ML21130A230
Text
V>
z 0 !
0 z
(
I (soA GANG OPERATED HORN GAP SWITCH HIGH VOLTAGE PRIMARY FUSE CUTOUT DISCONNECT SWITCH -
SIZE AS INDICATED (3 POLE UNLESS OTHERWISE NOTED)
- If-/-
GROUNDING SWITCH 3
L.A.
.1 I
_L
'T 0------0 100A N(\\ OE A bl J.,2 T
')
I
..L 1 [SJ 1~
2 rsl2s
µ::i I' I 2 L_:-.!!J 1 liiiJ LIGHTNING ARRESTER (NUMBER INDICATES QUANTITY)
CAPACITOR DISCONNECT LINK TRANSFER SWITCH A -
AUTOMATIC SIZE AS INDICATED N -
NORMAL M -
MANUAL E -
EMERGENCY L -
LOAD GROUNDING TRANSFORMER SIZE & RATING AS INDICATED GROUND DETECTION CURRENT TRANSFORMER -
NUMBER INDICATES QUANTITY -
RATIO AS NOTED CURRENT TRANSFORMER -
NUMBER INDICATES QUANTITY RATIO AS NOTED BUSHING TYPE CURRENT TRANSFORMER NUMBER INDICATES QUANTITY RATIO AS NOTED BUSHING TYPE POTENTIAL DEVICE NUMBER INDICATES QUANTITY RATING AS NOTED POTENTIAL TRANSFORMER NUMBER INDICATES QUANTITY RATING AS NOTED POWER TRANSFORMER SIZE & RATING AS NOTED (NUMBER OF WINDINGS AS SHOWN)
MEDIUM OR HIGH VOLTAGE DRAWOUT TYPE ELECTRICALLY OPERATED CIRCUIT BREAKER, INTERRUPTING CAPACITY, SIZE & VOLTAGE AS NOTED AIR CIRCUIT BREAKER DRAWOUT TYPE ELECTRICALLY OPERATED, MAGNETIC OVERCURRENT TRIP -
CURRENT RATING
& INTERRUPTING CAPACITY AS NOTED AIC = AMP INTERRUPTING CAPACITY AF = AMP FRAME AT = AMP TRIP U = UNDERVOLTAGE ATTACHMENTS M = MANUALLY OPERATED AIR CIRCUIT BREAKER 3 POLE UNLESS OTHERWISE NOTED GROUND CONNECTION DRAWOUT DISCONNECT DEVICE MAGNETIC STARTER WITH THERMAL OVERLOADS, SINGLE SPEED, NON-REVERSING FULL VOLTAGE -
NUMBER INDICATES NEMA SIZE (SYMBOL WITH "RV" INDICATES REDUCED VOLTAGE)
MAGNETIC STARTER WITH THERMAL OVERLOADS, SINGLE SPEED, REVERSING FULL VOLTAGE -
NUMBER INDICATES NEMA SIZE (SYMBOL WITH "RV" INDICATES REDUCED VOLTAGE)
MAGNETIC STARTER WITH THERMAL OVERLOADS, 2S=MULTI SPEED NON-REVERSING. FULL VOLTAGE NUMBER INDICATES NEMA SIZE THIS SYMBOL ABOVE STARTER OR CONTACTOR INDICATES COMBINATION STARTER OR CONTACTOR F -
INDICATES FUSED DISC SWITCH & FUSE B -
INDICATES CIRCUIT BREAKER S -
INDICATES UNFUSED DISC SWITCH MAGNETIC CONTACTOR NUMBER INDICATES NEMA SIZE NANUAL MOTOR STARTER, 1 POLE WITH THERMAL OVERLOAD ONE LINE ELEMENTARY DIAGRAMS G
10 MOT HP 71/2 GEN KW
---E---
NO NC TS
-H-0 GENERATOR SIZE & RATING AS NOTED MOTOR -
NUMBER INDICATES HORSEPOWER MOTOR -
GENERATOR SET SYNCHRONOUS MOTOR -
NUMBER INDICATES HORSEPOWER EXCITER BATTERY HEATER FUSE SHUNT RESISTOR RESISTANCE TEMPERATURE DETECTOR INTERLOCKS:
E -
ELECTRICAL K -
KEY M -
MECHANICAL NORMALLY OPEN NORMALLY CLOSED CONTROL SWITCH WITH INDICATING LIGHTS START -
STOP MAINTAINED CONTACT PUSH BUTTON START -
