05000354/LER-2022-002, Inoperable Isolation Actuation Instrumentation Caused by Failure to Remove Electrical Jumper
| ML23018A201 | |
| Person / Time | |
|---|---|
| Site: | Hope Creek |
| Issue date: | 01/18/2023 |
| From: | Agster T Public Service Enterprise Group |
| To: | Office of Nuclear Reactor Regulation, Document Control Desk |
| References | |
| LR-N23-0007 LER 22-002-00 | |
| Download: ML23018A201 (1) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3542022002R00 - NRC Website | |
text
PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 LR-N23-0007 January 18, 2023 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-001 Hope Creek Generating Station Renewed Facility Operating License No. NPF-57 Docket No. 50-354 10 CFR 50.73
Subject:
Licensee Event Report 2022-002-00, Inoperable Isolation Actuation Instrumentation Caused by Failure to Remove Electrical Jumper In accordance with 10 CFR 50.73(a)(2)(i)(B), PSEG Nuclear LLC submits Licensee Event Report (LER) 2022-002-00.
There are no regulatory commitments contained in this letter.
Should you have any questions regarding this submittal, please contact Mr. Harry Balian at (856) 339 - 2173.
Sincerely, Thomas R. Agster Plant Manager, Hope Creek Generating Station Attachment: Licensee Event Report 2022-002-00
Page 2 LR-N23-0007 cc:
USNRC Regional Administrator Region 1 USNRC NRR Project Manager - Hope Creek USNRC Senior Resident Inspector - Hope Creek NJ Department of Environmental Protection, Bureau of Nuclear Engineering President & Chief Nuclear Officer, PSEG Nuclear Senior Vice President, PSEG Nuclear Operations Site Vice President, Hope Creek Plant Manager, Hope Creek Vice President, PSEG Nuclear Engineering Executive Director Regulatory Affairs & Nuclear Oversight Director Site Regulatory Compliance, Regulatory Affairs Manager, Nuclear Oversight Corporate Commitment Coordinator Records Management
Abstract
Hope Creek Generating Station
354 4
Inoperable Isolation Actuation Instrumentation Caused by Failure to Remove Electrical Jumper 10 28 2022 2022 002 00 01 18 2023 5 - Refueling 000
Harry Balian, Compliance Specialist (856) 339 - 2173 A
BO IEL N/A Y
On November 30, 2022, Hope Creek Generating Station (HCGS) discovered an electrical jumper that was installed on October 5, 2022 and should have been removed on October 10, 2022. The cause is human performance error. The jumper bypassed isolation actuation instrumentation associated with residual heat removal (RHR) system shutdown cooling (SDC) mode isolation. Specifically, it rendered one channel of a two-channel interlock that protects the RHR system from over-pressurization inoperable. The interlock prevents opening SDC valves when reactor pressure is above 82.0 psig. HCGS did not take required action required by technical specifications (TS) for this condition before entering applicable operational conditions on October 28, 2022. Consequently, HCGS was in a condition prohibited by TS from October 28 to November 30, 2022. HCGS removed the jumper to restore operability of the interlock shortly after discovery and completed individual performance management.
1¥,\
,..~.,,.,
~o{>
I Page of
- 3. LER NUMBER YEAR SEQUENTIAL NUMBER REV NO.
052 050
SAFETY CONSEQUENCES AND IMPLICATIONS
There was no safety consequence or implication because the redundant isolation actuation instrumentation channel was operable throughout this event to provide over pressure protection for the RHR SDC piping, and the affected valves remained closed for the entirety of the event.
PREVIOUS EVENTS No similar licensee event report (LER) or corrective action occurrences were found following a review of station LERs and the corrective action program for the past three years.
CORRECTIVE ACTIONS
- 1. The jumper was removed;
- 2. Performance management for the individual(s) involved was completed.
COMMITMENTS
There are no regulatory commitments in this LER.
4 4
Hope Creek Generating Station 354 2022 002 00
~¥'
i
<--+_,
~o" I
I~
I I I I D