ML20135H797
| ML20135H797 | |
| Person / Time | |
|---|---|
| Site: | Rancho Seco |
| Issue date: | 05/29/1985 |
| From: | SACRAMENTO MUNICIPAL UTILITY DISTRICT |
| To: | |
| Shared Package | |
| ML20135H794 | List: |
| References | |
| E.07, E.7, TAC-57558, NUDOCS 8509240240 | |
| Download: ML20135H797 (20) | |
Text
..
05-29-85 Rev.' l~
.[
WP0006F D-0063P E 07
'ICC Operator Action
...........................................~........................
~
3 CAUTION l
On SFAS actuation AFW Bypass Valves SFV-20577.(A OTSG)'and' 1
SFV-20578 (B OTSG) open.
These. valves have NO level control:
- signals.
Will require' throttling or_ shutting.-
(Rule 3 and 4) 1-+
NOTE Breakers 52-A2101 and 52-B2101 must be closed to operate high-a' 1
point vents. HV-21528, HV-21522. HV-20533. HV-20579, HV-20534 -
'r and HV-20580.
-23 1.
-Initiate HPI and 1.
(Rule 1, 2 &.5) --
- I-LPI.
~
.1 At panel H1RC, actuate SFAS channels lA and B, 2A and B.
.2 Max allowable flow through HPI pump is 525,gpa.
.3 E LPI is delivering flow, ensure maximum flow, not to exceed (3,000 gpa per pump) as read on H2SFA and H2SFB.
LPI injection flow A and.LPI injection flow B.
t b
8509240240 850919 PDR ADOCK 05000312 P
-(
Rev. 1 E.07-1 r
k f
k
i E.07
(
ICC 2.
Increase OTSG 1evel 2.
Increase'OTSG level to 95% on the P
(
to 95% on, Operating Range.
j the'Op Range.
1
- i. >.
s '
i j.
.1 Start / verify start AFW Pp.P-319 t
at HISS.-
j m
- + -
.0 Take;manualicontrol:of{AFW g
,;e
control.valvestat ElRC and. raise
'm level to:.95%-on Op Range.'. Rapid:
contro11ed' manner..
t u
<c VeifyAFWflowonPanelH2Ph'for
4
.4 Place AFW Pump-P-318 on electric' i
power.'
.1 LShut SFV-30801 AFW Pump Steam ~
- Inlet on H2SFB.
.2 2At HISS,2 push close button for SFV-30801.
.3 -At; HISS. bypass the AFW Pump j.
Diesel output breaker
-interlock, If Diesel
~
Generator is supplying the bus.
.4 Start P-318 motor.on HISS.
h 3.
Lower OTSG pressure 3.
Lower OTSG pressure to induce' heat
,c
-to induce heat transfer.
transfer.
.1 At H1RI open TBVs in manua1, 1 ' Lower OTSG Tsat lowering;OTSG pressure to decreasexv'.
90-110*F'below
'OTSG Tsat 90-110*F below T at
?
s Tsat for RCS for RCS pressure.
If,TBVs are pressure unavailable, use ADVs until TBVs
.and hold this are available.. Tsat cain be read. ; r.---
temperatur~e.
on:SPDS Post Trip Purple Ver.tical L
Line OR use OTSG prescure on HlRI j
or SPDS. and use steam tables, i;
g.
t 14
.2 When heat
.2 When heat' transfer is required 7
transfer is establish highest cooldown rate required possible not to exceed 100*F/hr.
establish I
highest cool-i down rate possible not to exceed 100*F/hr.
i 8
Rev. 1
- r t
E.07-2
~
L-
7_
- e.
E.07 ICC r
3.
.3 Maintain level at 95% on Op Range.
1+
.4 If RCS pressure increases to EMOV setpoint (2450) open EMOV. -Close EMOV when RCS. pressure decreases to4100 PSI above 0TSG pressure.
~ 4.- EnsureICore Flood 4.
. Ensure # Core > Flood Tankiisolation... uu:
i' Tank isolation _
valves 3(HV-26513 and-HV-26514).are f-valves (EV-26513 open. -l Indications at H2SFA and H2SFB.-
i and EV-26514) are open.
'5.
Take action based 5.
Take action based on'SPDS ICC' display i
on SPDS ICC display or Figure 2.
i or Figure 2.
4 Region Action
.1 Average of the five incore T/c_
1 Go to temperatures.
'2 Continue Preferred Alternate Step 1.0-
-T-9254 T-9256 e
1+*
5.0 above T-9258 T-9260 1
3 Go to T-9263 T-9252
(
Step 6 T-9272 T-9266 i
4 Go to T-9286 T-9270 Step 13
.2 SPDS Normal or Post Trip Display with incore button OR ICC Display.