STOP MAINTAINED CONTACT PUSH BUTTON WITH INDICATING LIGHTS START -
STOP MOMENTARY CONTACT PUSH BUTTON START -
STOP MOMENTARY CONTACT PUSH BUTTON WITH INDICATING LIGHTS T = TEST INDICATING LIGHTS SELECTOR SWITCH WITH INDICATING LIGHTS STOP LOCK-OUT PUSH BUTTON PERMISSIVE SWITCH WITH INDICATING LIGHTS CONTROL DEVICE: TYPE AS NOTED TS -
TEMP SW CONTACT T -
THERMOSTAT LVS -
PNEU-ELEC PS -
ELEC-PHEU FS -
FLOAT SW CONTACT H -
HUMIDISTAT LS -
LIMIT SW CONTACT FR -
FIRE RELAY CONTACT METERS &
INSTRUMENTS SWITCHES PREFIX "R" DENOTES RECORDING TYPE, NUMBER NEXT TO SYMBOL DENOTES QUANTITY IF MORE THAN ONE IS REQD A AMMETER AS-AMMETER SW VS-VOLTMETER SW SYN SW-SYNCHRO SW V VOLTMETER W WATTMETER VAR VARMETER WH WATTHOUR METER F FREQUENCY METER WHD DEMAND WATTHOUR METER SY SYNCHROSCOPE PF POWER FACTOR METER THC THERMAL CONVERTER TR TEMP RECORDER TI TEMP INDICATOR TACH TACHOMETER TM TRANSMITTER ITRDI TRANSDUCER HS-HAND SW SS-SEL SW CS-CONTROL SW TS-TEST SWITCH
~
VOLTAGE ADJUSTING RHEOSTAT TRANSFORMER CONNECTIONS 6
3¢, 3W DELTA L
3¢, OPEN DELTA
/
SINGLE PHASE 3¢, WYE OR STAR RELAY SW RELAYS DEVICES NUMBER NEXT TO SYMBOL DENOTES QUANTITY IF MORE THAN ONE IS REQUIRED 2
TIME DELAY CLOSING RELAY 21 DISTANCE 25 SYNCHRONIZING CHECK 27 UNDERVOLTAGE 30 ANNUN ALARM 32 DIRECTIONAL POWER RELAY 40 LOSS OF FIELD 46 NEGATIVE SEQUENCE 48 INCOMPLETE SEQUENCE 49 THERMAL OVERLOAD RELAY 50 INSTANT OVERCURRENT 50-1 INSTANT ELEMENT SHORT CIRC TRIP 50-2 INSTANT ELEMENT LOCKED ROTOR TRIP 50/51 OVERCURR-INSTANT &
TIME DELAY 51 AC OVERCURRENT-TIME DELAY CR CONTROL RELAY AR AUXILIARY RELAY LR LATCHING RELAY 55 POWER FACTOR 59 OVERVOLTAGE 60 VOLTAGE BALANCE 62 TIME DELAY OPENING RELAY 63 PRESSURE 64 GROUND PROTECTIVE 67 AC DIRECTIONAL OVERCURRENT 74 ALARM AUX RELAY 76 DC OVEREXCITATION 81 FREQUENCY 86 LOCKOUT 87 DIFFERENTIAL
{LATCH OR UNLATCH COIL AS SHOWN)
TDR TIME DELAY RELAY COIL: TDPU -
TIME DELAY PICK UP TDDO -
TIME DELAY DROP OUT CONTACT TDCAE -
TIME DELAY CLOSE AFTER ENERGIZATION TDOAE -
TIME DELAY OPEN AFTER ENERGIZATION TDCAD -
TIME DELAY CLOSE AFTER DE-ENERGIZATION TDOAD -
TIME DELAY OPEN AFTER DE-ENERGIZATION DEVICES 20 ELEC OPER VALVE 52 AC CIRCUIT BREAKER 33 POSITION OR LIMIT SW 71 LEVEL SWITCH 41 FIELD CIRCUIT BREAKER 72 DC CIRCUIT BREAKER 42 MOTOR STARTER 80 FLOW SWITCH RELAY OR DEVICE "SUFFIX LETTERS" F FIELD G GROUND N NEUTRAL TELM TELEMETRERING V VOLTAGE X AUXILIARY GN GENERATOR DIFFERENTIAL GD GENERATOR DISTANCE GF GENERATOR FIELD GG GENERATOR GROUND GNS GENERATOR NEG SEQUENCE GT GENERATOR TRANSFORMER GOE GENERATOR OVER EXCITATION L 345KV LINE TGP MAIN TRANSFORMER GAS TN MAIN TRANSFORMER NEUTRAL LGT LINE GEN TRANSF OVERALL NGP NORM STA SERV TRANSF GAS NT NORM STA SERV TRANSF SGP START UP STA SERV TRANSF GAS ST START UP STA SERV TRANSF STL 161 KV LINE EGP EMERG TRANSF GAS T TURBINE
