Requests Review of Comanche Peak Response Team Plan,For Resolution of Concerns in NUREG-0797,Suppl 11,App P. Lead Engineer Should Be Assigned to Task by 851223
ML20210D123
Person / Time
Site: Comanche Peak  
Issue date: 12/16/1985
From: Shao L
NRC - COMANCHE PEAK PROJECT (TECHNICAL REVIEW TEAM)
To: Landers D
TELEDYNE ENGINEERING SERVICES
Shared Package
ML20209E570 List:
References
FOIA-86-657, RTR-NUREG-0797, RTR-NUREG-797 NUDOCS 8702100021
Download: ML20210D123 (24)


Text

..

./

UNITE 3 STATES p***%g'g NUCLEAR REGULATORY COMMISSION g*

s-y WASHINGTON. D.C. 20505

?

j DEL i6 h4 NOTE T0:

D. Landers, TES FROM:

L. Shao, Group Leader, C/P

SUBJECT:

RESOLUTION OF APPENDIX P ISSUES IN NUREG-0797 SUPPLEMENT NO.11 As you are aware Texas Utilities Electric Company (TVEC), in their Comanche.

I Peak Response Team (CPRT) Program Plan, has comitted to addressing and resolving the generic concerns expressed by the NRC Technical Review Team (TRT) as presented in NUREG-0797 Supplement No. 11 Appendix P.

We have recently learned that TUEC is.in the process of resolving issues identified in Appendix P.

1 I would like Teledyne Engineering Services (TES) to follow TUEC's implementa-tion of the CPRT Plan with particular attention to the applicant's method of resolution of the concerns.in Appendix P (40 concerns in Mechanical / Piping and 34 concerns in Civil / Structural). Your contacts at the NRC CP Project will be S. Nien Hou for M/P and D. Jeng for C/S. The purpose of your review is to i

assure that TUEC is responding properly to the concerns expressed in Appendix i

P, and has detemined the root cause and and address the generic implications-of each concern. Teledyne should assign a lead engineer to this task and l

identify this individual to me by December 23, 1985.

L L. Shao, Group Leader l

Comanche Peak Project L

cc:

V. Noona C. Tramel A. Vietti-Cook S. Hou D. Jeng R. Piasterson Foz n - u M 7 8702100021 870129 PDR FOIA GARDE 86-657 PDR

r t'

Acsudcw Pssx 4N/' pGC 6.Jerrwer/o.J kes/cs7?od.<C<so/er

&cvss<

co,<.)arsecr/o.d 6 ss<asnoJ

.~'a <

/3r e.oa.co os.~

{ @ -c/rsea, w s. esso assasw, QN ' :.d m aoos a#. m

.a.# A #vA em ceas w4.h nAu c.y.mt) 6/sser

@ - jf.o.o< n o s %e e.4.Joem a,.9x a r / a m

~

/onur-oa 7mr es.r c.aaers w e,y J/cd///cAdcd.

Cf - Affc,%Q/4 J.*9ff -

s3/ WF & ced SifFLl% -

l A I l'l.5 L l)

~: illis l'u G 7

c30 -Lao-<

F,--n~,

s,---,

e sarasnos. (.Aeoor s.

as-r o.c v a a a,. m n s u$//fdsf/.1"'A./f G^,,T r -- u.W h ~

ALoA:/ Add"

  1. fA?/f/c4rsod ds.AdJ*e/c 7~

o, w -aoa-<asar /anarsss.

C D - f e c /.o.d e

/D ars a n o D,a s s.u r<

69 cbsca Assw Gm /asssar<o.J

.cssacra.

(5) ~ // S S OYod/4 / Jh.tl A26*av/sre

@ /bGR i ud Cah'e k:y /cc-&:J h, y. ;t, t

3 ic o)

A z L

<= c L p y n g r p;..

upy>J punn-cA7 8/6

s-T1( U W

/O-3-Vs MTG-(f OW OBJECTIVE OF ISAP VII.C COLLECT INFORMATION ON THE ADEQUACY OF CONSTRUCTION WORK ACTIVITIES USING STATISTICAL SAMPLING TECHNIQUES.

t 0

B/1,

a 4,

A

+

A.

u W=

a d.

g

.(

METHODOLOGY CATEGORIZE INSTALLED SAFETY RELATED HARDWARE INTO POPULATIONS MADE UP 0F HOMOGENE0US WORK ACTIVITIES FROM WHICH STATISTICAL SAMPLES CAN BE DRAWN FOR EVALUATION.

