed by Maintenance Depament Type Code Symbol Stamp WA Name Authorlzatlon No.
WA Rant Vogile Explratlon Date WA Address
- 4.
Identification of System 1202 /Nuclear Service C d n g Water System
- 6.
(a) Applicable Construction Code ASME SEC 111 19 77 Editiin, Wnter 1977
- Addenda, IVA Code Case (b)Applicable Edition of Section XI Utilized tor Repairs or Replacements 1889
- 8.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Rekf Valve W N56900-00-0025 was removed h r inservice testing and was repfaced by re6ef valve Smr N56900-00-0049. Relief velve S N N56900-00-0049 was originaUy installed during construction as 2PSV-8121 andis now being M z e d as, Name of Component SAFETY VALVE 6
- 8.
Test Conducted:
~ n e u m a t i c a Nominal Operating ~ressurem I
Test Temp.
WA OF
- 8.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be anached Name of Manufacturer CROSBY VALVE d GAGE CO.
I CERTIFICATE OF COMPLIANCE I
We certify that the statements made in the report a n correct and this replacement confonns to the rules of the I ASME Code,Section XI.
repair or mecement I
Manufacturer Serial No.
N5690090-0025 Type Code Symbol Stamp N/A Expiration Date MA Team Leader OVmerfi Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECT ION I
National Board No.
N/A I, the undersigned, holding a valid comnission issued by the natlonal Board of Balk and Pressure Vessel Inspectors and the stke Province of Geomia and employed by Hatfford Steam W r
lnsmcfbn and ~nsufance Co. of F f
7 c
4 of Connecticut have inspected the components described in thls Owner's Report during the period to S 0 4
, and state that to the best of my knowkdge and belief, the Owner has performed examinations and taken corredive measures described in this Owners Report In accordance wlth the requirements of the ASME Cade, Se-ction XI.
By signing this certificate. neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Repoh Furthemore, neither the Inspector nor his employer shall injury or property damage or a loss of any kind aridng from or connected with this ins comnlssions G ~ a o ~ 3 National Board, State, Province and Endorsements Other Identification 1PSV-8121 Year Built 1884
- Repaired, Replaced, or Replacement REPLACEMENT ASME Code S-l (Yes or No)
YES I
FORM NIS-2 OWNER'S REP0 b;)H &ild&LACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
041 20
- a Owner Southem Nudear Operating Company Date May 13,2005 Name 40 lnvemess Center Parkway, Birmingham AL Sheet 1
of 1
Address Plant Vogtle UecMc Genemting Plant Unit 1
Name Waynesboro. GA 30830 10200856 I
Address Repair Organization P.O. No.. Job No., etc.
I I
Work Performed by Melntenance Department Type Code Symbol Stamp WA Name Authorlzatlon No.
NLA
&nt VogUe Expiration Date WA Address I
identification of System.
1305 / Maln Feedwater System I
(a) Applicable Constructlon Code ASME SEC 111 1 8 7 7 Edition.
Wnter 1977
- Addenda, N/A Code case (b)ApplicaMe Edition of Section XI Utilized for Repairs or Replacements 18@
ldentikation Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work I
Name of Component PIPE SYSTEM I
- 8.
Test Conducted:
~neumatlc [g Nominal Operating PressureD NIA Other Pressure N/A PSI Test Temp.
N/A OF
- 8.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I
We certify that the statements made in the report are correct and this REPLACEMENT confornu to the rules of thb ASME Code. Sectlon XI.
repair or replacement Type Code Symbol Stamp N/A Name of Manufacturer PULLMAN POWER w
A.
( Certificate of Aythorizatiin No.
Expiration Date N/A r
I Year Built 1987 Signed d & 0 Team Leader Ownedt'Owner's Designee, Title Manufacturer Serial No.
W A I
CERTIFICATE OF INSERVICE INSPECTION I
- Repaired, Replaced, or Replacement REPLACEMENT I, the undersigned, holding a valid conmission issued by the national Board of Boiler and Pressure Vessel inspectors and the State : w Province of Geomie and employed by H
a m
of H a m a g
m have inspected the components described in this Owner's Report during the period Februaff 22. 2005 to.4-/7-4<
, and state that to the best of my knowledge and belief, the Owner has performed examlnatlons and taken corrective measures described in this Omers Report in accordance with the requirements of the ASME Code, Section !XI.
National Board No.
WA ASME Co+
(Yes or Nd)
Srnped!
YES !
I I
I I
By slgning this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinatiins and corrective measures described in this Owners Report.
Furthemre, neither the Inspector nor his' employer shall r property dr-ge or a loss of any kind arising from or connected wlth this Convnissions C-Q National bard. State, Province and Endorsements Other ldentificatin NLA
FORM NIS-2 OWNER'S R REPLACEMENTS As Required By The Provisions Of The ASME Coda Section XI I
Traveler#
04121 Date July 6,2005
- 1.
Owner Southern Nuclear Operating Company Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Address 8
- 2.
Plant Vogfle Electric Generafing Plant Unit 1
Name
~ a ~ n e s b o m.
GA 308%
19802040 Address Repair Organization P.O. No.. Job No.. etc.
- 3.
Work Performed by Maintenance Depament Type Code Symbol Stamp I
Name Authorlz~lon No.
WA Plant Vogtle Explratlon Date WA 1
Address
- 4.
ldentikakon of System 1305 /Main Feedwater System I I
- 6.
(a) Applicable Construction Code ASME SEC 111 1 8 7 7 Edition, Winter 1977
- Addenda, MA Code c a b (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 18&
I
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- Repaired, ASME Co$e Name ot Name of Other
- Replaced, Starnpcd Component I Manufacturer (
Serial No.
1 No.
1 Identification
(
Built
( or ~eplacement ( (Yes & Nb)
PIPE SYSTEM I PULLMAN 1
N/A I
N/A 1
lK2-1305-157-01 1
1987 1 REPLACEMENT I YES !
- 7.
Description of Work Replace pipe section between weldofet and k t downstream elbow. Code Case N-4161 was used for the insta~abn of this piping.
i I
POWER
- 8.
Test Conducted:
~neumaticm Nominal Operating pressurea I
N I A ~
Other Pressure N/A PSI Test Temp.
N/A
.F I
I I
- 9.
Remarks Seeltem 7 I
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I
We certify that the statements made in the report are correct and this REPLACEMENT confomts to the rules of the ASME Code,Section XI.
repair or replacement I
Type Code Symbol Stamp N/A i
Expiration Date MA i
Team Leader 0wnedr Owner's Designee. Title
/
I CERTIFICATE OF INSERVICE INSPECTION I
I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomie and employed by Hartford S z of ~a&or&
Connecticut have inspected the components described In this Owner's Report during the perkd _Merch 2605 to 7-7-ax and M e that to the best of my knowledge and belief, the Owner has performed examinations and taken conedtive measures described' in thls Owners Report in accordance with the requirements of the ASME Code.
Sedion 1 XI.
I By signing this certificate, neither the Inspector nor his employer h k e s any warranty, expressed or implied, concerning the exarninatpns and corrective measures described in this Owners Report.
Furthermore, neither the Inspector nor his employer shall b e liable in any mannef for any personal injury or property damage or a loss of any klnd arislng from or connected with ]this
' 1 Commissions G
w National Board. State. Province and Endorsements Date I
I
FORM NIS-2 O W N E R ' S ~ ~ h ! & Y O R REPLACEMENTS As Required By The ~rovisions Of TheiASME Code Section XI Traveler #
04123
- 1.
Owner Southem Nuclear Operating Company Date July 1, 2005 Name Sheet 1
1 40 lnvemess Center Padway, Birmingham, AL of Address
- 2.
Plant Vogue Electric Generating Plant una 1
Name Waynesbom. GA 30830 19802040 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA WA Name Aulhorizatlon No.
Plant Vog&
Explratlon Date WA Address
- 4.
Identification of System 1305 /Condensate and Feedwater System
- 6.
(a) Applicable Construction Code ASME SEC 111 19 74 Editkn, Summer 75
- Addenda, WA Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19@
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Replace studs and nuk on 4" Mind flange.
- 8.
Tesl Conducted:
Hydrostatii pneumatic NNomi~l Operating Pressure N I A D Other Pressure N/A PSI Test Temp.
N/A OF ASME Code Stamped (Yes or No)
YES
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp WA N/A N/A Signed Team Leader Other Identification N/A I
Name of Component PIPE I
CERTIFICATE OF INSERViCE INSPECTION I
Manufacturer Serial No.
N/A Name of Manufacturer PULLMAN POWER I, the undersigned, holding a valid comrnlsslon issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ge0qi8 and employed by Hartford Steam Boiler Insaeclion and Insurance Co. of Conneclicut of Harthd.
Connecticut have inspected the components described in this OwnerSs Report during the period March 18. 2005 to 7-7-05
. and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correct'ive measures described in this Owners Report In accordance with the requirements of,the ASME Code,Section XI.
Year Built 1987 National Board No.
M A By signing thls certificate, nelther the Inspector nor hls employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report.
Furthermore, neither the Inspeclor nor hls employer shall anal injury or propedy damage or a loss of any kind arising from or connected with thls Commissions (7,q ap q InspeNr's Signature National Board, State, Province and Endorsements Repaired.
Replaced.
or Replacement REPLACEMENT
.<?.!,-b.
'a r ? -4, FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler#
04127 I-L+
I
- 1.
Owner Southern Nuclear Operaling Company Date A@ 8,2005 Name 40 lnvemess Center P a h a y, Binnlngham AL Sheet 1
of 1
Address
- 2.
Plant V o w Uectrfc Generating Plant Unlt 1
Name I
Waynesboro, GA 308%
10402535 I
Address Repair Organization P.O. No.. Job No.. etc.
I
/
I
- 3.
Work Performed by Maintenance Department Type Code Symbd Stamp WA Name Authorlzat\\on No.
WA Plent Vogue
' Explralion Date NLA Address 1
- 4.
identiflcatlon of System 1208 /Chemical end Volume Control System
\\
I
- 6.
(a) Applicabk Construction Code ASME SEC 111 1 B Z Edition, Mnter 1977
- Addenda, N-249-1 Code Ca$e (b)Applicable Edition of Section XI Utilized for Repairs or Replacements lo@
I I
- 6.
Identification Of Components Repaired or Repleced and Repkcment Components I
- 7.
Description of Work Snubber AD153, se"a1 MWiwes repleced with snubberAD153, se"a1 ~sfJpportsunmk0ance tesb'ng.
C l l l 903 A I
- 8.
Ted Conduaed:
~ n e u k a t l c m Nominal Operating ~ i e s s u r e a N I A a Other Pressure
- A PSI Test Temp.
WA OF I
- 0.
Remarks See Item 7 I
Applicable Manufacturer's Data Reports to be attached I
Name of Component PIPE SUPPORT F
CERTIFICATE OF COMPLIANCE i
We certify that the datements made in the report are correct and this replacement conforms to the rules of t+
ASME Code, Section Xi.
repair or replacement N/A Type Code Symbol Stamp I
N/A I
I Team Leader Date Name of Manufacturer PULLMAN POWER CERTIFICATE OF INSERVICE INSPECTION I
i, the undersigned, holding a valid commlsslon Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by m t
t of Hatif$
Connecffcut have inspected the components described in this Owner's Report durlng the perlad Julv 22. 2004 to 4-/$-OX
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcllve measures described in thls Owners Report in accordance with the requirements of the ASME Code.
Section 1x1.
By signing this cectiflcate, nenher the Inspector nor h k employer makes any warranty, expressed or implied, concerning the examinati?ns and corrective measures describad in this Owners Report.
Furthermore, nelther the inspsctor nor his employer S F #
sonal Injury or property damage or a loss of any kind arising from or connected with thls Commissions GA30.3 InspectaPs Signature National Board, State, Province and Endorsements I
Date 4 - JI - o r
, I Manufacturer Serial No.
N/A Year Buih 1987 National Board No.
N/A
- Repaired, Replaced, or Replacement REPLACEMENT Other identification V1-1208-009-H004 ASME C+e Stamped (Yes or N&),
YES i
FORM NIS-2 OWNER'S RE Q R b G ! M & R E P m c E M E N T s As Required By The Provisions Of The ASME Code Section XI Traveler #
04128 4
- 1.
Owner Southern Nuclear Operating Company ate Apt# 7,2005 I
Name 40 l n v e m e Center Parkway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant Vogue Electric Generaling Plant Unit 7
Name
~aynesbom. GA 30830 10402534 Address Repair Organization P.O. No., Job No.. etc.
- 3.