~ SOLENOID (8}
WIRE TERMINAL POINT
!AS 4160V SWGR START-UP BKR 1A IAN 4160V SWGR NORMAL BKR 1A
!BS 4160V SWGR START-UP BKR 18 IBN 4160V SWGR NORMAL BKR 18 res 4160V SWGR START-UP BKR 1C ICN 4160V SWGR NORMAL BKR 1C IDS 4160V SWGR START-UP BKR 1 D IDN 4160V SWGR NORMAL BKR 1 D IFS 4160V SWGR EMERG BKR 1 F
!GS 4160V SWGR EMERG BKR 1G DG1 DIESEL GEN NO 1 DG2 DIESEL GEN NO 2
!GE DIESEL GEN NO 2 BKR 1 GE NB 4160V SWGR NORMAL SUPPLY SB 4160V SWGR START-UP SUPPLY
f WIRE CONNECTION POINT I
--0 0--
INDICATING R-RED G-GREEN W-WHITE LIGHT WITH DROPPING B-BLUE C-CLEAR A-AMBER INDICATING LIGHT RESISTOR TEST JACK CONNECTION POINT PUSH BUTTON-MOMENTARY CONTACT NORMALLY CLOSED PUSH BUTTON-MOMENTARY CONTACT NORMALLY OPEN PUSH BUTTON-MAINTAINED CONTACT
~ ~-L MANUAL MOTOR STARTER -
__ ~
"-.;-WITH THERMAL OVERLOAD SINGLE POLE OL
"l_r-OVERLOADS (THREE LINE DIAGRAM)
~
BLOCKING DIODE OL
-,ft Ar Ar OVERLOADS
-I I-CONTACT -
NORMALLY OPEN (NO)
At CONTACT -
NORMALLY CLOSED (NC)
BA
I l--
52A
11--
528 At
-22....
TCS
-I I-
~
IN At 52H OUT
-I I-
.cs
-I~
.cs T
-I~
D
--rn-BELL ALARM CONTACT {OPEN OR CLOSED AS INDICATED)
BREAKER CONTACT (OPEN WHEN BREAKER IS OPEN)
BREAKER CONTACT (CLOSED WHEN BREAKER IS OPEN)
LOCAL BREAKER TEST CONTROL SWITCH {CONTACTS AS INDICATED IN CONTROL SWITCH DEVELOPMENT)
BREAKER POSITION SWITCH (CLOSED WHEN BREAKER IS IN OPERATING POSITION)
BREAKER POSITION SWITCH (OPEN WHEN BREAKER IS IN OPERATING POSITION)
CONTROL SWITCH, CONTACTS AS INDICATED IN CONTROL SWITCH DEVELOPMENT CONTROL SWITCH TEST, LOCATED AT 4160V SWGR C -
INDICATES CLOSED POSITION T -
INDICATES TRIP POSITION MULTIPLE CONDUCTOR -
SHIELDED CABLE (TWO CONDUCTOR SHOWN)
MULTIPLE CONDUCTOR -
SHIELDED CABLE -
SHIELD GROUNDED {TWO CONDUCTOR SHOWN)
SIGNAL CONNECTOR (MULTI CONDUCTOR)
TWISTED SHIELDED PAIR CONDUCTORS
- ..____ ____________________________ __,7 POWER, GROUNDING, & LIGHTING PLANS FIRE ALARM &
COMMUNCATION PLANS POLE LINE & UNDERGROUND DISTRIBUTION PLANS LIGHTING PANEL (SEE LIGHTING PANEL SCHEDULES)
PANEL -
MISCELLANEOUS AS NOTED ON PLAN DWGS W&
POWER PANEL
--e-MOTOR HORIZONTALLY MOUNTED 0
MOTOR -
VERTICALLY MOUNTED
- I CONTACTOR 1><1
[.---?1 MOTOR STARTER OR CONTROLLER I
h TRANSFER SWITCH-SIZE & TYPE AS NOTED DISCONNECT OR SAFETY SWITCH SIZE AS NOTED D
ro
~
~
OL.