4 I

I l

ORGANIZATION BASED ON PREVIOUS PROGRAM EXPERIENCE - ENGINEERING GROUP ORGANIZED INTO THREE DISCIPLINES WHICH ARE STAFFED WITH-ENGINEERS EXPERIENCED IN ALL ASPECTS OF CONSTRUCTION /

INSTALLATION ACTIVITIES CIVIL / STRUCTURAL ELECTRICAL MECHANICAL I

9

.l l

[

---r

. - -. _.. - _... _, -.. ~ _ -,.. -,,,. - -. _ -

-?

CIVIL / STRUCTURAL CONCRETE PLACEMENT STRUCTURAL STEEL INSTALLATION i

HANGER AND SUPPORT INSTALLATIONS LINER INSTALLATIONS FILL & BACKFILL PLACEMENT 4

8 e

I l

l l

I e,',

ELECTRICAL t

/

CONDUIT AND CABLE TRAY INSTALLATION CABLE INSTALLATION ELECTRICAL EQUIPMENT INSTALLATION INSTRUMENTATION EQUIPMENT INSTALLATION e

D 1

5 9

e l

i

9 MECHANICAL

\\

PIPING'lNSTALLATION HVAC INSTALLATION MECHANICAL EQUIPMENT INSTALLATION FIELD FABRICATED TANK INSTALLATION t

4 0

e J

i I

l l

l

CIVIL / STRUCTURAL ELECTRICAL MECHANICAL CONCRETE PLACEMENT CONDUIT AND CABLE TRAY PIPING INSTALLATION INSTALLATION STRUCTURAL STEEL INSTALLATION CABLE INSTALLATION HVAC INSTALLATION i

HANGER AND SUPPORT ELECTRICAL EQUIPMENT MECHANICAL EQUIPMENT INSTALLATION INSTALLATION INSTALLATION LINER INSTALLATIONS INSTRUMENT EQUIPMENT FIELD FABRICATED INSTALLATION TANK INSTALLATION FILL & BACKFILL PLACEMENT l

DISCIPLINES CONDUCT EVALUATION FOR ASSIGNED INSTALLATION ACTIVITIES AND IDENTIFY 0

WORK PROCESSES O

DRAWINGS, SPECIFICATIONS, CODES, STANDARDS 0

ATTRIBUTES & ACCEPT / REJECT i

CRITERIA 0

ORGANIZATIONS / CRAFTS /

INSPECTION GROUPS l

CIVIL / STRUCTURAL ELECTRICAL MECHANICAL POPULATIONS POPULATIONS POPULATIONS i

r -.

9 O

POPULATION WORK WORK PROCESS PROCESS

- ATTRIBUTE

- ATTRIBUTE

- ATTRIBUTE

- ATTRIBUTE

- ATTRIBUTE

- ATTRIBUTE P

.l I

i

~.. -.

A 4

t 4

-I DURING ESTABLISHMENT OF POPULATION-THE FOLLOWING TESTS ARE APPLIED 1.

WORK PROCESSES ARE THE SAME 2.

SIMILARITY OF EACH WORK PROCESS O

ATTRIBUTES AND ACCEPTANCE CRITERIA 0

CODES AND STANDARDS 0

ORGANIZATION O

CRAFTS E

dla h ' I ' '

g,3, g s O

INSPECTION GROUPS a+ t /

~r l

_ _ - _ _ _ _,. _.. _ _ _ _ _ _ -. -. ~.. _ _ _ _ _ _,.. - - _. _ _, - _..

k f; !