~ o r k ' ~ e r f o ~ d by Maintenance Depament Type Code Symbol Stamp WA Authorization No.
M A Name Plant Voglle Explratlon Date M A Address I
- 4.
Identification of System 1201 /Reactor Codenl System
- 6.
(a) Applicable Construction Code ASME SEC 111 1 9 7 7 Edition.
Wnter 1977
- Addenda, N-249-1 Code Caw (b)Applicable Ediilon of Section XI Utilized for Repairs or Replacements 1089
- 6.
ldentification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD151, seW #I59 was replaced with AD151, serial#427 lo suppori survdence tesfinng.
- 8.
Ted Conducted:
~ n e u m a t i c a Nomlnal Operating pressurea N I A N Other Pressure N/A PSI Test Temp.
M A T
S.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached Name of Component PIPE SUPPORT CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp M A N/A Expiration Date N/A Team L e e r I
Other Identification
' 'V1-1201-030-H055 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cormnission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of G e o M and employed by HerflPrd Steam Boiler Inswcbbn end Insurance Co. of Connec&ut of Hampd!
Connecticut have inspected the components described In this Owner's Report during the period - JuPi 22. 2004 to.A//-&
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken comctive measures described in thls Owners Report in accordance 4 t h the requirements of the ASME Code. Section 1x1.
By signing this certiflcate, neither the Inspector nor his employer makes any warranty, expressed or i m p l i, concerning the examinations and correctbe measures described in this Owners Report.
Furthermore. neither the Inspector nor hls employer shell erronal injury or property damage or a loss of any kind arising from or connected wlth !his Commissions GA 3
Natlonal Board, State, Provlnce and Endorsements Date 4-fl-5 Natlonal Board No.
N/A Name of Manufacturer PULLMAN POWER Year Built 1987 Manufacturer Serial No.
N/A
- Repaired, Replaced, or Replacement REPLACEMENT AS ME Code s t a m y (Yes or No)
YES.
- r - - T-I ORIGINAq,
! I FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS I
I As Required By The Provlsions Of The ASME Code Section XI Traveler W 04 132 1 9 I
- 1.
Owner Soulhem Nuclear Operating Company Date 0 4 ~ 1 m 5 I
Name 40 lnvemess Center Parkway, Birminoham, AL Sheet
. 1 of 1
I f
I Address I
- 2.
Plant Vogtle Electric Generating Plant Unlt 1
I Name I
Waynesbom, GA 30830 WO# 10303320 I
. Address Repair Organization P.O. No., Job No., etc.
I I
- 3.
Work Performed by Maintenance Department Type Code Symbol Sump WA Name Authorlzatlon No.
N/A I
Plant Vogtle Explratlon Date M A Address I
- 4.
ldentificatlon of System 1208 /Chemical and Volume Contrd System I
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 7 Edltlon, Winter 1977 Addenda, WA code c a b (b)Appiicable Edition of Section XI Utillzed for Repairs or Replacements 1 9 s I
I
- 6.
ldentlficatlon 01 Components Repaired or Replaced and Replacement Components 1
I Name of Name of Other I
- 7.
Description of Work Snubber PSA-1, serial I23069 was repkced with a Lisega Type 30 snubber serial #W61596(Y057 in accordance with DCP 99-VANOO3.3.
I Component PIPE SUPPORT I
- 8.
Test Conducted:
~neumaticn Nomlnal Operating ~ r e s s u r e n I i N I A ~
Other Pressure WA PSI TestTemp.
WA
.F 1
I
- 9.
Remarks See Item 7 i
Applicable Manufacturer's Data Reports to be attached
' I Manufacturer :
PULLMAN POWER ROWCTS I
I CERTIFICATE OF INSERVICE INSPECTION Serial No.
WA i
I, the undersigned, holding a valid commlsslon issued by the national Board of Boiler and Pressum Vessel Inspectore and the state or Province of and employed by Hartford Steam Boiler In~oection end Insumrice Co. of Connecticut ; of HartfOld. Connecticut have Inspected the components described in this Owner's Report during the period 07/22/04 1 to,5 and state that to the best of my knowledge and bellef, the Owner has performed examlnatlons and ta'ken c o r r e c t i v t z u r e a b s c r l ~
in th\\a.Ownera Report in accordance wlth the requirements of the *PME code, Sectd Xi.
I By algnlng this certificate, nelther the Inspector nor hlr employer makes any warranty, expressed or Implled. concernlngi the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be llable In any manner for any personal injury or propem dsmage or a loss of any klnd arlslng from or connected with fthis I No..
WA CERTIFICATE OF COMPLIANCE replacemnt I
We certify that the statements made in the report are correct and this conforms to the rules of the ASME Code,Section XI.
repair or replacement I
I Type Code Symbol Stamp WA I
Certificate WA Expiration Date WA Signed Team Leader Date OyaBr or O 3
w r
~.
Commissions GXdaf Natlonat Board, State, Province and Endorsements 1
ate 5 f I I ldentlfication V1-1208-488-H002 Built 1987 or ~eplacement REPLACEMENT (Yes or ~ b )
YES )
I
FORM NIS-2 OWNER'S Q f
l 6
U B
h R
REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
041 34 Owner Southem Nuclear Operating Compeny Date Aptil 11, 2005 1
Name I
40 lnvemess Center Padway. Birmingham, AL Sheet 1
of 1
Address I
Plant VogLle Electric Generating Uant Unit 1
I Name Waynesbom, GA 30830 I
10303325 I
Address Repair Organization P.O. No., Job No., etc.
W A Work Performed by Maintenance Department Type Code Symbol Stamp Name Authorization No.
NIA Rant Vogue Explratlon Date W A Address Identification of Systm 1302 / Auxihary F eedwater System (a) Applicable Construction Code.
Wnter 1977 Addenda.
N-249-1 Code C a e (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 I
Identincation Of Components Repaired or Replaced end Replacement Components
- 7.
Description of Work Snubber AD1601, serial #322 was repleced with snubber Usega 306256RF3. seriel#03615425tD30 in accordend.
Name of Component UPE SUPPORT
- 8.
Test Conducted:
~neumatica Nominal Operating pressurea NIAB Other Pressure WA PSI Test Temp.
N/A
- F B.
Remarks See Item 7 I
Applicable Manufacturer's Data Reports to be attached Name of Manufacturer PULLMAN POWER CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this mplacement i
conforms to the rules of the ASME Code.Section XI.
repair or replacement Type Code Symbol Stamp WA N/A N/A Certificate of Authorization No.
Expiration Date Signed Team Leader Date Manufacturer Serial No.
N/A CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State, or Province of Geomie and employed by HaMord S t
e e
of lfat&d Conneclicut have inspected the components described in this Owner's Report during the period July 22, 2004 I
to 4 - 1 2 - u. ~, and state that to the best of my knowledge and belief, the Owner has performed e x a m i n a t i and taken corredthre measures described in this Owners Repor( in accordance with the requirements of the ASME Code.
Section 1 XI.
By signing this certificate, neither the tnspectoimi his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report.
Furthemre, neither the Inspector nor his employer dhall be llable in any manner for any personal lnlury or property damage or a loss of any kind arising fran or connected wlth fhls I inspe i Commlsslons GAm-?
Inspect0 s Signature National Board, State. Province and Endorsements National Board No.
M A Year Built 1987 Other Identification 1-1302-107-H010
- Repaired, Replaced, or Replacement REPLACEMENT ASME Co&
Stamped (Yes or N&)
YES i
QRlGlNAL FORM NIS-2 OWNER'S REPORT O EPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code S e d i XI Traveler#
04135 Owner Southern Nuclear Operating Company Date April 17,2005 Name 40 lnvemess Center Parkway, Wingham, AL Sheet 1
of 1
Address Plant Vogue Electdc Generating Plant Unit 1
Name Waynesbom. GA 30830 10303324 Address Repair Organization P.O. No., Job No.. etc.
Work Performed by, Maintenance Department Type Code Symbol Stamp WA Name Authorlzatlon No.
WA Plant Vogue Expiration Date WA Address Identification of System 1302 /Auxitary Feedwater System (a) Applicable Constmction Code ASME SEC 111 1 9 7 7 Edition.
Wnter 1977
- Addenda, N-249-1 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements la@
ldentification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AG1601. serial #I01 was replaced with snubber Usega 306256RF3, serial#O3615425Q22 in accord8n~e.
with DCP 99-VAN0033.
- 8.
Test Conducted:
~neumatic[SJ Nominal Operating ~ r e s s u r e D NIA Other a Pressure N/A PSI Test Temp.
N/A O F.
Name of Component PIPE SUPPORT
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be anached National Board No.
N/A CERTlF ICATE OF COMPLIANCE We certify that the slat-nts made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp M A Name of Manufacturer PULLMAN POWER CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Provlnce of Geonria and employed by Hamord Sham Boiler Inspection and Insurence Go. of Connecticut of Hartford.
Connecficut have inspected the components described in this Owner's Report during the period Julv 22. 2004 to 4-12-d.47
, and slate that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Chvners Report in accordance with the requirements of the ASME Codc Sectinn XI.
By signing this certificate. neither the Inspector nor his employer makes any warranty, expressed or implled, concerning the examinations and corrective measures described in this Owners Report.
Furthermore, neither the Inspector nor his employer shall nal injury or property damage or a loss of any kind arising from or connected with this Commissions f
f a
National Board. State, Province and Endorsements Date 4 / 2 - 8 5 Manufacturer Serial No.
WA Other Identification 1-1302-1 10-H013 Year Built 1987 Repaired.
Replaced.
or Replacement REPLACEMENT ASME Code stanped (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Sectlon XI Traveler lD W 138
- 1.
Owner Southem Nuclear Operating Company Date W21/05 Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant Vogtle Electrlc Generating Plant Unit 1
Name Waynesboro, GA 30830 WO# 1 W02525 Address Repair organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp hVA Name Aulhorizatlon No.
WA Plant Vogfie Expiralion Date WA Addresa
- 4.
Identification of System 1201 /Reactor Coolant System
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 1 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Applicable Edition of Sectlon XI Utilized for Repairs a Replacementa l9@
- 6.
ldentificatlon Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD-501, serial #502 was replaced with an AD-501 serial #406 to support surveillance lesting.
- 8.
Test Conducted:
Hydrostatic 0 pneumatic0 Nominal Operating pressure0 N l A m Other Pressure M A PSI Test Temp.
M A "F
- 9.
Remarks See Item 7 Applicable Manufacturer's Date Reports to be attached National Board No.
WA Other ldentiflcatlon V1-1201-029-HO21 Name of Component PIPE SUPPORT CERTIFICATE OF COMPLIANCE We certity that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp N.A rylA Expiration Date IWA Owner #owner's Desianem. Title Team Leader Date
- Aae-CERTIFICATE OF INSERVICE INSPECT ION I, the undersigned, holding a valid commission issued by the natlonal Board of Boiler and Pressure Vessel inspectors and the State or Province of Geomia and employed by Boiler Insaection and Insurance Co. o f Con necticuf of toHaF9f ~wrnecticut, have inspcted the cornponenta described in this Owner's Report during the period 07/2&104 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective meesures described In this Owners Report in accordance with the requirements of the ASME Code, W i n XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations end corrective measures described in this Owners Repoh Furthermore, neither the Inspector nor his employer shall property damage or a loss of any kind arising from or connected with this Commissions GA National Board, State, Province and Endorsemenis Data 5 0. r Year Built 1987 Name of Manufacturer PULLMAN POWER RODUCTS Manufacturer Serial No.
WA
- Repaired, Replaced, or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES
ORIGINAL FORM.NIS-2 OWNER'S REPORT FOR REPAlRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
W 142 4
- 1.
Owner Southern Nuclear Operating Company Date 04/25/05 Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant voQie Electric Generating Plant Unlt 1
.Name Waynesboro, GA 30830 WO# 10402522 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorization No.
WA Plant V a l e Expiration Date WA Address
- 4.
ldentificatlon of System 1201 /Reactor coolant System
- 5.
(a) Applicable Construction Code ASME SEC 111 1977 Edition, Winter 1977 Addenda,
- A Code Case (b)Applicable Edition of Sectlon XI Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Components I
I I
I National 1 I
I
- Repaired, I =ME Code I Name at Component PIPE
- 7.
Description of Work Snubber PSA-35, serial #11250 was replaced with a PSA-35 sedal #I2257 to support surveillance testing. A replacement load stud with nuts was also installed on this support.
SUPPORT
- 8.
Test Conducted:
Hydroshtlc
~neumatic[7 ~ominal Operating ~ r e s s u r e n
. N/A@
Other Pressure MA PSI Test Temp.
