.. -.. _.. ~ _... - -

4 EYRON NUCLEAR POWER STAf!ON UNIT 1/2 DOCRET NUMBER STN 50-454/455 RADICACTIVE EFFLUENT RELEASE REPORT Januarv 1997 THROUGH Dec =ber

_1997 Supplemental Information 1.

Regulatery Limits a.

Fission and activation gases:

Tech Spec Whole Body = 500 mrem / year Skin = 3000 mrem / year 10CFR50 Gamma = 5 mrad / quarter; 10 mrad / year Beta = 10 mrad / quarter; 20 mrad / year b.

Iodine:

(summed with particulate, see below) c.

Particulates with half-lives > 8 days:

Tech Spec Organ = 1500 mrem / year 10CFR50 Organ = 7.5 mrem / quarter; 15 mrem / year d.

Liquid effluents:

10CFR50 Whole Body = 1.5 mrem / quarters 3 mrem / year Organ = 5 mrem / quarter; 10 mrem / year e.

Total Effective Dose Equivalent 10CFR20 TEDE = 100 mrem / year 2.

Maximum Permissible Concentratian a.

Fission and Activation Gases:

10CFR20 Appendix B Table 2 b.

Iodine:

10CFR20 Appendix B Table 2 c.

Particulates:

10CFR20 Appendix B Table 2 d.

Liquid Effluents:

10CFR20 Appendix B Table 2 Average Energy: This item is not applicable. Release rates are calculated using an isotopic mix rather than average energy.

4.

Measurements and Approximations of Total Radioactivity a.

Fission and Activation Gases:

Prior to release, the isotopic content is determined.

Released activity is-calculated using volume of release, which is determined by the change in tank or containment pressure. Additional methods of calculaticn utilize historical data and assign an isotopic mix which is representative of nort..al vent stack isotopics, 9903100254 980306 PDR ADOCK 05000454 R

PDR Report Page 1 of _,,21 (p:97t hrOOM066 wp0 ~

9

4 BYRON NUCLEAR POWER STATION UNIT 1/2 DOCI;Ef NUMBER STN-50-454/455 RADIOACTIVE XFFLUENT RELEASE REPORT Januarv

_1D_L THROUGH December

_1997 Supplemental Information (continued) b.

Particulate, Tritium and Iodine sampling media for_the plant vent stacks are collected and isotopically analyzed weekly for the plant vent stacks, c.

Liquids effluents:

Batch releases are isotopically analyzed prior to release. Total release activity is calculated using volume of release. Total tritium activity released is calculated from the highest of a monthly circulating water blowdown composite activity or a sum of the input composite activities, d.

Analysis results which are less than the lower linit of detection

'(<LLD) are reported in units of Ci/ml unless otherwise noted, All LLD valves are listed in Attachment A.

5.

Batch Releases:

a.

Liquid:

1.

Number of batch releases = 251 2,

Total time period for batch releases = 20,095 minutes 3.

Maximra time period for a batch release = 264 minutes 4.

Averag cime period for a batch release = 80.1 minutes 5.

Minimum time period for a batch release = 1 minute 6.

Average stream flow during periods of release of effluent into a flowing stream = 7,175 cfs, based on information from the National Weather Service or Army Corps of Engineers for the Rock River.

b.

Gaseous:

1.

Number of batch releases = 401 2.

Total time period for batch releases = 124,183 minutes 3.

Maximum time period for a batch release = 24,268 minutes 4.

Average time period for batch releases = 309.7 minutes 5.

Minimum time period for a batch release, 28 minutes 6.

Abnormal Releases:

a.

Liquid - None L.

Gaseous - Steam Generator Replacement Project related ground level release data are listed in Attachment B.

Dose attributed to these releases is included in dose ca.culations.

Report Page 2 of __18 (p:97byhtc98066 wpt,

Approved 6/1N97

~ Facsimib

^

BRP 6106-6TU Rsvision 4 BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN-50 454 RADIOACTIVE EFFLUENT RELEASE REPORT 3

JANUARY,1997 THROUGH DECEMBER,1997 4

4 GASEOUS EFFLUENTS -SUMMATION OF ALL RELEASES l

UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l A. FISSION AND ACTIVATION GAS RELEASES

1. Total Release Activity:

Ci 7.36F-01 1.15E+00 1.35E+00 2.46E+00

2. Maximum Release Rate for Quarter:

uCi/sec 1.53E+00 3.17E+00 2.53E+00 1.56E+00

3. % of Tech. Spec. Limits *
a. Whole Body (500 mrem /yr):

0.00 0.00 0.00 0.00

b. Skin (3000 mrem /g):

0.00 0.00 0.00 0.00 -

4. % of 10CFR50 Limits

. a. Gamma Quarterly (5 mrad);

0.00 0.00 0.00 0.00

b. Beta Quarterly (10 mrad):

0.00 0.00 0.00 0.00

c. Gamma Annual (10 mrad):

0.00 0.00 0.00 0.00

d. Beta Annual (20 mrad):

0.00 0.00 0.00 0.00 B. LODINE RELEASES "

1. Total 1131 Activity:

Ci

,, 8.06 E-03 5.71E 05 0.00E+00 0.00E+00

2. Average 1-131 Release Rate:

uCi/sec 1.04E 06 7.26E-06 0.00E+00 0.00E+00 C. PARTICULATE (>8 day half life) RELEASES "

1. Total Particulate Activity:

Ci

<LLD 2.10E n6 2.91E-06 5.46E-06

2. Average Particulate Release Rate:-

uCi/sec 0.00E+00 2.67E-07 3.66E 07 6.87E 07 4'

3. Gross Alpha Activity for Quarter:

Ci

<LLD

<LLD

<LLD

<LLD D. TRITIUM RELEASES "

1. Total Tri'ium Activity:

Ci 2.50E-01 2.23E-01 5.74E-02 8.12E-02

2. Average Tritium Release Rate:

uCi/sec 3.21 E-02 2.83E-02 7.22E-03 1.02E-02

  • % of Tech. Spec. limits is based on the maximu:,1 release rP*i, for the period considered.

" lodine, particulate, and trhium are expressed as a totallimit. See Step E.

Report Paae 3 of 28 (9916SS/XLS/051397)

Apprsved 5/13/97 FccSimils BRP 6100-6T1 Revision 4 BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN 50-454 RADIOACTIVE EFFLUENT RFl. EASE REPORT J ANUARY,1997 THROUGH DECEMBER,1997 QASEOUS EFFLUENTS -SUMMATION OF ALL RELFASES (CONT,d l

UNITS l 1st Quarter l 2nd O'Jarter l 3rd Quarter l 4th Quarter l l

E. TOTAL OF IODINE, PARTICULATE (>8 day half life), AND TRITIUM RELEASES 1 Total Activity; l

Ci l 2.50E-01 l 2.23E-01 I 5.74E 02 I B.12E 0').

I

2. % of Tec'h. Spec. Limits
a. Any Organ (1500 mrem /yr):

I 0.00 l

0.00 1

0.00 1

0.00 l

3. % of 10CFR50 Lim!t
a. Quarterly Any Organ l

l 0.00 l

0.00 l

0.00 l

0.01 l

(7.5 mrem):

b. Annu.!! Aity Organ l

l 0.00 l

0.00 1

0.00 l

0.01 l

(15 mrem):

GASEOUS EFFLUENTS -VENT STACK RELEASES - BATCH MODE F. FISSION AND ACTIVATION GAS RELEASES Ar-41:

Cl 1.72E-02 1.80E-02 1.19E-02 5.17E-02 Kr 85:

Ci

<LLD

<LLD

<LLD

<LLD Kr-85m:

Ci 1.61 E-04 4.28E-04 2.12E-04 1.25E 03 Kr 87:

Ci

<LLD

<LLD

<LLD

<LLD Kr-88:

Ci

<LLD 3.90E 04

<LLD 5.60E-04 Xe-131m:

Ci

<LLD

<LLD

<LLD

<LLD Xe 133:

Ci-2.16E-01 2.92E-01 3.06E-01 5.29E-01 Xe 133m:

C1 1.d5E-03 1.30E-03 1.27E-03 5.59E-03 Xe-135; Cl 7.74E 03 7.05E-03 1.26E-02 5.46E-02 Xe-138:

Ci

<LLD

<LLD

<LLD

<LLD Ci Ci Ci Ci Ci Report Page 4 of 28 (9916SS/XLS/051397)

Appr ved 5/13/97 Fcesimits BRP 6100-6T1 Rtvision 4 BYRON NUCLEAR POWER STATION UNIT 1 OOCKET NUMBE:1 STN-50-454 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEVBER,1997 GASEOUS EFFLUENTS -VENT STACK RELEASES - BATCH MODE (CONT.)

l UNITS l 1st Quarter l 2nd Quorter l 3rd Quarter l 4th Quarterl G. IODINE RELEASES l 131:

Ci l 133:

Cl l135:

Cl

  • Value reported as CONTINUOUS RELEASE MODE.

H. PARTICULATE (>B day half life) RELEASES Sr-89:

Ci Sr 90:

Cl 9

Cl Cl

  • Value reported as CONTINUOUS RELEASE MODE.