(Question mark following value means it's a questionable reading.)
.2 Determine which r'egion of Figure 2 or ICC Display ~on SPDS that the RCS is in basedoon steps
.1.
.3 Using the' region determined in Step 5.2.
take action a' cording c
to the following Table.
Incores Read Region Action Saturated 1
Go to CP.103 Superheated 2
Continue J' l Step 1.0 -
!)
-l++
5.0 above, T Clad >1400*F 3
Go to' Step 6 T Clad >1800*F 4
Go to Step 13 Rev. 1 E.07-3 t
f 9
[
~
~
E L
i E.07
-(
f ICC s
t INCORE T/C TEMPERATURE IS'IN REGION 3 T~
s.
6.
~ Start ONE RCP per:
- 6.
Start.ONE RCP.per, loop..
'i6?
. '270,
i'
'l s
g
- m; loop;.
.1DO'NOTooverride.RCP interlocks.~
RCP, interlocks are: -I : ; i j:
t
.1:030. Percent -Rx Power.:
l:
.2.I RCP, motorf oililif t ;>l17hio psig.
s
.3 jRCP motor upper bearing l oil.
~
1 l
clevel; 2 inches.
.4
.RCP motor lower bearingLoil.
~
clevel't.2 inches: 9' i
.5 Seal injection flow'> 3 gpm
.6..'RCP Pump / Motor.CCW flow > 307
> gpm i
.7< To start fourth-RCP-Tc > 500*F
.8 ;-Motor' 86 Lockout (Motor.
. Protection Relay)'.
Normal -' Green Light: Dim 4
. Abnormal - Green Light Bright 7.
Lower OTSG pressure 7.
Lower OTSG pressure'to induce: heat '
Fi2? r 4
'~-
to. induce heat.
transfer.
10
, transfer.
~-- :(.: r
":t
.1 Depressuri::e
.1 At ElRI, open TBVs in manual, OTSG to 400 lowering OTSG pressure to 400 psig.
psig OR_ lower or'as low as needed to achieve a 1.F,_ necessary 100*F decrease in OTSG'Tsat to achieve a (decrease pressure capidly).' IF, 3
m 100*F decrease TBVs are unavailable,'use ADVs ac: '
in OTSG Tsat.
until TBVs are available.
Tsat j
can be read on SPDS Post Trip Purple Vertical Line OR use OTSG i
l pressure'on ElRI or'SPDS and use steam tables.
j
.2 Maintain OTSG level at 95% on'Op i
Range.
8.
Open all 8.
Open all high point vent valves.
high point vent e
valves.
.1 At H2SP open HV-20533 HV-20534, 1*
HV-20579, HV -20580.
i e,
Rev. 1 E.07-4 O
t t
E.07 ICC
(
, NOTE Guidelines for when the high point vents may be shut.-
1.
When core cooling in decay heat mode is established OR, 2.
When on natural circulation the RCS temperature is < 212*F,la..
'L then close high point vents.
~
Je' f
-.-y
[
9.
IP incore T/cs 9.
IF incore T/cs increase to region ; i' ;a ; -
[
increase to region 4,
go to Step.13.
Continue.-s a cr p r -
i 4
f 4, go to Step 13.
, '
- T r 4.'E F
)
Continue.
~ '
ni'r' 10..WHEN incore T/c
- 10. WHEN incore T/c returns to the i:. el; -
w:t
{
returns to the saturation temperature for the
- : 'a r m saturation tempera-existing RCS pressure, THEN continue n 6tc' ture for the exist-with Step 11.
~,;
ing RCS pressure,
. ' JiC i
THEN continue with
.1 Allow RCS to depressurize until'Tl ':
l i
Step 11.
HPI/LPI/CFT return incore T/c to 'D 1 i
saturation temperatures.
- 11. IF Primary to
- 11. JP_ Primary to Secondary Heat Tran'sf er.
.s-Secondary Heat is NOT established. THEN open the. > N i.. y e
Transfer is NOT EMOV and go to CP.104.
Otherwise. 'J AT.d : ;
established, THEN continue.
at.
I' open the EHOV and 7 - 1 _.'
>8 go to CP.lO4.
.1 Indications of Heat Transfer. M 1 Otherwise continue.
.1 Incore Temp within 10*F of.;'.r-Th
.2 Max expected RCS AT of 50*
to 60*F.
.3 T approx equal Tgat OTSG.
e
.4 Lowering OTSG Pressure causes corresponding decrease in TC.
NOTE Guidelines for closing the CFT l'olation valves.
s 1.
JF the RCS subcooled margin is established, the i
t depressurization is being controlled, and the RCS pressure 3-is below 700 psig, close the CFT isolation valve.
OR 2.