MA S
Name of Manufacturer PULLMAN POWER RODUCTS
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the etatements made in the repart are correct and thle replacement conforms to the rules of the ASME Code,Section XI.
repalr or replecement
. Type Code Symbol Stamp WA Manufacturer Serial No.
- A Team Leader Date
" Owner MOwner's Designee, Title I
I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, hoidlng a valid commission issued by the national Board of Boiler and Pressure Veml Inspectors and the State or Province of Geomia and employed by Hadford Steam Boiler Insmction and lnsumm Co. of Connectticut of Hartlord. Connecticut have inspected the components described in thls Owner's Report during the period 07127/04 to,5-c/-=
, and state that to the best of my knowledge and bellef, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Sectlon Xi.
By slgnlng thls certificate, neither the Inspector nor hls employer makes any warranty, exproseed or implied, concerning the this Owners Report. Furthermore, neithsr the Inspector nor hls employer shall property damage or a loss of any kind arlslng from or connected with this Commissions GA 30-3 National Board, State, Provlnce and Endorssments Date 5 @,
Board No.
WA Other Identification VI-1201-053-H005 Year Built 1987
- Repled, or Replacement REPLACEMENT Stamped (Yes or No)
YES
ORIGINAL !
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler l 04 145
- 1.
Owner Southem Nucleer Operating Company Date 04/25/05 Name 40 lnvemess Center Padway, Birmingham, AL Sheet 1
of 1
Add-
- 2.
Plant Vogtle Electric Generetina Plant Unit 1
Name Waynesboro, GA 30830 WO# 10402516 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorization No. '
WA Plant Vogtle Expiration Date WA Address
- 4.
Identification of System 12W /Safety Injection System
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 n
- Edltlon, Winter19?7Addmda, N/A Code Ca (b)Appllcabie Edition of Section XI Utillzed for Repalrs or Replacements 19&
- 6.
Identification Of Components Repaired or Replaced and Replacement Components National
- Repaired, ASME Ca Name of Name of Manufacturer Board Other Year pi^,
Stampe Component Manufacturer Serial No.
No.
ldentlflcetlon Built or Repiecement (Yes or h PIPE PULLMAN POWER MA WA V1-1304423-010 1987 REPLACEMENT YES SUPPORT RODUCTS
- 7.
Description of Work Snubber PSA-10, serial #I7531 was replaced with a PSA-10 serial #I5827 to support su#eiI&nce testing. fhe removed snubber (serial# 17531) failed an insewice functional test as documented by CRX 2005102199.
- 8.
Test Conducted:
Hydrostatic pneumatic0 Nominal Operating pressure0 N I A ~
Other Pressure WA PSI Test Temp.
N/A OF
- 9. Remarks See Itam 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this r e p l a m n t conforms to the rules of ASME Code,Section XI.
repair or replacement
\\
Type Code Symbol Stamp W A W A Expiration Date WA I
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Boerd 01 Boiler and Pressure Vessel Inspectors and the !
or Province of Georgie and empioysd by H r l f n ecticut have inspected the components described in this Owner's Report during the period 0 7 E W a3!$s$ and state that to the best of my knowledge and belief, the Owner has performed examinations and t corrective measures described In this Owners Report In accordance wlth the. requirements of the ASME Code. Sectlor By signing thls certificate, neither the Inspector nor his employer makes any warranty, expressed or implii, concerning examinations and cormctive measures described In this Owners Repoh Furthermore, neltnef the Inspector nor his employer nal injury or property damage or a loss of any kind arising from or connected wlth Commissions G, a jr National Board, State, Province and Endomements
(
Date 57 4 - 0 5
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
04 150 Y
r 1
Owner Southern Nuclear Opemting Company Date Wn1/05 Name 1
of 1
40 lnvemess Center Parkway, Birmingham, AL Sheet Address
- 2.
Plant Vogtle Electric Generating Plant Unit 1
Name Waynesboro, GA 30830 WO# 10402521 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorization No.
WA Plant Vogtle Expiration Data WA Address
- 4.
Identification of System 1204 / Safety Injection System
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 n
- Edition, Winter 1977 Addenda, N/A Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19@
- 6.
ldentification Of Components Repaired orReplaced and Replacement Components
- 7.
Description of Work Snubber PSA-35, serial W11484 was replaced with a PSA-35 serial 11 1253 to support surveilIance testing.
- 8.
Teat Conducted:
Hydraatetic
~neumaticu Nominal Operating ~ r e s a u m O MIA@
Other q pressure WA PSI
~ e s t
~emp.
WA O F Name of Component PIPE SUPPOFlT
- 9.
Remarks Seeltem 7 Applicable Manufacturer's Data Reports to be attached Manufacturer Serial No.
NLA Name of Manubcturer PULLMAN POWER RODUCTS CERTiflCATE OF COMPLIANCE We certify that the stapments made in the report are w m c t and this replacement conforms the rules of t$e ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp WA I, the undersigned, holding a valld commission Issued by the national Board of Boiler and Pressure Veosel Inspectors and the StJlte S;eoroie and employed by.
Hartfonl Steam Boiler lnsoection and Insurance Co o Con ecticul or Province of f
n of Hadford. Connecticut have inspected the components described in thls Owner's Report during the p l o d 07i27/04 to 5-3-CS
, and state that to the best of my knowledge and belief, the Owner has vrtormed examinatlona and ta9n correctlw measures described in this Owners Report in accordance with the requirements of the ASME Code. Sectlon 0x1.
By signing thls certificats, neither the Inspector nor hls employer makes any warranty, expressed or implled, mncerning the examinations and oorrectlve measures descrlbed In this Owners RepoR Furthermore, nelther the Inspector nor his employer s4all property damage or a loaa of any kind ariaing horn or connected with @is Commlasions GI al National Bsrd, State, Province and Endorsembnta Year Bullt 1987
- Repaired, Replaced, or Replacement REPLACEMENf National Bosrd No.
WA ASME Code Stamped (Vw or No)
YES :
Other Identification V1-1204-125-HO17
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPA1R.S OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler l C4 152
- 9
- 1.
Owner Southern Nuclear Operaling Company Date 04nYo5 Name 40 lnverness Center Pamay, Birmingham AL Sheet 1
of 1
Address
- 2.
Plant Vogtle Electric Generating Plsnt Unit 1
Name Waynestwm, GA 30830 WO# 104(12504 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Sump hUA Name Authorization No.
hUA M A Plant Voglle Expiration Date Address
- 4.
ldentffiiatlon of System 1208 /Chemical and Vdume Conttvl System
- 5.
(a) Applicable Construction Code ASME SEC 111 19n Edith, Winter 1977 Addenda, N-2441 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD4 1, serial #a92 was replaced with an A041 serial Y698 lo supjmrt surveillilnce testing.
I Name of Component PIPE SUPPORT
- 8.
Test Conducted:
Hydrostatic q ~neumatico Nominal Operating ~ressureO N I A ~
Other 0 Pressure MA PSI Test Temp.
MA OF
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report am correct and thls replacement conforms to tha rules of the ASME Code.Section XI.
repalr or replacement Name of Manufacturer PULLMAN POWER RODUCTS 1 T ype Code Symbol Stamp Othw Identification V1-12OB-449-H013 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the Sfets or Provlnce of Georoia and employed by k o
f H
m
'ler Har?ford. Connecticut have inspected the components described in this Owner's Fieport during the period 0 7 1 2 7 ~ ~
to C--B-n5
, and state that to the best of my knowledge and belief, the Owner has pedonned examiwtiona and taljen corrective measures described in thls Owners Report In accordance with the requirements of the ASME Code,Section XI.
9 Manufacturer Serial No.
WA I
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or lmpiled, concerning the examinations and cortectlve measurns described in this Owners RepoR Furthermore. neither the Inspector nor his employer s*ll be liable in any mwner for any personal injury or property damage or a loss of any kind arising from or connected with this I National Board No.
M A Cornmissions Nationai Board, State, Province and Endorsements ASMEC*
s u m w (Yes or No)
YES :
Year Built 1987 Date.<-.yaJZ I
- Repaired, Replaced, or Replacement REPLACEMENT
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI reveler #
041 55 Y
- 1.
Owner Southem Nuclear Operating Company Date Apt# 8,2005 Name 40 lnvemess Center Parkway. Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant VogUe Electric Generating Plant Unit 1
Name Waynesboro, GA 30830 10402528 Address Repair Organization P.O. No., Job No.. etc.
- 3.
Work Performed by Maintenance Oepattment Type Code Symbol Stamp WA Name Authorlzatlon NO.
WA Plant Vogue Expiration Date WA Address
- 3.
Work Performed by Maintenance Oepattment Type Code Symbol Stamp WA WA Plant Vogue Expiration Date WA
- 4.
ldentlfication of System
- 1301 /Main Steam System
- 5.
(a) Applicable Construction Code ASME SEC 111 1B 77 Edition.
Wnter 1977
- Addenda, N-249-1 Code Caqe (b)Applicable Edition of Section XI Utilized for Repairs or h3acements 1989
- 6.
ldentification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD-5501, serfal#254 was replaced with snubber Lisega 307256RF4, serial W4616450/029 to suppori surveilance testing. The removed snubber (setfal#254) failed en insembe hinclional test 8s documented by CR#2005102107 '
- 8.
Test Conducted:
~ n e u m a t k a Nominal Operating ~ressurem NIA a Other Pressure N/A PSI Test Temp.
WA
.F Name of Component PIPE SUPPORT
- 9.
Remarks Seeltem 7 Applicable Manufacturer's Data Reports to be attached Manufacturer Serial No.
N/A Name of Manufacturer PULLMAN POWER CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the ruks of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp N/A hVA Expiration Oate WA Team Leader Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holdlng a valid comrnisslon Issued by the national Board of Bolkr and Pressure Vessel inspectors and the State or Province of Geomia and employed by of Ha@ni, Connecllcut have inspected the compgnents d-crlbed in this Owner's Report durlng the period Juhr 27. 2004 to L/,//-6
, and slate that to the bed of my knowledge and belW. the Owner has performed exslllinatkns and taken cornctjve measures descrlbad in this Owners: Report In accordance wlth ths requirements of the ASME Code,Section XI.
By signing thls certificate, neither the Inspector nor his employer makes any warranty, expressed or implled, concemlng the examinations and corrective measures descrikd in.this Owners Report.
Furthermore, nelther the Inspector nor hls employer shall mnal injury or property damage or a loss of any kind arbsing from or connected with this Commissions GA;lbf Natlonal Board, State, Province and Endorsements Date 4-/)45 National Board No.
hVA
- Repaired, Replaced, or Replacement REPLACEMENT Other Identification V1-1301-107-HOO5 ASME C w
Stamped (Yes or No)
YES ;
Year Built 1987
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR. REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
04 157
- 1.
Owner., Souihem Nuclear Opefating Company Date 04/2 1/05 Name 40 lnvemess Center Parkway, Blmingham, AL Sheet 1
of 1
Address
- 2., Plant Voglle Electric Generating Plant
.Unit 1
Name Waynesboro, GA 30830 WO# 10303331 Address Repair Organization P.O. No., Job No., etc.
Work Peflormed by hfaintenance Department Type Code Symbol Stamp N/A Name Authorization No.
WA Plant V0gtle Erplrsdon Dote WA Address Identification of System 1208 / Chemical and Volume Control System
- 5.
(a) Applicable Construction Code ASME SEC U 1 9 7 7 Edltlon, Winter 1977 Addenda, N-249-1 Code C a y (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19@
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD-153, sehl#212 was replaced with a Lisega Type 30 snubber serial #0361596Q1067 in accordance with DCP 99-VAN0033 The removed snubber (serial# 212) failed an insewice functional test as documented by CR# 200510214 1.
- 8.
Test Conducted:
Hydrostatic [7 ~neumatic[7 Nominal Operating ~ r e ~ u r e m WAN Other Pressure WA PSI Test Temp.
NLA "F
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We cenlfy that the statements made In the reporl are correct and thle replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp WA W A Expiration Date M A Team leader Date 4 A
-/-
CEWFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valld commlsslon Issued by the national Board of Boller and Pkssure Vessel Inspectors and the State or Province of Geomia and employsd by Hartfotd S t
e e
a of
,Hartlord, Connecticut have Inspected tha components described in thls Owner's Reporl durlng the perlod 07/2&04 to 5-3-0s,
and state that to the best of my knowledge and belief, the Owfmr has perfwmed examinations and taken corrective measures described In thls Owners Report In accordance wlth the requirements of the ASME Code, Sectlon XI.