GASEOUS EFFLUENTS -VENT STACK RELEASES - CONTINUOUS MODE

1. FISSION AND ACTIVATION GAS RELEASEG Xe-133:

Ci 4.00E-01 7.81 E-01 1.02E+00 1.69E+00 Xe-135:

Cl 9.30E-02 4.00E-03

<LLD 8.00E-03 Ar 41:

Ci

<LLD 4.55E 02

<LLD 1.17E-01 Ci Ci Cl Ci Ci Ci l

Ci Cl Ci ep d age 5 of18 (9916SS/XLS/051397) m

Appr;ved 5/13/97 Facsimils BRP 6100-6T1 Rcvision 4 BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN 50-454 RADIOAC TlVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 GASEOUS EFFLUENTS - VENT STACK REl FASES - CONTINUOUS MODE (CONT.)

l UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l J. IODINE RELEASES l 131:

Ci 8.06E 06 5.71 E-05

<LLD

<.LLD l-133:

Cl 8.50E 05 1.47E-04

<LLD

< LLC l 135:

Cl 1.58E 05 2.05E 04

<LLD

<LLD l-132:

Ci

<LLD 1.02E 04

<LLO

<LLD K. PARTICULATE (>8 day half-iife) RELEASES St89:

Ci

<LLD

<LLD

<LLD

<ulD Sr-90:

Ci

<LLD

<LLD

<LLD

<LLD Br-82:

Ci

<LLD

<LLD

<LLD 7.87E-07 Co-60:

Ci

<LLD 2.10E 06 2.91 E-06 4.67E-06 Sb-125; Ci

<LLD

<LLD

<LLD

<LLD LIQUID EFFLUENTS -SUMMATION OF ALL RELEASES L. FISSION AND ACTIVATION PRODUCT RELEASES

1. Total Activity Released:

Ci 4.04E 02 7.22E-02 4.37E 02 6.61 E-02

2. Average Concentration uCi/mi 1.78E-08 2.82E-08 1.54E-08 2.98E-08 Released For Quarter:
3. % of 10CFR50 L!mits a Quarterly Whole Body l

l 0.17 l

0.06 l

0.43 l

0.06 l

(1.5 mrem):

b. Quarterly Any Organ l

l 0.07 0.07 l

0.19 l

0.02 l

(5.0 mrem):

c. Annual Whole Body l

l 0.08 l

0.03 l

0.22 l

0.03 l

(3.0 mrem):

d. Annual Any Organ l

l 0.04 l

0.04 l

0.10 l

0.01 l

(10.0 mrem):

Report Page 6 of 28 (9916SS/XLS/051397) m

Rtvision 4 1

BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN 50-454 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES (CONT.)

l UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l M. TRITlUTA

1. Total Activity Released:

Ci 3.35E+02

,1.93E+02 2.16E+02 3.19E+02

2. Average Concentration uC !!ml 1.47E 04 7.53E 05 7.61 E-05 1.44E 04 Released For Quarter:
3. % of 10CFR20 Limit l

l 14.74 l

7.53 l

7.61 l

14.39 l

(1.00E 3 uCi/ml):

N. DISSOLVED NOBLE GASES

1. Total Activity Released:

Ci 1.28E 02 1.23E-02 3.94E-03 2.61E 02

2. Average Concentration uCi/rni 5.63E 09 4.80E-09 1.39E-09 1.18E 08 Released For Quarter:
3. % of Admin. Tech. Reo.t. Limit f

l 2.82E 03 l 2.40E 03 l 6.93E 04 l 5.89E-03 l (2.00E-4 uCi/ml):

O, GROSS ALPHA

1. Total Actlvity Releasad:

Cl

<LLD

<LLD

<LLD

<LLD

2. Average Concentration uCi/mi

<LLD

<LLD

<LLD

<LLD Released For Quarter:

P. VOLUME OF WASTE l

liters l 1.82E+06 l 1.99E+06 l 2.47E+06 l 3.66E+06 l RELEASED PER UNIT:

Q. VOLUME OF DILUTION l

liters l 2.27E+09 l 2.56E+09 l 2.84E+09 l 2.22E+09 l WATER PER UNIT:

klQUID EFFLUENTS - CONTINUOUS MODE R. LIQUID EFFLUENTS

  • Value reported as LIQUID EFFLUENTS - BATCH MODE Fe-55:

Ci Sr 89:

Ci Sr 90:

Ci Ci Ci Report Page 7 of 28 (9916SS/XLS/051397)

Approved 5/13/97 FCesimilo BRP 6100-6T1 RGvision.4 BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN-50-454 RAr..OACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - BATCH MODE l-l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l UNITS S. LIQUID EFFLUENTS Fe-55:

Ci

,,1.12E 03 2.62E-03 8.55E 04

?

St-89:

Cl i.61 E-04 2.62E 04 9.24E-04

?

Sr 90:

Ci

<LLD

<LLD

<LLD

?

H 3:

Cl 3.35E+02 1.93E+02 2.16E+02 3.19E+02 Ar-41:

Ci 2.39E 04

<LLD

<LLD 1.09E-03 Cr-51:

Cl 4.73E-04 2.67E 04 4.28E-04 3.58E-04 Mn-54:

Ci 3.29E 04 1.79E-03 6.20E 04 4.07E 04 Fe-59:

Ci-5.04E-04

<LLD

<LLD 1.21 E-04 Co-57:

Ci 1.84E-05 1.13E-04 2.02E-06 9.87E 05 Co 58:

Ci 6.52E 03 9.23E 03 1.75E-03 2.30E-02 Co-60:

C6 1.88E-02 3.36E 02 1.17E-02 7.91E 03 Zn-65:

Ci

<LLD 9.38E-04 1.37E 04 4.96E-05 Kr-85:

Ci 1.19E-02 1.15E-02 3.54E-03 1.04E-02 Kr 85m:

Ci

<LLD

<LLD

<LLD 2.50E 05 Kr-87:

Ci

<LLD

<LLD

<LLD

<LLD Kr-88:

Ci

<LLD 2.25E 05

<LLD 2.21E-05 Sr 92:

Cl 5.09E-06 1.04 E-04

<LLD

<LLD Nt>.95:

Ci 2.30E-04 1.28E 03 1.76E-04 7.95E-05 Zr 95:

Ci 9.40E-05 4.16E-04

<LLD 1.20E-05 Zr 97:

Ci

<LLD

<LLD

<LLD 3.13E 06 Mo-99:

Cl 1.01 E-05

<LLD

<LLD

<LLD Tc-99m:

Ci

<LLD

<LLD

<LLD

<LLD Tc-104:

Ci

<LLD

<LLD

<LLD

<LLD Ag 110m:

Ci 2.64E 4.86E-04 4.38E-05

<LLD Sn-113:

Ci

<LLD 2.22E-04

<LLD

<LLD Te-121m:

Ci

<LLD

<LLD

<LLD

<LLO Te-123m:

Ci 2.11 E-04 4.63E-04 9.51E-05 7.38E-03 Te-125m:

Ci 8.75E-03 9.47E 03 5.30E-04 9.08E-03 Sb-122:

Ci

<LLD

<LLD

<LLD 2.38E-04 Sb-124:

Ci 1.32E-05 4.23E 04 3.19E-04 7.30E-03 Sb-125:

Ci 6.02E-04 1.29E 02 1.68E-02 9.42E-03 Sb 126:

Ci

<LL D 3.62E-06.

<LLD 3.45E-05 l

i Report Page 8 of 28 (9916S3/XLS/051397) l

Approvsd 5/13/97 Facsimile BRP 6100-6T1 Revision 4 BYRON NUCLEAR POWER STATION UNIT 1 DOCKET NUMBER STN-50454 RADIOACTIVE EFFLUENT R8:8 EASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - BATCH MODE (CONT.)

l UNITS 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l i

S. LIQUID EFFLUENTS (CONT.)

1131:

Cl 1.75E-06

<LLD

<LLD 1.64E-06 l-132:

Ci

<LLD

<LLD

<LLD 1.58E 05 l-133:

Ci

<LLD

<LLD

<LLD

<LLD l-135:

01 1.72E 05

<LLD 1.08E 05

<LLD Xe-131rr.:

Ci (LLD

<LLD

<LLD

<LLD Xe-133:

Cl 7.08E-04 7.36E-04 3.90E 04 9.42E-03 Xe 133m:

Cl

<LLD

<LLD

<LLD 1.30E-04 Xe 135:

Ci 2.86E 06 8.17E-06 3.51 E-06 5.09E 03 Xe-135m:

Ci

<LLD

<LLD

<LLD

<LLD Xe-138:

Ci

<LLD

<LLD

<LLD

<LLD C 134:

Ci 2.41 E-06 4.93E 04 6.01 E-04 3.63E-04 l -137:

Ci 3.81 E-03

<LLD 1.04E-02 1.21 E-04 Ba-140:

Ci

<LLD

<LLD

<LLD

<LLD La-140; Ci

<LLD

<LLD

<LLD

<LLD Ce-141:

Ci

<LLD

<LLD

<LLD

<LLD Ce-144:

Ci

<LLD

<LLD

<LLD

<LLD Na-24:

Ci

<LLD

<LLD

<LLD 3.26E-05 Te-132:

Ci

<LLD

<LLD

<LLD ___

5.02E-05 Cs-136:

Ci

<LLD

<LLD

<LLD 1.73E-05 Ci Ci Ci Ci T.10CFR20 PUBLIC TEDE COMPLIANCE

1. % OF 10CFR20 TEDE LIMIT l

l 0.00 l

0.00 l

0.00 l

0.00 l

(100 mrem /yr):

t' Report Page 9 of 28 (9916SS/XLS/051397)

Approved 3/13/97 Fcesimila BRP 6100-6T1 R: vision 4 4

DYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN 50-455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 GASEOUS E*FLUENTS -SUMMATION OF ALL RELEASES UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l A. FISSION AND ACTIVATION GAS RELEASES

1. Total Release Activity; Cl 6.18E 01 9.40E-01 1.12E+00 2.23E+00
2. Maximum Release Rate for Quarter:

uCl/sec 1.20E+00 1.71E+00 1.16E+00 1.61E+00 l

3. % of Tech. Spec. Limits:*
a. Whole Body (500 mrem /yr):

0.00 0.00 0.00 0.00

b. Skin (3000 mrem /yr):

0.00 0.00 0.00 0.00

4. % of 10CFR50 Limits
a. Gamma Quarterly (5 mrad):

0.00 0.00 0.00 0.00

b. Beta Quarterly (10 mrad):

0.00 0.00 0.00 0.00 i-

c. Gamma Annual (10 mrad):

0.00 0.00 0.00 0.00

d. Beta Annual (20 mrad):

0.00 0.00 0.00 0.00 B. IODINE RELEASES "

1. Total 1-131 Activity:

Ci

<LLD

<LLD

<LLD

<LLD

2. Average I 131 Release Rate:

uCi/sec 0.00E+00 0.00E+00 0.00E+00 0.00E+00 C. PARTICULATE (>8 day half-life) RELEASES "

1. Total Particulate Activity:

Ci 2.14E 05 1.74E-05 7.44E-06 6.71 E-06

2. Average Particulate Release Rate:

uCi/sec 2.75E-06 2.21 E-06 9.36E-07 8.44E-07

3. Gross Alpha Activity for Quarter:

Ci

<LLD

<LLD

<LLD

<LLD D. TRITIUM RELEASES "

1. Total Tritium Activity:

Ci 2.27E-01 1.46E-01 1.00E-01 1.57E-01

2. Average Tritium Release Rate:

uCt/sec 2.92E-02 1.86E-02 1.26E-02 1.97E-02

  • % of Tech. Spec. limits is based on the maximum release rate for the period considered.

