TEST NUMBER
+
- g27, Independent i Textile Tot <a5 Service,Inc.
P.O. Box 1948 /1503 Murray Avenue Dalton, Georgia 30722-1948 / Phone 404-278-3013 REPORT CUSTOMER:
BOSTON EDISON MARCH 4, 1987 i
SUBJECT:
Specimens of the submitted samples were prepared and tested in accordance with ASTM E-648 and/or Federal Test Method 372. NFPA 253 FLOORING RADIANT PANEL TESI Sample Description Style:
PATTERN:
L8203 Color:
363 Roll No.:
DYE LOT H 18261 Fiber:
Pile:
Secondary Backing:
Test Assembly (SAME AS TEST
- 8274)
Test Results Specimen No.1 Specimen No. 2 Specimen No.3 Critical Radiant Flux:
,81 watts /cm2 1.01 watts /cm2 1,00 watts /cm2 Total Burn Length:
24.0 cm.
11.0 cm.
12.0 cm.
Flame Front Out:
31.0 minutes 23.0 minutes 28.0 minutes Average Critical Radiant Flux:
,94 watts /cm2 gg Estimated Standard Deviation
,JJ watts /cm2 gn-I2%
coefficient of variation go NOTE: SOME SEPARATION OF PRIMARY BACKING FROM SECONDARY OCCURED DURING TESTING DUE 1
to o TO MELTING OF PRECCAT LAMINATE.
l l
0:s:
I c30 b
y Authorized Signa e pg INDEPENDENT TEXTl TESTIN SERVICE, INC.
mgn ct our letters and reports are for the exclusive use of the customer to whom they are addressed. and their communication to any others or the use of the
. name of independent T entae Teating service. inc.. must receive our pnor wntten approvat our letters and reports apply onsy to the sarr.pte tested and are not necessaray indicative of the quakties of apparently identical or similar products The reports and letters and the name of the independer,t j
Textde Testing Service. Inc., are not to be used under any circumstances in advertising to the general public j.400 l