By signing this certlicste, neither the Inspector nor hls employsr makes any warranty, expressed or implled, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor hls employsr qhall sonal injury or property damage or a loss d any klnd arlclng from or connected wlth this Commissions G A ;ld3 National Board, State, Province and Endorsements Date 5-3-05' Other identification V1-1208-055-H046 Name of Component PIPE SUPPORT Manufacturer Serial No.
NLA Name of Manufacturer PULLMAN POWER RODUCTS National Board No.
WA ASME Code stamped (Yes or Nb)
YES Year Built 1987
- Repaired, Replaced, or Replacement REPLACEMENT
As Required By The Provisions of The ASME Code Section XI Traveler #
04158
- 1.
Owner SorrMem Nuclear Operating Company Name 40 lnvemess Center Parkway, Birmingham. AL Address
- 2.
Plant Vogile Electric Generaiing Plent Name Weynesbom. GA 30830 Address Date A pd 1 1. 2005
/
Sheet 1
of 1
Unit 1
10402530 Repalr Organization P.O. No.. Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorlzatlon No.
WA Rent Vogtle Explratlon Date N/A Address
- 4.
Identification of System.
1302 / Auxitary Feedwater System 6
(a) Applicable Construction Code ASME SEC 111 19 77 Edltlon, Wnter 1977
- hddenda, K249-1 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Conlponents
- 7.
Description of Work Snubber AD1601, s e w #688 was replaced with snubber Lisega 306256RC7, senal#0461594QX)56 in accordande.
witt, DCP 99-VAN0033.
- 8.
Test Conducted.
~ n e u m a t i c n Nominal Operating pressurea N I A m Other Pressure WA PSI Test Temp.
WA OF Name of Component PIPE SUPPORT
?
- 9.
Remarks See Item7 Applkable Manufacturer's Data Reports to be alteched Manufacturer '
Serial No.
WA Name of Manufacturer PULLMAN POWER CERTIFICATE OF COMPLIANCE We certlty that the statements made in the report are correct and this mP,acement conforms to the rules of the ASME Code.Section XI.
repair or replacement Type Code Symbol Stamp WA MA Expiration Date WA Team Leader Date National Board No.
WA CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geode and employed by m m of ~ a o f r a Conneckut have inspected the components described in thls Owner's Repolt during the period Auaust 3. 2004 to &-o$
. and state that to the best of my knowledge and belief. the Owner has performed examinatlons and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code.
S e c t i i XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty. expressed or Implii. concerning the examinations and corrective measures described In this Owners Report.
Furtbrmore, nelther the Inspector nor his employer shaH nal Injury or property damage or a loss of any kind arising from or connected with this Commissions 203 National Board. State, Province and Endorsements oate 4/305 Other Identification 1-1302-70&H010 Year Built 1987
- Repaired, Replaced.
or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code W o n XI Traveler #
04 1 70 I
- 1.
Owner Southern Nuclear Operating Company Date WW Name 40 lnvemess Center Palkway, Bimingham, AL Sheet 1
of 3
Address
~ ~. -.-
- 2.
Plant VogNe Electric Generstlng Plant Unit 1
Name Waynesbom, GA 30830 WO# 1010031501 Address Repair Organization P.O. No., Job No..etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stmp WA Name Authorbalm No.
WA Plant Vogtle Explratlon Date WA Address
- 4.
Identification of System 1208 /Chemical and Volume Control System
- 5.
(a) Applicable Construction Code ASME SEC 111 1977 Edition, Winter 1977 Addenda, NLA Code Case (b)Applicabb Edition of Section XI Utilized tor Repairs or Replacements 198Q Mm Code Case N-554-2
- 6.
Identification Of Components Repaired or Replaced and Replacement CompofIentS
- 7.
Description of Work Valve plug was replaced. A copy of Fom N-2 for the replacement plug (S/N AEB987-1) is alteched.
- 8.
Test Conducted:
Hydrostatic q ~neumaticO N o m i ~ l Operating ~ r e s s u m O W A B Other Pressure NLA PSI Test Temp.
NLA O F
- 9.
Remark8 See Item 7 Applicable ~anufacturer's Data Reports to be attached Other Identification 1HV0128 Year Built 1978 CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rubs of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp NLA Expiration Date NLA Team Leader t
$A 4 c CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission imued by the national Board of Boiler and Pressure Vessd Inspectom and the State or Province of and employed by Ha-er-nd Insurance Co. of Connecljcut Connecf&&
haw inspected the components &scribed in this Owner's Report during the period OfHemord.
12/14/W to R-30-w
, and state that to the best of my knowledge and b e l i, the Owner has performed examinations and taken conectiva mesrurer described In this Ownem Report in accordance with the requirements of the AWE Code,Section XI.
By signing this certificate, neither the Inspector nor his empkyw makes any warranty, expressed or impliad, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inepector nor hi$ employrr shall rsonal injury or property damage or a loan of any kind arising from or connected with this Commmsions 20.3 National Board, S v, Province and Endorwmenta Date p-30-05 Name of Component VALVE Manufacturer Serial No.
6499379
- Repaired, Replaced.
or Replacement REPLACEMENT Name of Manufacturer FISHER CONTROLS co.
National Board NO.
3238 ASME Code Stamped (Yes or No)
YES
FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL k b r # 0+1,70 NUCLEAR PARTS AND APPURTENANCES*
As Required by the Provisions of Ihe ASME Code, Section Ill she* 2 043,
~ o t to exceed One Day's Production 025-N230160764 I. M.nufbeUd and fmified h!.
FISHER CONTROLS lNT'L.LLC, 205 SOUTH CENTER STREET, MARSHALLTOWN, 1A 50158 (name a d &s) of NPT Crrtilcn~ Holdct)
- 2. h4mubctu~d for Control. Southenr Nuclw Plank 3850 Lakcfield Dr. Suwmce, GA 30024
(
n
~
~d ~ddrcS3 of p ~ r c b m )
- 3. h t i o n ofinp(lJLtiaa VOEUC Ucchic Gm. Plant, 7821 River R o d Warnthorn. CSA 30830 (nunc andddles)
- 4. Type 11,432 1 1 Rev. B SA479S31600 75 KSl NIA 2004 (drawingno.)
(mal'l. spa, no.)
(Imsile mgh)
(Cm)
(yur built)
- 5. ASME Codc. Section Ill:
1971 Sunmn 1972 2
NlA (cditioa)
(addcodadatc)
(dm)
(Code Cucw.) :
- 6. Fabriakd in.fcordaM wiwonst Spsc. (?a 2 only)
- 7. R t ~ m l k s Dcsipn: ASME B W C ' S ~ ~ :
111,1971 Edition S u m 1972 Adden&. Class 2 OUlcr. ASME BWC Slc llI, 1989Edition, No AMcndq CI.g 2
- 8. Nom Ibicknes (in.)
NIA Min. dtoigp thick-(in)
NIA Dir ID (A Bin.)
. LmgUI ownll (A & in)
NIA :
- 9. When appliable, W ~ c l t r Holders' D.lr R q m ~
u c for uch itan of this repotl:
- 10. Dedp Rclsurc 600 psi.
Trmp.
400 T.
Hydm. fed prraure NIA at m. T (whm appliublc)
Fhi m Appurtc~na Sai J Ntmhr
+-(I)
AE89R7-I (2)
AEA987-2 (3)
(4)
(5)
(6)
(7)
(8).
(9)
(10)
(1 1)
(12)
(13)
(14)
(1s)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(25)
'Supplanen(ll info&iom in tbc f m ofhaq Qetcber, or dmwilyr may b c. u d provided (1) d= is 8 112 x 11, (2) i n f d o n in ilrrnt 2 and 3 on (his I)rlr. R v
is included on u c b &cat, (3) each e&ct is aumhmd lad the n u d m of sheets is rccor&d at h e f ~ p of Ibis fonn Heat Number 13949 13949
FORM N-2 (back) 4 Mk Serinl No.
AER9R7-I.-2 CERTIFICATION OF DESlGN Dcigr rpecihulipnr certified hy Hmry P. Leon~ld P.E. Sulc PA Rc& no.
23938-E (when clppliublc)
Deigr repo~i* certified hy NIA P.E. She NIA Reg. no.
NIA (when applicable)
CERTIFICATE OF SHOP COMPLIANCE We cerlit) &at Lhe grtnncnh nn& in this r e p l am correct a d ( h t this (these)
Piu@SCrm Asy wnhms tn (bc rules ofconmclion of the ASME C&. Section 111.
NIT Cdfiark of AuLborization No.
1930 Expins 11-1 1-20U4) h me g-26
- o c/ ~m FISHER CONTROLS WTL LLC
/&Ad (NPT Ccrlifrak Holder)
(authoril$d tqtresmtaiive)
CERTlFlCATE OF SHOP 1NSPECTlON I. (be undnsipcd holding CI valid comr6aiom iasued by the National Boud ofBuilcr and Rtssurr V d
Inqcctnrs and Lhc state or Province of I o w ud cq~loycd by HwtLrd Stem Bailer of CT of Hadord,CT have inspected (btsr item dcsnhcd in his Data Rqmi on 9-36-eoy a n d N t c ~ 1 I n l h c best of my knwrlodgr md belief. the Cnri6ute Holdsr hs Eabriukd BCIC p m ot rppurlenanon, in accorQaa wicb & ASME Code, Section 111. Escb +
liakd hr been s
u
~
~
f o
r
~
o o
L h
c t
e
~
~
By signing (his &6cak, n e i k (be inrpec(mnw his anploys d e s any wmanty, e x p r e d or implied, c o d a g chc equipment &mi in (his the RcpDfi Furlbcm#m. nsilkr (be inspector nor his eaploya shll k l i l e in any rmumer for my p d
injury or
&mqc or loss of any kind d i g Sum a with thin m@op 43-dw-7 h e @ d ~ Y signed
~onrmissions 83% a (Aubtind lqcclm (N.l'l.Bd.(i.sndoncmslra)~orprov.~dno.)
>-. PRlGlNAL FORM NIS-2 OWNER'S RE ORT FOR REPAIRS OR REPLACEMENTS As Required By he Provisions Of The ASME Code Section XI Traveler #,
041 73 4
I Owner Soulhem Nudeer Operating Company Date Apt# 15,2005 Name 40 lnvemess Center Parkway, Bimdngham, AL Sheet 1
of 1
Address Plant Voglle Electric Generating Plant Unit 1
Name 4
Waynesboro, GA 30830 roraJm ~oUuwUia 41bl"?
Address Repair Organization P.O. No., Job No., etc.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorlzatlon No.
WA Plant VogL Explratbn Date WA Address Identification of System 1201 /Reactor Coolant Sysfem (a) Applicable Construction Code ASME SEC 111 1 8 7 7 Edition, Wnter 1977 Addenda.
N-249-1 Code C a y (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1088 Identification 01 Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber AD-151. seriel#154 was repfaced wifh snubber AD-151, serial #482 to support survdance festing.
Name of Component PIPE SUPPORT
- 8.
Test Conducted:
~neurmtic Nominal Operating Pressurea N I A B Other Pressure MA PSI Test Temp MA O F
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Repotts to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of tpe ASME Code, Sectbn XI.
repair or replacement
- /A Type Code Symbol Stamp Name of Manufacturer PULLMAN POWER N/A Team Leader National Board No.
NLA Manufacturer Serial No.
N/A I
CERTIFICATE OF INSERVICE INSPECTION 1
I. the undersigned, holding a valid comnission issued by the national Board of Boiler and Pressure Vessel lnspactors and the State - or Province of Geomia and employed by Hartlbrd Steam Boi/er lns~ection and Insurance Co. of Conneclic~t d Harthrtla Conne #cut have Inspected the components described in this Owner's Report during the period - Januarv 04. 2005
&&-a>
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcho measures described in this Owmrs Report in accordance with the requirements of the ASME Code.
Section ; XI.
Other Identification V1-1201-030-H601 1
I By signing this certlfme, nelther the Inspector nor his employer makes any warranty, expressed or hplled, concerning the examinations and ~0Vocthre measures described in this Owners Report.
Futthermore, neither the Inspector nor his employer shall be liable in any mannehfor any personal injury or property demage or a loss of any kind arising from or connected wlth this Commissions
&A a-National W r d. State. Province and Endorsements I
Year Built 1987
- Repaired, Replaced.
or Replacement REPLACEMENT ASME Code Stamped IYes or No)
I '
YES j
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provlsloqs Of The ASME Code $ectlon XI Tmvelerl 05004 cl
- 1.