ELECTRICAL POPULATIONS rELECTRICAll rC BLE CABLES ICONbuYT1 IiNSTRUMENTATION I

EQ 8

L._UIPMENT

_ TRAY

'_ _ _.J EQUIPMENT

_ __. a l

L-J ACTIVITIES / ATTRIBUTES WORK PROCESS PREPULL PULL TERMINATE ATTRIBUTES

- SIZE

- LUBRICANT *

- IDENTIFICATION

- TYPE

- ROUTING

- TESTING **

- COLOR

- BEND RADIUS **

- INSULATION"

- DEFECTS *

- SPACING

- CONDUCTORS **

RACEWAY *

- SLACK

- TERMINALS **

- PULL TENSION *

- HARDWARE **

- SEPARATION

- LANDINGS DAMAGE **

- HEAT SHRINK **

REPAIR **

- SECURE DOCUMENTATION REVIEW ONLY REINSPECTION AND DOCUMENTATION REVIEW

PAGE 1 0F 3,

BASIS FOR SIMILARITY OF WORK ACTIVITIES POPULATION: CABLES J

WORK' ACTIVITIES COMMON TO ALL CABLES PRE-PULL PULLING I

TERMINATION ATTRIBUTES AND ACCEPTANCE CRITERIA COMMON TO ALL CABLES DERIVED FROM COMMON SPECIFICATION, DRAWINGS AND PROCEDURES

  • ONE PULLING PROCEDURE FOR ALL CABLES
  • BROWN a ROOT PROCEDURE EEI-7, CABLE PULLING
  • ONE TERMINATIONS PROCEDURE FOR ALL CABLES
  • BROWN & ROOT PROCEDURE EEI-8, CLASS 1E AND NON CLASS 1E CABLE TERMINATIONS
  • ExCEPT LIGHTING AND NIS CABLES BROWN & ROOT PROCEDURE eel-4 CABLE PULLING AND TERMINATION OF LIGHTING WIPE BROWN & ROOT PROCEDURE EEI-18 FIELD INSTALLATION OF NIS TRIAXIAL CABLES A CONNECTORS

(

BASIS FOR SIMILARITY OF WORK ACTIVITIES POPULATION:

CABLES (CONT'D)

CODES AND STANDARDS REQUIREMENTS OF APPLICABLE CODE AND STANDARDS INCORPORATED INTO ELECTRICAL ERECTION SPECIFICATION GIBBS a HILL SPECIFICATION 2323-ES-100 INSTALLATION PROCEDURES DERIVED FROM ERECTION SPECIFICATION ORGANIZATION BROWN 8 ROOT CONSTRUCTION MANAGEMENT TEAM SUPERVISED ALL CABLE PULLING AND TERMIFATION ACTIVITIES.

a f

i f

r 2

L

BASIS FOR SIMILARITY OF WORK ACTIVITIES f

POPULATION:

CABLES (CONT'D)

CRAFTS BROWN & ROOT EMPLOYED AND TRAINED ELECTRICIANS PERFORMED ALL CABLE PULLING AND TERMINATING 1

ACTIVITIES.

THE SAME CREW PULL ALL CABLES AND THE SAME CREWS TERMINATE ALL CABLES.

INSPECTION TUGC0 INSPECTION PROCEDURE QI-QP-11.3-26 IS USED TO INSPECT ALL CABLE PULLING ACTIVITIES

  • TUGC0 INSPECTION PROCEDURE QI-0P-11.3-28 IS USED TO INSPECT ALL CABLE TERMINATING ACTIVITIES
  • TUGC0 INSPECTORS CERTIFIED TO THESE PROCEDURES HAVE INSPECTED ALL CABLES.

EXCEPT LIGHTING & NIS CABLES TUGC0 INSPECTION PROCEDURE 01-0P-11.3-25, LIGHTING INSPECTION TUGC0 INSPECTION PROCEDURE QI-0P-11.3-43,NIS CABLES 2

EtttiRICAL

-IELECTRiCALI ICABLEl CONDUIT 9NSTRUMENTATION'l

~

F ~BLE1 CA 1' EQUIPMENT e

i i

l l

i I

L g

u_a y

EQUIPMENT _ 2, TRAY _j g

WORK PROCESS SELECTION PREPARATION INSTALLATION ATTRIBUTE

- SIZE / MATERIAL

- CONDUIT /

- IDENTIFICATION FABRICATION (1)

