TEST NUMBER
_g-8279 Independent / Textile (4a5 Service,lnc.
P.O. Box 1948 /1503 Murray Avenue Dalton, Georgia 30722-1948 / Phone 404-278-3013 REPORT CUSTOMER:
BOSTON EDISON MARCH 4, 1987
)
SUBJECT:
Specimens of the submitted samples were prepared and tested in accordance with l
ASTM E-648 and/or Federal Test Method 372, NFPA 253 i
FLOORING RADIANT PANEL TEST Sample Description Style:
PATTERN:
L8203 Color:
354 Roll No.:
DYE LOT e 17472 Fiber:
Pile:
Secondary Backing:
Test Assembly Burlington's pressure sensitive adhesive was used to give the carpet, described above, directly to 1/4 inch asbestos / cement board for testing.
Test Results Specimen No.1 Specimen No. 2 Specimen No.3 Critical Radiant Flux:
.79 watts /cm2
.86 watts /cm2
.84 watts /cm2 Total Burn Length:
25.0 cm.
21.0 cm.
22.0 cm.
Flame Front Out:
24.0 minutes 18.0 minutes 22.0 minutes Average Critical Radiant Flux:
,g3 watts /cm2 Estimated Standard Deviation
.04 watts /cm2 n
5%
coefficient of variation N00 Some separation of primary backing from secondary occured during testing due to ge w
melt.ing of precoat Laminate CD O i}h OQ 04 Authorized Signa u 'e INDEPENDENT TEXTIL ' TESTI SERVICE, INC.
OCc our letters and reports are for the exclusive use of the customer to wnom they are addressed. and ineir communication to any others of the use of the I' Q name of Independent Textile Testing service. Inc., must receive our prior wotten approval our let'ers and reports appiy only to the sample tested and (D O.o-are not necessarily indicative of the quahties of apparently identical or simiiar products The reports and lettera and the name of the indep indent Textde Testing service. inc, are not to be used under any circumstances in as<ertising to the general public 1 400