ML20237A036

From kanterella
Jump to navigation Jump to search
Suppl 8 to Improved TS (Its),Combining Units ITS Pages to Facilitate Ease of Use & Significantly Reduce Vol of Paper That Must Be Processed & Controlled
ML20237A036
Person / Time
Site: Catawba  Duke Energy icon.png
Issue date: 08/05/1998
From:
DUKE POWER CO.
To:
Shared Package
ML20237A031 List:
References
NUDOCS 9808130040
Download: ML20237A036 (45)


Text

i ENCLOSURE 1 CATAWBA NUCLEAR STATION COMBINED UNIT 1 AND UNIT 2 ITS PAGES 9908130040 990905 ADOCK 05000413 PDR PDR p

SLs 2.0 670 DO NOTOPERATEIN THIS AREA 660 650 2455 grJa 640 2400 pelo CL 630 2200 paio I

h620 2100 pelo 610 1945 psia 400 590 ACCEPTA8UE OPERATION 500 O.0 0.2 0.4 04 0.8 14 1.2 Fraction of Roted Thermal Power l

Figure 2.1.1-1 (UNIT 1 ONLY)

Reactor Core Safety Limits -

Four Loops in Operation Catawba Units 1 and 2 2.0-2 Amendment No.

L_____________________________._____._____.._

SLs 2.0 670 00 NOT OPERATE IN THIS AREA.

660 2455 psia 650 g

2GAsia 1

c M*

t,630 I

h620 2100 pelo 610 3

600 t

590 ACCEPTA8LE OPERADON sao O.0 0.2 0.4 04 0.8 1.0 1.2 Eroction of Roted ThermalPower i

Figure 2.1.1-1 (UNIT 2 ONLY)

Reactor Core Safety Limits -

l Four Loops in Operation Catawba Units 1 and 2 2.0-3 Amendment No.

i RTS Instrumentation 3.3.1 i

Table 3.3.1-1 (page 5 of 7) i Reactor Trip System Instrumentation Note 1: Overtemperature AT l

The Ove temperature AT Function Allowable Value shall not exceed the following Trip Setpoint by more than 4.5% of RTP.

AT ((1 + r, s) '

sATo K - K, (1 + r, s) ' T 1

l

- T'

+ K (P - P')- /, (AI) i 3

1 + r, s

, 1 + r, s,

(1 + r, s) _ (1 + r. s)

Where: AT is the measured RCS AT by loop narrow range RTDs, *F.

ATo is the indicated AT at RTP, *F.

s is the Laplace transform operator, sec.

j T is the measured RCS average temperature *F.

i T' is the nominal T.v at RTP (allowed by Safety Analysis), s 585.1 *F (Unit 1) s 590.8'F (Unit 2).

{

P is the measured pressurizer pressure, psig P'is the nominal RCS operating pressure, = 2235 psig K

Overtemperature AT reactor trip setpoint, as presented in the COLR, i

=

K Overtemperature AT reactor trip heatup setpoint penalty coefficient, as 2

=

presented in the COLR, K3 Overtemperature AT reactor trip depressurization setpoint penalty coefficient,

=

as presented in the COLR, Time constants utilized in the lead-lag compensator for AT, as presented in t, t,

=

i

- the COLR, Time constant utilized in the lag compensator for AT, as presented in the x

=

COLR, Time constants utilized in the lead-lag compensator for T.vo, as presented in t., t.

=

the COLR, l

Time constant utilized in the measured T.vg lag compensator, as presented in t.

=

the COLR, and fi(AI) a function of the indicated difference between top and bottom detectors of the

=

power-range neutron ion chambers; with gains to be selected based on measured instrument response during plant startup tests such that:

(i) for qi-go between the " positive" and " negative" fi(AI) breakpoints as presented in the COLR; f (Al) = 0, where qi and go are percent RATED i

THERMAL POWER its the top and bottom halves 9 the core respectively, I

and qi + go is total THERMAL POWER in percent of RATED THERMAL POWER; (ii) for each percent Al that the magnitude of qi-go is more negative than the f (AI) " negative" breakpoint presented in the COLR, the AT Trip Setpoint i

shall be automatically reduced by the f (AI) " negative" slope presented in i

the COLR; and (continued)

Catawba Units 1 and 2 3.3.1-18 Amendment No.

RTS Instrum:ntation 3.3.1 Table 3.3.1 1 (page 6 of 7)

Reactor Trip System instrumentation (iii) for each percent Al that the magnitude of qi-qu is more positive than the f (AI) " positive" breakpoint presented in the COLR, the AT Trip Setpoint i

shall be automatically reduced by the f (41) ' positive" slope presented in i

the COLR.

Note 2: Overpower AT The Overpower AT Function Allowable Value shall not exceed the following Trip Setpoint by more than 3% of RTP.

A T (' * *' *) '

D#

T-K T

- T'

-f,(AI) s ATa (1 + r, s),1 + r, s,

Ka - K,1 + r, S,1 + r, s,

, 1+r,s f

s Where:

AT is the measured RCS AT by loop narrow range RTDs, "F.

' ATo is the indicated AT at RTP, *F.

d s is the Laplace transform operator, sec.

J T is the measured RCS average temperature, *F.

T'is the nominal Tm t RTP (calibration temperature for AT instrumentation),

a s 585.1 *F (Unit 1) $ 590.8"F (Unit 2).

K4

=-

Overpower AT reactor trip setpoint as presented in the COLR, Ks 0.02/*F for increasing average temperature and 0 for decreasing average

=

temperature, Ke Overpower AT reactor trip heatup setpoint penalty coefficient as

=

- presented in the COLR for T > T and Ke = 0 for T s T",

Time constants utilized in the lead-lag compensator for AT, as presented ri, r,

=

'in the COLR, Time constant utilized in the lag compensator for AT, as presented in the r,

=

COLR, Time constant utilized in the measured Tm lag compensator, as t.

=

presented in the COLR,-

Time constant utilized in the rate-lag controller for Tm, as presented in t,

=

the COLR, and f,(AI) a function of the indicated difference between top and bottom detectors of

=

the power-range neutron ion chambers; with gains to be selected based on measured instrument response during plant startup tests such that:

l (i) for gi-go between the " positive" and " negative" f (AI) breakpoints x 2

l.

presented in the COLR; f (61) = 0, where qi and go are percent

)

2 l.

RATED THERMAL POWER in the top and bottom halves of the core respectively, and gi + go is total THERMAL POWER in percent of RATED THERMAL POWER; J

/

(continued)

Catawba Units 1 and 2 3.3.1-19 Amendment No.

t

ESFAS Instrumentation 3.3.2 TaNa 3.3.2-1 (page 3 of $)

Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE TRIP SETPOINT

4. Steam Line Isolaton (continued) l (2) Negative 3(b)(c) 3 per steam D

SR 3.3.2.1 5122.8(d) psi s 100(d)

Rate High line SR 3.3.2.5 psi SR 3.3.2.9 SR 3.3.2.10 5.