On low level in CFTs, close the CFT isolation valves.
r i:
I
< \\
(
Rev. 1 E.07-5
\\
).:
il 11 P '
E.07
[
- 12. IF Primary to_
- 12. IF Primary to Secondary Heat Transfer 3
Secondary Heat IS established. THEN go to CP.103. S Transfer IS esta-
~ -
-^ -
-~'blished,!THEN go
.1, -Indication'of' Heat Transfer.
I K~
to CP.103.
.1
.IncoreLTemp.within 10*F of
- }
4.; Th-
.2? Maxf. expected RCS AT of150' a
to'60*F.
4
.3.:: Tc" approx equal' T at OTSG.
S
.4 l Lowering OTSG Pressure ~causes s
'. corresponding _ decrease in Tc.
.2 Maintain Primary System. pressure
,j 25-50 psig greater than OTSG.
j pressure by:
.1-Cycling ~the pressurizer vent
!l
.1+*
valves HV-20528 and.HV-21522
+
E--FIRST CHOICE-- on Panel
'H2SP.
.2' Cycling-the EMOV-- SECOND CHOICE-.
(
e h
4 9
Rev. 1 E.07-6 t
I i
~
l
t.
E.07 ICC
(
INCORE T/C TEMPERATURE IS IN REGION 4.
I:~
~
~
'13.
Start ALL RCPs.
- 13. Start ALL RCPs.
'A.
UM <
.1 Bypass : interlocks,-if; necessary by.
F, manuallyfclosing'the' breakers;in
{
.theiWest4160V Switchgear; Room.,
i
- t
+
- ' ~ -
.2 DO'NOTidefeatioverloaditripf '
circuit..
i ~
.3 RCl Pump interlocks:-
f
<~30% Rx power RCP' motor. oil: lift >'1750 psig RCP, Motor. upper bearing oil level j
2 inches' RCP Motor-lower bearing oil level.
l 2-inches i
Seal injection flow'> 3 gpm RCP: Pump / Motor CCW flow > 307 gpm To. start-fourth RCP Tc > 500*F Motor 86l. Lockout (Protection j
Relay)
(
Normal - Green Light Dim Abnormal
. Green Light Bright
.4 Allow starting current on RCP to return to normal before starting the next RCP.
- 14. Lower OTSG pressure
- 14. Lower OTSG pressure to inducelheat-c:-
to induce heat transfer.
transfer.
.1 Jf_ Aux Boiler
.1 At.HIRI'open TBVsLin manual, and. 4 is operating, lower OTSG pressure as quickly as_
THEN decrease possible to' atmospheric pressure OTSG to atmos-IF.the-Aux Boiler-is operating, c.
pheric pressure IF:the: Aux: Boiler IS NOT r-4 operating, lower OTSG pressure to
.2 IF Aux Boiler 100 psig.
IF,.TBVs are not IS NOT operat-available, use ADVs until TBVs il ing, THEN are available.
I decrease OTSG pressure to
.2 Maintain OTSG level at 95% on 100 psig.
the Operating Range.
-(
Rev. 1 E.07-7 5
i
i E.07 ICC
_. - - _ ~
- 15. Depressurize the
- 15. Depressurize the RCS, open all high t
RCS, open all high point vents and EMOV.
Il point vents j!
and EMOV.
.1
- At Panel H2SP, open 4-
- j
.1 Hot Leg Vent Valves b
.2 HV-20534
[.
- .1-HV-20S33 14 -
.3' HV-20579 f
r - (. o :
ing RCS pressure, i
THEN continue with Indications
^' ' t' Step 17.
.1 Average of the five incore T/c temperatures.
Preferred Alternate T-9254 T-9256 T-9258 T-9260 T-9263 T-9252 T-9272 T-9266
-T-9286 T-9270
.2 SPDS Normal or Post Trip Display with incore button OR ICC Display.
(Question mark following value means it's a questionable reading.)
i
!s' b
Rev. 1 l
E.07-8 r
i f
f 1
'~
i E.07 ICC COOLDOWN FOLLOWING ICC (INCoaE TEMPERATURES HAVE BEEN IN REGION 4, NOW SATURATED)'%
~ i-i-
17., Decrease running..
117. Decreaseirunning RCPs:t'otone periloop. -
g!
.RCPs.to<one per
. ;1c
- c...
loop.
- s.
.,m e,c r
1'
- 18.TMaintain AFW flow.".
118. iMaintaini AFW flow.;.
b- - Aas. 7 : i:.l!'
2
- g' o.