(/)
SEL 0
TRANSFORMER -
DRAW TO SCALE SIZE & RATING AS NOTED MOTOR OPERATED VALVE AIR OPERATED VALVE LOCAL PUSHBUTTON STATION OR LOCAL CONTROL STATION, TYPE AS NOTED SINGLE POLE MANUAL MOTOR STARTER WITH THERMAL OVERLOAD SEL = SELECTOR SWITCH J -
JUNCTION BOX TB -
TERMINAL BOX PB -
PULL BOX RIGID CONDUIT -
RUN EXPOSED RIGID CONDUIT -
RUN CONCEALED
<O CONDUIT OR CABLE TURNING UP OR TOWARDS OBSERVER CONDUIT OR CABLE TURNING DOWN OR AWAY FROM OBSERVER DIRECT BURIAL CABLE FLEXIBLE CONDUIT CONDUIT "SEALING" FITTING HORZ VERT
[p [Q] UNIT HEATER TS
- CONTROL DEVICES: TYPE AS NOTED TS -
LEVEL SWITCH PS -
PRESSURE SWITCH FS -
FLOAT SWITCH LS -
SELECTOR SWITCH CS -
CONTROL SWITCH PMS -
RESIST TEMP DETEC T -
THERMOSTAT TE -
TEMP ELEMENT PE -
PNEU-ELECT RELAY SP -
ELECT-PNEU SWITCH T/C -
THERMOCOUPLE H -
HUMIDISTAT FT -
FLOW TRANSFMITTER PT -
PRESSURE TRANS LT -
LEVEL TRANS FI -
FLOW INDICATOR FLS -
FLOW SWITCH A -
ALTERNATOR SD -
SMOKE DETECT V -
VALVE Fl CABLE TRAY OR CABLE LADDER (SIZE & ELEVATION AS NOTED ON PLAN DWGS)
--IG-INSTRUMENT GROUND CABLE
--G-GROUND CABLE -
RUN EXPOSED
-G -
GROUND CABLE -
RUN CONCEALED OR BELOW GRADE 0
- 1"111111 40-27 F
[gJ 40-11 GROUND ROD 5/8" DIA x 20' -0" LONG COPPER WELD GROUND CONNECTION "THERMO PROCESS" WELD "CADWELD" OR APPROVED EQUAL GROUND CONNECTION -
PRESSURE TYPE SOLDERLESS CONNECTOR INDICATES AUXILIARY RELAY CABINET INDICATES LOCAL DEVICE INDICATES LOCAL DEVICE ON LOCAL PANEL INDICATES EQUIPMENT LOCATED AT BENCHBOARD LETTER OR NUMBER DESIGNATION AS SHOWN INDICATES EQUIPMENT LOCATED AT CABINET NUMBER DESIGNATION AS SHOWN INDICATES EQUIPMENT LOCATED AT VERTICAL BOARD, LETTER OR NUMBER DESIGNATION AS SHOWN INDICATES EQUIPMENT LOCATED AT COMPUTER EQUIPMENT DESK, LETTER OR NUMBER DESIGNATION AS SHOWN INDICATES ANNUNCIATION -
LETTER DENOTES BOARD OR PANEL LOCATION 3
"A" INDICATES FIXTURE TYPE "2-40" INDICATES NO. & WATTAGE OF LAMPS "3" INDICATES NO. OF FIXTURES 1 O' -0" INDICATES MOUNTING HEIGHT 10'-0" CEILING MTD C-2 0
WALL MTD I-@