Turbine Trip and Feedwater Isolation a.

Automatic Actuation Logic 1,2(e) 2 trains i

SR 3.3.2.2 NA NA l

and Actuation SR 3.3.2.4 i

Relays SR 3.3.2.6 b.

SG Water Level-1,2(e) 4 per SG J

SR 3.3.2.1 5 85.6 %

5 83.9 %

High High (P 14)

SR 3.3.2.2 (Unit 1)

(Ur"i)

SR 3.3.2.4 2 78.9 %

2 7/.1%

SR 3.3.2.5 (Unit 2)

(Unit 2)

SR 3.3.2.6 SR 3.3.2.9 SR 3.3.2.10 c.

Safetyinjection Refer to Function 1 (Safety injection) for all initiation funcbons and requirements.

I l

d.

Tm-Low 1,2(e) 4 J

SR 3.3.2.1 2 561*F 2 564*F SR 3.3.2.5 i

SR 3.3.2.9 coincident with Refer to Function 8.a (Reactor Trip, P-4) for all initiation functions and Reactor Trip, P-4 requirements. -

e.

Doghouse Water 1,2(e) 2 per L

SR 3.3.2.8 s 12 inches s 11 inches Level High High doghouse above 577 ft above 577 floor level ft floor level f.

Trip of alltrain 1,2(a) 3 per MFW K

SR 3.3.2.8 NA NJ feedwater pumps pump (continued) l (a) Above the P 11 (Pressurizer Pressure) interlock.

(b) Except when all MSIVs are closed and de-activated.

(c) Trip function automatically blocked above P-11 (Pressurizer Pressure) interlock and may be blocked below P-11 when Steam Line Isolation Steam Une Pressure Low is not blocked.

(d) Time constant utilized in the ratMag controller is 2 50 seconds (e) Except when all MFIVs, MFCVs, and associated bypass valves are closed and de-activated or isolated by a closed manual valve.

j r

Catawba Units 1 and 2 3.3.2-13 Amendment No.

}

ESFAS InStrum:mtation 3.3.2 Table 3.3.2-1 (page 4 of 5)

Engineered Safety Feature Actuation System lostrumentatxm APPLICASLE MODES OR OTHER SPECIFIED REQUIRED.

SURVEILLANCE ALLOWABLE TRIP l~

FUNCTION CONDmONS CHANNELS CONDITIONS REQUIREMENTS VALUE SETPOINT 6.

. Auxiliary Feedwater l

a.

Automatic 1,2,3 2 trains H

SR 3.3.2.2 NA NA Actuation Logic SR 3.3.2.4 l

and Actuation SR 3.3.2.6 Rep b.

SG Water Level-1,2,3 4 per SG D

SR 3.3.2.1 29%

2 10.7%

Low Low SR 3.3.2.5 (Unit 1)

(Unit 1)

SR 3.3.2.9 2 35.1 %

2 36.8 %

SR 3.3.2.10 (Unit 2)

(Unit 2) c.

Safetyinjection Refer to Function 1 (Safety injection) for all initiation functiors and requirements.

d.

Loss of Offsite 1,2,3 3 per bus D

SR 3.3.2.3 2 3242 V 2 3500 V Power SR 3.3.2.9 SR 3.3.2.10 e.

Trip of all Main 1,2(a) 3 per pump K

SR 3.3.2.8 NA NA Feedwater SR 3.3.2.10 Pumps f.

Aumliary 1,2,3 3 por train M

SR 3.3.2.8 A) 2 9.5 psig A) 210.5 Feedwater Pump SR 3.3.2.10 psig Train A and Train B Suction B) 2 5.2 psig B) 2 6.2 Transfer on (Unit 1) psig Suction Pressure 2 5.0 psig (Unit 1)

-Low (Unit 2) 2 6.0 psig (Unit 2)

7. Automatic Switchover -

to Containment Sump a.

Automatic 1,2,3,4 2 trains C

SR 3.3.2.2 NA NA Actuation Logic SR 3.3.2.4 and Actuation SR 3.3.2.6 Relays b.

Refueling Water 1,2,3,4 4

N SR 3.3.2.1 2 162.4 2 177.15 Storage TaA SR 3.3.2.7 inches inches (RWST) Level-SR 3.3.2.9 Low SR 3.3.2.10 Coincident with Refer to Function 1 (Safety injection) for all initiation functions and requirements.

Safety injection (continued)

(a) Above the P-11 (Pressurizer Pressure) interlock.

I i

l l

Catawba Units 1 and 2 3.3.2-14 Amendment No.

RTS Instrumentation B 3.3.1 BASES APPLICABLE 9.

Pressurizer Water Level-Hiah (continued)

SAFETY ANALYSES, LCO, and fourth channel is not required to address control / protection interaction concerns.

The level channels do not actuate the safety valves, and the high pressure reactor trip is set below the safety valve setting. Therefore, with the slow rate of charging available, pressure overshoot due to level channel failure cannot cause the valve to lift before reactor high pressure trip.

In MODE 1, when there is a potential for overfilling the pressurizer, the Pressurizer Water Level-High trip must be OPERABLE. This trip Function is automatically enabled on increasing power by the P-7 interlock. On decreasing power, this trip Function is automatically blocked below P-7.

Below the P-7 setpoint, transients that could raise the pressurizer water level will be slow and the operator will have sufficient time to evaluate unit conditions and take corrective actions.

10.

Reactor Coolant Flow-Low a.

Reactor Coolant Flow-low (Sinole Loool The Reactor Coolant Flow-Low (Single Loop) trip Function ensures that protection is provided against violating the DNBR limit due to low flow in on.e or more RCS loops, while avoiding reactor trips due to normal variations in loop flow.

Above the P-8 setpoint, which is approximately 48% RTP, a loss of flow in any RCS loop will actuate a reactor trip.

The setpoints are based on a minimum measured flow of 95,500 gpm (Unit 1) 96,250 gpm (Unit 2). Each RCS loop has three flow detectors to monitor flow.

The flow signals are not used for any control system input.

The LC0 requires three Reactor Coolant Flow-Low channels per loop to be OPERABLE in MODE 1 above P-8.

In MODE 1 above the P-8 setpoint, a loss of flow in one RCS loop could result in DNB conditions in the core.

In MODE 1 below the P-8 setpoint, a (continued)

Catawba Units 1 and 2 B 3.3-19 Supplement 8 l

[

l RTS Instrumentation l

l B 3.3.1 I

BASES APPLICABLE a.