.1-Maintain.95% on Op Range (SPDS.-
H2PS).1 j
.2
. Verify?AFW. flow on.H2PS.-
~
- 19. Continue this mode
- 19. Continue.this mode.until EITHER,
f..
it. r_
.until.EITHER n; i
~
j i
. 1 Lo-Lo level
.1 Lo-Lo-LevelIalarm on BWST,-Window h -Tg 9
. alarm on BWST, 29 on-H2SFB.' Verify level with ale,-
Window 29 on LI-25001 on H2SFB~THEN go to' Step A V H2SFB.. Verify 27.
. ;-JJ
)
. level with
. +d.
L.
4
?!c LI-25001'on l
- H2SFB,lTHEN go
'Fi t"
to Step 27.
', 2 t. 2 -.
OR OR
.2 LPI flow is
.2 LPI~ flow in 1,000 gpm per train greater than for at least 20 minutes as read 1,000 gpm per on-H2SFA and H2SFB..THEN go to e
train for at Step 20.
least 20 minutes, THEN go to Step 20.
6 20.. Isolate the CFT.
increases to a 1,000'gpm per.. train.
.1 Rack in breakers 2D228 and 2D229 forICFT outlet isolation valve HV-26513 and HV-26514.
J
,\\
~
.2 WHEN LPI flow has increased to kl l,000 gpm per train, THEN close
{'
4 CFT isolation valve HV-26513 at 1
panel H2SFA, and HV-26514 at l
panel H2SFB.
<(
Rev. 1 E.07-9 I
i i
7
~
g E.07
(
~
- 21. Secure HPI.
- 21. Secure HPI.
i'
.1 WHEN LPI: flow iscl.000 gpm-in I
each train.for'20 minutes as read l
~
}
on H2 SPA :and H2SFB.' stop HPI. --,,
.1 At panel.H2SFA.'.;take manual l
-control.and' secure..
u-1. li Makeup.Pp ; P--23 6 ' ,;.
l
- 2
- HP I 4 Pp ' " ' P--23 8A m -
j
.2 At. panel.H2SFB.'itake manual i
control and secure.
, ^
f j
.1'-Makeup Pp P-236
.2-HPI Pp P-238B
.3
'At panel'H2 SPA and H2SFB.'
f take manual control and;close.
..l~;HPI Valve Loop A
-l SFV-23809
. 2: HPI Valve Loop A
~
[
SFV-23811
.3
-HPI Valve Loop B SFV-23810
.4 HPI Valve Loop B
~
i SFV-23812
(
,{
- 22. Close High
- 22. Close High Point Vents.
- . ~
r ;c Point Vents.
.1 At panel H2SP, close
.1 HV-20533 Loop A Vent 1**
.2 HV-20579 Loop A Vent
.3 HV-20534 Loop B Vent 1+
.4 HV-20580 Loop B Vent
.5 HV-21528 Pressurizer Vent
.6 HV-21522-Pressurizer Vent
- 23. Close EMOV.
- 23. Close EMOV at H1RC.
r..
- s.
v.
If RCS pressure increases to 150 psig, open the EMOV.
I CAUTION:
DO NOT ESTABLISH A PLOW PATH IN ANY SYSTEM ISOLATED BY SFAS WITHOUT REVIEW OF THE POTENTIAL RELEASE OF RADIOACTIVE GAS OR LIQUID.
4 Rev. 1 E.07-10 e
i
f E.07
/
ICC CAUTION:
Prior to transferring LPI suction from the BWST to the RB i
Emergency Sump, evacuate the -20 and -47 foot of the t
Auxiliary Building.
(
- ~
i i
t
- 24. Transfer LPI suc-
- 24. Transfer-LPI: suction to RB Emergency: '
i
-tion.to,RB Emer.
Sump on Lo-Lo Level BWST-alarm :
I gency Sump;on Lo-Lo on.H2SFB :(transfer within 4
- 402,
(
Level BWST alarm minuteslof receiving alarm).
i.
{
(transfer within 4 i
minutes of receiv-
.1 Verify Lo-Lo Level using LI-25001 i
ing alarm).
on H2SFB.
k.
i t
.2 Open'HV-26105 and HV-26106 RB Emergency Sump outlets on Panel l
H2 SPA and;H2SFB.
THEN close SFV-25003'and SPV-25004 BWST i!
L outlets.on Panel'H2SFA and
^li H2SFB.- Push buttons must be held i!
in until the valve is in the Full
(
Closed Position.
g l
.3 IF DH High Flow alarm is
' r j(
received. (DH Cooler Flow) THEN throttle SPV-26039 (Loop A) and/or SFV-26040 (Loop B) on H2SFA and H2SFB to decrease flow to 3.000 gpm per train as read on FI-26003 and FI-26004 on H2 SPA and H2SFB.
- 25. Stop the operating
- 25. Stop the operating RCPs.
i RCPs.
.1 WHEN the LPI suction has been shifted to the RB Emergency Sump AND LPI System is operating properly (NSCW. NSRW. and DH Flow). THEN stop the operating RCPs.
