05000220/LER-2020-001-01, Control Room Air Treatment System Inoperable

From kanterella
(Redirected from ML20269A248)
Jump to navigation Jump to search
Control Room Air Treatment System Inoperable
ML20269A248
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 09/15/2020
From: Tierney T
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NMP1L3353 LER 2020-001-01
Download: ML20269A248 (7)


LER-2020-001, Control Room Air Treatment System Inoperable
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(v), Loss of Safety Function
2202020001R01 - NRC Website

text

Exelon Generation NMP1L3353 September 15, 2020 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Nine Mile Point Nuclear Station, Unit 1 Renewed Facility Operating License No. DPR-63 Docket No. 50-220 10 CFR 50.73

Subject:

NMP1 Licensee Event Report 2020-001, Revision 1, Control Room Air Treatment System Inoperable In accordance with the reporting requirements contained in 1 O CFR 50.73(a)(2)(v)(D), please find enclosed NMP1 Licensee Event Report (LER) 2020-001, Revision 1, Control Room Air Treatment System Inoperable.

There are no regulatory commitments contained in this letter.

Should you have any questions regarding the information in this submittal, please contact Brandon Shultz, Site Regulatory Assurance Manager, at (315) 349-7012.

Respectfully,

~

cl.\\. l~,,tA)fUy Todd A. Tierney ~-----,,-3 Plant Manager, Nine Mile Point Nuclear Station Exelon Generation Company, LLC TAT/OW

Enclosure:

NMP1 Licensee Event Report 2020-001, Revision 1, Control Room Air Treatment System Inoperable cc:

NRC Regional Administrator, Region I NRG Resident Inspector NRG Project Manager

Enclosure NMP1 Licensee Event 2020-001, Revision1 Control Room Air Treatment System Inoperable Nine Mile Point Nuclear Station, Unit 1 Renewed Facility Operating License No. DPR-63

7 NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 03/31/2020 (04-2020)

Estimated burden per response to comply with this mandatory collection request: BO hours.

,_v,RR[(:1/<-.

Reported lessons learned are incorporated into the licensing process and fed back to industry.

+-:,'t.

~o

~

LICENSEE EVENT REPORT (LER)

Send comments regarding burden estimate to the Information Collections Branch (T-5 F53), U.S.

~

Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to

.,,.+,,

.Jt (See Page 2 for required number of digits/characters for each block) lnfocollects.Resource@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503. If (See NUREG-1022, R.3 for instruction and guidance for completing this form a means used to impose an information collection does not display a currently valid 0MB control htt12://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1022/r3/)

number, the NRG may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. PAGE Nine Mile Point Unit 1 05000220 1 OF 5
4. TITLE Control Room Air Treatment System Inoperable
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED YEAR I SEQUENTIAL I REV FACILITY NAME DOCKET NUMBER MONTH DAY YEAR NUMBER NO.

MONTH DAY YEAR N/A N/A FACILITY NAME DOCKET NUMBER 05 03 2020 2020 - 001

- 01 09 15 2020 N/A N/A
9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply) 0 20.2201 (b)

D 2O.22O3(a)(3)(i) 0 5O.73(a)(2)(ii)(A)

D 5O.73(a)(2)(viii)(A) 0 20.2201 (d)

D 2O.22O3(a)(3)(ii) 0 5O.73(a)(2)(ii)(B)

D 5O.73(a)(2)(viii)(B) 1 D 2O.22O3(a)(1)

D 2O.22O3(a)(4)

D 5O.73(a)(2)(iii)

D 5O.73(a)(2)(ix)(A)

D 2O.22O3(a)(2)(i) 0 5O.36(c)(1 )(i)(A)

D 5O.73(a)(2)(iv)(A)

D 5O.73(a)(2)(x)

10. POWER LEVEL D 2O.22O3(a)(2)(ii) 0 5O.36(c)(1 )(ii)(A)

D 5O.73(a)(2)(v)(A)

D 73.71 (a)(4)

D 2O.22O3(a)(2)(iii)

D 5O.36(c)(2)

D 5O.73(a)(2)(v)(B)

D 73.71 (a)(5)

D 2O.22O3(a)(2)(iv)

D 5O.46(a)(3)(ii)

D 5O.73(a)(2)(v)(C)

D 73.77(a)(1) 100 D 2O.22O3(a)(2)(v) 0 5O.73(a)(2)(i)(A)

IZJ 5O.73(a)(2)(v)(D)

D 73.77(a)(2)(i)

D 2O.22O3(a)(2)(vi) 0 5O.73(a)(2)(i)(B)

D 5O.73(a)(2)(vii)

D 73.77(a)(2)(ii) 0 5O.73(a)(2)(i)(C) 0 OTHER Specify in Abstract below or in C. INOPERABLE STRUCTURES, COMPONENTS, OR SYSTEMS THAT CONTRIBUTED TO THE EVENT:

No other systems, structures, or components contributed to this event.