- ORIGIN /

- CUTTING DESTINATION

- DE-BURRING

- FITTINGS

- REPAIR

- BENDS (2)

PULL POINTS (2)

FLEXIBLE CONDUIT

- INTEPFACE (TRAY)

CLEARANCE l

FIRE STOPS i

AND SEALS SEPARATION l

(1)

DOCUMENT REVIEW l

(2)

THIS ATTRIBUTE WAS ORIGINALLY CONSIDERED FOR THE CHECKLIST BUT SUBSEQUENTLY EXCLUDED FOR ALL CONDUIT EXCEPT NUCLEAR INSTRUMENTATION SYSTEM (N.I.S) CONDUIT BECAUSE OF NOT BEING SAFETY SIGNIFICANT.

l l

4 CONDUIT WORK PROCESS PROCEDURE APPLICATION INSTALLING INSPECTION ORGANIZATION GROUPS SELECTION BROWN & ROOT RIGID & FLEX BROWN & ROOT BROWN & ROOT y

PROCEDURES EXPOSED

' 'l '

CONDUIT INSTALLATION ECP -19 & 19A J

~

1 PREPARATION BROWN & ROOT RIGID & FLEX BPOWN & ROOT BROWN & ROOT-PROCEDURE EXPOSED

  1. ~

~

CONDUIT INSTALLATION ECP -19 & 19A 1

INSTALLATION BROWN & ROOT RIGID & FLEX BROWN & ROOT "acha s R0oT-PROCEDURE EXPOSED

~IU C CONDUIT INSTALLATION ECP -19 & 19A BROWN & ROOT RIGID & FLEX BROWN & ROOT BRUWN t~ ROUT y

PROCEDURE 7 '5 3 '-

l FIELD INSTALLATION OF FIRE BARRIER l

MATERIAL eel-25 i

~

i l

1

CONCRETE PLACEMENTS PREPLACEMENT PLACEMENT POSTPLACEMENT DESIGN MIX

' PLACEMENT PROCEDURES SURFACE. INSPECTION FORMS

  • VIBRATORS USE CORED HOLES l

LOCATION

  • CONCRETE TEMPERATURE CRACKS SIZE RECORDS PATCHES i

REBARS

  • CURING RECORDS CADWELDS
  • COMPRESSIVE STRENGTH EMBEDMENTS TEST RESULTS ANCHOR BOLTS WATER STOPS CONSTRUCTION JOINTS I

l DOCUMENTATION REVIEW ONLY l

DOCUMENTATION REVIEW AND REINSPECTION l

e G

.~

.o BASIS FOR SIMILARITY OF CONCRETE PLACEENTS ACTIVITIES GIBBS & HILL'S " CONCRETE" SPECIFICATION IS THE BASIC DOClNENT FOR CONCRETE PLACEMENTS AND IT IMPACTS ALL POURS.

ALL CONCRETE PLACEEnr PERFORED BY BROWN & ROOT CONCRETE PREPLACEENT PROCEDURES AND INSPECTION CHECKLIST, Com0N TO ALL POURS.

PLACEE NT AND POSTPLACEMENT PROCEDURES AND CHECKLIST, COMMON TO ALL P00RS.

REQUIREMENTS FOR TESTING OF CONCRETE, C0m0N TO ALL POURS.

ALL CONCRETE PLACEMENTS ARE SUBJECT TO ALL APPLICABLE ASTM AND ACI CODES AND STANDARDS.

f 6

.,-,-.y

.. v

ELECTRICAL POPULATIONS I CABLE 7 I '5DUITl INSTRUMENTATION TLECTRICALt rchBL'E '

CO EQUIPMENT

' EQUIPMENT '

'. TRAY L.-

_ J H -- -- 4 L-.

- - -- 4 I-

-.J WORK I

PROCESS TUBING / PIPING INSTRUMENT AND COMPONENT INSTALLATION INSTALLATION ATTRIBUTE

- MATERIAL IDENTIFICATION

- IDENTIFICATION

- TUBING SIZE & MARKING

- LOCATION

- ROUTING

- SEPARATION

- SLOPE

- DAMAGE

\\

- AIR GAP y

.p

- SEPARATION

/,./

2m

'y d

- SYSTEM BENDS

., i s P

- FLEX HOSE INSTALLATION

[,%ln ( C t:

ATTRIBUTES NOT INCLUDED:

FITTING TIGHTNESS - ALL INSTALLATIONS ARE EITHER HYDR 0 STATICALLY OR PNEUMATICALLY TESTED.