INCANDESCENT OR MERCURTY LTG FIXTURE "A" INDICATES FIXTURE TYPE "c-2" INDICATES LTG PNL "c", CIRCUIT 2 (SMALL CIRCLE FOR INDIVIDUAL IDENTIFICATION)
EXIT LIGHTING FIXTURE I c > I I l J I FLUORESCENT LIGHTING FIXTURE a
l:A p
3 CKTS/
LP9,11,15 4#12 cg CR cg R
BARE LAMP FLUORESCENT STRIP STREET LIGHTING FIXTURE FLOODLIGHT FIXTURE EMERGENCY LIGHTING UNIT AC/DC EMERGENCY LIGHTING REMOTE LAMP GOOSENECK LIGHING STANCHION AND FIXTURE REMOTE LAMP MOUTNED ABOVE EMERGENCY LIGHTING UNIT SWITCH SINGLE POLE 120V 20A TOGGLE a -
INDICATES ASSOCIATED CONTROLLED FIXTURES 3 -
INDICATES 3 WAY SWITCH P -
INDICATES SWITCH WITH PILOT LIGHT HOME RUN TO PANELBOARD -
ALL UNMARKED CONDUITS ARE 3/ 4" IN SIZE AND CONTAIN 2#12 UNLESS OTHERWISE NOTED SWITCH & SINGLE CONVENIENCE RECEPTACLE COMBINATION SWITCH & DUPLEX CONVENIENCE RECEPTACLE COMBINATION 20A, 125VAC, GE 5951-1 OR EQUAL SINGLE RECEPTACLE, CONVENIENCE, 2P 3W 15A 125V HUBBELL TYPE 5261 OR APPVD EQUAL DUPLEX RECEPTACLE, CONVENIENCE, 2P 3W 15A 125V HUBBELL TYPE 5262 OR APPVD EQUAL DUPLEX RECEPTACLE, CONVENIENCE, 2P 3W 15A 125V -
"CR" INDICATES CORROSION RESISTANCE. HUBBELL TYPE 52CM62 WITH 52CM08 CAP OR APPVD EQUAL DUPLEX RECEPTACLE, CONVENIENCE, 2P 3W 15A 125V HUBBELL TYPE 52621 OR APPVD EQUAL -
"R" INDICATES REGULATED VOLTAGE SINGLE RECEPTACLE 2P 3W GROUNDING 20A 250V NEMA 6-20R, HUBBELL TYPE 5461 WITH SUPER STAINLESS PLATE HUBBELL 93091 OR APPVD EQUAL POWER RECEPTACLE 3W 4P 60A 600VAC CROUSE-HINDS TYPE "AREA" CAT NO. AREA6425 OR APPVD EQUAL POWER RECEPTACLE 3W 4P 30A 600VAC CROUSE-HINDS TYPE "ARE" CAT NO. ARE3423 OR APPVD EQUAL PLUG-IN STRIP -
TYPE AS NOTED ON DWGS CEILING MTD WALL MTD
@)
@)
0 c@)
e@)
r) c@
c{)
FAN OUTLET CLOCK OUTLET REELITE DROP CORD PORCELAIN LAMP HOLDER (PC INDICATES PULL CHAIN)
OUTLET BOX r@
STROBE LIGHT TELEPHONE SWITCHBOARD PUBLIC TELEPHONE CO. TELEPHONE WITH ACCESS TO PUBLIC EXCHANGE, DESK TYPE PUBLIC TELEPHONE IN FULL BOOTH kl D INDUSTRIAL TYPE TELEPHONE D = DESK SET W = WALL SET WP = WEATHERPROOF WALL SET SOUND POWERED TELEPHONE SET
[!I S.P.