Reactor Coolant Flow-Low (Sinole Loool j

SAFETY ANALYSES, (continued) j LCO, and l

APPLICABILITY loss of flow in two or more loops is re actuate a reactor trip (Function 10.b) quired to because of the lower power level and the greater margin to the design limit DNBR.

b.

Reactor Coolant Flow-Low (Two Lc 35.),

The Reactor Coolant Flow-Low (Two Loops) trip Function ensures that protection is provided against violating the DNBR limit due to low flow in two or more RCS loops while avoiding reactor trips due to normal variations in loop flow.

Above the P-7 setpoint and below the P-8 setpoint, a loss of flow in two or more loops will initiate a reactor trip. The setpoints are based on a minimum measured flow of 95,500 gpm l

(Unit 1) 96,250 gpm (Unit 2). Each loop has three flow detectors to monitor flow.- The flow signals are not used for any control system input.

The LC0 requires three Reactor Coolant Flow-Low channels per loop to be OPERABLE.

In MODE I above the P-7 setpoint and below the P-8 setpoint, the Reactor Coolant Flow-Low (Two Loops) trip must be OPERABLE. Below the P-7 setpoint, all reactor trips on low flow are automatically blocked since power distributions that would cause a DNB concern at this low power level are unlikely. Above the P-7 setpoint, the reactor trip on low flow in two or more RCS loops is automatically enabled. Above the P-8 setpoint, a loss of flow in any one loop will actuate a reactor trip because of the higher power level and the reduced margin to the design limit DNBR.

l (continued) l Catawba Units 1 and 2 8 3.3-20 Supplement 8

RCS Pressure, Temperature, end Flow DNB Limits l

3.4.1 POWER DISTRIBUTION LIMITS j

385,820 A penalty of 0.1% for undetected feedwater p,,3,,;g venturi fouling and a measurement uncertainty (M

of 2,1% for fkm are induded in this igure.

(98, 382,000)

"*9' "

382,000 E

Ei 378,180 I

7 Restricted g

Operatxm o

Region (94, 374,360)

[t 374,360 E

(92, 370,540)

Prohituted m

c 370,540 operation 2

Region 8

0 (90, 366,720) g 366,720 362,900 359,080 86 88 90 92 94 96 98 100 102 Percent of Rated Thermal Power i

Figure 3.4.1-1 (UNIT 1 ONLY)

RCS TOTAL FLOW RATE VERSUS RATED THERMAL POWER - FOUR LOOPS IN OPERATION Catawba Units 1 and 2 3.4.1-5 Amendment No.

RCS Pressure, Temp:ratura, cnd Flow DNB Limits 3.4.1 1

POWER DISTFilBUTION LIMITS 388,850 A penalty of 0.1% for undetected feedwater 8D*

venturi fouling and a measurement uncertainty of tu 2.1% for flow are included in this figure.

(98, 385,000)

Region 385,000 E

$ 381,150 k

Restncted y

operation o

Region (94, 377,300)

Z 377,300 E

M (92, 373,450)

Prohibited c 373,450 operaton Region 8o

[o (90, 369,600) g 369,600 365,750 361,900 86 88 90 92 94 96 98 100 102 Percent of Rated Thermal Power 1

Figure 3.4.1-1 (UNIT 2 ONLY)

RCS TOTAL FLOW RATE VERSUS RATED THERMAL POWER-FOUR LOOPS IN OPERATION l

l I

Catawba Units 1 and 2 3.4.1-6 Amendment No.

I L---__--------------------------------------

RCS P/T Limits 3.4.3 l

MATERIAL PROPERTY BASIS UMfTING MATERIAL: LOWER SHELL FORGING 04 UMITING ART AT15 EFPY:

1/4-T, 43'F 3/4 T, 26*F l

2,5 0 0

,,i i i i ii i i i i i.

l LEAK TEST UMIT --y l

[

2,250

/

l J

l I

I i

I I

i i

f I

i 2,000 l

i Q

l I

I

/

i

(/)

UNACCEPTABLE j

j l

c.1,750 l

OPERATION

/

/

i

/

/

i i

$ 1,500

&)

HEATUP RATE '

/

/

ACCEPTABLE

(/)

UP TO 60 F/HR r

OPERATION 2 1,250

/

/

L l

l V 1,000

/

o

+*

l (U

.9 750 t

l C

+

500

~

l q _.

'CRITICAUTY UMIT BASED ON 250 INSERVICE HYDROSTATIC TEST

~~--

l TEMPERATURE (176*F) FOR THE ::

SERVICE PERIOD UP TO 15 EFPY ::::

Uilililiiilii'iii'iiill 0

0 50 100 150 200 250.300 350 400 450 500 Indicated Temperature (Deg. F)

Figure 3.4.3-1 (UNIT 1 ONLY)

RCS Heatup Limitations Catawba Units 1 and 2 3.4.3-3 Amendment No.

l

RCS P/r Limits 3.4.3 MATERIAL PROPERTY BASIS l

LDCIING MATERIALS Dr1ERMEDIATE CHR T B8605-2 LIMII1NG ART AT 15 EFPY.

1/4-t,112.6 T l

3/4-t, 96.0 7 2.,500 LEAK TEST LIMIT-i I

t i

m 2.,250 l

r i

J n

l l

C) 2.,000 U)

)

I h 1.,750 inccEPTABLE OPERATION f

f G

y 1.,500 l

/

l y)

[

[

ACCEPTABLE (f)

/

I OPERATION

~"~~

c) 1,250 HEATUP RATE

~"~~~

L UP TO SO _ 'F/ HR r

r D-l l

1.,000

/

O@

l

+J r

.M 750 O

/

f 500

~

l

, CRITICALITY LIMIT BASED ON INsEwicE mOnosTAric TEsr 250 TEMPERATURE (245 *F) FOR THE SERVICE PERIOD UP TO 15 EFPY iiiiiiiiiiiiiiiiiiiiiii g

0 50 100 150 200 250 300 350 400 450 500 Indicated Temperature (Deg. F)

Figure 3.4.3-1 (UNIT 2 ONLY)

RCS Heatup Limitations t-Catawba Units 1 and 2 3.4.3-4 Amendment No.

