Forwards Info Re Relief Valve Setpoint Drift Reported in LER 83-74.Info Concluded That Crosby Relief Valves Have Lift Settings Affected by Adjustments of Nozzle Ring.W/O Encl
ML20210T983
Person / Time
Site: Palisades 
Issue date: 03/01/1984
From: Jorgensen B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Paulson W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20210T938 List:
References
FOIA-86-266 NUDOCS 8606020144
Download: ML20210T983 (1)


Text

, -

'r.

lit!Ci L

-i t

i 5

_.t, y

7 ste.....

(.

i llarch 1, 1984 r

Memorandum For:

Walt Paulsen, NRR Project Manager - Palisades r

From:

B. L. Jorgetesen, Senior Resident Inspector - Palisades l

SUB.IECT:

MAIN $TTE1 SA) ETY VALVE SETPOINT DRIF'T (CROSBY RV'S) i t

I i

Attached is a clean copy of informat ion faxed earlier covering the relief valve setpoint drift reported per LER 83 '!4 (Attachment 1).

Also attached j

is additional information (Attachment 2) which I think points very strongly

}

to the conclusion these Crosby relief valves can have their lif t settings I

affected by adjustments of the nozzle ring (to control leakage or adjust blowdown i

rate, for example).

l

[

-The symetry of the 1981 and 1983 "as founds" about the intended serpoint shown i

on the figure is particularly striking. The 1981 "as founds" were actually I

taken afte'r nozzle ring adjustment to limit blowdown rate to a value com-patible with the capacity of the test rig then in use.

Spring tension was increased in 1981 to establish correct "as left" valves which were then forced out-of-spec on the high side by nozzle ring readjustment to the pre-test position.

This yielded the high 1983 "as founds", taken without prior l

nozzle ring adjustment because test rig capacity was increased in the interim.

l Note also Attachment 2 purports to find the valves are capable of performing i

their design function.

The more important question may be were they so i

capable through the 1981-1983 operating cycle, when seven valves would f

apparently still not have lifted at 1050 psig? The Tech. Spec. limit is about 1035 psig.

{

l i

i B. L. Jorgensen

)

Senior Resident Inspector j

i I

Attachments j

4 B606020144 060516 ppR FOIA..

Pp MURPHYS6-266 4,1vt.