[!I T JACK FOR SOUND POWERED TELEPHONE OUTLET FOR PLUG-IN PORTABLE INDUSTRIAL TELEPHONE
[I]
<l LOUDSPEAKER, HORN TYPE, SINGLE UNIT LOUDSPEAKER, SPECIAL TYPE LOUDSPEAKER, OFFICE TYPE WITH VOLUME CONTROL TWO-WAY INTERCOM SET MICROPHONE (RADWASTE AREA)
CLOSED CIRCUIT TELEVISION RECEIVER
~
C CLOSED CIRCUIT TELEVISION TRANSMITTER & CAMERA TRANSF SWGR MCC PDP LDP pp LP GND CND PT CT POS( +)
NEG(-)
RP EP WP VT DT WT EC DP ABBREVIATIONS TRANSFORMER SWITCHGEAR MOTOR CONTROL CENTER POWER DISTRIBUTION PANEL LIGHT DISTRIBUTION PANEL POWER PANEL LIGHTING PANEL GROUND CONDUIT POTENTIAL TRANSFORMER CURRENT TRANSFORMER POSITIVE NEGATIVE RELAY PANEL EXPLOSION PROOF WEATHER PROOF VAPOR TIGHT DUST TIGHT WATER TIGHT {SUBMERSIBLE)
EMPTY CONDUIT DRIP PROOF SIGNIFICANT NUIIIBER 35-5 EXISTING POLE 0
LENGTH & CLASS AS NOTED 35-5 NEW POLE e
LENGTH & CLASS AS NOTED 35-5-6M POLE WITH DOWN GUY & ANCHOR-LENGTH &
1------9 CLASS & STRENGTH OF GUY IN POUNDS AS NOTED 35-5-6M
--a
[j]
CT]
X
...t_L.A.
_#8_
_3#2_
<J--
POLE WITH STREET LIGHTING FIXTURE LENGTH & CLASS AS NOTED SINGLE PHASE TRANSFORMER SIZE & RATING AS NOTED THREE PHASE TRANSFORMER SIZE & RATING AS NOTED STREET LIGHTING REGULATOR RATING AS NOTED SECTIONALIZING SWITCH-MOUNTED ON CROSSARM -
NORMALLY OPEN SECTIONALIZING SWITCH-MOUNTED ON CROSSARM -
NORMALLY CLOSED POLE TOP SWITCH LIGHTING ARRESTER IN EACH PHASE WIRE PRIMARY LINE -
NO. & SIZE OF WIRE AS NOTED SERIES STREET LTG CKT 1 /C OF SIZE NOTED 3¢ SECONDARY LINE -
NO. & SIZE OF WIRE AS NOTED 1 ¢ SECONDARY LINE -
NO. & SIZE OF WIRE AS NOTED CONDUCTOR DEAD END MH¥MANHOLE
.1::ll::1/i r HANDHOLE TOP OF DUCTBANK (ELEV AS NOTED)
INDICATES NUMBER & ARRGT OF DUCTS IN DUCTBANK INDICATES it OF DUCTBANK
{LOCATE WITH DIMENSIONS OR CO-ORDINATE NUMBERS) c_ _____ ARROW INDICATES DIRECTION OF DUCTBANK TOWARDS LOW POINT NOTES
- 1. FOR ADDITIONAL SYMBOLS RELATED TO BENCHBOARD
& CABINET DESIGNATIONS SEE DWG 3032.
DRAWN I DATE RGA 8/18/05 AS BUILT 454003947 STATUS: Release STATUS DATE: 01/15/2015 DS APPROVED: SCSCHUL VER: AE REV: 13 SIZE: F FOR PREVIOUS REVISIONS, SEE SUPERSEDED CARDS GROUP 4
CHEa<ED I DATE 0
VERSIONS/REVISIONS BY N.P.P.D.
NO.
DESCRIPTION AB 11 DR-2013-0591 AD 12 DR 2014 0413
/lE. 13 DR-2015-0002 DFTI DATE ENG DJB~9/JD 1 EMNELSO DJB 23 1 BDSEIDL DLR 1115 15 SCSCHUI COOPER NUCLEAR STATION ELECTRICAL SYMBOL LIST APPROVED 7 DATE SEE ~TED BURNS & ROE i;j 0
0
~u
~--~---'---------~
C FILMED 3070
~