INSTRUMENT EQUIPMENT POPULATION THE INSTALLATION WORK PROCESS INVOLVED IS THE SAME FOR ALL INSTRUMENTS, THE FOLLOWING PROCEDURES / SPECIFICATION WERE USED IN THE INSTALLATION BROWN a ROOT CONSTRUCTION PROCEDURE -ICP4 GIssS & HILL'S ELECTRICAL ERECTION SPEC, - 2323-ES-100 GIsas & HILL'S TUBING AND FITTING SPEC. - 2323-MS-625 3

l TUGCO'S PROCEDURE FOR THE INSPECTION - QI-QP-11,8-5 0F I

INSTRUMENT TUBING FABRICATION, INSTALLATION AND INSTPUMENT INSTALLATION.

THE SAME PROCEDURES APPLY TO ALL THE INSTRUMENTATION EQUIPMENT, BROWN A R00T'S INSTRUMENTATION GROUP IS RESPONSIBLE FOR THE SUPERVISION OF INSTALLATION OF INSTRUMENTS, BROWN 8 R00T'S INSTRUMENTATION CRAFTSMEN DID THE INSTALLATION, TUGCO'S INSPECTORS DID THE INSPECTION AND ACCEPTANCE OF THE INSPECTION, I

l i

1

LARGE BORE PIPING CONFIGURATION WORK ACTIVITIES INSTALLATION TYPICAL ATTRIBUTES COMPONENT SEQUENCE LOCATION DIMENSIONS IDENTIFICATION CODES AND STANDARDS ASME.III INSTALLATION RESPONSIBILITY BROWN AND ROOT RESPONSIBLE FOR INSTALLATION INSPECTION RESPONSIBILITY BROWN AND ROOT RESPONSIBLE FOR INSPECTION

a 6

4 9

i N '

  • 9 2

s RE E

l 81R l

t t'

I l

E l

~

a

-W E

5 g

~

l' E

5 36

- i s

.'a!!

s

=I a

8 8

y _1 1

3

.t,1 IV 5

3 i

8 I

I

~

5 E

gI I

l jl B I b

i 3

=

jh n' I t3 k

._ s ag 3

3

=

3 c3

}i i

i i

8 I

3 t

f y

j I

~

-l!

l i

i 1

a e

a 1

3

)a a

i fl=

l 1

.! )

a 1

5 z

~

yy c

r B-3 I

I 1

-lef 1

51 6 c ag .I r J il 55. J/ 35 1 5 5 ! ] I II

MEASUREMENTS AND/OR INSPECTIONS CPSES CPSES REINSPECTION DOCUMENT REVIEW s j 25 POPULATIONS 25 24 POPULATIONS AVERAGE 9.0 AVERAGE 6.8 ATTRIBUTES PER ATTRIBUTES PER POPULATION / POPULATION \\ 225 ATTRIBUTES 163 ATTRIBUTES AVERAGE 4.7 SUB AVERAGE 2.8 SUB ATTRIBUTES PER ATTRIBUTES PER MAIN ATTRIBUTE MAIN ATTRIBUTE 1057 SUB ATTRIBUTES 457 SUB ATTRIBUTES I AVERAGE 89.7 SAMPLES AVERAGE 90 SAMPLES l - PER POPULATION PER POPULATION l 94800 TOTAL SUB ATTRIBUTES ' 41126 TOTAL SUB ATTRIBUTES l (MEASUREMENTS AND/OR INSPECTIONS PER 1.5 INSPECTIONS PER l SUB ATTRIBUTE IS RANSING FROM 1 TO 40 SUB ATTRIBUTE ASSUMING AN AVERAGE OF 5 tu i 61,700 474000 n 7 , ^ ^ 535,700; TOTAL T l INSPECTIONS AND/aR MEASUREMENTS i., I l ,s .}}