RCS P/T Limits 3.4.3 i

MATERIAL PROPERTY BASIS UMITING MATERIAL: LOWER SHELL FORGING 04 UMITING ART AT 15 EFPY:

1/4-T, 43*F 3/4-T, 26*F i

2,500

)

l 2,250

~

{

l

_ 2,000 f

{

CD

UNACCEPTABLE i

l

'5 OPERATION

/

cl.1,750

/

t I

O

[

l

!:5 1,5 0 0

/

l

(/)

j ACCEPTABLE j

(/)

r OPERATION l

S 1,250

/

CL

/

4 V 1,000 l

0

. BOOLDOWN k

R_ATES F/HR._

o 750 o

g
20 C

~~~'

500 too 250 1

I 0

O 50 100 150 200 250 300 350 400 450 500 I

Indicated Temperature (Deg. F)

Figure 3.4.3-2 l

(UNIT 1 ONLY)

RCS Cooldown Limitations Catawba Units 1 and 2 3.4.3-5 Amendment No.

u

RCS P/T Limits 3.4.3 MATFRIAL PROPFR~IY BASIS LIhnTING MATERIALS: INTERMEDLM SHELL, B8605-2 LIMIITNG ART AT 15 ITPY:

1/4-t,112.6 T 3/4-t. 96.0 7 2,500 3

l 2,250 i

,1 CD 2,000

/

U)

I d

mmew V 1,750 O?ERATs0N

/

l L

1,,500

/

l D

U)

/

1,,250

~~~

/

AZEPTABLE j

OPEAATloN D.

l' 1,000 D

j G

s

+>

cooLDOWN (0

750 RATEU 'F/HR.

$N

()

o vi 4

20

ff y

500 40 g

C so 3

100 250 i

0 O

50 100 150 200 250 300 350 400 450 500 I nd i cated Temperature (Deg.

F)

Figure 3.4.3-2 (UNIT 2 ONLY)

RCS Cooldown Limitations Catawba Units 1 and 2 3.4.3-6 Amendment No.

LTOP Syst:m 3.4.12 I

Table 3.4.12-1 (Page 1 of 1)

(UNIT 1 ONLY)

)

Reactor Coolant Pump Operating Restrictions for Low

)

Temperature Overpressure Protection

)

i Reactor Coolant System Cold Log Maximum Number of Pumps Allowed in Temperature Operation 2 67 F 1

> 68*F 2

273*F 4

l l

Catawba Units 1 and 2 3.4.12-6 Amendment No.

I LTOP Syctem 3.4.12 Table 3.4.12-1 (Page 1 of 1)

(UNIT 2 ONLY)

Reactor Coolant Pump Operating Restrictions for Low Temperature Overpressure Protection Reactor Cociant System Cold Leg Maximum Number of Pumps Allowed in Temperature Operation 2 67 F 1

I 2 73*F 2

2 95*F 4

f i

1

)

Catawba Units 1 and 2 3.4.12-7 Amendment No.

I

-J

I RCSP/TLimits B 3.4.3' BASES ACTIONS-L1 and C.2 (continued)

Condition C is modified by a Note requiring Required Action C.2 to be completed whenever the Condition is entered. The Note emphasizes the need to perform the evaluation of the effects of the excursion outside the i

allowable limits.

Restoration alone per Required Action C.1 is insufficient because higher than analyzed stresses may have occurred and may have affected the RCPB integrity.

SURVEILLANCE SR 3.4.3.1 REQUIREMENTS Verification that operation is within the specified limits is required every 30 minutes when RCS pressure and temperature conditions are undergoing planned changes. This Frequency is considered reason 0ble in view of the control room indication available to monitor RCS status. Also, since temperature rate of change limits are specified in hourly increments, 30 minutes permits assessment and correction for minor deviations within a reasonable time.

Surveillance for heatup, cooldown, or ISLH testing may be discontinued when the definition given in the relevant plant procedure for ending the activity is satisfied.

This SR is modified by a Note that only requires this SR to be performed during system heatup, cooldown, and ISLH testing. No SR is given for criticality operations because LCO 3.4.2 contains a more restrictive requirement.

)

l REFERENCES 1.

10 CFR 50, Appendix G.

2.

M 4E, Boiler and Pressure Vessel Code,Section III,

% bndix G.

-l' 3.

ASTM E 185-73, 1973 (Unit 1), E 185-82, 1982 (Unit 2).

)

4.

10 CFR 50, Appendix H.

(continued)

Catawba Units 1 and 2 B 3.4-16 Supplement 8

ll CVlWS 3.6.17

~ 3.6 CONTAINMENT SYSTEMS i-IL 3.6.1'7 Containment Valve injection Water System (CVlWS) -

t i

LCO 3.6.17 -

Two CVlWS trains shall be OPERABLE.

~ APPLICABILITY:-

MODES 1, 2,' 3, and 4.

ACTIONS I

l CONDITION

' REQUIRED ACTION COMPLETlON TIME A. '

One CVlWS train A.1 Restore CVlWS train to 7 days inoperable.

OPERABLE status.

B.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion

. Time not met.

AND l

B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> l

L i

c SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY-SR 3.6.17.1. Verify system surge tanks pressure is 2 36.4 psig.

31 days SR-3.6.17.2 Verify valve injection flow rate is < 1.29 gpm (Unit 1) 18 months

< 1.21 gpm (Unit 2) for Train A and 1.16 gpm for Train B

' with a surge tank pressure 2 36.4 psig.

SR 3.6.17.3 Verify each automatic valve actuates to its correct 18 mont'it position on an actual or simulated actuation signal.

l

' Catawba Units 1 and 2 3.6.17-3 Amendment No.

I i

Programs and Manuals 5.S 5.5 Programs and Manuals 5.5.9.2 Steam Generator Tube Sample Selection and Inspection (continued) 2.

The inspections belude those portions of the tubes where imperfections were previously found.

The results of each sample inspection shall be classified into one of the following three categories:

Cateaorv inspection Resu;ts C-1 Less than 5% of the total tubes inspected are degraded tubes and none of the inspected tubes are defective.

4 1

C-2 One or more tubes, but not more than 1% of the

)

total tubes inspected are defective, or between 5%

and 10% of the total tubes inspected are degraded tubes.

)

C-3 More than 10% of the total tubes inspected are

{

degraded tubes or more than 1% of the inspected tubes are defective.

Note: In all inspections, previously degraded tubes must exhibit significant (greater than 10%) further wall penetrations to be included in the above 1

percentage calculations.

j i

5.5.9.3 inspection Frequencies l

The above required inservice inspections of steam generator tubes shall be performed at the following frequencies

  • l a.

The first inservice inspection after steam generator replacement shall be performed after at least 6 Effective Fuli Power Months but within 24 calendar months of initial criticality after steam generator replacement I

(Unit 1). The first inservice inspection shat! be performed after 6 Effective Full Power Months but within 24 calendar months of initial criticality (Unit 2). Subsequent inservice inspections shall be performed at intervals of not less than 12 nor more than 24 calendar months after the previous inspection. If two consecutive inspections, not including the preservice i

l inspection, result in all inspection results falling into the C-1 category or if two consecutive inspections demonstrate that previously observed degradation has not continued and no additional degradation has occurred, the inspection interval may be extended to a maximum of once per 40 months; (continued)

Catawba Units 1 and 2 5.5-8 Amendment No.