" lodine, particulate, and tritium are expressed as a total limit. See Step E.

Repod Page 10 0f 28 (9916SS/XLS/051397)

. Approved 5/13/97 Facsimils BRP 6100-6T1 Rsvision 4 i

BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN 50-455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (CONT.)

l UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l E. TOTAL OF IODINE, PARTICULATE (>8 day half life), AND TRITIUM RELEASES

1. Total Activity:

l Cl l 2.27E-01 l 1.46E 01 l 1.00E 01 l 1.57E-01 l

2. % of Tech. Spec. Limits
a. Any Organ (1500 mrem /yr):

l l

0.00 l

0.00 l

0.00 l

0.00 l

3. % of 10CFR50 Limit
a. Quarterly Any Organ l

l 0.00 l

0.00 l

0 00 l

0.00 l

(7.5 mrem):

a. Annual Any Organ l

l 0.00 l

0.00 l

0.00 l

0.00 l

(15 mrem):

GASEOUS EFFLUENTS -VENT STACK RELEASES - BATCH MODE F. F'SSION AND ACTIVATION GAS RELEASES Ar-41:

Ci 2.30E-03 8.80E-03 8.28E-03 3.96E-02 Kr-85:

Cl

<LLD

<LLD

<LLD

<LLD Kr 85m:

Cl 1.61 E-04 4.28E-04 2.12E-04 1.255-03 Kr-87:

Ci

<LLD

<LLD

<LLD

<LLD Kr 88:

Ci 1.52E-03 3.90E-04

<LLD 5.60E 04 Xe-131m:

Ci

<LLD

<LLD

<LLD

<LLD Xe 133:

Cl 1.12E-01 9.24E-02 7.69E-02 3.17E-01 Xe 133m:

Ci 1.45E-03 1.30E-03 1.27E-03 5.59E 03 Xe-135:

Ci 7.22E-03 7.05E-03 1.04E-02 5.20E-02 Xe 138:

Ci

<LLD

<LLD

<LLD

<LLD Ci Cl Ci Ci Ci Repod Page 11 of 28 (9916SS/XLS/051397)

Approved 5/13/9f Fcesimila BRP 6100-6T1 R vision 4 BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN-50-455 RADIOACTIVE EFFLUENT. RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 GASEOUS EFFLUENTS -VENT STACK RELEASES - BATCH MODE (CONT.)

l UNITS l 1st Quarter l 2nJ Quarter l 3rd Quarter l 4th Quarter l G. IODINE RELEASES l 131:

Cl

~

I 133:

Cl l.135:

Ci

  • Value reported as CONTINUOUS RELEASE MODE.

H. PARTICULATE (>8 day half life) RELEASES Sr 89:

Cl Sr 90:

Ci Cl Cl Ci

  • Value reported as CONTINUOUS RELEASE MODE.

GASEOUS EFFLUENTS -VENT STACK RELEASES - CONTINUOUS MOE~_

l. FISSION AND ACTIVATION GAS RELEASES Xe-133:

Ci 4.00E-01 7.81 E-01 1.02E+00 1.69E+00 Xe 135:

Ci 9.30E-02 4.00E-03

<LLD 8.00E-03 Ar 41:

Ci

<LLD 4.55E-02

<LLD 1.17E-01 Cl Ci Ci Ci Ci Cl-Ci Ci Ci Report Page 12 of 28 (9916SS/XLS/051397)

Approved 6/13/97 Focsimilo -

BRP 6100-6T1 Rovision 4 BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN 50-455 RADtOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DEC&BER,1997 GASEOUS EFFLUENTS -VENT STACK RELEASES - CONTINUOUS MDDE (CONT.}

l UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l J. IODINE RELEASES l131:

Ci

<LLD

<t.LD

<LLD

<f.LD l-133:

Ci 4.21 E-06

<LLD

<LLD

<ulD l135:

Ci

<LLD

<LLD

<LLD

<LLD l-132:

Cl 2.27E-05

<LLD

<LLD

<LLD K. PARTICULATE (>8 day half life) RELEASES Sr-89:

Ci

<LLD

<LLD

<LLD

<LLD Sr90:

Ci

<LLD

<LLD

<LLD

<LLD Sb-125:

Cl 1.30E 05 1.14E 05

<LLD 3.62E-07 Br-82:

Ci 8.42E-06 4.62E-06 3.47E-06 4.17E-06 Co-60:

Ci

<LLD-1.33E-06 3.97E 06 2.17E-06 LIQUID EFFLUENTS - SUMMA 160N OF ALL RELEASES L. FISSION AND ACTIVATION PRODUCT RELEASES

1. Total Activity Released.

Ci 4.04E-02 7.22E-02 4.37E-02 6.61 E-02

2. Average Concentration uCi/mi 1.78E 08 2.82E-08 1.54E-08 2.98E-08 Released For Quarter:
3. % of 10CFR50 Limits
a. Quarterly Whole Body l

l 0.17 l

0.0C l

0.43 l

0.06 l

(1.5 mrem):

b. Quarterly Any Orgaa-l l

0.07 l

0.07 l

0.19 l

0.02, _]

(5.0 mrem):

c. Annual Whole Body l

l 0.08 l

0.03 l

0.22 l

0.03 l

(3.0 mrem):

d. Annual Any Organ l

l 0.04 l

0.04 l

0.10 l

0.01 l

(10.0 mrem):

Repod Page 13 of 28 (9916SS/XLS/051397)

\\

Rovision 4 BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN-50-4s';

RADIOACTIVE EFFLUENT RELEASE REPCRT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES (CONT.)

l UNITS l 1st Qua;ter l 2nd Quarter l 3rd Quarter l 4th QJarter l M. TRITIUM

1. Total Activity Released:

Cl 3.35E+02 1.93E+02 2.16E+02 3.19E+02

2. Average Concentration uCi/mi 1.47E-04 7.53E-05 7.61 E-05 1.44E-04 Released For Quarter:
3. % of 10CFR20 Limit l

l 14.74 l

7.53 l

7.61 1

14.39 l

(1.00E 3 uCl/ml):

N. DISSOLVED NOBLE GASES

1. Total Activity Released:

Cl 1.28E-02 1.23E-02 3.94E-03 2.61 E-02 l

2. Average Concentration uCi/ml m.63E 09 4.80E-09 1.39E-09 1.18E-08 Released For Quarter:
3. % of Admin. Tech Reqt. Limit l

l 2.82E 03 l 2.40E-03 l 6.93E-04 l 5.89E 03 l (2.00E-4 uCi/ml):

O. GROSS ALPHA

1. Total Activity Released:

Ci

<LLD

<LLD

<LLD

<LLD

2. Average Concentration

_ uCi/mi

<LLD

<LLD

<LLD

<LLD Released For Quarter:

P. VOLUME OF WASTE l

liters l 1.82E+06 l 1.99E+06 l 2.47E+06 l 3.66E+06 l RELEASED PER UNIT:

Q. VOLUME OF DILUTION l

liters l 2.27E+09 l 2.56E+09 l 2.84E+09 l 2.22E+09 l WATER PER UNIT:

LIQlJID EFFLUENTS - CONTINUOUS MODE R. LIQUID EFFLUENTS

  • Value reported as LIQUID EFFLUENTS - BATCH MODE Fe Ci Sr-89 Ci Sr 90:

Ci Ci Ci Reped Page 14 ot 28

-(9916SS/XLS/Cb1397)

\\

Approved 5/13/97 FcesimiIi BRP 6100-6T1 RSvision 4 BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN-50-455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - BATCH MODE l

UNITS l 1st Quarter l 2nd Quarter l 3rd Quarter l 4th Quarter l S. LIQUID EFFLUENTS Fe-55:

Cl 1.12E-03 2.62E-03 8.55E-04

?

Sr 89:

Cl 1.61 E-04 2.62E 04 9.24E-04

?

Sr-90:

Ci

<LLD

<LLD

<LLD

?

H-3:

Ci 3.35E+02 1.93E+02 2.16E+02 3.19E+02 Ar 41:

Ci 2.39E-04

<LLD

<LLD 1.09E-03 Cr-51:

Ci 4.73E-04 2.67E-04 4.28E-04 3.58E-04 Mn-54:

Ci 3.29E-04 1.79E 03 6.20E-04 4.07E-04 Fe-59:

Ci 5.04E-04

<LLD

<LLD 1.21 E-04 Co-57:

Cl 1.84E-05 1.13E-04 2.02E-06 9.87E-05 Co-58:

Ci 6.52E-03 9.23E-03 1.75E-03 2.30E-02 Co-60:

Cl 1.88E-02 3.36E-02 1.17E-02 7.91 E-03 Zn-65:

Ci

<LLD 9.38E-04 1.37E-04 4.96E-05 l

Kr-85:

Ci 1.19E-02 1.15E-02 3.54E-03 1.04E-02 l

Kr-85m:

Ci

<LLD

<LLD

<LLD 2.50E-05 i

Kr-87:

Ci

<LLD

<LLD

<LLD

<LLD Kr-88:

Ci

<LLD 2.25E-05

<LLD 2.21 E-05 Sr-92:

Ci 5.09E-06 1.04E-04

<LLD

<LLD Nb 95:

Cl 2.30E-04 1.28E-03 1.76E-04 7.95E-05 Zr-95:

Ci 9.40E 05 4.16E-04

<LLD 1.20E-05 Zr-97.