Owner Southem Nuclear Opemtlng Company Date W11/05
/
Name 40 lnvemess Center Padrway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant Vogtle Eiectric Generating Plant Unit 1
Name
~a~nesboro, GA 30830 WO# 10403140 Address Repair OrganlreUon P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Coda Symbol Stamp WA Name Authorhtlon No.
NLA Plant Vogtle Gcpiratlon Dam WA Address
- 4.
Identification of System 1204 /Safety Injection System 1553-1
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 4 Edition, Summer 1974 Addenda, 8 1649 Code Case (b)Applicable Edition of Sectlon XI Utillzed for Repairs or Replacements 1989
- 6.
Identification 01 Components Repaired or Repleced and Replacement Components
- 7.
Description of Work Circular mounting pads (appmdmately 1' diameter and 11" thick) for acoustic sensors were fabhted from SA-240 TP 304 plate and welded to the valve. One pad is located on the external-top-side of the valve oubt and the second is located on the external-bottom-side of the valve body. Installation of the mounting pads was completed in accordance with MDC 04-V1 M055.
Name of Component VALVE
- 8.
Test Conducted:
Hydrostetic
~neumaticn Nominal Operating ~ r e s s u r e n N I A ~
Other 0 Pressure WA PSI Test Temp.
WA OF
- 9.
Remarks See Item 7 Appllcable Manufacturer's Date Reports to be attached Name of Manufacturer WESTINGHOUSE h
CERTIFICATE OF COMPLIANCE We certity that the stetements made in the report are correct end this replacement conforms to the rubs of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp WA Expiratlon Data Team Leader Date Manufacturer Serial No.
10001CS990000 00005740002 Owner or Mner's Designee, Title
- - I
- 7 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the Stab or Provlnce of Geomia and employed by _
H e
r H
o r
d m
m of Hartfont. Connecticut have Inspected the components described in this Owner's Report during the period a to,T-11-65, and state that to the best of my knowledge and belief, the Owner has performed examlnatlons and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certlflcate, neither the Inspector nor hls employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor hls employer shall be Ilable In any manner for any personal injury or property damage or a loss of any kind arising from or connected wlth this Commissions -
Natlonal Board, State, Provlnw and Endorsements Date 5 - / ? - a 5 National Board No.
W18317 Other ldentlflcatlon 1 -1204-U6-079 Year BuiR 1978
- Repaired, Replad, or Replacement REPlACEMEM ASME Code Stamped (Yea or NO)
YES -
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
05005 I /
- 1.
Owner Southem Nuclear Operating Company Date 05/11/05 Name Y
40 lnvemess Center Parkway, Blrrningham, AL Sheet 1
ol 1
AddtBss
- 2.
Plant Vogtle Electric Generating Plant Unit 1
Name Wayneslwro, GA 30830 WO# 10403140 Addresa Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code symbd Stamp Name Authoridon No.
WA Plant Vogtle Expiration D m WA Address
- 4.
Identification of System 1204 /Safety Injeciion System 1553-1
- 6.
(a) Applicable Construction Code ASME SEC 111 1 9 2 Edition, Summer 1974 Addenda, 8 1649 Code Case (b)Appllcable Editlon of Section XI Utilized for Repairs or Replacements 1 9 a
- 6.
ldentlficatlon Of Components Repaired or Replaced and Replacement Components
- 7.
Descrlptlon of Work Circular mounting pads (approximately 1' diameter and 16-thick) for acoustic sensors were fabricated from SA-240 TP 304 plate and welded to the valve. One pad is located on the exiemal-topside of the valve oulet and he second is located on the external-bottom-side of the valve body. Installation of the mount in^ pads was completed in accordaI)C8 with MDC 04-VIM055.
Name of Component VALVE
- 8.
Test Conducted:
~neumaticn Nominal Operating ~ r e s s u r e o N / A B other q Pressure WA PSI Test Temp.
WA
.F
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached Name of Manufacturer WESTINGHOUSE CERTIFICATE OF COMPLIANCE We certify that the statements mede in the report are correct and this replacement conforms to the rules ol the ASME Code, W o n XI.
repair or replacement
\\,
( Type Code Symbol Stamp N/A I
Manufacturer Serial No.
10001CS990000 0000s740004 CERTIFICATE OF INSERVICE INSPECTION 1, the underslgned, holdlng a valid commission issued by tho national Board of Boiler and Pressure Vessel Inspectors and the State or Province ol Geomia and employed by Hatiford Stea ~I of nn t m t have Inspected the components described in this Owner's Report during the period A i
1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance wlth the requiremanta of the ASME code^,Section XI.
By signing this certificate, nelther the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor h b employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arislng from or connected wlth this Commissions GA d&
Inspeci6r's Signature National Boerd. Stem, Province and Endorwrnenta Data 5 - / 7 - 6 5 Natlonal Board No.
W18388 Year Elullt 1978 Other ldentiflcation 1-1204-U6-080
- Repaired, Replaced, or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES
I ORIGINAL.,
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions 01 The ASME Code Section XI Traveler #
05006 4
- 1.
Owner Southern Nuclear Operating Company Date 091 1/05 Name 40 lnvemess Center Parkway, Blrrningham, AL Sheet 1
of 1
Address
- 2.
Plant Vogtle Electric Genemting Plant Unit 1
Name Waynesbom, GA 30830 WO# 10403140 Address Repair Organlzstlon P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code. Syrnbd Stamp WA Name Authorization No.
WA Plant Vogtle Gcplration Date WA Address
- 4.
Identification of System 1204 / Safety Injection System 1553-1
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 4 Edition, Summer 1974 Addenda, 8 1649 Coda Caw (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19&
- 6.
Identification Of Components Repaid or Replaced and Replacement Components
- 7.
Description of Work Circuler mounting pads (approximate& 1" dismeter and %"thick) for acoustic sensors wen, fabricated from SA-2.40 Name of Component VALVE TP 304 plate and welded to the valve. One pad is located on the external-top-sida of the valve oulet and the second is located on the external-bottom-side of the valve body. lnstallation of the mounting pads was completed in accordance with MDC 04-V1M055.
- 8.
Test Conducted:
Hydrostatlc
~neumatlcO Nominal Operating ~ r e a s u r e n N I A ~
Other Pressure WA PSI Test Temp.
MA O F
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached Name of Manufacturer WESTINGHOUSE CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, m i o n XI.
repalr or replacement Type Code Symbol Stamp WA WA Expiration Date WA Team Leader Owner downer's Desi$nw, Title National Board No.
W18389 Manufacturer Serial No.
10MllCS990000 OWOS740005 CERTIFICATE OF INSERVICE INSPECTlON I, the undersigned, holdlng a valid commlsslon issued by the national Board of Boiler and Premure Vessel Inspectors and the State or Provlnce of Geomia and employed by Hartford Steam Boil r of Hartford. Connecticut have inspected the components described In this Owner's Report during the period 02/01MS to 5 - / 7 d S
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measurer described in thls Owners Report In accordance wlth the requlrements of the ASME Code.Section XI.
By slgnlng thls certlflcate, ndther h Inspector nor hls employer makes any warranty, expressed or Implled, concerning the examlnatlons and corrective measurea described In this Owners Repoh Furthermore, neither the lnrpector nor his employer shell bellable In any manner tor any personal lnlury or property damage or a loss of any kind arislng from or connected with this Commissions G!
a03 National Board, Stab, Province and Endormmenb Date-C Other Identification 1-1204-U6-081 Year Built 1978
- Repaired, Replacod, or Replacement REPLACEMENT ASME Coda Stamped (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code SFion XI Traveler #
05007 4
- 1.
Owner Southem Nuclear Operating Company Date 05/l1&5 Name 40 lnvemess Center Parkway, Blrmlngham. AL Sheet 1
of 1
Addrew
- 2.
Plant Vogtle Electric Generating Plant Untt 1
Name Waynesbotu, GA 30830 WO# 10403140 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Typn Code Symbol Stamp WA Name Authorlzn~lon No.
WA Plant Vogtle Expiration Data WA Address
- 4.
IdentHlcation of System 1204 /Safely In]ection System 1553-1
- 5.
(a) Applicable Construction Coda ASME SEC 111 1 9 7 4 Edition, Summer 1974 Addenda, 8 1649 Code Caw (b)Applicable Editlon of Section Xi Utilized for Repairs or Replacements lS@
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Descriptlon of Work Circular mounting pads (approximately 1" diameter and Y" thick) for acoustlc sensors were fabricated from SA-240 TP 304 plate and welded to the valve. One pad is located on the external-top-side of the valve oulet and the second is located on the external-bottom-side of the valve body. Installation d the mounting pads was completed in accordance wlih MDC 04-V7M055.
Name of Component VALVE
- 8.
Test Conductsd:
~neumatic[7 Nominal Operating ~ressurem N I A ~
other pressure WA PSI
~ e s t
~emp.
WA O F
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be atlached Name of Manufacturer WESTINGHOUSE Team Leader Owner wner's Designee, Title Manufacturer Serial No.
100alCS990000 00005740001
\\
, ( Certiflcete of Aythorization No.
/ WA Expiration Date WA CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and thls replacement conforms to the rules of the ASME Code, Sectlon XI.
repair or replacament Type Code Symbol Stamp WA CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomia and empioyed by -
g of
_Hartford. haw inspected the components described in this Owner's Report during the period 02/01/05 to 5-i7-d<
and state that to the best of my knowledge and bellef, the Owner has performed examinations and taken corrective measures described in this Owners Rbport in accordance wlth the requirements of tho ASME Code, Section Xi.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examlnetions and corrective measures described in this Owners Report. Furthermore. neither the inspector nor his empioysr shall be liable In any manner for m y personal injury or property damage or a loss of any kind arbing from or connected with this Commissions a d d 3 National Board. State, Province and Endorsements Date
.q-
/7&
National Board No.
W18316 Other Identification 1 - 1204-U6082 Year Built 7978
- Repaired, Replaced, or Replacement REPLACEMENT ASME Code Stamped
. (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Sectlon XI Traveler#
05008 r
- 1.
Owner Southem Nuclear Opemtlng Company I
Date 0 9 1 1/05 Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant Voglle Electric Generating Plant Unlt 1
Name Waynesboro, GA 30830 W&
10403140 Address Repair Organlzetlon P.O. No., Job No., etc.
Work Performed by Maintenance Department
~ y p e code Symbol Stamp NLA Name AuthorizaUon No.
WA Plant VogtIe Expirallon Data NLA Address Identification of System 3204 /Safety Injection System 1553-1
- 5.
(a) Appllceble Construction Code ASME SEC 111 1974 Edltlon, Summer 1974 Addenda,
& 1649 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacementa l9a
- 6.
ldentlficetion Of Components Repaired or Replaced end Replacement Components
- 7.
Description of Work Circular mounting pads (approximately 1' diameter and %" thick) lor acoustic sensors were fab~cated from SA-240 TP 304 plate and welded to the valve. One pad is located on the extemal-fop-side of the valve oulef and the second is located on the external-bottom-side of the valve body. Installation of the mounting pads was completed in accordance with MDC 04-V1 M055.
Name of Component VALVE
- 8.
Test Conducted:
Hydrostatic q pneumatic0 Nominal Operating ~ r c a s u r e a NIAO Other q Pressure N/A PSI Test Temp.
N/A OF Manufecturer Serial No.
10001CS990000 00005740006 Name of Manufacturer WESTlNGHOUSE
- 9. Remerks See Item 7 Applicable Manufacturer's Data Reports to be anached CERTIFICATE OF COMPLIANCE We certlfy that the statementa made In the report are correct and this replacement conforms to the rules of the ASME Code.Section XI.
repeir or replacement Type Code Symbol Stamp MA National Board No.
W18390 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding e valid commission Issued by the natlonel Board of Boiler and Pressure Veasel Inepectors and the State or Province of Geomia and employed by H e
r t
f o
r d
a of H a M d. Connect&ut have in+W the components descrIbd In this Owner's Report during the period 02/01/05 to 7 and state that to the beet of my knowledge and belief, the Owner hes performed examinations and taken
~rrective measures describd In this Owners Report in accordance with the requlrementa of the ASME Code,Section XI.
By signing this certlticuto, neither the Inspector nor his employer makes any warrenty. expressed or implkd, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employsr shdl a1 Injury or property demage or a loss 01 any kind arising lrom or connected wlth thls Commissions a a 3 National Board, State, Provlnce and Endorsements ate 5-17-45' Other Identification 1-1204-U6-083 ASME Code stamped (Yes or No)
YES Year Built 1978
- Repaired, R e p l a,
or Replecement REPLACEMENT
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler W 05009
- 1.