I
- 26. Continue LPI
- 26. Continue LPI cooling until further
[
cooling until fur-instructions are given - END.
!i i
ther instructions l
are given - END.
7 i
l r
i
!('
Rev. 1 i
j E.07-11 e
f i
5 I
I' i
e E.07 ICC
,BWST LO-LO LEVEL ALARM.
LPI FLOW IS <1000 GPM PER TRAIN.
5I 7
r j
' 27. E both Decay Heat.
27.-,IP_ both Decay 1 Heat ' Systems ;are " ~
'r Systems are
/
. operable,1,THEN go t to. Step 34 7 IP ' 7i t i
k operable THEN'go to only,one; Decay Heat System 41s1~
CW1 -.'
[
Step 34.
E only operable.)THEN[ continue.-
l}
". c e t
of one Decay ~ Heat--
--System -is ' operable.
W.
4' n.
1:
W' i
I.
1
+m THEN continue.
'as a L -
1, i
......................-r--
~
e-t CAUTION
- c u t-Emergency-Sump, evacuate the -20 and -47 foot of the: "
"t
- rw r i;
' Auxiliary Building.
Tu c *a
-- )
- -...................................................................~m--
.t 1
t
- 28. One DHR System
t:
operable.. Align pump piggyback to operable DHS pump :rcten
[.
HPI/MU pump piggy-AND shift the operable DHS pump: lU": /,4 pen - p
.back to operable suction'from' the BWST to the Emergency tm i
p; <
,fr/
pump suction from
.1 Align HPI/MU pimp piggyback to1-'
.c; the BWST to the-the operable DIS pump.
Emergency Sump.
.1~
Stop the HPI/MU pump not aligned to the operable DHS pump.-.
.2
- Open appropraite piggyback valve:
A Train B Train HV-26007 HV-26008
~
.2 Shift operable DHS pump suction from the BWST to the Emergency Sump.
.1
.Open Appropriate Emergency
' Sump valve:
A Train B Train HV-26105 HV-26106
.2 Close appropriate BWST
[
suction valve:
I A Train B Train SFV-25003 SPV-25004
.3 WHEN TWO DH Systems are operable, THEN to to Step 34; otherwise, continue.
Rev. 1 i
E.07-12 o
6
l t
r 1
E.07 i
a l('
\\
J_F_ Primary Tempera ture can-be. . :
' h.
I
- 29. J.F. Primary Temp 29.
F
~"
j can be controlled controlled by steaming the OTSGs. :n 2: :."
i by steaming the THEN go;to Step 32; otherwise~
1 0 7 '., '.
I i
OTSGs THEN go to continue.;
UTE W, 1P1 l Step 32; otherwise
' J: 4 rJ 111 l'
continue.
~
,,?i't.,.
I 1, '.
- ~
i i
- 30. Ensure maximum HPI
- 30. Ensure maximum 'HPI flow.".' Observe 'HPIf t =
, l
~'
flow.
flow on:H2SFA~and~H2SFB Or; Max HPItE;D l
flow is;525fgpm PER PUMP.
I
.1 Additional;HPI/MU Pump'MAY b'e.
i I-aligned and started on the.
operating DES Pump.:
i
.2 Throttle-HPI flow only.as necessary,to prevent exceeding j{
limits of Figure 1.-
l
'31.. Continue HPI cool-
- 31. Continue HPI cooling until futher 'anErm ing until futher instructions are given by Stationin,,
~
instructions are Management - END.
1:s;:.rcii:. !
given by Station aivu
.y.
.I(
Management - END.
/a n 1
j
- 32. Cool down the RCS
- 32. Cool down the RCS by steaming the-c i.
by steaming the operable OTSG while maintaining HPI operable OTSG while
- flow, c
maintaining HPI
- 1 ;.
flow.
.1 Throttle HPI flow to' prevent
(
exceeding limits of Figure 1.
l
.1 Close the EMOV i
and cycle as
.2 Close the EMOV and cycle as necessary to necessary to maintain.less.than
~ o-maintain less 150.psig RCS pressure.
.. : q than 150 psig RCS pressure.
- 33. Continue OTSG cool-
- 33. Continue OTSG cooling until further ac; ~
1 ing until futher instructions are given by Station -
instructions are Management - END.
given by Station 4;
Management - END.
I'
+
i I
1 1
l
(
Rev. 1 E.07-13 e
i a
I
$j f
4 i
~
E.07
(
ICC BOTH DH SYSTEMS OPERABLE. DHS FLOW LESS THAN 1.000 GPM PER -
TRAIN, BWST IS AT LO-LO LEVEL.