L_________________________-..__________________

Programs and Manuals 5.5 TABLE 5.5-f (Page 1 of 1)

MINIMUM NUMBER OF STEAM GENERATORS TO BE INSPECTED DURING INSERVICE INSPECTION Preservice inspection No Yes No.of Steam Generators per Unit Four Four First inservice inspection after the All Two Steam Generator Replacement (Unit 1)

First inservice inspection (Unit 2)

Second & Subsequent inservice One' One' Inspections T_able Notation 1.

The inservice inspection may be limited to one steam generator on a rotating schedule encompassing 3 N % of the tubes (where N is the number of steam generators in the unit) if the results of the first or previous inspections indicate that all steam generators are performing in a like manner. Note that under some circumstances, the operating conditions in one or mora steam generators may be found to be more severe than those in other steam generators. Under such circumstances the sample sequence shall be modified to inspect the most severe conditions.

2.

Each of the other two steam generators not inspected during the first inservice inspection after the steam generator replacement shall be inspected during the second and third inspections (Unit 1).

Each of the other two steam generators not inspected during the first inservice inspection shall be inspected during the second and third inspections (Unit 2). The fourth and subsequent inspections shd follow the instn>ctions described in 1 above.

l Catawba Units 1 and 2 5.5-11 Amendment No.

i I

Programs and Manuals 5.5 t

l 5.5 Programs and Manuals l

l 5.5.11 Ventilation Filter Testina Proaram (VFTP) (continued)

ESF Ve:1tilation System Penetration Flowrate I

Annulus Ventilation (Unit 1)

<1%

9000 cfm Annulus Ventilation (Unit 2)

< 0.05%

9000 cfm Control Room Area Ventilation

< 0.05%

6000 cfm Aux. Bldg. Filtered Exhaust (Unit 1)

<1%

30,000 cfm Aux. Bldg. Filtered Exhaust (Unit 2)

< 0.05%

30,000 cfm Containment Purge (non-ESF) (2 fans)

<1%

25,000 cfm Fuel Bldg. Ventilation (Unit 1)

<1%

16,565 cfm Fuel Bldg. Ventilation (Unit 2)

< 0.05 %

16,565 cfm b.

Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows the following penetration and system bypass when tested in accordance with Regulatory Guide 1.52, Revision 2, and ANSI N510-1980 at the flowrate specified below

  • 10%.

ESF Ventilation System Penetration Flowrate Annulus Ventilation (Unit 1)

<1%

9000 cfm Annulus Ventilation (Unit 2)

< 0.05%

9000 cfm Control Room Area Ventilation

< 0.05%

6000 cfm Aux. Bldg. Filtered Exhaust (Unit 1)

<1%

30,000 cfm Aux. Bldg. Filtered Exhaust (Unit 2)

< 0.05%

30,000 cfm Containment Purge (non-ESF) (2 fans)

<1%

25,000 cfm Fuel Bldg. Ventilation (Unit 1)

<1%

16,565 cfm Fuel Bldg. Ventilation (Unit 2)

< 0.05%

16,565 cfm c.

Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 5 30 C and greater than or equal to the relative humidity specified below.

ESF Ventilation System Penetration RH Annulus Ventilation

<4%

P Control Room Area Ventilation

< 0.95%

9a Aux. Bldg. Filtered Exhaust

<4%

95 %

i Containment Purge (non-ESF)

<6%

95 %

f Fuel Bldg. Ventilation

<4%

95 %

l l

(continued)

Catawba Units 1 and 2 5.5-14 Amendment No.

l l

I l

l ENCLOSURE 2 CATAWBA NUCLEAR STATION CHANGES TO ITS SECTION 3.0 I

l t

LCO Applicability 3.0 3.0 LCO APPLICABILITY (continued)

LCO 3.0.5 Equipment removed from service or declared inoperable to comply with ACTIONS may be returned to service under administrative control solely to perform testing required to demonstrate itt.; OPERABILITY or the 1

OPERABILITY of other equipment. This is an exception to LCO 3.0.2 for the system returned to service under administrative control to perform the required testing to demonstrate OPERABILITY.

LCO 3.0.6 When a supported system LCO is not met solely due to a support system LCO not being met, the Conditions and Required Actions associated with j

this supported system are not required to be entered. Only the support system LCO ACTIONS are required to be entered. This is an exception to LCO 3.0.2 for the supported system. In this event, additional evaluations and limitations may be required in accordance with Specification 5.5.15, " Safety Function Determination Program (SFDP)." If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

When a support system's Required Action directs a supported system to be declared inoperable or directs entry into Conditions and Required 3

Actions for a cupported system, the applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.

LCO 3.0.7 Test Exception LCOs 3.1.8 and 3.4.17 allow specified Technical Specification (TS) requirements to be changed to permit performance of special tests and operations. Unless otherwise specified, all other TS requirements remain unchanged. Compliance with Test Exception LCOs is optional. When a Test Exception LCO is desired to be met but is not met, the ACTIONS of the Test Exception LCO shall be met. When a Test Exception LCO is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.

LCO 3.0.8 LCOs including the associated ACTIONS shall apply to each unit individually unless otherwise indicated as follows:

a.

Whenever the LCO refers to systems or components which are shared by both units, the ACTIONS will apply to both units i

simultaneously; b.

Whenever the LCO applies to only one unit, this will be identified in j

the Applicability section of the Specification; and (continued)

Catawba Units 1 and 2 3.0-2 Amendment No.

LCO Applicability 3.0 3.0 LCO APPLICABILITY (continued)

Whenever certain portions of a Specification contain operating c.

parameters, setpoints etc., which are different for each unit, this will be identified in parentheses or footnotes. (For example, "... flow rate of 54,000 cfm (Unit 1) or 43,000 cfm (Unit 2)...").

Catawba Units 1 and 2 3.0-3 Amendment No.

l l

l SR Applicability 3.0 3.0 SR APPLICABILITY (continued)

SR 3.0.4 Entry into a MODE or other specified condition in the Applicability of an LCO shall not be made unless the LCO's Surveillance have been met within their specified Frequency. This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS.