Owner Southem Nuclear Operating Company Date OVl1DS I
Name 40 lnvemess Center Parkway, Bimingham, AL Sheet 1
of 1
Address
- 2.
Plant Vogtle Electric Generating Plsnt Unit 1
Name Waynesborv, GA 30830 WOAY 10403140 Address Repair Organlzetion P.O. No., Job No., stc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name Authorization NO.
WA Planf V a l e Expiration Date WA Address
- 4.
Identification of System 1204 /Safely lnlectlon System 1553-1
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 4 Edition, Summer 1974 Addenda, 8 1649 Code Case (b)Appllcable Edltion of Section XI Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description ot Work Circular mounting pads (appmximately l'diameter and 14" thick) for acoustk sensors were fabriceted fmm SA-240 Name of Component VALVE
- 8.
Test Conducted:
~neumaticO Nominal Operating ~ressureO W A N Other Pressure NLA PSI Test Temp.
N/A S
B.
Remarks See Item 7 Appllcabk Menufecturer's Data Reports to be etbxhad Name ot Manufacturer WESTINGHOUSE CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and thls mplacement conforma to the rules of the ASME Code, Sectlon XI.
repair or replacement Type Code Symbol Stamp N/A Expiration Date MA Team Leader Date CERTIFICATE OF INSERVICE INSPECTION I, the underalgned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspecton, and the Smte and employed by Harfford Ste f Connecticut or Province of Geomia am Boiler Insoection and In-umnce Co. o of Hatiford. Connecticut have Inspected the components described in this Owner's Report during the perlod 02/011Y)5 to 5 - 1 7 - S
, and state that to h best of my knowledge and belief, the Owner has pertormed exsminstlons end taken corrective measures described in this Owners Report in accordance wlth the requirements ot the ASME Code,Section XI.
By signing thb certificate, neither the inspector nor his employer makes any warranty, expmasad or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his emplopr ahall proparty damage or a loss of any kind arising from or connected wlth this Commisaiona GA -3 Natlonai Board, State, Province and Endorsements Date S w - / f - d Manufacturer Serial No.
10001CS990000 00005740003 National Board No.
W18318 Other ldentitlcation 1-1204-U6-084 Yeer Built 1978
- Repaid, Replaced, or Replacement REPLACEMENT ASME C&
Stamped (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler t 050 10
- 1.
Owner Southern Nuclear Operating Company Date 091 1/05 Name 7
40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant VogNe Electric Generating Plant Unit 1
Name Waynesbom, GA 30830 WO# 10403140 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by.
Maintenance Department Type Code Symbol Sump N/A Name Authorization No.
NLA Plant Vogtle Expiration Date NLA Addreas
- 4.
Identification of System 1204 /Safety Injection System 1553-1
- 5.
(a) Applicable Construction Coda ASME SEC 111 1974 Edition, Summer 1974 Addenda,
& 1649 Code Caw (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
- 6.
Identification Ol Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Cin:uIar mounting pads (appmximately 1" diameter and %' thick) tor acoustic sensors were fabricated fmm SA-240 TP 304 plate and welded to the valve. One pad is located on the exfemaktopside of the valve oulet and the second is located on the external-bottom-side of the valve body. Installation of the mounting pads was completed in accordance with MDC 04-VIMOSS.
Name of Component VALVE
- 8.
Test Conducted:
~neumaticO Nominal Operating ~ressureO W
A
~
0 t h q pressure MA PSI lest femp.
WA OF
- 9.
Remarke See Item 7 Applicable Manufacturer's Data Reports to be^ attached Name of Manufacturer WESTINGHOUSE CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp N/A W A Expiration Date WA Owner or Owner's Designee, Title Data -$;/Lcu~
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission iaeued by the national Board of Boiler and Pressure Verurel Inspectors and the State or Province of Gsorpia and employed by Hanford Steam Boiler Insmction and lnsunrnce Co. of Connecticut of H a r t l o r d. L have Inspected the components described In this Owner's Report during the period Oml/OS to a - / 7 - 6 5
, and state that to the best of my knowledge and belief, the Owner has pedormed exemlnations and taken corrsctlve measures described In thls Owners Report in accordance with the requirements of the ASME Code. W o n XI.
Manufacturer Serial No.
10001CS99OOW 0000s74ooaB I
By signing thls certlficete, neither the inspector nor his employer makes any warranty, expressed or impiied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be iiabie in any manner tor any personal injury or property damage or a loss of any kind arising hom or c o n n k t d with this I Commissions 283 National Board, State, Province and Endorsements National Board No.
W17476 Date 5-17-a5 I
Other ldentificatlon 1 - 1204-U6-085 ASME Code Stamped (Yes or No)
YES Year Built 1978
- Repaired, Replaced, or Replacement REPLACEMENT
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #
0501 1 Ll 1
Owner Southem Nuclear Operating Company Date 054 7/05
/
Name 40 lnvemess Center Parkway. Birmingham. AL Sheet 1
of 1
Address
- 2.
Plant Voglle Electric Generatlng Plant Unit 1
Name Waynesbom, GA 30830 WO# 10403140 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Name AulhorlzeUon No.
WA Plant Vogtle Expiralion Date WA Address
- 4.
Identification of System 1204 /Safety Injection System
- 5.
(a) Applicable Construction Code ASME SEC 111 i 9 7 4 Edition, Summer 1974 Addenda,
& 1649
. Code Case (b)Applicable Edition of Section XI Uti1ized for Repairs or Replacements 1989
- 6.
ldentlfication Of Components Repaired or Replaced and Replacement Components
- 7.
Description ot Work Circular mounting pads (appmximately 1' diameter and I&" thick) for acoustic sensors were fabricated from SA-240 TP 304 plate and welded to the valve. One pad is located on the external-top-side of the valve wlef and the second is located on the external-bottom-side of the valve body. Installation of the mounting pads was wmpleted h accordance with MDC 04-V1M055.
- 8.
Teat Conducted:
~neumatlcm Nominal Operating ~ r e s s u r e 0 WAN Other 0 Pressure WA PSI Test Temp.
WA OF Name d Component VALVE
- 9.
Remarks See Item 7 Appiicabie Manufacturer's Data Reports to be attached Name of Manufacturer WESTINGHOUSE CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, W o n Xi.
repair or replacement Manufacturer Serial No.
10001CS990000 0000s740007 Type Cock Symbol Stamp WA
- WA Expiration Date WA Team Leader Date OwneptG Owner's Designee, Title Other Identification 1 - 12W-U6-086 National Board No.
W18391 b
CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commiaslon issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomia and employed by a m
Boiler Insmction and Insurance Co, of Connecticut of Harffom'. Connecticut have inspected the components described in this Owner's Report during the perlod -
0ZG1/05 to /-/7dF,
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate, neither the Inspector nor his empioyer makes any warranty, expreasd or impiled, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor hie cwnploysr shall be llable In any manner tor any personal injury or property damage or a loas of any kind arlslng from or connected with thls Commissions GA a 3 National Board, State, Province and Endorsements Date
& - - / 7 6 5 Year Built 1978 Repaired.
- Repiad, or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES
FO.RM NIS-2 OWNE a b k b k % k 3 S OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Trader#
05012
- 1.
Owner Southem Nuclear Operating Company Date Apn? 4, 2005 Nanm 40 lnvemess Center Pamay, Bimngham. AL Sheet 1
of 1
Address
- 2.
Plant Vogue Electric Generating Plent Unit 1
Name Waynesboro. GA 30830 1040319601 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work P e r f o w by Maintenance Department Type Code Symbol Stamp WA Name Authorlzatlon No.
WA Rant Vog&
Explratlon Date WA Address
- 4.
Identification of System 1204 / SaBly Injection System
- 6.
(a) Applicable Construction Code ASME SEC 111 19 77 Editin.
Wnfer 1977
- Addenda, WA Code Case (b)Applkable Edition of Section XI Utilized for Repairs or Replacements 19@
- 6.
ldentification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Replace pipe support 1-1204021-H019 b suppo~
MDC OCVlM033
- 8.
Test Conducted:
~ n e u m a t i c n Nominal Operating ~ r e s s u r e m NIA Other [g Pressure MA PSI Test Temp.
N/A OF
- 9.
Remaas Seeltem 7 Applicable Manufacturer's Data Reports to be attachad Other identification
' V1-1204021-HOlO Name of Component PIPE SUPPORT CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of tlr ASME Code,Section XI.
repair or replacement Manufacturer Serial No.
N/A Name of Manufacturer PULLMAN.
POWER Type Code Symbol Stamp N/A N/A
~x~irati&l Date MA Teem Leader Date or Owner's Desi$nee. Tltle Year Built 1987 National Board No.
NLA CERTIFICATE OF INSERVICE INSPECTION I, the undersigned. holding a valid commission issued by the national Board of Boikr and Pressure Vessel I n m o m and the State or Province of Georuia and employed by H
a r
t f
o r
d
?
of Harthd.
Connecaut have inspected the components described in this Owner's Report during the perkd -
February 3. 2005 to 7 - L -&, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, elipressed or implied, concerning the examlnatlons and corrective measures descrikd in, this. Owners Report.
Furthermore, neither the lnsptxtor nor his employer shall for any personal injury or property damage or a loss of any kind arlsing from or connected with this Commissions National Board, State. Province and Endorsements Date 7 4 I
Repaired.
- Replaced, or Replacement RERACEMENT ASME Code stamped (Yes or No)
YES
FORM NIS-2 OWNER'S As Required By The Provisions Of The ASME Code Section XI Tmveler#
05075 4
Owner Southern Nuclear Operabhg Company Date A@ 29.2005 Name 40 lnvemess Center Parkway, Birmingham. AL Sheet 7
of
- 1 Address Plant Voglle Electric Generating Bent Unit 7
Name Waynesbom, GA 30830.-
10201413 Address Repair Organization P.0. No., Job No.. etc.
W m Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorlzatlon No.
N/A Pbnt Vogue Expiration Date WA Address Identifmtion of System 1201 /Reactor Coolant System (a) Applicable Construction Code ASME SEC 111 1 9 7 1 Edition, Summer 1972
- Addenda, N - 4 S l Code Case (b)ApplicaMe Edition of Section XI Utllized for Repairs or Replacements 1889 Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Instal replacement threaded hdcal-coil insert and replacement bolt on cold leg inspection port handhab (Ul-SGQCUPH), b ~ l f hde #3.
- 8.
Test Conducted:
Hydrostatic (g ~ n e u m a t i i a Nominal Operating ~ r e s s u r e a N I A a.
Other Pressure N/A PSI Test Temp.
N/A OF Name of Component STEAM GENERATOR
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached Name of Manufacturer WESTINGHOUSE ELECTRIC CORP.
CERTIFICATE OF COMPLIANCE We certify thal the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.
repair or replacement Manutacturer Serial No.
GAGT 1884 1 Type Code Symbol Stamp N/A I
Other Identification 1-1201-86-004 National Board No.
NIA Expiration Date WA
- / 1 I
Team Leeder Oat,,
I C.
I CERTIFICATE OF INSERVICE INSPECTION 1
Year Built 1981.
I, the undersigned, holding a valid commission issued by the national ~oard'of Boiler and Pressure Vessel Inspectors andsthe State or Province of Geomia and employed by Hu~iford Steam Boiler Ins~ection and Insurance Co. d Conneciicut of Connec8cuf have inspected the components described in this Owner's Report during the period M a r ' 8. 2005 to a, and state that to the best of my knowledge and be~lhf, the Owner has performed examinations and taken corrective measures described in thls Ormcrs Report In accordance wlth the requirements of the ASME Code,Section XI.
By signing this certificate, nelther the Inspector nor his employer makes any warranty, expressed or implled. concerning the examinations and corrective measures described In thls Owners Report.
Furthermore, nelther the Inspector nor his amployer shall rsonal injury or property damage or a loss of any kind arising from or c o d & d t h this Commissions GA 30 1 National Board, State. Provlnce and Endorsements
- Repaired, Replaced.
or Replacement REPLACEMENT Date 5 - 9 -05' ASME Code Stamped.
(Yes or No)
YES
R M L N L S o R w m c E, E w s FORM NIS-2 OWNER'S As Required By The Provisions Of The ASME Code Section XI Traveler #
05016 1
Owner, Southem Nuclear Operating Compeny Date Aprir 15.2005 I
Name 40 lnvemess Center Parkway. Birmingham. AL Sheet 1
of 1
Address
- 2.
Plant Vogue Electric Generating Plant Unit 1
Name Waynesbotu. GA 30830 10201414 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Depertment Type Code Symbol Stamp WA Authorlzatlon No.
WA Name Plant Vogfle Explratlon Date WA Address
- 4.