CAUTION:
.,. Prior to transferring.LPI suction ~from the'BWST to the'RB -
Emergency Sump, evacuate the;-20 andE-47; foot of the 2
- ~ -Auxiliary. Building.
i mode and transfer from the BWST to the Emergency Sump.
- t DHS pump suction from the BWST to
.1 Open the following valves to '
the Emergency Sump.
establish piggyback mode:
"r
(
Valve Panel HV-26007 A DHS to A HPI H2 SPA-HV-26008
.2 Transfer DHS pump suction from BWST to Emergency Sump.
.1 Open the following valves:
Valve Panel EV-26105-A DHS Emerg H2SFA Sump Suction EV-26106 B DHS Emerg H2SFB Sump Suction
.2 Close the following valves:
Valve Panel SPV-25003 A DHS BWST H2SFA Suction SPV-25004 B DHS BWST H2SFB Suction l
i Rev. 1 E.07-14 1
1
~.,. _ _ _. _ _
4,:
'_o.,
4 E.07 ICC
~
{
35 Throttle HPI to
- 35. Throttle HPI:t'o' maintain minimum!sub-; ' '
maintain minimum cooling. margin (Rule 2) and interim -"'
4 subcooling margin brittle fracture limit (Figure.1).. -'
d, (Rule :2)-and inter-Continue this. mode of operation until:a -
y!
o im brittle' fracture
_RCS. press is reduced to 250'psig...-~' L f
~~
limit.(Figure 1).
THEN go;to Step 36.
.L:lt i -
7.
Continue'this mode 6
' P r i. m of' operation _until.
ar cm.
tc
- RCS' press is
'T' (f
i jJ reduced'to:250 en?v t' psig.
THEN go to
.(
'"m.'? 1 O:9 l' _
4
. Step 36.-
,-4
- 36. WHEN RCS pressure
- 36. WHEN RCS pressure is less than.250
'N n '_ '
t Lis less than 250 psig.. place B LPI, train.in the DHS -
't
_i i
(-
psig,. place B LPI-mode.
0
't train in the DHS la*/
.j ;
s mode.
.1 Stop B HPI' pump.
' l f.
l t
.2 Close core! flood tank isolation valves *
=
i Valve
' Panel
{
HV-26513 A CFT Isol
~H2SFA
{
HV-26514 B CFT~Isol
'H2SFB t
.3 Stop B DHS pump on Panel'H2SFB.
.4 Shut the following valve:
i:
Panel Valve' HV-26106 B DHS Emerg H2SFB Sump. Suction
.5 Open the following valves:
Valve Panel HV-20001 Drop Line Isol H2PS 4
HV-20002-Drop Line Isol H2PS' HV-20006 B DHS Drop Line H2SFB Isol.
j i
.6 Start B DHS pump on Panel H2SFB.
i and throttle to maintain 3,000 j
gpm.
l.
Rev. 1 E.07-15
i B
E.07 ICC y
1 36.
.7 Maintain cooldown rate as per
{
~
Tech Specs.
t
.1 Temp >270*F_- 100*F/hr.
l
.2 270*F > Temp >.170'-
50*F/hr
~
.3 170*F > Temp >.70*F 10*F/hr l
4 37.:WHEN RCS press is
- 37. WHEN RCS press is lessLthan 1504psig,'n a' I
11ess than 150 psig, establ.ish LPI/DHR' cooling.
~. c r.-y 1 s
^
.~ establish LPI/DHR A i.. -
l 9 :- ; ;
[
cooling.
.1 Stop RCPs.-
.2 Secure HPI.
l
.1 At panel.H2 SPA, take manual control and secure.
.1 : Makeup Pump P-236
.2 HPI Pump P-238A l'
.2 At panel H2SFB, take manual i
control and secure.
j
.1 Makeup Pump P-236 1
'2 HPI Pump P-238B i
.3 At panel H2 SPA and.H2SFB, take manual control and close.
4
.1 HPI Viv Loop A SFV-23809
.2 HPI Vlv Loop A SFV-23811
.3 HPI Vlv Loop B SPV-23810
.4 HPI Vlv Loop B SFV-23812 I
.3 Close all High Point Vents.
.1 At Panel H2SP, close:
.1 Hot Leg Vent Valves
.1 HV-20533 I
.2 HV-20534 1+
.3 HV-20579
+
.4 HV-20580
.2 Pressurizer Vent Valves, 1+*
HV-21528 and HV-21522.
.4 Close EMOV'.
Reopen EMOV if pressure goes above 150 psig.
[
f
.5 Establish overpressure protection.
- 38. Further actions
- 38. Further actions will be directed by will be directed Station Management.
r by Station Management.