SR 3.0.5 Surveillance Requirements shall apply to each unit individually unless otherwise indicated as stated in LCO 3.0.8 for individual Specifications or l --

whenever certain portions of a Specification contain surveillance parameters different for each unit, which will be identified in parentheses or footnotes.

l l'

l I

Catawba Units 1 and 2 3.0-5 Amendment No.

a

LC0 Applicability B 3.0 B 3.0 -LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY BASES i

LCOs LCO 3.0.1 through LCO 3.0.8 establish the general l

l requirements applicable to all Specifications and apply. at all times, unless otherwise-stated.

t LCO 3.0.1 LC0 3.0.1 establishes the Applicability statement within each individual Specification as the requirement for when the LC0 is required to be met (i.e., when the unit is in the MODES or other specified conditions of the Applicability t

statement of each Specification).

LCO 3.0.2 LC0 3.0.2 establishes that upon discovery of a failure ~ to I

meet an LCO, the associated ACTIONS shail be met.

The l

Completion Time of each Required Action for an ACTIONS i

Condition is applicable from the point in time that an l

ACTIONS Condition is entered. The Required Actions

{

l establish those remedial measures that must be taken within l'

specified Completion Times when the' requirements of an LCO are not met.

This Specification establishes that:

L

[

a.

Completion of the' Required Actions within the specified Completion Times constitutes compliance with a Specification; and

b..

Completion of the Required-Actions is not required when an LC0 is met within the specified Completion Time, unless otherwise specified.

There are two basic types of Required Actions. The first L

type of Required Action specifies a time limit in which the-LC0 must be met. This time limit is the Completion Time to restore an inoperable system or component to OPERABLE status 1

or to restore. variables to within specified limits.

If this type of Required Action is not completed'within the specified Completion Time, a shutdown may be required to place the unit in a MODE or condition in which the Specification is not applicable.

(Whetherstatedasa Required Action or not. correction of the entered Condition is an action that may always be considered upon entering (continued)

I Catawba Units 1-and 2 B 3.0-1 Supplement 8

LC0 Applicability B 3.0 I

i BASES LC0 3.0.7 allow specified Technical Specification (TS) requirements to (continued) be changed to permit performances of these special tests and operations, which otherwise could not be performed if I

required to comply with the requirements of these TS.

Unless otherwise specified, all the other TS requirements remain unchanged. This will ensure all appropriate requirements of the MODE or other specified condition not directly associated with or required to be changed to perform the special test or operation will remain in effect.

The Applicability of a Test Exception LC0 represents a condition not necessarily in compliance with the normal requirements of the TS. Compliance with Test Exception LCOs is optional. A specia! operation may be performed either under the provisions of the appropriate Test Exception LC0 or under.the other applicable TS requirements.

If it is desired to perform the special operation under the provisions of the Test Exception LCO, the requirements of the Test Exception LC0 shall be followed.

LC0 3.0.8 LC0 3.0.8 delineates the applicability of each specification to Unit 1 and Unit 2 cperations.

l I

l Catawba Units 1 and 2 B 3.0-9 Supplement 8 t

SR Applicability B 3.0 B 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY BASES l SRs SR 3.0.1 through SR 3.0.5 establish the general requirements applicable to all Specifications and apply at all times, unless otherwise stated.

SR 3.0.1 SR 3.0.1 establishes the requirement that SRs must be met during the MODES or other specified conditions in the Applicability for which the requirements of the LC0 apply, unless otherwise specified in the individual SRs. This Specification is to ensure that Surveillance are performed to verify the OPERABILITY of systems and components, and that variables are within specified limits. Failure to meet a Surveillance within the specified Frequency, in accordance with SR 3.0.2, constitutes a failure to meet an LC0.

Systems and components are assumed to be OPERABLE when the associated SRs have been met. Nothing in this Specification, however, is to be construed as implying that systems or components are OPERABLE when:

a.

The systems or components are known to be inoperable, although still meeting the SRs; or b.

The requireme..ts of the Surveillance (s) are known not to be met between required Surveillance performances.

Surveillance do not have to be performed when the unit is in a MODE or other specified condition for which the requirements of the associated LC0 are not applicable, unless otherwise specified. The SRs associated with a test exception are only applicable when the test exception is used as an allowable exception to the requirements of a Specification.

Unplanned events may satisfy the requirements (including applicable acceptance criteria) for a given SR.

In this case, the unplanned event may be credited as fulfilling the performance of the SR. This allowance includes those SRs whose performance is normally precluded in a given MODE or other specified condition.

]

\\

Surveillance, including Surveillance invoked by Required

)

Actions, do not have to be performed on inoperable equipment (continued) l l

Catawba Units 1 and 2 8 3.0-10 Supplement 8 l

L--______---------_-----

I SR Applicability i

B 3.0 BASES SR 3.0.4 the Surveillance may be stated in the form of a Note as not (continued)

' required (to be met or performed) until'a particular event, condition, or time has teen reached. Further discussion of the specific formats of SRs' annotation is found in Section 1.4, Frequency.

SR 3.0.5 SR 3.0.5 delineates the applicability of the surveillance activities to Unit 1 and Unit 2 operations.

i Catawba Units 1 and 2 B 3.0-15 Supplement 8 l

Specific tion 3.0 INSERT 5 (continued)

LCO 3.0.7 Test Exception LCOs 3.1.8 and 3.4.17 allow specified Technical Specification (TS) requirements to be changed to A3 permit performance of special tests and operations. Unless otherwise specified, all other TS requirements rernain unchanged. Compliance with Test Exception LCOs is optional. When a Test Exception LCO is desired to be met but is not met, the ACTIONS of the Test Exception LCO shall be met. When a Test Exception LCO is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.

LCO 3.0.8 LCOs including the associated ACTIONS shall apply to each unit individually unless otherwise indicated as follows:

QL a.

Whenever the LCO refers to systems or compunents which are shared by both units, the ACTIONS will apply to both units simultaneously; b.

Whenever the LCO applies to only one unit, this willbe identifiedin the Applicability section of the Specif; cation; and c.

Whenever certain portions of a Specification contain operating parameters, setpoints etc., which are different for each unit, this will be identified in parentheses or footnotes.

(For example, *... flow rate of 54,000 cfm (IJnit 1) or 43,000 cfm (Unit 2)...").

)

{

' Catawba I fog H sl 8

__A

SpecificEon 3.0 INSERT 8 If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is less. This delay period is permitted to allow performance of the Surveillance.

If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition (s) must be entered.

When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immedMaly be declared not met, and the applicable Condition (s) must be entered.

INSERT 9 A.t Entry into a MODE or other specified condition in the Applicability of an LCO shall not be made unless the LCO's Surveillance have been met within their specified Frequency. This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS.

INSERT 10 SR 3.0.5 Surveillance Requirements shallapply to each unit individually unless othenvise indicated as stated in LCO 3.0.8 for individual Specifications or whenever certain portions of a Specification l

contain surveillance parameters different for each unit, which will

(

be identified in parentheses or footnotes.