Identification of System 7201 /Reactor Codant System I
- 6.
(a) Applicable Construction Code ASME SEC 111 1 9 2 Edition, Summer 1972
- Addenda, N-4961 Code ~ a i e (b)Appiicable Edition of Section Xi Utliized for Repairs or Replacements 19Bg I
- 8.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Instal meplacement threaded helical-coi insert end replacement bolt on cold leg inspeclion port handhde (Ul-SGl-CUPH), bbdl hole t i.
- 8.
Testconducted:
Hydrostatic Pneumatic 1 Nominal Operating ~ r e s s u r e m N I A ~
other Pressure N/A PSI Test Temp.
MA OF Name of Component STEAM GENERATOR
- 9.
Remarks Seeltem 7 Applicable Manufacturer's Data Reports to be attached National Board No.
NLA CERTNICATE OF COMPLIANCE I
We certify that the statements made in the report are correct and this meplacement conforms to the rules oft?
ASME Code,Section XI.
repair or replacement Type Code Symbol stamp N/A Certificate of Authorizatkn No.
A NLA Expiration Date NLA Spned &&&f er Team Leader I
ner' ignee, Title Name of Manufacturer WESTINGHOUSE ELECTRIC CORP.
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomia and employed by Harllbtti S t
e e
of Ha#btd.
have ~nspected the components described in this Owner's Repatt during the period - March 8. 2005 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owmrs Report in accordance with the requirements of the ASME Code, Saction ;XI.
By signlng this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concemlng the examinatkns n this Owners Report.
Furthennore, neither me Inspector nor hls employer +all nal injury or property damage or a loss of any kind arislng from or conmcted with p i s Commissions GA 30.3 National Board, State. Province and Endorseme&
1 a.
Other Identification I-1201-B6-001 Manufacturer Serial No.
GAGT 1881 Year Built 1981
- Repaired, Replaced, or Replacement REPLACEMENT ASME Code stamped:
(Yes or No)
YES '
FORM NIS-2 OWNER'S M i W b d & R REPUCEMENTS As Required By 'The Provlskns Of The ASME Code Section XI Traveler#
0501 7 4
- 1.
Owner Southern Nuclear Operating Company Date Apn? 18.2005 Name
. i 40 lnverness Center Parkway. Birmingham, AL Sheet 1
of 1
Address
- 2.
Plant VogUe Electric Generating Plent Unit 1
Name Waynesboro. GA 30830 1050495601 Address Repair Organization P.O. No.. Job No.. etc.
Work Performed by Maintenance Depafiment Type Code Symbol Stamp WA Authortzatlon No.
WA Name Plant Vogfle Expiretlon Date WA Address Identification of System 1205 /Residual Heat Removal System
- 6.
(a) Applicable Construction Code ASME SEC 111 1 9 7 7 Edition, Wnter 1977
- Addenda, WA Code Case (b)Applkable Edition of Section XI Utilized for Repalrs or Replacements lo@
- 6.
Identif~ation 01 Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Replace stud end nut due to bomn reddue in gasket area.
Name of Component VALVE
- 8.
Test Conducted:
~ n e u m t k Nomlnal Operating ~ r e s s u r e a N I A ~. Other Pressure WA PSI Test Temp.
WA T
- 9.
Remarks See #em 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conform to the rules of the ASME Code.Section XI.
repair or repLacmnt Type Code Symbol Stamp WA WA Expiration Date WA Team Leader Date Owner I
Name of Manufacturer FISHER CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued by the national Board of Wler and Pressure Vessel Inspectors and the State or Province of Geonrria and employed by H
a t
i f
o m
of &&&&
C o n n e M have inspected the components described in this Owner's Report during the period -Match
- 14. 2005 to.q-36$. and date that to the bed of my knowbdge and belief. the Owner has perford exadnatlons and taKen carre@ive measures described in this Owners Report In accordance with the requirements of the ASME Code, Section' XI.
By signing this certificate. neither the Inspector nor his employer makes any warranty. expressed or implied. concerning the examinations rs Report.
Furthermore, neither the Inspector nor hfs employer fihall property damage or a loss of any kind arlslng from or connected with this Commissions c-3 NationalB6ard. State, Province and Endorsements Date 5-3-aF National Board No.
WA Manufacturer Serial No.
WA Other ldentlfication 1FV-0619 Year Built 1980
- Repaired, R e p k d,
or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES :
I
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler #
0501 8 Owner Southern Nuclear Operating Company Date May 16,2005 Name 40 lnvemess Center Parkway, Birmingham. AL Sheet 1
of 1
Address Plant VogUe Electric Generating Rant Unit 1
Name Waynesbom, GA 30830 10515086 Address Repair Organization P.O. No., Job No., etc.
Work Performed by Melntenance Department Type Code Symbol Stamp WA Name Authorltstlon No.
WA rae Explratlon Date WA Pknt V q '
Address Identife&~on of System 1301 / Main Steam System (a) Applicable Construction Code. ASME SEC 111 1 9 7 7 Edition, Winter 1077
- Addenda, W A Code Case (b)Appliable Edition of Section XI Utilized for Repdrs or Replocamants I@@
Identifcation Of components Repaired or Replaced and Replacement Components
- 7.
Description of Work Installed repl~cement valve. TNs replacement valve is a mtating spare. orginadry instahd during constmfhn In location 1-PSV-3031.
Name of Component SAFETY VALVE
- 8.
Test Conducted:
~ n e u m a t k a Nominal Operating pressure@
N I A D Other a Pressure N/A PSI Test Temp.
N/A T
S.
Remarks Seelfem 7 Appilcable Manufacturer's Data Reports to be attached Name of Manufacturer CROSBY CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Scctlon XI.
repair or replacement W A Type Code Symbol Stamp
/ N/A Expiration Date N/A Team Leader Owndor Owner's Designee, Title h t e c/t</idF I
CERTIFICATE OF INSERVICE INSPECTION I
Manufacturer Serial No.
M A I, the undersigned, holding a valid c m i s s i o n issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geon?ie and employed by H
a m
r d
d of UaCo.nl, Connecticut have inspected the components described In this Owner's Report during the perlod Match 15. 2005 to 17-6<
, and State that to the bed of my knowledge and belief, Me Owmr has performed examinations and taken corrective measures described in this Owners Report in accordance with Me requirements d the ASME Code,Section XI.
By slgnlng this certlfiite. neither thc Inspector nor his ampioyer makes any warranty, expressed or.mplied, concerning the examinations and corrective measures described in this Owners Report.
Furthemre, neither the inspector nor his empbyer shall property damagc or a loss of any kind arising from or connected wlth this Commissions 3
Natlonal Board. State, Province and Endorsements N a t i i i Board No.
N/A Date
,377-176 I
Other Identification 1-PSV-3021 Year Bulk 1979 Repaired.
Replaced.
or Replacement REPLACEMENT ASME Code Stamped (Yes or No)
YES
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler W 05022
' q
- 1.
Owner Southern Nuclear Opemting Company Date 04M2H)5 I
Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
ot 1
Address
- 2.
Plant Vogte Electn'c Generating Plant Unit 1
Name Waynesboro, GA 30830 WOU 10403740 Address Repair Organhation P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stamp WA Authorbetion No.
nv!'
Name Plant Vogtle Expiration Dab WA Address
- 4.
Identification of System 1201 /Reactor Coolant System
- 5.
(a) Applicable Construction Code ASME SEC 111 1Qn
- Edition, Winter 1977 Addenda, N-2441 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19M
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Descriptlon of Work Snubber AD-501,.Sehl#364 was replaced with an AD-501 serlal#552 to support su~~illance testing.
Name of Component PIPE SUPPORT
- 8.
Test Conducted:
Hydrostatic PneumatlcO Nominal Operating ~ressureO N l A O Other Pressure WA PSI Test Temp.
WA
.F
- 9.
Remarks Seeltem 7 Applicable Manufacturer's Date Reports to be attached I
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of @e ASHE Code, Sectlon XI.
repair or replacement Type Code Symbol Stamp WA Name of Manufacturer PULLMAN POWER RODUCTS CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holdlng a valid commis8ion Issued by the national Board of Boller and Pressure Veawl Inspecton, and the State or Province of and employed by Hartford Steam Boiler I~SmCtiOn and Insurance Co. of Conneciicui of
- %ep-,
have Inspected the components described In thls Owner's Report during the p l o d
~
7
/
w and sLek that to the best of my knowledge and belled, the Owner has performed examlndons and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Coda, Section, XI.
I By slgning thls certlflcate, nelther the Inspector nor his employer makes any warranty, expressed or implied, concerning 'the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employsr shall be llable In any manwr tor any personal Injury or property damage or a loss of any klnd arislng from or connected with *la I Manufacturer Serial No.
NIA Other Identification V1-1201-03O.HW9 omm miss tons G&a-3 National Board, Sbte, Provlnce and Endorwmenta
- Repaired, Replaced, or Replacement REPLACEMENT Netional Bollrd No.
UIA Year Built 1987 ASME Code Stamped (Yes or No)
YES :
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Requlred By The Provisions Of The ASME Code Section XI Traveler (l 05024
- b
- 1.
Owner Southem Nuclear Operating Company Date 04/2W05 7-Name 3
40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of Addreaa I
- 2.
Plant Vogtle Electric Generating Plant UnM 1
Name Waynesbom, GA 30830 WO# 10515569 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Coda Symbol Stamp N/A Name Authorhtlon No.
WA Plant Vogtle Expiratlon Data N A Addrbsa
- 4.
Identification ot System 1208 / Chemlcal and Volume Control System
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 7 4 Edition, WA
- Addenda, 1637 Codecaw (b)Appllcable Edition of Section XI Utilized for Repairs or Replacementa 19&
I
- 6.
Identification Of Components Repaired or Repleced and Replacement Components
- 7.
Description d Work Valve plug /stem assembly was replaced. A copy of Fom N-2 for the replacement plug send numberAG2446-1 is attached.
Name of Component VALVE
- 8.
Test Conducted:
Hydroatatic
~neumatica Nominal Operating ~ r e a e u r e u N I A B Other q Preaaure WA PSI Teat Temp.
WA OF
- 9.
Remarks See Item 7 Applicable Manufacturer's Data Reporta to be attached CERTIFICATE OF COMPLIANCE I
We certify that the statements made in the report am correct and this replacement conforms to the rules d the ASME Code.Section XI.
repalr or replacement WA Type Cock Symbol Stamp EUA Expiration Date EUA Team Leader Date Name of Manufacturer FISHER CONTROLS CO.
I CERTIFICATE OF INSERVICE INSPECNON 1
National Board No.
3240 Manutacturer Serial No.
649954 1 I, the undersigned, holding a valid cornmisalon iaeued by the national Board of Boiler and Preaaure Vessel Inspectors and the or Province ot Geomk and employed by _HertfoJd-d-n$urance Co. of Connecticut of have Inspected the components described in this Owner's Report during the period to &./-&C,
and state that to.the best of my knowledge and bellof, the Owner ha8 performed examinstions and ?ken corrective measures deecribed in this Ownera Report in accordance with the requirements of the ASME Code, Section; XI.
I By signing this certlflcate, neither the inspector nor his employer makes any warranty, expmwd or implied, concerning, the examinations and corrective measures described in thia Ownera Report. Furthermore, neither the inspector nor his employer :hall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected wlth,this I Other Identification 1HV8149C I
ins t.
Commissions fldad inspect a Signature National Board, State, Province and Endorsemanta I Data ;T-.J-r\\l
- I ASME Coda stern&
(Yes or Nb)
YES I t I I
Year Built 1978
- Repaired, Replaced, or Replacement REPLACEMENT
T r a ~ e b r 4 05024 FORM N-2 CERTIFICATE BOLDERS' DATA REPORT FOR IDENTICAL she&
2 04 3 NUCLEAR PARTS AND APPURTENANCES*
As Required by tbe Providons oltbe ASME Code, Section IlI I
Not to exceed One Daypa Productio~
Pg-1 of 1
- 1. M-anddIsdb FISHER COWR0L.S LN7"L MC., 205 SOUTH CENlR STREET, MARSHALL'TOWN. IA SOLS8 (nrmc id dNPT Mia&
H o k )
COMROL SOUTHERN. NUCLEAR PLAHIS, 3850 IAJWWLD DR. ! W W m OA, 30024
(-.ad*d*)
- 3. L o c ~ o f ~ l. L i m VOGRZ ELECTRIC GEN. KT., 7811 RIVER RD., WAYNESBORO, GA, 30830
(-.nd.dctou)
I
m.1 (rms'l. ~pcr. m.)