1 Rev. 1 5
E.07-16 li e
t
-we l
FIGURE 1
[
REACTOR COOLANT SYSTEM INTERIM FRACTURE LIMIT NO FORCED FLOW AND THERMAL SHOCK OPERATING REGION 3200 -
5 NOTE: -Maintaining the reactor E coolant subcooled takes
,a000 -5precedenceovertheInterim N0' FORCED FLOW-i E Brittle Fracture Curve OPERATING BAND '--
2800 -g(B&W74-1122501page6)
W/HPI' i
5 INTERIM BRITTLE FRACTURE
. VARIABLE :
2600 E
CURVE BREAK POINTS 5
- =
SUSC00 LED :
INTERIM ERITTLE-
-- MARGIN E ETEMPERATURE PRESSURE FRACTURE CURVE m L
2400
-E E
303 250 N. ' ~~
E 500 1500
'.Y II OE ' i
,c' d 200 -
y m
=
C 2000 -
RESTRICTED i
~
/
~
g REGION e
=- -
g 3_.
- y z
~
h.
1800 -
i T. S. CURVE 3.1.2-2 V
' 'I NOT LIMIT
/
~
8._7600 -
\\
u
.x E 1400 4- -
b THERhIbS[0b 5
7200 --
GPERATING REGION _.'
'~
I
-e
.n, z
2:._ -
3 INCORE TC'S TO MONITOR.
es.
N 1000 -:
4
_ SATURATION.:
^'.
g EPREFERRED ALTERNATE:
' N -'
- k,',-
CURVE g
L-
'X
.1
-i -
800 -il) T9254 T9256
\\'.
I' j2)T9258 T9260
' N. '_
~C'?
- 23) T9263 T9252
/'
~
- 54) T9272 T9266
- 5. -
f' i
T9270
' ve'..
~ ~M " /
600
~
i ES) T9286
- f'--/'
RESTRICTED REGION E:
z 400 -
-n,-l
/
, g.-
_ ;fj
~
=_-
_~;
200 --
~
~'
r t
0 0
10 260 360 460 500 6d0 700 INDICATED RC TEMPERATURE
- F Rev. 1 E.07-17
4 t
r
~
FIGURE 2 CORE EXIT THERMOCOUPLE TEMPERATURE i
FOR INADEQUATE CORE COOLING
+,.
i-3000
..b It
-~
2300
.i u.
i.
f-A'.
...... ~ '
asww
~.
i
- = =
,9.ua j
I C
Luco k
AEGICM 2
... -~
g,, 9,,
~ " ' ~ ~
f 2200 seneration At* lCN ')
^ ^ ^ ' ~~ ' " f
~ ~ ~' I {
I ano fuel pia '
lt I
l.-- - f -. ~~ ~ ~ -.
-, e -
damage possible.'.
i
d e noger,
_ Gas generation;_.
+
damage likely.'
I!.
8"* 'u*' " i
'f 2000 F
I t
7.,la e el 300'.r.
I 1300
.0 l,
_(
p.
~
14C0 a
^
hf f
^
AESICN~ k
~_'
t 1200
- /
/
Significant gas
.._ generation and cl ad.
}
l
. ds:=. age stonable.
e~-
~
i 1000
~~'
~
'~^
AECICM l_
...d i
i i
"'S'*"'
300
~
- +4
/
1
- : cent ric e. urtt j
600 -
/
~.. =vo i mi s :a.-o e a rc a f
)
400 l
1)f1254 19216
_.. :) isrsa tirso
- 3) 11251 11252 i
f 4)istra 19zss 200 si nzas nzio r
l 0
6 6
6 6
1000 1200 1400 0
200 400 600 800 I
INCORE TEMPERATURE
'F l
Rev. 1 It 1
E.07-18
_ ~... -. _
i l
t.
FIGURE 3 HIGH PRESSURE INJECTION Fl.0W 4
VS.
REACTOR COOLANT SYSTEM PRESSURE 1000
_ =:--.= -. _ _._ _
-.=-._ ~-
,=_=---_.-_.---;=.._......
= _ _
-_.=.==.:._
_..==__ _
.._.__..._..2:
M.*_: :*.:..*.!.:"=.* : : ~- --
" * =. -
.4
?:
C., Q Q - ----.s__.---
- - - - -'----**:*.-_._!_".=-.=-'
+.
y.
1 n
y_____
m--
~_ _
_f..__..__:_._~:__~_--
~
_x 800 _. _
. _.x_. _
_ _. _ _ _. _ _.. _. - _ _ - _... = -
_ = _ _.=_ g._.. _ ; =
3_: =_ =..
_,e-
- Th r ee ' H P I Pwp s. _._...= ;. : :g.:,,,:. _
c
^
- - -- : __h
-. -. --.- -_ E '.
N
'm
._.__.___.__._._-------.-=...==f:=.
