Flooring Radiant Panel Test
ML20236M111
Person / Time
Site: Pilgrim
Issue date: 03/04/1987
From:
INDEPENDENT TEXTILE TESTING SERVICE, INC.
To:
Shared Package
ML20236M030 List:
References
8275, NUDOCS 8708100473
Download: ML20236M111 (1)


Text

--

TEST NUMBER 8275

~

Independent / Textile Totta$

Service. loc.

j l

P.O. Box 1948 /1503 Murray Avenue Dalton, Georgia 30722-1948 / Phone 404-278-3013 REPORT CUSTOMER:

BOSTON EDISON MARCH 4, 1987

SUBJECT:

Specimens of the submitted samples were prepared and tested in accordance with ASTM E-648 and/or Federal Test Method 372. NFPA 253 FLOORING RADIANT PANEL TEST Sample Description Style:

L8203 Color:

354 Roll No.:

pyE LOT # 17472 Fiber:

Pile:

Secondary Backing:

Test Assembly BURLINGTON PRESSURE SENSITIVE ADHESIVE WAS USED TO ADHEPETHE CARPET, DESCRIBED ABOVE, DIRECTLY TO ALUMINUM PLATES, WHICH WERE SUPPLIED BY THE CUSTOMER.

Test Results Specimen No.1 Specimen No. 2 Specimen No.3 Critical Radiant Flux:

.46 watts /cm2

,39 watts /cm2

.5; watts /cm2 Total Burn Length:

43.0 cm.

79,o cm.

40.0 cm.

Flame Front Out:

20.0 minutes 21.0 minutes 40.0 minutes 1

Average Critical Radiant Flux:

.62 watts /cm2 i

l Estimated Standard Deviation

.24 watts /cm2 l

n coefficient of variation y

39g ruga.

i yo NOTE: SOME SEPARATION OF PRIMARY BACKING FROM SECONDARY OCCURED DURING TESTING y

DUETpMELTINGOFPRECOATLAMINATE.

l 05

$U' k/h W Authorized Signh ure 5

INDEPENDENT TEXT E TESTIN SERVICE, INC.

O T.

our letters and reports are for the exclusive use of the customer to whom they are addressed and their communication to any others or the use of the bQ name of Independent Textile T esting service,Inc.. must receive our prior written approval Our letters and reports apply only to the sample tested and 000-are not necessarily indicative of the qualities of apcarently identical or semitar products The reports and letters and the name of the independent l

Textile Testing Service. Inc. are twt to be used under any circumstances in advertising to the general public 1-400 l

.____________A