(mik mgth)
(CRN)
(yarbuill) :
- 6. F.bricoiobinaewrdrocr*ritbw Spcc(Div.2ady)
(-1
- 7. Remulo:
DESIGN: ASME BBtWC, IIl, 1914 EDITION, NO ADDEND4 CLASS I 1
a N a n ~ c k n a Ci)
~ i h dddrnae(h.)
N/A Dir ID (tt Bbr)
WA
-a*.na(n&Sr)
WA
- 10. Desi@l R6alr~
U B S pd.
ragr 6%
- 1.
HydFo.Mpteovc NIA T
(when rppliable)
FORM K-2 (bYck)
T r ~ u e i e re 05024-sheet 30C3 Mb. SaLl Nc.
A02446 101 I
Dtsign rpecircuti~ ccmficd by HENRY P. LEONARD P.E. State PA Rg. no.
23938-E Cwkn rgplimbk) h W Ccd*nrc d ArnhorhJim No.
1930 EJ+-
11-1 1-2001
[hlc 9-7 4 0 Nme FISHER colUlROW IKT'LTNC (NPT k M i Hdds)
L U l c r u d a ~ b @ ~ d i n g ~ n l i d ~ ~ i a a n a r c d b y 6 r N a i ~ t ~ d b e o i l a d P l a e ~ V ~ L u p a p n u d ( h r ~ o r ~ o l IOWA d
d d b.
WllRTFOaD S3.L & I. m 7-00 s+d (Nd'L Bd. (id mdammmm)m a yav. ad no.) I
ORIGINAL 2
-FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
/
Ae Required By The Provisions Of The ASME Code Section XI Tmveler #
05025 0 9 1 m 5 I
r
- 1.
Owner Southem Nuclear Opemling Company Date I
Name 40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Addreee 1
- 2.
Plant Vogtle Electric Genemting Plant Unit 1
I Name WO# 10401555 Waynesboro, GA 30830 I
Address Repair Organization P.O. No., Job No., etc.
MA
- 3.
Work Petiormed by Maintenance Department Type Code Symbol Stamp WA Name Authorizelion No.
I NIA Plant Vogtle Expiration Date t
Addreas
- 4.
ldentification of System 1201 /Reactor Coolant System I
- 5.
(a) Applicable Construction Code ASME SEC 111 1971 Edition, Summer 1872 Adhnda, MA code ~ a *
(b)Applicabb Edition of Section XI Utllized for Repalre or Replacementa lQ&
I
- 6.
identification Of Components Repaired or Replaced and Replacement Components National
- Repaired, I Nameof I Nameof I Manufacturer I Board I Other
- 8.
Test Conducted:
~neumatlcO Nominal Operating ~ r e s s u r e ~
NIAO Other Pressure MA PSI Teat Temp.
MA OF VESSEL
- 9. Remarks See Item 7 Applicable Manufacturer's Data Reporb to be attached 1
CERTIFICATE OF COMPLIANCE We certlfy that the statements m e
in the report are correct and this replacement conforms to the rules of !he ASME Code.Section XI.
repair or replacement I
Type Code Symbol Stamp MA i
i
- 7.
Description of Work Replaced male flange on reactor vessel, penetration #78, thennocouple instwment port column assembly.
I ENGINEERING, INC.
Certificate ol uthoriution No.
MA MA i
Team Leader Date 0
r or Owner's De ignee, Title I
I I
I 1
CERTIFICATE OF INSERVICE INSPECTION 1
I I, the undersigned, holding a valid commission issued by the natlonai Board of Boiler and Preeeure Vraeel Inepectora and the dtata or Province of Geomia and employed by Hartford Steam Boiler lnsoeclion and Insurance Co. of Connecticut : of Hadford. Connecticut have inepected the components described In this Owner's Report during the period a to 4-16-85 and state that to the beat of my knowledge and belbf, the Owner has perlormod examinetione and tdken corrective measures bstribed In thie Ownere Report in accordance with the requiremanta of the ASME Code, ~ectionl XI.
I By signing thle certificate, neither the Inepeetor nor hie employer makes any warranty, expreesed or implied, concernlngjthe examinations and corrective meaeureo dmribed In thie Owners Report. Furthermore, neither the inepector nor hie employer shall injury or property damage or e iocu, of any kind arising from or connettad with ithis Commlseions GA 303 Inspector% Signature National Board, State, Province and Endonemanta 4
As Required By The Provisions Of The ASME Code Section XI Traveler#
05027 Owner Southern Nucleer Operaling Company Date Apn'r 8,2005 Name 40 lnverness Center Parkwey, Blnnlnghern. AL Sheet 1
01 1
Address 1
Plant VogUe Electric Generating Plant Unit Name 10515616 Waynesboro. GA 30830 Address Repair Organization P.O. No., Job No., etc.
Work Perto-by Malntenence Department Type Code Symbol Stamp NIA Name Authorlzatlon No.
NIA Plant VogUe Explratlon Date NIA Address ldentlfication of System 1204 / Sahty lnjecllon (a) Applicable Construction Code ASME'SEC 111 1 9 7 7 Edition.
Mlinter 1977
- Addenda, N/A Code Cay?
(b)Applicabk Edition of Section XI Utilized for Repairs or Replacements 1989 ldentificatlon Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Snubber PSA-lL?, serial #I9923 was replaced with PSA-lL?. serlel #I9719 to support surveillance testing..
- 8.
Test Conducted:
~ n e u t n a t k a Nomlnal Operating ~ m s s u r e m NIA Other a Pressure N/A PSI Test Temp.
N/A T
- 8.
Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached Manufacturer Serial No.
IWA Name of Component PIPE SUPPORT L
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the ruks of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp N/A Explratimn Date M A Team Leader Date National Board No.
M A Name of Manufacturer PULLMAN POWER I
CERTIFICATE OF INSERVICE INSPECTION 1
Year Built 1987 Other Identification 1-1204431-HOT5 By signing this certlkate, neither the Inspector nor his employer makes any warranty. expressed or Implied, concerning the examinations and comctiw measures describsd in this. Owners Report.
Furthermore, nelther the inspector nor his employer shall be liable In any macner for any personal 'inJury or property damage or a loss of any kind arising from or connected wlth this
- I I
- Repaired, Replaced.
or Replacement REPLACEMENT I ma*--
ins Commissions G-x In or's Signature National bard, State, Province and Endorsements I
ASME Coik stamped (Yes or No)
YES t
I, the undersigned, M d i n g a valid cammisston issued by the national Board of Boiler and Pressure Vessel l n s p e d ~ ~ s and the State or Province of Geomia and employed by Hartlord S t
t of Ha@nl.
Connecticut have inspected the components described In this Owner's Report durlng the period March 23. 2085 to 4-1
, and state that to the best of my knowledge and belief, the Owner has performed examlnatiins and taken corrective measures-described in tMs Owners Report In accordance with the requirements of the ASME Code,Section XI.
- @MGA FORM NIS-2 OWNER'S REPORT FOR NTS i
As Required By The Provisions Of The ASME Code Section Xi Traveler #
05029
- 5
- 1.
Owner Southem Nuclear Operating Company Date May 11,2005 I
Name 1
40 Invemess Center Parkway, Binnhrghem. AL Sheet 1
of Address I
- 2.
Plant Vogt/e ElecMc Generating Plant Unlt 1
Name Waynesbom, GA 30830 10402418 i
Address Repair Organization P.O. No., Job No.. etc.
I Work Perfomred by Maintenance Deperiment Type Code Symbol Stamp WA Authorlzalbn No.
WA Name Plant Vogfb Expiration Date WA 1
Address identifiation of System 1201 /Reactor Coolant System
- 6.
(a) Applkabk Construction Code ASME SEC 111 1 S E
- Edition, Wnter 1977
- Addenda, AMA code cake (b)Applkable Edition of Section Xi Utilized for Repairs or Replacements 1889 I
I
- 8.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Replace Steam Generator primary manway stud et 1ocabbn.HL 14.
i i
- 8.
Test Conducted:
Hydrostatk
~neurnaticm Nominal Operating ~ressurem NIA Other Pressure MA PSI Test Temp.
AMA Y
I ASME Co$e Stamped (Yes or No)
YES I,
I Name of Component STEAM GENERATOR
- 9. Remarks Seeltem 7 I
I Applicable Manufacturer's Data Reports to be attached Name of Manufacturer WESTINGHOUSE CERTlFiCATE OF INSERVICE INSPECTION I
CERTIFICATE OF COMPLIANCE I
We certify that the statements made in. the report are correct and this mpracement conforms to the rules of t+e ASME Code, Section Xi.
repair or replacement I
Type Code Symbol Stamp MA I
Expiration Date AMA Team Leader I, the undersigned, holding a valid commission issued by the national Board of Boiier and Pressure Vessel Inspectors and the State or Province of Georuia and employed by Hartford Steam Boiler Ins~ection and lnsunnce Co. of Conneclicut of Haprd, Connecficut h y e inspected the components described in this Owner's Repotl during the period March 25. 2005 to j-/kc-ds
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken cor+ive measures described in this Owners Report-in accordance with the requirements of thc ASME Code, Section : XI.
Manufacturer Serlal No.
GAGT 1881 By signing this certificate, neither the inspector nor his empioyer makes any warranty, expressed or implied, concerning the examinat~s and corrective measures described in this Owners Repoh Furthermore. neither the Inspector nor his employer shall er for any personal injury or property damage or a loss of any kind arising from or connected with ithis Commissions rd, State, Province and Endorsemmts National Board No.
N/A Year Bulll 1981 Other identifition 1-1201-66-001
- Repaired, Replaced, or Replacement REPLACEMENT
ORIGINAL FORM NISQ OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions 01 The ASME Code Section XI A
t Traveler #
06071 I
I
- 1.
Owner Soufhem Nuclear Operating Company Dale 05/02/06 I
Name I
40 lnvemess Center Parkway, Birmingham, AL Sheet 1
of 1
Addresa 1
1
- 2.
Plant Vogtle Electric Generating Piant Unlt Name Waynesboro. GA 30830 WO# 1049001002 and PO# 7071578 1
I Addreis Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by Maintenance Department Type Code Symbol Stomp N/A Name Authorbation NO.
WA i
Plant Vogtle Expiration Dab WA Address
- 4.
Identification of System 1201 /Reactor Coolant System 1
I
- 5.
(a) Applicable Construction Code ASME SEC 111 1 9 2 Edltion, Summer 1972 Addenda, WA Cod. CS+
(b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 19&
I
- 6.
Identification Of Components Repaired or Replaced and Repl8cement Componenb 1
- 7.
Description of Work The male flange assembly on the instrument port column was replaced by a new design corn exil themwcouple I node assembly (CETNA). The CETNA assembly was installed on vessel penetration 76 in accordance with DCP 1049001 001.
1
- 8.
Test Conducted:
~neumaticn Nominal Operating ~ressureB NIAO Other Pressure WA PSI Te8tTmp.
WA "F
Name of Component REACTOR
.VESSEL
- 9.
Remerka Seeltem 7 1
Applicable Manufecturer's Data Reports to be attached I
Named Manufacturer COMBUSTION ENGINEERING, INC.
CERTIFICATE OF COMPLIANCE We certlfy that the statements made in the report are correct and thls replacement I
conforms to the rules of the ASME Code,Section XI.
repair or replacement Type Code Symbol Stamp WA I
I Certiflcate of Authorization No.
WA Expiration Date WA 1
Manufacturer Serial No.
8971 I
Signsd Team Leader Date D 9 10 v /06 I I
/
/
Year Built 1976 I
I CERTIFICATE OF INSERVICE INSPECTION 11 National Board No.
2 1668 1
I, the undersigned, holding a valld commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the Stiate or Province of Geoma and employed by Hartford Steam Boiler Insoecifon and Insum1148 Co. of Connecticut 1 of
&Ifford, Connecticut have inspected the components described in this Owner's Report during the period W/18/06 A
to S/U/~O= and state that to the bast of my knowledge and bslld, the Owner has performed examinallone and te*n c o d v e messures described in thla Owners Repfl in accordance wlth the requirements of the ASME Code, Section Xi.
I Repalred.
- Replad, or Replacement REPLACEMENT Other identlflcatlon 1-1201-V6-001 I
By signlng this certiflcate, neither the Inspactor nor hle employer mahs any warranty, expreesed or implied, concerning examinations and corrective measures describsd in thls Owners RepoR Furthermore, neither the Inspector nor hls employer sh,ell bn llable in any manner lor any personal injury or properly damage or a loss of any kind arising from or connactbd with this I ASME Code stamped(
(Yes or No)
YES i 1