_

May 29,1986 Docket Nos. 50-325/324 DISTRIBUTION RBernero (Docket-File :, N Thompson Mr. E. E.

Utley NRC PDR~~~'

EJordan Senior Executive Vice President _

Local PDR JPartlow Power Supply and Engineering & Construction PD#2 File BGrimes Carolina Power & Light Company SNorris ACRS (10)

Post Office Box 1551 ESylvester OELD Raleigh, North Carolina 27602 OPA TBarnhart (8)

WJones DVassallo

Dear Mr. Utley:

LFMB EButcher

SUBJECT:

CHANGE TO BASES OF BRUNSWICK TECHNICAL SPECIFICATION 3/4.5.3.1, " CORE SPRAY SYSTEM (CSS)"

Re:

Brunswick Steam Electric Plant, Units 1 and 2

\\

By letter dated December 3, 1985, the Carolina Power & Light Company (CP&L) submitted proposed changes to the Bases to the Technical Specifications appended to Facility Operating License Nos. DPR-71 and DPR-62 for the Brunswick Steam Electric Plant (BSEP), Units 1 and 2.

The proposed changes would modify the Bases for Technical Specification Section 3/4.5.3.1 related to the operability of the core spray system. The proposed change would clarify the Bases to indicate that 50,000 gallons of water is the minimum required in the condensate storage tank to assure operability of the core spray system during operational conditions 4 or 5.

We have reviewed your request and agree that the minimum volume of water required for core spray system operability in operational condition 4 or 5 is 50,000 gallons. This volume corresponds to a condensate storage tank (CST) level of 150,000 gallons where the lower 100,000 gallons is dedicated, by way of stand pipes, for use by the high pressure coolant injection system and reactor core isolation cooling system. We concur that the proposed change to the Bases is appropriate to clarify that it is not 150,000 gallons that is required for core spray system operability, but that the water in the CST must be at the 150,000 gallon level. A copy of our evaluation is enclosed.

Because the proposed change is to the Bases and not to the Technical Specifications, en amendment to the license is not required and is not being issued. We have, however, revised page B 3/4 5-2 for Brunswick Unit 1 and page B 3/4 5-2 for Unit 2.

A copy of these revised pages is enclosed.

Sincerely, Original signed by/

Daniel R. Muller, Director BWR Project Directorate #2 Division of BWR Licensing j

Enclosures:

As stated cc w/ enclosures: See next page DB :PD#2 DBL:PD#2 df) DBL:PD#2 S

s: s ESylvester Dpl/Rf 5/4.l/86 5/2t/86 5/y/86

$ N $ $ $ $$$24 p

PDR

Mr. E. E. Utley Brunswick Steam Electric Plant Carolina Power & Light Company Units 1 and 2 cc:

Richard E. Jones, Esquire Vice President and Senior Counsel Carolina Power & Light Company 411 Fayetteville Street Mall Raleigh, North Carolina 27602 Thomas A. Baxter, Esquire Shaw, Pittman, Potts & Trowbridge 1800 M Street, N.W.

Washington, D.C.

20036 Mr. D. E. Hollar Associate General Counsel Carolina Power & Light Company P. O. Box 1551 Raleigh, North Carolina 27602 Mrs. Chrys Baggett State Clearinghouse Budget and Management 116 West Jones Street Raleigh, North Carolina 27603 Resident Inspector U. S. Nuclear Reculatory Commission Star Route 1 Post Office Lox 208 Southport,iiorth Carolina 28461 Regional Administrator, Region II U. S. Nuclear Regulatory Commission 101 Marietta Street, Suite 2900 Atlanta, Georgia 30323 Mr. Dayne H. Brown, Chief Radiation Protection Branch Division of Facility Services N.C. Department of Human Resources Post Office Box 12200 Raleigh, North Carolina 27605 Mr. Christopher Chappell, Chairman Board of Commissioners Post Office Box 249 Bolivia, North Carolina 28422