LCA 138 Page 1 of 1 REACTOR COOLANT SYSTEM 3.4.10 STRUCTURAL INTEGRITY ASME CODE CLASS 1. 2. and 3 COMPONENTS LIMITING CONDITION FOR OPERATION 3.4.10.1 The structural integrity of ASME Code Class 1, 2 and 3 com-ponents shall be maintained in accordance with Specification 4.4.10.1.
APPLICABILITY: ALL MODES ACTION:
a.
With the structural integrity of any ASME Code Class 1 com-ponent(s) not conforming to the above requirements, restore the structural integrity of the affected component (s) to within its limit or isolate the affected component (s) prior to increasing the Reactor Coolant System temperature more than 50*F above the minimum temperature required by NDT considerations.
[
b.
With the structural integrity of any ASME Code Class 2 com-ponent(s) not conforming to the above requirements, restore the structural integrity of the affected component (s) to within its limit or isolate the affected component (s) prior to increasing the Reactor Coolant System temperature above 200*F.
l c.
With the structural integrity of any ASME Code Class 3 com-ponent(s) not conforming to the above requirements, restore the structural integrity of the affected component (s) to within its limit or isolate the affected component (s) from service.
d.
The provisions of Specification 3.0.4 are not applicable.
LIMITING CONDITION FOR OPERATION 4.4.10.1 ASME Code Class 1, 2, and 3 components shall be inspected in accordance with the requirements of Specification 4.0.5.
In addition, each reactor coolant pump flywheel shall be inspected per the recommenda-tions of Regulatory Position C.4.b of Regulatory Guide 1.14, Revision 1, August 1975.
$f)[$Db 4
P TROJAN-UNIT 1 3/4 4-29 Amendment No. 81