LER-2022-001, B EDG Inoperable Resulting in a Condition Prohibited by Technical Specifications
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3542022001R00 - NRC Website

text

PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, New Jersey 08038-0236

@ PSEG LR-N22-0020 March 18, 2022 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington DC 20555-001

Subject:

Hope Creek Generating Station Renewed Facility Operating License No. NPF-57 Docket No. 50-354 Licensee Event Report 2022-001-00 B EOG Inoperable Resulting in a Condition Prohibited by Technical Specifications NuclearLLC 10CFR50.73 In accordance with 10 CFR 50. 73(a)(2)(i)(B), PSEG Nuclear is submitting Licensee Event Report (LER) number 2022-001-00, "B EOG Inoperable Resulting in a Condition Prohibited by Technical Specifications."

There are no regulatory commitments contained in this letter.

If you have any questions or require additional information, please contact Mr. Justin Wearne.

Steven R. Poorman Plant Manager Hope Creek Generating Station Attachment: Licensee Event Report 2022-001-00 cc:

Regional Administrator - USN RC Region I USNRC Project Manager - Hope Creek USNRC Senior Resident Inspector - Hope Creek (X-24)

Manager IV, NJ Bureau of Nuclear Engineering Corporate Commitment Coordinator

Abstract

On January 19, 2022 during the performance of the B Emergency Diesel Generator (EDG) 24-hour surveillance test, the B EDG did not achieve the required load of 4652 kW-4873 kW (105 - 110 percent of rated load). The maximum load achieved was 4650 kW (104.9 percent). The B EDG was determined to be inoperable due to failing to meet the acceptance criteria.

Investigation identified that the B EDG fuel supply linkage mechanism (fuel rack) required adjustment. Following adjustment, the B EDG was re-tested satisfactorily. The B EDG was returned to operable status on January 23, 2022 at 0700.

Technical Specification (TS) 3.8.1.1 allows the B EDG to remain inoperable for up to 14 days. Based on a review of the B EDG maintenance history, it was determined that the condition existed prior to discovery and for a period greater than 14 days.

Therefore, an Operation or Condition Prohibited by Technical Specifications occurred, and this report is being made per the requirements of 10CFR50.73(a)(2)(i)(B). Page of 05000-

3. LER NUMBER YEAR SEQUENTIAL NUMBER REV NO.

CORRECTIVE ACTIONS

On January 22, 2022, the B EDG fuel rack mechanical linkage was adjusted to allow the required loading of 4652 kW -

4873 kW to be achieved.

The remaining three EDGs (A, C and D) were verified to have successfully completed TS surveillance requirement 4.8.1.1.2.k (105 - 110 percent loaded run) subsequent to refueling outage 23. A review of maintenance activities found no history of fuel rack adjustments since the last successful completion of surveillance requirement 4.8.1.1.2.k.

A cause evaluation is in progress to identify additional actions.

COMMITMENTS

None 3