1 l

Catawba l 7,c g L

[

.i Specification 3.0 INSERT 5 (continued)

LCO 3.0.7 Test Exception LCOs 3.1.8 and 3.4.17 allow spechied Technic-l Specification (TS) requirements to be changed to A3 permit performance of special tests and operations. Unless ott.9rwise specified, all other TS requirements remain unct anged. Compliance with Test Exception LCOs is optional. When a Test Exception LCO is desired to be met but is not met, the ACTIONS of the Test Exception LCO shall be met. When a Test Exception LCO is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.

LCO 3.0.8 LCOs including the associated ACTIONS shallapply to each unit individually unless otherwise indicated as follows:

k(L a.

Whenever the LCO refers to systems or components which are shared by both units, the ACTIONS will apply to both units simultaneously; b.

Whenever the LCO applies to only one unit, this will be identifiedin the Applicability section of the Specification; and

\\

c.

Whenever certain portions of a Specification contain twating parameters, setpoints etc., which are different for t. h unit, this willbe identifiedin parentheses or footnotes.

(For example, "... flow rate of 54,000 cfm (Unit 1) or 43,000 cfm (Unit 2)...").

l 1

l Catawba 1 fag H L 8

Specification 3.0 INSERT 8 If it is discovered that a Surveillance was not performt within its specified Frequency, then compliance with the requirement to d :lare the LCO not met may be delayed, from the time of discovery, up to 24

  • surs or up to the limit of the specified Frequency, whichever is less. This dela/ period is permitted to allow performance of the Surveillance.

If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition (s) must be entered.

When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immediately be declared not met, and the applicable Condition (s) must be entered.

INSERT 9 f.lb Entry into a MODE or other specified condition in the Applicability of an LCO' shall not be made unless the LCO's Surveillance have been met within their

]

specified Frequency. This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS.

I INSERT 10 SR 3.0.5 Surveillance Requirements shall apply to each unit individually unless otherwise indicated as stated in LCO 3.0.8 for individual l

Specifications or whenever certain portions of a Specification l

contain surveillance parameters clifferent for each unit, which will be identified in parentheses or footnotes.

L Catawba 1 7/g a____-____________

Discussien of Ching2s S;cticn 3.0 - LC0 cnd SR Applicability ADMINISTRATIVE CHANGES A.11 The technical content of CTS 4.0.5 has been moved to ITS Specification 5.5.8, " Inservice Testing Program". Any technical changes to this requirement are addressed in the Discussion of Changes for Section 5.5.

The movement of these requirements within the TS is considered administrative.

This change is consistent with NUREG-1431.

A.12 The CTS for each unit is currently contained within separate

~ volumes.

The ITS combines both Units 1 and 2 into a single volume, consistent with the CTS prior to Amendments 148 and 142.

ITS LCO 3.0.8 and SR 3.0.5 are added to clearly state that each individual specification and surveillance requirement applies to each unit independently, unless otherwise specifically stated.

In those instances, the specification or surveillance denotes limits for each unit individually, or the specification is identified as only being applicable to a particular unit.

This is consistent with CTS 3.0.5 and 4.0.6 which existed prior to the above amendments.

This change is administrative since it only restates the requirements which already exist when each unit is provided in

. separate volumes and maintains all of the technical requirements.

I i

i l

l i

i l

l 1

t i

C$tawbaUnits1and2 Page A - 5 Supplement 65/20/97l

i LCO Applicability 3.0 3.0 LCO APPLICABILITY (continued)

LCO 3.0.6 When a supported system LCO is not met solely due to a support system LC0 not being met, the Conditions and Required Actions associated with this supported system are not required to be entered. Only the support system LCO ACTIONS are required to be entered. This is an exception to LCO 3.0.2 for the supported system. In this event, additional evaluations and 1 titations may be required in accordance with Specification 5.5.15. " Safety function Detensination Program (SFDP)."

If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

When a s rtsbtem'sRequiredActiondirectsasupported system to dec red inoperable or directs entry into Conditions and Required Actions for a supported system, the l

applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.

Cv.te W_

m LC0 3.0.7 Test Exception LCOs(TT.i.3.41.m w i in and 3.4.qZP allow specified Technical Specification (TS) requirements to W

be changed to permit performance of special tests and operations. Unless otherwise s requirements remain unchanged. pecified, all other TS Compliance with Test Exception LCOs is optional. When a Test Exception LCO is 1

desired to be met but is not met, the ACTIONS of the Test Exception LC0 shall be met. When a Test Exception LC01s i

not desired to be met, entry into a MODE or.other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.

t (continued) 3.0-3 Rev 1. 04/07/95 w~

l l

l

[

INSERT 1 LCO 3.0.8 LCOs including the associated ACTIONS shallapply to each unit individually unless otherwise indicated as follows:

a.

Whenever the LCO refers to systems or components which are shared by both units, the ACTIONS will apply to both units simultaneously; b.

Whenever the LCO applies to only one unit, this willbe identifiedin the Applicability section of the Specification; and c.

Whenever certain portions of a Specification contain operating parameters, setpoints etc., which are different for each unit, this willbe identifiedin parentheses or footnotes.

(For example, *,.. flow rate of 54,000 cfm (Unit 1) or 43,000 cfm (Unit 2)...').

l I

1 INSERTPage 3.0-3 Catawi>a l

L_-.__--___________________----.

SR Applicability 3.0 3.0 SR APPLICABILITY I

SR 3.0.3 declared not met, and the applicable Condition (s) must be (continued) entered.

l SR 3.0.4 Entry into a N00E or other specified condition in the Applicability of an LCO shall not be made unless the LCO's Surveillance have been met within their specified Frequency. This provision shall not prevent entry into MODES or other specified conditions in the Anlicability that are required to comply with ACTIONS 6r71at"are'part o) a(sii[ItdovorAne un1D SR 3.0.41s ly applicable for e ry into a MODE o otner specified ition in the Appl ability in MODES. 2. 3 and 4.

~

i Revi

's Note: SR 3.0.4 s been revised that changes

~

in S or other specifi conditions in t Applicability

{

tha are part of a shut of the unit sh not be

/

pr vented. In additio. SR 3.0.4 has bee revised so that is only applicabl for entry into a or other specified condition n the Applicabili-in MODES 1. 2. 3.

and 4.

The MODE ante restrictions SR 3.0.4 were

/

previously a li oble in all MODES.

fore this version f SR 3.0.4 can implemented on a p nt. specific basis.

licensee sus review the existing echnical specifica' ons to deterai where spcific rest ictions on MODE cha es or Required ions should be inc in individual Os to

, justify is change: such an aluation should be ummarized in a rix of all existing s to facilitate staff revi of a c0:1 version to STS.

t-i i

l M

3.0 5 Rev 1. 04/07/95 CdA l

\\

INSERT 2 SR 3.0.5.