Ci

<LLD

<LLD

<LLD 3.13E-06 Mo-99:

Ci 1.61 E-05

<LLD

<LLD

<LLD Tc-99m:

Ci

<LLD

<LLD

<LLD

<LLD Tc.104:

Ci

<LLD

<LLD

<LLD

<LLD Ag-110m:

Ci 2.64E-05 4.86E-04 4.38E-05

<LLD Sn-113:

Ci

<LLD 2.22E-04

<LLD

<LLD Te-121m:

Ci

<LLD

<LLD

<LLD

<LLD Te-123m:

Ci 2.11E 04 4.63E-04 9.51 E-05 7.38E-03 Te-125m:

Ci 8.75E-03 9.47E-03 5.30E-04 9.08E-03 Sb 122:

Ci

<LLD

<LLD

<LLD 38E-04 Sb-124:

Ci 1.32E-05 4.23E-04 3.19E-04 7.30E-03 Sb-125:

Ci 6.02E 04 1.29E-02 1.68E-02 9.42E-03,

Sb-126:

Ci

<LLD 3.62E-06

<LLD 3.45E-05 i

Report Page 15 of 28 (9916SS/XLS/051397) e m.

Appr:yed 6/13/97 Facsimila BRP 6100-6T1 Rsvision 4 BYRON NUCLEAR POWER STATION UNIT 2 DOCKET NUMBER STN-50 455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY,1997 THROUGH DECEMBER,1997 LIQUID EFFLUENTS - BATCH MODE (CONT.)

l UNITS l 1st Quarter l 2 rid Quarter l 3rd Quarter l 4th Quarter l S. LIQUID EFFLUENTS (CONT.)

1131:

Cl 1.75E 06

<LLD

<LLD 1.64E-06 l132:

Ci

<LLD

<LLD

<LLD 1.58E-05 l 133:

Ci

<LLD

<RD

<RD

<RD l-135:

Cl 1.72E 05 (LLD 1.08E 05

<LLD Xe 131m:

Ci

<LLD

<LLD

<LLD

<LLD 1

Xe-133:

Ci 7.08E 04 7.36E-04 3.90E-04 9.42E-03 Xe 133m:

Ci

<LLD

<LLD

<LLD 1.30E-04 Xe 135:

Ci 2.86E 06 8.17E-06 3.51E-06 5.09E-03 Xe 135m:

Ci

<LLD

<LLD

<LLD

<LLD Xe 138-Ci

<LLD

<LLD

<LLD

<LLD Cs 134:

Ci 2.41E 06 4.93E-04 6.01 E-04 3.63E 04 Cs-137:

Ci 3.81E 03

<LLD 1.04E 02 1.21 E-04 Ba-140:

Ci

<LLD

<LLD

<LLD

<LLD La-140:

Ci

<LLD

<LLD

<LLD

<LLD Ce-141:

Ci

<LLD

<LLD

<LLD

<LLD Ce 144:

Ci

<LLD

<LLD

<LLD

<LLD Na 24:

Ci

<LLD

<LLD

<LLD 3.26E-05 I

Te-132:

Ci

<LLD

<LLD

<LLD 5.02E-05 CS-136:

Ci

<LLD

<LLD

<'LD 1.73E 05 Cl Ci Ci Ci T.10CFR20 PUBLIC 'i EDE COMPLIANCE

1. % OF 10CFR20 TEDE LIMIT:

l l

0.00 l

0.00 l

0.00 l

0.00 l

(100 mrem /yr)

Repod Paga 16 of 28 (991GSS/XLS/051397)

m --

=. _

BRP 6100-671 R2 Vision 4 BYRON NUCLEAR POWER STATION UNIT 1/2 DOCKET NUMBER FIN 50454/4*S RADIOACTIVE EITLUENT RELEASE REPORT Januarv

,1997 THROUGli December. 1997 l

SOLID RADIOACTIVE WARIT FOR Bt'RI AL lst OUARTT.R 1997 DISPOSITION OF MATERIAL VOLUME PER j

DATE (DESCRIPTION, CLASS, TYPE, AND MODE OF DESTINATION SillPMENT CURIES

  • PER SOLIDIFYING AOENT)

TRANSPORT (CUBIC M)

SillPMENT Dewatered Bend Resm,14w Specife Activity, Exclusive Use

Barnwell, 4.84 29.8 4

01/22/97 NOS 7, UN 2912. Class A Stable, lilC, None SC 02/06/97 Dry Active Waste, Low Specific Actatty, NOS Exclusive Use Oak Ridge, 72.5 1.14 7, UN 2912, Strong Tight Container, None TN 03/12/97 Dewatered Bead Resm & DAW, low Specific Exclusive Use

Barnwell, 5.83 17.0 Acuvity, NOS 7 UN 2912, filC, None SC f

83,2

~47.9 QUARTERLY TOTALS NUMBCR OI Sil!PMENTS:

3 CUBIC M CURIES

-

  • CALCULATED USING MEASURED RATIOS I

a j

t d

Report Page 17 of 20 (p 97byltrs\\9%wpr,

BRP 6100-6T1 Revision 4 BYRON NUCLEAR POWER STATION UNIT 1/2 DOCKET NUhfBER STN-56454/455 RADIOACTIVE EFFLUENT RELEASE REPORT Januart IM7 THROUGli.. Deceinber. 1997 SOLID RADIOACTIVE WA5'IT. FUR Bt' RIAL 2ND OUAR1TR l#7 9

DISPOS!110N OF MATERIAL VOLUME PER DATE (DESCRIITION, CLASS, TYPE, AND MODE OF DESTINATION SillPMENT CURIES

  • PER SO).lDIFYING AGENT)

TRANSPORT (CUBIC M)

Sil!PMENT 5/07/97 Compacted DAW - Drums. Low Specifs Exclusive Use Oak Ralge, TN 17.2 0 454 Actal:y, NOS 7 UN 2912, Strong Tight Contamer, None 5/10/97 Dewatered Bead Resm, bw Spectfs Actnety Exclusive Use Salt Lake City, 22.8 0 078 NOS 7. UN 2912. HIC, None UT 5/14/97 Dematered Bead Resm. Low Specifs Acuvity, Exclusive Use

Barnwell, 159.0 2.83 NOS 7, UN 2912, IllC, None SC 5/27/97 Dewatertd Bead Resin, Low Specifs Activity Excluuve Use Salt Lake City, 22.9 0.0W NOS 7 UN 2912,lilC None UT 6/18/97 Dewatered Bead Renm, Low Spectfm Activity, Excluuve Use Bann.11, 3.65 2 68 NOS 7, UN 2912, filC, None SC 225.6 6,13 QUARTERLY TOT ALS NUMHER OF SHIPMENTS:

5 CUBIC M CURIES

'CALCULATI:D USING MEASURED RATIOS l

Report Page 18 of 28 (p 97bylim9m*6 w; O

BRP 6100-6T1 Revision 4 BYRON NUCLEAR POMER STATION UNIT 1/2 DOCKET NUMBER filN-$NS4/45$

RADIOACTIVE ERMT.NT RELEASE REPORT Januart

.1997 THROUGH Ikcember 1**7 SOllD RADIOACTIVE WAFTE FUR Bt' RIAL 3rd OUARTTR IM7 DISPOSITION OF MATERIAL VOLUME PER DATE (DFSCRIPTION, CLASS. TYPE, AND MODE OF DESTINATION SillPMENT CURIES' PER SOLIDIFYING AGENT)

TRANSPORT (CUBIC M)

SHIPMENT 8/11/97 Scrap Metal, Low Specife Activity, NOS 7. UN Exclusive Use

Memphis, 29,0 0.025 2912. Strong Tight Contamer, None TN l

l l-f 29.0

.025 QUARTERLY TOTALS - NUMBER OF Sil!PMENTS:

1 CUBIC M CURIES

  • CALCULATED USINO MEASURED RATIOS Report Page 19 of J (p:97byttnWmmwpn

BRP 6100-6T1 Revision 4 BYRON NUCLEAR POWER FIATION UNIT 1/2 DOCKET NUMBER STN-50-454/455 RADIOACTIVE EFILUENT RELEASE REPORT Januarv

. IM7 THROUGH. December. IM7 SOLID RADIOACTIVE WAS!T FDR PURI AL 4th OUARTER IM7 DISPOSITION OF MATERIAL VOLUME PER DATE (DESCRIITION, CLASS. TYPE, AND MODE OF DESTINA1!ON SHIPMENT CURIES' PER SOLIDIFYING AGENT)

TRANSPORT CGIC M SHIPMENT 10/20/97 Dewatered Bend Resin, low Specific Activity, Exclusive Use

Barnwtll, 2.69 46.7 NOS 7, UN 2912, IllC, None SC 10/22/97 Dewatered Bead Resm. Low Specific Activity, Exclusive Un
Barnwell, 4.%

19.6 NOS 7, UN 2912, IllC None SC 11/21/97 Uncrarpacted DAW, Low Speci6c Acuvity, tiOS Exclusive Use Oak Rktge, 72.5 0,164

[

7. UN 2912 Strong Tight Container, None TN 12/19/97 Scrap Metal, low Specific Acuvity, NOS 7 UN Exclusive Use
Memphis, 36.3 0.0062 2912, Strong Tight Container, None TN 12/30/97 DAW, Low Specific Acuvity, NOS 7. UN 2912, Exclusive Use Oak Rkige, 72.5 0.060 Strong Tight Container, None TN 189 66.5 QUARTERLY TOTALS - NUMBER OF 5

CUBIC M CURIES

' CALCULATED USING MEASURED RATIOS j

Report Page 20 of 28 ip 97byItrs\\98hpf)

ADDENDUM A.

There were no major changes or modifications to the PCP, or to any liquid gaseous or solid redwaste treatment systems for this period.

B.

Error Analysis The following is an estimate of the errors associated with effluent monitoring and analysis. The estimate is calculated 'asing the square root of the sum of the squares methodology.

1.

Gaseous Effluents Sampling error. 1 to 3.5%

Calibration error. 10%

Counting Statistics error = 5%

Vent Stack Flowrates error = 1,5%

Total error. 11 - 12%

2.

Liquid Effluents Sampling error = 1%

Calibration error = 10%

Sample volume error = 1%

Discharged volume error. 2%

Total error = 10%

3.

Waste Resin Sampling error = 5%

Counting Statistics error = 7%

Weight error = 1%

Volume error-5%

Total error = 10%

4.

DAW Counting Statistics arror= 7%

Calibration error = 10%

Weight error = 2%

Total error 12%

Report Page 21 of 28 (p 97bylmWM066 wp0

____a

4 C.

Mateorological end environmental impact information is reported in tha Station Annual Radiological Environmental Op3 rating Rsport as required by Technical Specifications 6.9.1.6.

D.

No limits were exceeded in liquid hold up tanks as scated in Technical Specifications 3.11.1.4 or in waste gas decay tanks as stated in Technical Specifications 3.11.2.6.

E.

There were no irradiated fuel shipments during this period.

F.

There were no elevated releases.

All releases are considered vent or ground level releases.

G.

The Offsite Dose Calculation Manual (ODCM) was revised in February of 1997 The revision is another step in implementing a uniform radiological effluent monitoring program (REMP) consistent among all Commonwealth Edison sites. The primary changes include reducing the frequency with which iodine cartridges are changed out from the eight (8) environmental monitoring stations from weekly to bi-weekly, and adding a third groundwater monitoring well sampling locatiori which is downgradient from Byron Station.

The site specific portion of the ODCM was revised in October of 1997 The revision reflected updated sampling locatiers based on a 1997 survey performed using a global positioning syatem. Additionally, surveillance requirements for the newly constructed Old Steam Generator Storage Facility were added. The changes do not affect the level of safety of the plant or affect the dose to the public or environment. A copy of the latest revision of the ODCM was submitted to the NRC under a separate cover by Cored's, Health Physics Support Dept.

H.

Attached are the Offsite Dose Calculations for January through Decemorr of 1997.

Report Page 22 of 28 (p 97b> hrs \\9h64pf)

I.

Tha following data is the estimated composition of Byron's solid waste.

1.

Dry Active Waste (DAW) 2.

Primary Resin H-3

<0.01%

H-3

<0.01%

C-14 0.32%

C-14

<0.01%

Mn-54 0.23%

Mn-54 11.72%

Fe-55 39.10%

Fe-55 34.80%

Co-57 0.01%

Co-57 0.38%

Co-58 3.88%

Co-58 5.39%

Co-60 22.47%

Co-60 20.00%

Ni-63 30.34%

Ni-63 27.05%

Sr-90 0.03%

Zn-65 0.27%

Zr-95 1.18%

Sr-89

<0.01%

Nb-95 2.21%

Sr-90

<0.01%

Tc-99

<0.01%

Nt-95

<0.01%

Ag-110m

<0.01%

Tc-99

<0.01%

Sn-113 0.12.

Te-323m

<0.01%

Te-123m

<0.01%

Sb-124

<0.01 Sb-124

<0.01%

Sb-125

<0.01 Sb-125 0.10%

Te-125m

<0.01%

Te-125m

<0.01%

I-129

<0.01%

I-129

<0.01%

Cs-134

<0.01%

Cs-134

<0.01%

Cs-137

<0.01%

Cs-137

<0.01%

Pu-238

<0.01%

Pu-238

<0.01%

Pu-239

<0.01%

Pu-239

<0.01%

Pu-241

<0.01%

Pu-241 0.01%

Am-241

<0.01%

Am-241

<0.01%

Cm-242

<0.01%

Cm-242

<0.01%

Cm-244

<0.01%

Cm-244

<0.01%

Report Page 23 of 28 (p Abptrc94h w pf)

I.

(Continu2d) 3.

Radwaste Resin m

H-3 0.15%

C-14 0.20%

Mn-54 0.90%

Fe-55 23.40%

Co-57 0.45%

Co-58 35.10%

Co-60 12.60%

Ni-63 14.05%

Zn-65 0.05%

Sr-90

<0.01%

Tc-99

<0.01%

Ag-110m

<0.01%

Te-123m

<0.01%

Sb-124 0.20%

Sb-125 2.50%

Te-125m 0.20%

I-129

<0.01%

Co-134 3.00%

Cs-137 7.20%

Pu-238

<0.01%

Pu-239

<0.01%

Pu-241 0.01%

Am-241

<0.01%

Cm-242

<0.01%

Cm-244

<0.01%

J.

No process radiation monitors were out of service longer thea allowed by the Offsite Dose Calculation Manual.

Report Page 24 of 28 (p 97bylin19x066 wpn

ATTACHMENT A BYRON NUCLEAR POWER STATION UNIT 1/2 DOCKET NUMBER STN-50-454/455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY, 1997 THROUGH DECEMBER, 1997 LLD VALUES FOR GASEOUS RELEASES i

i Isotopes LLD(C1/ml) l H-3 3.85E-14 Ar-41 3.83E-13 Co-58 5.42E-19 Co-60 4.34E-19 Kr-85 5.89E-11 Kr-85m 2.33E-13 Kr-87 6.75E-13 Kr-88 7.92E-13 Sr-89 3.07E-21 Sr-90 8.40E-22 Sn-113 6.26E-19' Te-123m 3.42E-19 I-131 6.48E-19 I-132 9.44E-19 r

I-133 7.71E-19 I-135 2.96E-18 Xe-131m 7.97E-12 Xe-133 5.18E-13 Xe-133m 1.60E-12 Xe-135 2.03E-13 Xe-135m 3.78E-12 Xe-138 1.05E-11 Cs-137 5.65E-19 Ce-141 5.62E-19 Ce-144 2.51E-18 Report Page 25 of 28 (p:97bylirs\\98066.wpf)

ATTACEMENT A (Ocnt.)

BYRON NUCLEAR POWER STATION UNIT 1/2 DOCKMT NUMBER STN-50-454/455 RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY, 1997 THROUGH DECEMBER, 1997 LLD VALUES FOR LIQUID RELEASES Isotopes LLD(Ci/ml)

H-3 1.49E-12 Ar-41 5.12E-14

-Cr-51 2.37E-13 Mn-54 3.32E-14

-Fe-55 2.40E-14 Fe-59 6.76E-14 Co-57 2.20E-14 Co-58 3.3BE-14 Co-60 5.90E-14 Zn-65 7.00E-14 Kr-85 7.51E-12 Kr-85m 2.90E-14 Kr-87 8.58E-14 Kr-88 9.97E-14 Sr-89 2.25E-14 Sr-90 6.17E-15 Sr-92 4.59E-14 Nb-95 3.43E-14 Zr-95 6.39E-14 Zr-97 3.46E-14 Mo-99 2.48E-13 j

Tc-104 2.81L 13 t

Ag-110m 3.44E-14 I

Sn-113 3.97E-14 i

i Sb-122 4.02E-14 f

Sb-124 3.20E-14 i

Sb-125 8.76E-14 l

1 Report Page 26 of 28 (p 97bylus\\98066 wp0 -

ATTACHMENT A (cant.)

BYRON NUCLEAR PONER STATION UNIT 1/2 DOCKET NUMBER STN-50-454/455 RADIOACTIVE EFFLUENT RELEASE RRPORT JANUARY, 1997 THROUGH DECEMBER, 1997 LLD VALUES FOR LIQUID RELEASES Isotopes LLD (Ci/ml)

Sb-126 2.15E-14 Te-121m 8.82E-14 Te-123m 2.28E-14 Te-125m 6.84E-12 Te-132 2.41E-14 Xe-125m 5.91E-12 Xe-131m 9.94E-13 Xe-133 6.61E-14 Xe-133m 2.02E-13 Xe 135 2.57E-14 Xe-135m 4.91E-13 Xe-138 1.14E-13 Cs-134 3.15E-14 Cs-136 3.33E-14 Cs-137 3.77E-14 I-131 2.95E-14 I-132 4.28E-14 I-133 3.51E-14 I-134 1.00E-13 I-135 1.31E-13 Ba-140 1.14E-13 LC-140 3.58E-14 Ce-141 3.96E-14 Ce-144 1.70E-13 Pr-144 2.60E-11 Hf-181 2.98E-14 Repcrt Page 27 of 28 tp:97bykn\\9*)h6 mpf)

ATTACHMENT B C

EYRON NUCLEAR PONER STATION UNIT 1, (DOCKET NUMBER STN-50 454)

RADIOACTIVE EFFLUENT RELEASE REPORT STEAM GENERATOR REPLACEMENT PROJECT RELATED GROUND LEVEL RELEASES During the Steam Generator Replacement Project (SGRP) several new effluent pathways were created to support the removal and installation of Steam Generators (S/Gs)in Unit 1 Containment. Approximately 63 uCi of particulate activity was calculated to have been released via SGRP related ground level effluent pathways during 1997, using conservative assumptions. No radioiodines were identified at any effluent sampling point during the course of the project.

GROUND LEVEL UNITS 3* Quarter 4* Quarter RELEASES July-September,1997 October - December,1997 l

11 3 :

Ci

< LLD 4.25E-01 l

Cr-51:

Ci

< LLD 1.32E-05 Co 58:

Ci

< LLD 2.18E-05 Co-60:

Ci 4.32E-06 2.20E-05 Nb-95:

Ci

< LLD 1.58E-07 Te-132:

Ci

< LLD 2.73E 10 Cs 134:

Ci

< LLD 6.58E-08 Cs 137:

Ci

< LLD 1.75E-06 Total Particulate:

Ci 4.32E-06 5.90E-05 These data were used to calculate 10CFR50 maximum doses to organs from Steam Generator Replacement Project Effluents (Particulate and tritium effluents only contribute to Organ doses using 10CFR50 methodology).

The following table lists the organ dose (in mrem) to the maximally exposed infant, child, teenager, and adult member of the public:

Maximally exposed member 3* Quarter

% of 10CFR50 4* Quarter

% of 10CFR50 of the public (mrem)

Limits (7.5 mrem)

(mrem)

Limits (7.5 mrem)

Infant 4.77E 05 0.00 5.06E-04 0.00 Child 4.92E45 0.00 5.31E-G4 0.00 Teenager 5.12E-05 0.00 4.79E-04 0.00 Adult 5.I1E 05 0.00 6.1 I E-04 0.00 Maximum 5.12E-05 0.00

6. l l E-04 0.00 (Final)

Report Page 28 of

,28 (p:97byttn\\98W4 wp0

BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 INFANT RECEPTOR IST 2ND 3RD 4TH TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC GAMMA AIR 5.47E-06 8.86E-06 6.04E-06 2.18E-05 4.22E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.36E-05 1.94E-05 2.08E-05 4.33E-05 9.71E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 4.00E-06 6.47E-06 4.30E-06 1.60E-05 3.08E-05 (MREM)

(SSE )

(SSE )

(S6E )

(SSE )

(SSE )

SMIN 1.03E-05 1.43E-05 1.13E-05 3.48E-05 7.06E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 1.12E-04 1.71E-04 6.13E-05 5.10E-04 8.32E-04 (MREM)

(NE )

(NE )

(SSE )

(NE )

ME )

THYROID THYROID LUNG LIVER THYROID THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10CFR 50 APP. I INFANT RECEPTOR


 % OF APP I. ------------

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SKIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 ORGAN (MREM) 7.5 0.00 0.00 0.00 0.01 15.0 0.01 THYROID THYROID LUNG LIVER THYROID RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

l e

i BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PEAIOD OF RELEASE - 01/01/97 70 12/31/97 CALCULATED 03/02/98 CHILD RECEPTOR l

1ST 2ND 3RD 4TH l

?YPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC GAMMA AIR 5.47E-06 8.86E-06 6.04E-06 2.18E-05 4.22E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.36E-05 1.94E-05 2.06Z-05 4.33E-05 9.71E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 4.00E-06 6.47E-06 4.30E-06 1.60E-05 3.08E-05 (MREM)

(SSE )

(SOE )

SEE )

(SSE )

(SSE )

SKIN 1.03E-05 1.43E-05 1.13E-05 3.48E-05 7.06E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 7.94E-05 3.00E-04 1.57E-04

5. ' !E-04 1.01E-03 (MREM)

(NE 5

(SSE )

(SSE )

(,

)

(S

)

THYROID THYROID GI_LLI LUNG THYROID THIS IS A REPORT roR ThE CALENDAR YEAR 1997 l

l COMPLIANCE STATUS - 10CFR 50 APP. I i

CHILD RE0EPTOR


 % OF AP P I.

QTkLY 157 QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.60 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SMIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 ORGAN (MREM) 7.5 0.00 0.00 0.00 0.01 15.0 0.01 THYROID THYROID GI_LLI LUNG THYROID RESULTS BASED UPONt ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 Jaraary 1995 l

Y

t P"RON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES RESULTING EPOM AIRBORNE RELEASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 TEENAGER RECEPTOR IST 2ND 3RD 4TH TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR t,PR-JUN JUL-SEP OCT-DEC GAMMA AIR 5.47E-06 8.06E-06 6.04E-06 2.18E-05 4.22E-05 (MRAD)

(SSE i (STE )

(SFt )

(SSE )

(SSE )

BETA AIR 1.36E-05 1.94E-05 2.LdE-05 4.33E-05 9.71E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 4.00E-06

-6.47E-06 4.30E-06 1.60E-05 3.08E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

SKIN 1.03E-05 1.43E-05 1.13E-05 3.48E-05 7.06E-05 (MP.EM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 5.21E-05 2.02E-04 1.2SE-04 5.11E-04 8.17E-04 (MREM)

(NE )

(SSE )

(SSE )

(S

)

(S

)

1 THYROID THYROID GI_LLI LUNG THYROID THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMP *IANCE STATUS - 10CFR 50 APP. I TEENAGER RECEPTOR

............ g or App I,............

OTRLY IST C'R 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.A 0.00 0.00 0.00 0.00 5.0 0.00 SXIN (MREM) 7.,

0.00 0.00 0.00 0.00 15.0 0.00 okGAN (MREM) 7.5 0.00 0.00 0.00 0.01 15.0 0.01 THYROID THYROID GI_LLI LUNG THYROID RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

=

a

BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PERIOD or RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 ADULT RECEPTOR IST 2ND 3RD 4TH l

TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC l

GAMMA AIR 5.47E-06 B.86E-06 6.04E-06 2.18E-05 4.22E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

l BETA AIR 1.36E-05 1.94E-05 2.00E-05 4.33E-05 9.71E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 4.00E-06 6.47E-06 4.30E-06 1.60E-05 3.08E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

gSSE )

SKIN 1.03E-05 1.43r-05 1.13E-05 3.48E-05 7.06E-05 (MT?.M)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE 1 ORGAN 7.20E-05 1.CSE-04 1.17E-04 6.49E-04 9.87E-04 (MREM)

(S

)

(S

)

(SSE )

(S

)

(S

)

THYROID THYROID GI_LLI GI_LLI THYROID THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10CFR 50 APP. I ADULT RECEPTOR


 % OF APP I. ------------

QTRLY 1ST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP CCT-DEC OBJ APP. I GAMMA AIR (MRAD) s.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.v 0.00 SKIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 ORGAN (MREM) 7.5 0.00 0.00 0.00 0.01 15.0 0.01 THYROID THYROID GI_LLI GI_LLI THYROID RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

)

4 BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE 01/01/97 TO 12/31/97

' ALCULATED 03/02/98 INFANT RECEPTOR i

IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER

"'TER ANNUAL JAN-MAR APR-JUN JUL-SEP 1 SEC TOTAL

$.01E-v4 3.37E-04 3.77E-04 b.51E-04 1.85E-03 BODY INTERNAL

$.92E-04 3.3BE-04 4.11E-04

$.52E-04 1.09E-03 ORGAN j

LIVER GI,LLI LIVER LIVER LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10 CFR 50 APP. I


 % OF APP I. ------------

QTRLY IST QTR 2ND QTR 3RP QTR_

OCT-DEC OBJ APP. I 4TH QTR YRLY

% OF.

OBJ JAN-MAR APR-JUN J11.- S EP TOTAL BODY (MREM) 1.5 0.04 0.0?

0.03 0.04 3.0 0.06 CRIT. ORGAN (MREM) 5.0 0.01 0.01 0.01 0.01 10.0 0.02 LIVER GI_LLI LIVER LIVER LIVER RESULTS BASED UPON:

ODCM A'"3X REVISION 1.1 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

BYRON STA*'ON UNIT ONE 1997 ANNUAL REPORT PROJECTED DOSE AT NEAREST COMMUNITY WATER SYSTEM

  • PERIOD OF RELEASE - 01/01/97 TO 1;'/31/97 CALCULATED 03/02/9d INFANT RECEPTOR i

i IST END 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 5.81E-34 3.37E-04 3.77E-04 5.51E-04 1.85E-03 BODY l

INTERNAL 5.92E-04 3.38E-04 4.11E-04 5.52E-04 1.89E-03 ORGAN LIVER GI_LLI LIVER LIVER LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

% OF LIMIT TOTAL 4.0 MREM 0.045 BODY INTERNAL 4.0 MREM 0.047 ORGAN LIVER THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWFJsLTH EDISON OFFSITE DOSE CALCULATION '%NUAL.

THESE TECHNIQUES DIFFER FROM THOSE DESCRIBED IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION _1.1 January 1995 t

l' ?POMI

BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 CHILD RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 1.12E 03 5.77E-04 1.74E-03 7.38E-04 4.17E-03 BODY l

INTERNAL 3.60E-03 1.15E-03 8.97E-03 1.08E-03 1.46E-02 l

ORGAN l

LIVER GI_LLI LIVER LIVER LIVER THIS IS A REPC"T FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10 CFR 50 APP. I


 % OF APP I. ------------

QTRLY 1ST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.07 0.04 0.12 0.05 3.0 0.14 I

CRIT. ORGAN (MREM) 5.0 0.07 0.02 0.18 0.02 10.0 0.15 LIVER GI LLI LIVER LIVER LIVER l

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 f

(

i

BYRON STATION UNIT ONE l

1997 ANNUAL REPORT PROJECTED DOSE AT NEAdST COMMUNITY WATER SYSTEM

  • PERIOD OF R'CLEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 CHILD RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER AN!J t %

JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 5.85E-04 3.39E-04 3.81E-04 5.55E-04 1.86E-03 l-BODY INTERNAL 5.92E-04 3.44E-04 4.04E-04 5.57E-04 1.89E-03 l

ORGAN l

LIVER GI_LLI LIVER GI_LLI LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

% OF LIMIT TOTAL 4.0 MREM 0.046 BODY

-INTERNAL 4.O MREM 0.047 ORGAN LIVFR THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWEALTH EDISON OFFSITE DOSE CALCULATION MANUAL. THESE TECHNIQUES DIFrER FROM THOSE DESCRIBED IN 40 CFR 141.

RESULTS BATED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 e

BYROM STATION UNIT ONE 4

ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 i

TEENAGER RECEPTOR 1ST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER NTNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC 4

TOTAL 1.52E-03 5.67E-04 3.58E-03 6.17E-04 6.2BE-03 BODY INTERNAL 3.58E-03 2.33E-03 9.55E-03 9.02E-04 1.49E-02 ORGN1 LIVER GI_LLI LIVER LIVER LI VER TilIS IS A REPORT FOR THE CALENDAR YEAR 1997

]

1

?

J COMPLIANCE STATUS - 10 CFR 50 APP. I 3


 % OF APP I. ------------

<~

QTRLY iST QTR 2ND QTR 3RD QTR 4TH CTR YRLY

% OF j

OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.10 0 4 0.24 0.04 3.0 0.21 CRIT. ORGAN (MREM) 5.0 0.07 0.05 0.19 0.02 10.0 0.15 LIVER Gl_LLI LIVER LIVER

LIVED, RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1 1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 i

I 4

1 I

_. _ _, = _, -

B740N STATION UNIT ONE 1997 ANNUAL REPORT PROJECTED DOSE AT NEAREST COMMUNITY WATER SYSTEM

  • PERIOD OF RELEA9E - 01/01/97 TO 12/31/97 JALCULATED 03/02/98 TEENAGER RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 3.06E-04 1.77E-04 2.01E-04 2.90E-04 9.73E-04 BODY INTERNAL 3.11E-04 1.87E-04 2.10E-04 2.94E-04 9.92E-04 ORGAN GI_LLI GI_LLI LIVER GI_LLI GI_LLI l

THIS IS A REPORT FOR THF CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

%,0F LIMIT I

TOTAL 4.0 MREM 0.024 BODY INTERNAL 4.0 MREM 0.025 ORGAN l

GI_LLI THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWEALTH EDISON OFFSITE DOSE CALCULATION MANUAL.

THESE TECHNIQUES DIFFER FROM THOSE DESCRIBE 0 IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATAE\\SE VERSION 1.1 January 1995

BYRON STATION UNIT ONE ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS

-PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 ADULT RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL

  • AN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 2.59E-03 8.47E-04 6.42E-03 9.34E-04 1.00E-02 BODY

-INTERNAL

.3.65E-03 3.33E-03 9.44E-03 1.05E-03 1.51E-02 ORGAN LIVER GI_LLI LIVEP LIVER

. LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 l

COMPLIANCE STATUS - 10 CFR 50 APP. I


 % OF APP I. ------------

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.17 0.06 0.43 0.06 3.0 0.36 CRIT. ORGAN (MREM) 5.0 0.07 0.07 0.19 0.02 10.0 0.15 LIVER GI_LLI LIVER LIVER LIVER RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATARASE VERSION 1.1 January 1995 l

l l

8 BYRON STATION UNIT ONE 1997 ANNUAL REPORT PROJECTED DOSE AT NEAMST COWUNITY WATER SYSTEM

  • PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 ADULT RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 4.34E-04 2.50E-04 2.88E-04 4.10E-04 1.38E-03

-BODY INTERN \\L 4.41E-04 2.67E-04 2.92E-04 4.18E-04 1.41E-03 l

ORGAN GI_LLI GI_LLI LIVER GI_LLI GI_LLI THIS IS A REPORT FOR THE CALENDAR YEAR 1997 I

COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

% OF LIMIT TOTAL 4.0 MREM 0.035 BODY INTERNAL 4.0 MREM 0.035 ORGAN GI_LLI THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWEALTH EDISON OFFSITE DOSE CALCULATION MANUAL. THESE TECHNIQUES DIFFER FROM THOSE DESCPIBED IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MAhJH 1996 ODCM SOFTWr.RE VERSION 1.1 January 1995 ODCM DATABASE VERSICN 1.1 January 1995 1

o

4 B(RON STATION UNIT ONE 10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/97 TO 12/31/97 CALCULATED 03/02/98 1.

10 CFR 20.1301 (a g1) ComplianceD 1

l Total-Effective DeJe Egivalent, mrem /yr 9.34E-03 l

l 10 CFR 20.1301 (a) (1) limit mrem /yr 100.0

% of limit 0.01 compliance Summary - 10CFR20 let 2nd 3rd 4th

% of Otr otr otr Qtt Limit TEDE 2.02E-03 1.2(F-03 4.64E-03 1.42E-03 0.01 RESULTS BASED UPON: ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM D/.TABASE VERSION 1.1 January 1995

=

l BYRON STATION UNIT ONE 10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/97 TO 12/31/97 l

CALCULATED 03/02/98 2.

10 CFR 20.1301 (d)/40 CPR 190 compliance Dose Limit

% of (mrem)

(mrem)

Limit Whole Body Plume 3.08E*05 IDDE)

Skythine 0.00E+00 Ground 3.34E-04 Total 3.65E-04 25.c 0.00 organ Dose Thyroid 7.75E-03 75.0 0.01 (CDE)

Gonads 9.01E-03 25.0 0.04 Breast 7. 6 9 E-33 25.0 0.03 i

Lung 7.80E-03 25.0 0.03 Marrow 8.46E-03 25.0 0.03 Bone.

.s9E-02 25.0 0.04 Remainder 1.02E-02 25.0 0.04 CEDE 8.98E-03 TEDE 9.34E-03 100.0 0.01 RESULTS BASED UPON: ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 4

I BYROM STATION UMIT TUO ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 INFANT RECEPTOR l

1ST 2ND 3RD 4TH i

TYPE QUARTER QUARTER QUARTER QUART's ANNUAL JAN-MAR APR-JUN JUL-SEP OCT LC t

GAMMA AIR 4.17E-06 7.46E-06 4.88E-06 2.01E-05 3.66E-05 l

(MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.14E-05 1.60E-05 1.72E-05 3.96E-05 8.41E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

70T. BODY 3.04E-06 5.45E-06 3.47E-06 1.47E-05 2.67E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

SKIN 8.29E-06 1.20E-05 9.18E-06 3.20E-05 6.14E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

i ORGAN 9.96E-05 6.63E-05 4.97E-05 7.18E-05 2.87E-04 (MREM)

(NE )

(NE )

(NE )

(NE )

(NE )

1 THYROID LUNG LUNG LUNG LUNG i

THIS IS n REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10CFR 50 APP. I INFANT RECEPTOR


 % OF APP I. ------------

QTRLY 1ST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SKIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 ORGAN (MRLM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 THYROID LUNG LUNG LUNG LUNG RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 193t ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

BYRON STATION UNIT TDO ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELTASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 CHILD RECEPTOR 1ST 2ND 3RD 4TH TYPE QUARTER QUARTER QUAhrER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC GAMMA AIR 4.17E-06 7.46E-06 4.BBE-06 2.01E-05 3.66E-05 (MRAD)

ISSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.14E-05 1.60E-05 1.72E-05 3.96E-05 8.41E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 3.04E-06 5.45E-06 3.47E 06 1.47E-05 2.67E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

SKIN 8.29E-06 1.20E-05 9.18E-06 3.20E-05 6.14E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 7.03E-05 2.02E-04 1.06E-04 7.14E-0$

4.76E-04 (MREM)

(NE )

(SSE )

(SSE )

($

)

(SE )

THYROID GI LLI GI LLI GI LLI

~

THIS IS A REPORT FOR THE CALE DAR YEAR 1997

~ '

GI LLI COMPLIANCE STATUS - 10CFR 50 APP. I CHILD RECEPTOR

- --- -------- % O F AP P I.

QTRLY IST OTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SXIN (MREM) 7.5 0.00 0.00 0.00 0.00-

-15.0 0.00 ORGAN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 THYROID GI,LLI GI_LLI GI_LLI GI_LLI RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

BYROM STATION UNIT TWO ACTUAL 1997 MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 TEENAGER RECEPTOR IST 2ND 3RD 4TH TYPE QUARTER QUARTEk QUARTER QUARTER ANNUAL JAN-MAR APR-JU14 JUL-SEP OCT-DEC GAMMA AIR-4.17E-06

.7.46E-06 4.88E-06 2.01E-05 3.66E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.14E-05 1.60E-05 1.72E-05 3.96E-05 8.41E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TOT. BODY 3.04E-06 5.45E-06 3.47E-06 1.47E-05 2.67E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

SKI!!

8.29E-06 1.20E-05 9.18E-06 3.20E-05 6.14E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 4.58E-05 1.33E-04 1.26E-04 5.36E-05 2.25E-04 (MREM)

(NE )

(SSE )

(SSE )

(S

)

(SE )

THYROID GI LLI GI LLI GI LLI

?t'IS IS A REPORT FOR THE CALE DAR YEAR 1997

~

GI LLI

~

l COMPLIANCE STATU3 - 10CFR $0 APP. I TEENAGER RECEPTOR

- - - - - - - - - - - - i O F AP P I. - - - - - - - - - - --

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I GAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 1

10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MREM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SKIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 ORGAN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 THYROID GI_LLI GI_LLI GI_LLI GI_LLI RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERS 1 0 1.1 January 1995

BYRON STATION UNIT T00 ACTUAL 1997 f

MAXIMUM DOSES RESULTING FROM AIRBORNE RELEASES PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 ADULT RECEPTOR IST 2ND 3RD 4TH TYPE QUARTER QUARTEP QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC GAMMA AIR 4.17E-06 7.46E-06 4.88E-06 2.01E-05 3.66E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

BETA AIR 1.14 E- 05 1.60E-05 1.72E-05 3.96E-05 8.41E-05 (MRAD)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

TO1. BODY 3.04E-06 5.45E-06 3.47E-06 1.47E-05 2.67E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

SKIN 8.29E-06 1.20E-05 9.18E-06 3.20E-05 6.14E-05 (MREM)

(SSE )

(SSE )

(SSE )

(SSE )

(SSE )

ORGAN 6.37E '"

1.22E-04 1.13E-04 6.55E-05 3.58E-04 (MREM)

(S

)

(3

)

(SE )

(S

)

(S

)

THYROID GI LLI GI LLI GI LLI GI LLI

~

THIS IS A REPCRT FOR THE CAI.E DAR YEAR 1997

~

COMPLIANCE ETATUS - 10CFR 50 APP. I ADULT RECEPTOR

% OF APP I.

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I JAMMA AIR (MRAD) 5.0 0.00 0.00 0.00 0.00 10.0 0.00 BETA AIR (MRAD) 10.0 0.00 0.00 0.00 0.00 20.0 0.00 TOT. BODY (MhEM) 2.5 0.00 0.00 0.00 0.00 5.0 0.00 SMIN (MREM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00

-ORGAN (MBEM) 7.5 0.00 0.00 0.00 0.00 15.0 0.00 THYROID GI_LLI GI_LLI GI_LLI GI_LLI RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995 A

~

,-,,,_.-._,.._,-...c.--.-.._.

.. ~

, ~,..

e BYRON STATION UNIT T00 ACTUAL 1997 MAXIMUM DOJC5 (HREM) RESULTING FROM AQUATIC EFFINENTS PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 INFANT RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTEA QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 5.81E-04 3.37E-04 3.77E-04 5.51E-04 1.85E-03 BODY l

INTERNAL 5.92E-04 3.38E-04 4.11E-04 5.52E-04 1.89E-03 l

ORGAN LIVER GI_LLI LIVER IIVER LIVER THIS IS A REPORT FOR THE CALENDAP YEAR 1997 COMPLIANCE STATUS - 10 CFR 50 APP. I

- - -- - - - - - - - - % O F A P P I. - - - - - - - - - -- -

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC "9J APP. I TOTAL BODY (MREM) 1.5 0.04 0.02 0.03 0.04 3.0 0.06 CRIT. ORGAN (MREM) 5.0 0.01 0.01 0.01 0.01 10.0 0.02 LIVER GI_LLI LIVER LIVER LIVER RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

~

e ^

BYRON STATION UNIT TWO 1997 ANNUAL REPORT PROJECTED DOSE AT NEAREST COMMUNITY WATER SYSTEM

  • PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 INFANT RECEPTOR IST 2ND 3RD 4TH

)

DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JaN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 5.81E-04 3.37E-04 3.77E-04 5.51E-04 1.0$E-03 s

BODY INTERNA 1.

5.92E-04 3.30E-04 4.11E-04 5.52E-04 1.89E-03 ORGAN-LIVER GI_LLI LIVER LIVER LIVER l

THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

% OF LIMIT TOTAL 4.0 MREM 0.046 BODY INTERNAL 4.0 MREM 0.047 ORQW LIVER THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWEALTH EDISON Ol'FSITE DOSE CALCULATION MANUAL. THESE TECHNIQUES DIFFER FROM THOSE DESCRIBED IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION:1.1 January 1995 e

4 BYRON STATION UNIT TUO ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS FERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 CHILD RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 1.12E-03

$.77E-04 1.74E-03 7.3BE-04 4.17E-03 BODY INTERNAL 3.60E-03 1.15E-03 8.97E-03 1.08E-03 1.46E-02 ORGAN LIVER GI,LLI LIVER LIVER LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10 CTR 50 APP. I


 % OF APP I. ------------

QTRLY IST QTR 2ND OTR.

3RD OTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I f

TOTAL BODY (MREM) 1.5 0.07 0.04 0.12 0.05 3.0 0.14 CRIT. ORGAN (MREM) 5.0 0.07 0.02 0.18 0.02 10.0 0.15 LIVER GI_LLI LIVER LIVER LIVER RESULTS BASED UPON:

ODCM ANNEX REVISION

-1.3 MARCH 1996

-ODCM SOFTWARE VERSION 1.1 January 1905 ODCM DATABASE VERSION 1.1 January 1995

O s

BYRON STATION UNIT TUO 1997 PNNUAL REPORT PROJECTED DOSE Ai' NEAREST COMMUNITY WATER SYSTEM

  • PERIOD OF RELEASE - 01/01/97 TO 12/31/97 C/ t.CULATED 03/02/98 CHILD RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUAL 7ER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 5.85E-04 3.39f-04 3.81E-04 5.55E-04 1.86E-03 BODY INTERNAL 5.92E-04 3.44E-04 4.04E-04 5.57E-04 1.89E-03 ORGN4 LIVER GI_LLI LIVER GI_LLI LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 l

COMPLIANCE STATUS - 40 CFR 141 l

TYPE ANNUAL LIMIT

% OF LIMIT TOTAL 4.0 MREM 0.046 BODY INTERNAL 4.0 MREM 0.047 ORGAN LIVER THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONNEALTH CDISON vFFSITE DOSE CALCULATION MANUAL. THESE TECHNIQUES DIFFER FROM T. LOSE DESCRIBEP IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

__.._.._.__._..__=.__..-._._..___._m l

1 BYRON STATION UNIT TWO ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFLUENTS PERIOD OF RELEASE - 01/01/97 TC 12/31/97 CALCULATED 03/02/98 TEENAGER RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUART 2R QUARTER QUARTER ANNUAL JAN-MAR APR-JVN JUL-SEP OCT-DEC TOTAL 1.52E-03 5.67E-04 3.58E-03 6.17E-04 6.2BE-03 BODY INTERNAL 3.58E-03 2.33E-03 9.55E-03 9.02E-04 1.49E-02 ORGAN LIVER GI_LLI LIVER 7IVER LIVER THIS IS A REPORT FOR THE CALFNDAR YEAR 1997 COMPLIANCE STATUS - 10 CTR $0 APP. I


 % OF APP I. ------------

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.10 0.04 0.24 0.04 3.0 0.21 CRIT. ORGAN (MREM) 5.0 0.07 0.05 0.19 0.02 10.0 0.15-LIVER GI_LLI LIVLR LIVER LIVER

-RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

4 BYRON STATION UNIT TWO 1997 ANNUAL REPORT P* OJECTED DOSE AT NEAREST COMMUNITY WATER SYSTEM

  • n PERIOD 0" RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/98 TEENAGER RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 3.06E-04 1.77E-04 2.01E-04 2.90E-04 9.73E-04 BODY INTERNAL 3.11E-04 1.87E-04 2.10E-04 2.94E-04 9.92E-04 ORGAN GI_LLI CI_LLI LIVER GI_LLI GI_,LLI THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT

% OF LIMIT TOTAL

/.0 MREM 0.024 BODY INTERNAL 4.0 MREM 0.025 ORGAN GI_LLI THIS CALCULATIOJ OF DOSE IS EASED ON TECIINIQUES DESCRIBED IN THE COMMONWEALTH EDISON OFFSITE EOSE CALCULATION MANUAL. THESE TECHNIQUES DIFFER FROM THOSE DESCRIBED IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCr4 SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

o

^

BYRON STATION UNIT 700 ACTUAL 1997 MAXIMUM DOSES (MREM) RESULTING FROM AQUATIC EFFtUENTS PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/90 ADULT RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTER QUARTER QUARTER ANNUAL JAN-MAR APR-JUN JUL-SEP OCT-DEC TOTAL 2.59E-03 8.47E-04 6.42E-03 9.34E 1.0BE-02 BODY INTERNAL 3.65E-03 3.33E-03 9.44E-03 1.05E-03 1.51E-02 ORGAN LIVER GI_LLI LIVER LIVER LIVER THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 10 CFR 50 APP. I


 % OF APP I. ------------

QTRLY IST QTR 2ND QTR 3RD QTR 4TH QTR YRLY

% OF OBJ JAN-MAR APR-JUN JUL-SEP OCT-DEC OBJ APP. I TOTAL BODY (MREM) 1.5 0.17 0.06 0.43 0.06 3.0 0.36 CRIT. ORGAN (MREM) 5.0 0.07 0.07 0.19 0.02 10.0 0.15 LIVER GI_LLI IIVER LIVER LIVER RESULT.9 BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTilARE VERSION 1.1 January 1995 ODCM DATA'5ASE VERSION 1 c 1 January 1995

t

+

BYRON STATION UNIT TWO 1997 ANNUAL REPORT PROJECTED DOSE AT NEAREST COMMUNITY WATER SYSTEM

  • PERIOD OF RELEASE - 01/01/97 TO 12/31/97 CALCULATED 03/02/96 ADULT RECEPTOR IST 2ND 3RD 4TH DOSE TYPE QUARTER QUARTEk QUARTER QUARTER ANNUAL JAN-MAR APR-J'JN JUL-SEP OCT-DEC TOTAL 4.34E-04 2.50E-04 2.88E-04 4.10E-04 1.38E-03 BODY INTERNAL 4.41E-04 2.67E-04 2.92E-04 4.18E-04 1.41E-03 ORGAN GI_LLI GI_LLI LIVER GI_LLI GI_LLI THIS IS A REPORT FOR THE CALENDAR YEAR 1997 COMPLIANCE STATUS - 40 CFR 141 TYPE ANNUAL LIMIT 4 OF LIMIT TOTAL 4.0 MREM 0.035 BODY INTERNAL 4.0 MREM 0.035 ORGAN GI_LLI THIS CALCULATION OF DOSE IS BASED ON TECHNIQUES DESCRIBED IN THE COMMONWEALTH EDISON OFFSITE DOSE CALCULAT' N MANUAL. THESE TECHNIQUES DIFFER FROM THOSE DESCRIBED IN 40 CFR 141.

RESULTS BASED UPON:

ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1 January 1995

BYRON STATION UNIT TMO 10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/97 TO 12/31/97 CALCULATED 03/02/98 1.

10 CFR 20.1301 (a) (1) Complier.ceD Total Effective D:se Eqivalent, mrem /yr 8.71E-03 10 CFR 20.1301 (a) (1) limit mrem /yr 100.0

% of limit 0 01

(

Compliance Summary - 10CFR20 ist 2nd 3rd 4th 4 of Otr Qtr Qtr Gtr Limit TEDE 2.02E-03 1.23E-03 4.63E-03 8.30E-04 0.01 RESULTS BASED UPON: ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1 January 1995 ODCM DATABASE VERSION 1.1. January 1995 I

t e

BYRON STATIC.f UNIT TWO 10 CFR 20 COMPLIANCE ASSESSMENT PERIOD OF ASSESSMENT 01/01/97 TO 12/31/97

-CALCULATED 03/02/98 2.

10 CFR 20.1301 (d)/40 CFR 190 compliance Dose Limit

% of (mrem)

(mrem)

Limit Whole Body Plume 2.67E-05 (DDE)

Skyshine 0.00E+00 Ground 3.11E-05 Total 5.7BE-05 25.0 0.00 organ Dose Thyroid 7.39E-03 75.0 0.01

~569E-03 25.0 0.03 (CDE)

Gonads 8

Breast 7.37E-03 25.0 0.03 Lung 7.44E-03 25.0 0.03

.i Marrow 8.14E-03 25.0 0.03-Bone-1.06E-02 25.0 0.04 Remainder 9.89E-03 25.0 0.04 CEDE 8.65E-03 TEDE 8.71E-03 100.0 0.01 RESULTS BASED UPON: ODCM ANNEX REVISION 1.3 MARCH 1996 ODCM SOFTWARE VERSION 1.1' January 1995 ODCM DATABASE VERSION 1.1 January 1995

_l