_i-4 TEST NUMBER Independent g Textile 8273 Tot *5 Service, lac, P.O. Box 1948 /1503 Murray Avenue Dalton, Georgia 30722-1948 / Phone 404-278-3013 CUSTOMER:
BOSTON EPISON MARCH 4, 1987
SUBJECT:
Specimens of the submitted samples were prepared and tested in accordance with the procedures proposed by the National Bureau of Standards, Technical Note 708 and NFPA 258, ASTM E-662.
SMOKE DENSITY TEST (NBS)
Operating Conditions Irradiance:
2.5 watts /cm' G Factor 132 Thermal Exposure:
FLAMING Furnace Voltage:
97 Burner Fuel:
PROPANE Sample Description Style:
PATTERN:
L8203 Color:
354 Roll No.:
DYE LOT e 17472 Fiber:
Pile:
Secondary Backing:
Test Results
- 1
- 2
- 3 Avg.
l Chamber Temperature,dF. (start) 95 95 95 Chamber Pressure Maintained positive, under 3" H2O Min. Transmittance (TM), %
96%
10%
73%
i et, minutes 9.70 8.15 5.95 7.93
]
Max. Spec. Opt. Density (DM) 398 528 387 436 Clear Beam, (DC) 47 41 51 46 DM, CORRECTED (DMC) 3bI 4S7 330 389 Spec. Opt Density at 1.5 min.
9 7
6 7
ha: Spec. Opt. Density at 4.0 min.
304 264 245 271
)
N Time to 00% DM. minutes 9.20 6.85 4.90 6.98 Time DS= 6
'rrit s 1.70 1.90 2.05 1.88 U
Ml rm nm At af AE;horized Sign'ature~
I
<r O C0 1
o<
INDEPENDENT TEX 1tLE ESTiNG SERVICE y
Cur letters and reports are fer the exclusive u.e of the customer to whom they are addressed,an tn, n.,no et iedeneneent 1e t,ie resting se,,,ce. inc..,nusi,eceive ou,,,,o,.,,tten.,,,ov., d thelf Communicat6on to any others or the une of ou,,etters.nd,eco,ts.,,,, on,y to ine s.,noie om gg totled and are not necessarily endicative of the quaintees of apparently identical or similar products The reports and letters and the name of the g o,,
inoeper,Jent Textae Testing Service. Inc., are not to be used under any circumstances in advert,smg to the general public.
1
-z_
t Independent 4 Textile 7sida$
Sernce,Inc.
TEST NUMBER 8273 CUSTOMER:
BOSTON EPISON MARCH 4, 1987
SUBJECT:
Specimens of the submitted samples were prepared and testedin accordance with the procedures proposed by the National Buieau of Standards, Technical Note 708 and NFPA 258, ASTM E-662.
SMOKE DENSITY TEST (NBS)
Operating Conditions Radiometer Reading:
7.7 mv; Irradiance:
2.5 watts /cm2 G Factor:
132 Thermal Exposure:
NON-FLAMING Furnace Voltage:
97 Burner Fuel:
Sample Description Style:
PATTERN:
L8203 Color:
354 Roll No.:
DYE LOT 1 17472 Fiber:
Pile:
Test Results al
- 2
- 3 Avg.
I Chamber Temperature, F. (start) 95 95 95 j
Chamber Pressure Maintained positive, under 3" H.O j
Min. Transmittance (TM), %
77%
13%
35%
at, minutes 18.40 78.70 20.00 19.03 Max. Spec. Opt. Density (DM) 259 249 192 233 Clear Beam,(DC) 9 17 20 15 DM, CORRECTED (DMC) 250 232 172 218 Spec. Opt. Density at 1.5 min.
2 2
1 2
Spec. Opt. Density at 4.0 min.
73 13 9
12 Time to 90% DM, minutes 74.25 13.85 76.25 14.78 Time DS = 1 ' ininiutes 4.40 4.30 4.70 4.47
[
b, M
/Y[