Surveillance Requirements shall apply to each unit individually.

unless otherwise indicated as stated in LCO 3.0.8 for individual Specifications or whenever certain portions of a Specification contain surveillance parameters different for each unit, which will be identified in parentheses or footnotes.

l INSERTPage 3.0-5 I

l Catawba l

l l

l i

LCO Applicability l

B 3.0 1

B 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY E

1

  1. 8 LCOs LCO 3.0.1 through LCO 3.0.

t ish the general 5

requirements applicable to all Specifications and apply at all times, unless otherwise stated.

LCO 3.0.1 LCO 3.0.1 establishes the Applicability statement within I

l each individual Specification as the requirement for when I

the LCO is required to be met (i.e.. when the unit is in the MODES or other specified conditions of the Applicability statement of each Specification).

LCO 3.0.2 LCO 3.0.2 estabibhes that upon discovery of a failure to l

meet an LCO. the associated ACTIONS shall be met. The i

Completion Time of each Required Action for an ACTIONS Condition is applicable from the point in time that an ACTIONS Condition is entered. The Required Actions establish those remedial measures that must be taken within 1

specified Completion Times when the requirements of an LCO d

are not met. This Specification establishes that:

a.

Completion of the Required Actions within the specified Completion Times constitutes compliance with a Specification: and b.

Completion of the Required Actions is not requked when an LCO is met within the specified Completion Tima, unless otherwise specified.

There are two basic types of Required Actions. The first type of Required Action specifies a time limit in which the LC0 must be met. This time limit is the Completion Time to restore an inoperable system or component to OPERABLE status or to restore variables to within specified limits. If this type of Required Action is not completed within the specified Completion Tire, a shutdown may be required to place the unit in a MODE or condition in which the Specification is not applicable. (Whether stated as a Required Action or not, correction of the entered Condition is an action that may always be considered upon entering (continued)

CafnA WOB'STS B 3.0 1 Rev 1. 04/07/95

1 i

LCO Applicability 1

B 3.0 1

BASES LCO 3.0.6 system are OPERABLE, thereby ensuring safety function is (continued) retained. If this evaluation determines that a loss of safety function exists, the appropriate Conditions and Required Actions of the LCO in which the loss of sefety function exists are required to be entered.

LCO 3.0.7 There are certain special tests and operations required to be performed at various times over the life of the unit.

These special tests and operations are necessary to demonstrate select unit performance characteristics, to perfors special maintenance activities, and_ to perform s

- al evolution Test Exception LCOs(13.1.5: 3.1(10M L and 3.4 allow specified Technical

@--5pecmcanon (I requirements to be changed to permit i

performances of these special tests and operations, which otherwise could not be performed if required to comply with

)

the requirements of these TS. Unless otherwise specified.

{

l all the other TS requirements remain unchanged..This will ensure all appropriate requirements of the MODE or other j

specified condition not directly associated with or required j

i to be changed to perform the special test or operation will remain in effect.

The Applicability of a Test Exception LCO represents a condition not necessarily in compliance with the normal requirements of the TS. Compliance with Test Exception LCOs is optional. A special operation may be performed either under the provisions of the appropriate Test Exception LCO or under thB other applicable a requirements. If it is desired to perform the special operation under the provisions of the Test Exception LCO, the requirements of the Test Exception LCO shall be followed.

I M

B 3.0-9 Rev 1 04/07/95 CdM i

(

INSERT i

I

)

LCO 3.0.8 LCO 3.0.8 delineates the applicability of each specification to Unit 1 and Unit 2 operation.

i 1

i

'l 1

i l

.1 l

i 1

j l

j Insert Page B 3.0-9 i

I i

Catawba l

SR Applicability B 3.0 8 3.0 SURVE'LLANCE REQUIREMENT (SR) APPLICABILITY BASES SRs SR 3.0.1 through SR 3.0 e tablish the general requirements applicable to all Specifications and apply at all times.

i

.],.

unless otherwise stated.

SR 3.0.1 SR 53.1 establishes the requirement that SRs must be met during the H00ES or other specified conditions in the Applicability for which the requirements of the LCO apply, unless otherwise specified in the individual SRs. This Specification is to ensure that Surveillance are performed to ver!fy the OPERABILITY of systems and components, and that variables are within specified limits. Failure to meet a Surveillance within the specified Frequency, in accordance with SR 3.0.2, constitutes a failure to meet an LCO.

Systess and components are assumed to be OPERABLE when the associated SRs neve been met. Nothing in this Specification. however, is to be construed as implying that systen or components are OPERABLE when:

The systems or components are known to be inoperable, a,

although still meeting the SRs: or b.

The requirements of the Surveillance (s) are known not to be met between required Surveillance performances.

Surveillance do not have to be performed when the unit is in a H0DE cr other specified condition for which the requirements of the associated LCO are not applicable, unless otherwise specified. The SRs associated with a test exception are only applicable when the test exception is O'7 used as an illowable exception to the requirements of a Specification.

gitOCRT't)

Surveillance, including Surveillance invoked by Required

{'.

Actions, do not have to be performed on inoperable equipment because the /CTIONS define the remedial measures that epply.

F /;, 4 '

Surveillance have to be net and performed in accordance with SR 3.0.2. prior to returning equipment to OPERABLE

status, f

(continued)

S B 3.0 10 Rev 1. 04/07/95 cw s

1 SR Applicability B 3.0 BASES SR 3.0.4 condition, or time has been reached. Further discussion of (continued) the specific formats of SRs* annotation is found in Section 1.4. Frequency.

ISR 3.0.4 s only applicab when enteri NOCE 4 from MODE S 3 from

. Mode 2 fr

3. or H00E t

f 2.

Furthe

e. SR 3.0.4 1 applicable when ring any other s ified conditi in the Anolicab ity ly while operati in MODES 1, 2. J. or 4. g 5

requirements of 3.0.4 do not a ly in NODES 5 an 6. or in other specif1 conditions of Applicability unless in H0 DES 1. 2. J. or 4) becau the ACTIONS of i tvidual S%pecificati sufficiently ine the remedial asures t mn 1

i i

M B 3.0 15 Rev 1. 04/07/95 aw i

\\____----_________--

INSERT SR 3.0.5 SR 3.0.5 delineates the applicability of the surveillance activities to Unit 1 and Unit 2 operations.

,1 1

i i

1 l

Insert Page B 3.0-15 catanta l

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _ _ _ _ _ _ _ -