Exhibit C Monticello Nuclear Generating Plant Supplement 1 to l
License Amendment Request Dated October 31,1997 Revised Technical Specification Pages l
l Exhibit C consists of revised Technical Specification pages that incorporate the proposed changes.
The pages included in the exhibit are as listed below:
Pages 5b 60d 71a l
l I
i l
i i
j C-1
'i-9809200328 980925
~
PDR ADOCK 05000263 P
pm
AQ. Core Ooerating Limits Recort The Core Operating Limits Report is the unit specific document that provides core operating limits for the current operating reload cycle. These cycle-specific operating limits shall be determined for each reload cycle in accordance with Specification 6.7.A.7. Plant operation within these operating limits is addressed in individual specifications.
AR. Allowable Value_ - The Allowable Value is the limiting value of the sensed process variable at which the trip setpoint may be found duting instrument surveillance.
1.0 Sb Amendment No. 70
Table 3.2.8 Other instrumentation Minimum No. of Minimum No. of Operable or Total No. of Instru-Operable or Operating Operating ment Channels Per Instrument Channels Required Function Trip Setting Trip System (1)
Trip System Per Trip System (1)
Conditions
- A.
RCIC Initiation
[
1.
Low-Low Reactor Level 26'6"& 56'10" 1
2 2
B above top of active fuel B.
HPCl/HCIC Turbine Shutdown a.
High Reactor Level s 14' 6" above 1
2 2
A top of active fuel C.
HPCi/RCIC Turbine Suction Transfer 4
a.
Condensate Storage 22' 3" above tank 1
2 2
C 2
Tank Low Level bottom Allowable Values (Two Tank Operation) 2 6' 9" above tank 1
2 2
C
[
bottom (One Tank Operation)
NOTE:
1.
Upon discovery that minimum requirements for the number of operable or operating trip systems or instrument channels are not l
l satisfied, action shall be initiated to:
a.
Satisfy the requirements by placing the appropriate channels or systems in the tripped condition (Turbine /Feedwater Trip only),
or j
b.
Place the plant under the specified required condition using normal operating procedures.
l Required conditions when minimum conditions for operation are not satisfied:
[
A.
Reactor in Startup, Refuel, or Shutdown Mode.
B.
Comply with Specification 3.5.D.
[
C.
Align HPCI and RCIC suction to the suppression pool.
l 3.2/4.2 60d Amendment No. 37,93 I
h
..e Bases 3.2,
,. id):
Trip Function Deviation Instrumentation for Safety / Relief Valve Reactor Coolant System i20 psig Low Low Set Logic Pressure for Opening / Closing Opening-Closing Pressure 260 psi Discharge Pipe Pressure inhibit 10 psid Timer inhibit
-3 sec
+10 sec Other Instrumentation
- High Reactor Water Level
+6 inches
- Low-Low Reactor Water Level
-3 inches
- This indication is reactor coolant temperature sensitive. The calibration is thus made for rated conditions. The level error at low pressures and temperatures is bounded by the safety analysis which reflects the weight-of-coolant above the lower tap, and not the indicated level.
A violation of this. acification is assumed to occur only when a device is knowingly set outside of the limiting trip settings, or, when a sufficient number o devices have been affected by any means such that the automatic function is incapable of operating within the allowable deviation while in a reactor mode in which the specified function must be operable or when actions specified are not initiated as specified.
3.2 BASES 71a Amendment No. 30,37,66,400a
-