D. DATES AND APPROXIMATE TIMES OF MAJOR OCCURRENCES AND OPERATOR ACTIONS:

The dates, times, and major occurrences and operator actions for this event are as follows.*

May 3, 2020 at 11 :00 - Step change heard in control room noise level above the ceiling.

Sound appears to be coming from the ventilation area.

May 3, 2020 at 11 :11 - Field operator reports higher than normal noise and vibration from the Control Room Ventilation ductwork and concurs that the noise is from the Control Room Ventilation Circulation Fan.

May 3, 2020 at 11 : 15 - Operator attempts to swap from #11 motor to #12 but noise continues.

May 3, 2020 at 11: 18 - Operator secures #12 fan motor to prevent possible further degradation and enters the Technical Specification 3.4.5.e 7-day Action Statement.

May 3, 2020 at 11 :34 - Control Room Ventilation is secured. Alternate Control Room Ventilation is placed in service.

May 3, 2020 at 17:20 - Declared control room envelope boundary inoperable and entered Technical Specification 3.4.5.f, 90-day action statement May 8, 2020 at 20:11 - Control Room Ventilation Air Treatment System is restored to operable and Technical Specifications 3.4.5.e and fare exited.

E. METHOD OF DISCOVERY

This event was discovered by Operations when abnormal noises were heard coming from the ventilation system.

F. SAFETY SYSTEM RESPONSES:

No operational conditions requiring the response of safety systems occurred as a result of this condition.

II. CAUSE OF EVENT

The cause of the failure for the Circulation Fan was the failure of the pillow block bearing. A Powerlabs failure analysis found the. cause of the premature bearing failure to be a moment load on the pillow block bearing. A moment load is a load on a rolling element bearing that is REV NO.

01 neither purely radial nor purely axial. This angular load caused premature wear of the raceway surface. There was insufficient evidence to determine if a manufacturing defect or misalignment was the cause of the moment load.

III. ANALYSIS OF THE EVENT

The failure of the Control Room Air Treatment System is reportable under 1 O CFR 50.73(a)(2)(v)(D) as any event or condition that could have prevented the fulfillment of the safety function of structures or systems that are needed to: (D) Mitigate the consequences of an accident. The Control Room Ventilation System Circulation fan was inoperable for a period of time.

With the Control Room Air Treatment System out of service, the heating and cooling function to maintain personnel comfort and control instrument protection was achieved by placing and maintaining the Smoke Purge system in service.

The Control Room Air Treatment System and envelope boundary were restored to service within the time frame allowed by the Technical Specification Action Statements.

Based on the above discussion, it is concluded that the safety significance of this event is low, and the event did not pose a threat to the health and safety of the public or plant personnel.

This event does affect the NRC Regulatory Oversight Process Indicator for safety system failures.

IV. CORRECTIVE ACTIONS

A. ACTION TAKEN TO RETURN AFFECTED SYSTEMS TO PRE-EVENT NORMAL STATUS:

The #11 fan pillow block bearing, #11 motor sheave and key were replaced. The fan was tested satisfactory in accordance with post maintenance testing requirements.

B. ACTION TAKEN OR PLANNED TO PREVENT RECURRENCE:

1. The control room ventilation maintenance procedure will be revised to clearly describe that belt tensioning and alignment must be an iterative process until tension and alignment is correct on both sides of the fan.
2. An inventory search was conducted confirming no other bearings exist on site from the same lot number.

REV NO.

01

V. ADDITIONAL INFORMATION

A. FAILED COMPONENTS:

FN-210-61 B. PREVIOUS LERs ON SIMILAR EVENTS:

None YEAR 2020 -

SEQUENTIAL NUMBER 001 C. THE ENERGY INDUSTRY IDENTIFICATION SYSTEM (EIIS) COMPONENT FUNCTION IDENTIFIER AND SYSTEM NAME OF EACH COMPONENT OR SYSTEM REFERRED TO IN THIS LER:

COMPONENT Control Room Ventilation Circulation Fan IEEE 803 FUNCTION IDENTIFIER FAN IEEE 805 SYSTEM IDENTIFICATION VI REV NO.

01 Page _5_ of _5_