~
~
~~
700
-~
_._. g-1
--__._...__.==-===_:::-._r
~"~===:='"
1 n
^
Two H'PI Pwps'_....
. _g g.-.
.=
= _ _ _ _.
-== - _S
. y_ =:
. _. _ _. _ + _ _ _
.y..
~...,
., " ~. - - ' ~ ~ - '.
- =_
--=;-_-:.._
__. v. _ A _. -._.
......._--2:.--:.-
- r g~ ~ "
N
=;.:_=.
7 o'00
' ~ ~ ~ ~ - - ~-___:=-- --"_--.-m-
~ *"----__#".'~,~~'"=""""-
7 :_
v
~
- =
2.__ _ _._.-.=
_ _x
--w___---
One HPl Pcp
.. +. -.
- a
_. = _..
__-n. - -_~.x_:,=,
~
_..=--T-,-7_: : y y _ _,,_.----=..:=..r--_.:__
7-
---x-------
- g. o
_ - - _ = -
_._.x-__.._.
,. _ _. _ _ = _,.__=..:=._=.=_.=_.:._.__.=_-.:...-.__.
~ - - - ~ ~ - - -.. _ =. - _ =. =.. _ -
=
_,.. - n_.
_. :. = :.==:.:: :._.
_N__ ;. _ _: pM___ __._."_;::._-_.Vi$ g:[.., 3.";. t x=
- - - - - + : :. s ___ ;..__ _ -_.
x
- a..._== = -_.:_:.:-
_'-.4--
_. _ "..\\ :.m\\=.=_.: :_ =_~=_:;.: :.:..
_t:a
. w.:
"' y --
_-... - = _. -.. _.. _.. _ -
o.
ww
.N -----
-...V
_ _ _ __=._
-=~_:=--~__ - __. ~==== _.== - :::. N:. -. ; ;:- - * ~ -
..__c
...._.=: =__:- =.u u=.:--
. _ - - -- - h- : -== =.: =:. ; %.. :. _:-......
=== _: :: -- -- -- :.
=
- =... - -. -..: _
'"a
_2:
M_.. :.- * ;. : =._ = -
.-___.w=..=-"...=..-.
N h
_g._.
N--...
- .%_-=."*
200
.:F :9.'_W= $...qu.
-- __.7
d
._._..__s.._._.... _
. s. _ - :=-. _ -
S
...a.__
.___A._===_=.
-h
._.\\..__..
=r-
. _ -= -- = ---
=
- -- _= :=l:-." 6_Y.:h6 100
+ =- _._ :
_ _ _ _ =...,
. =. - - - - - _ _.
&_ =.. =-~_._~.-;i. =_:-E_'=_.. _^:-~1
-~
__.._ r.:, _
2.-
_._..=:---.-
n l
l l
l h
8 0
$00 1000 1500 2000 g 2500 3000 AEACTOR COOLANT SYSTEM 99 ESSURE--PSIG ket. L E.07-19 i
i
i J
r**
E 07 FLOWCHART FOR E.07 e
13 27 80TN DMS TES enTIATE HPI AND LPt ST ART ALL RCP'S PUWPS OPER ASLE l
l 2
NO 28 RAISE CTSG LowEROTSG ALIGN MPt/uu PRESSURE LEVELS TO 90-95%
Puur PtGGYS ACK l
5S j
3 lower OTSC OpEN ALL Na f
PRESSURE.
PONT VENTS s
Riu ARY TEM m
CONTROLLED BY I
l 16 ST E AuiNG l
4
'~" '
VERTY CFT TC TEuP AT NO 30 IS1 ATKN SATURATION
,yg a v4LVES CPEN
=!
1 ENSURE l
'?
uaxiuuu HP l
5 OECREASE l
T Axt ACTION RUNNING RCP'S l l
3g 8ASEO ON TO T PER LOOP '
l SPOS-eCC OWY CONTINVE l
18 pet COOLwG l
6 ST ART ONE u AwT AIN j k RCP PER LOOP AFw Ftow
? I
{
l 7
s 32 I
19.9 lower OTSG I
LO LO AL ARu YES COOL DowN HCS PRESSURE ST STE AumG OTSG
[
ON SwST
..~,
~ ' ' ~ - " " ' ' '
' ^
No i 9.2 OPEN ALL Me CONTmVE OTSG COOLING j
PONT VENTS LPt 4000 GPu PER Tram FOR~20 um.
l 20 g
TC TEup m vts REG 10N 4 ISOL ATE CFT'S M
29 NO go PLACE OPER ASLE
- N"' S "
TC TEuP AT SteuR6 MPt PtGGY 8 ACK S ATUR ATK)N i
39 l
?!
CLOSE ALL REcuCE RCS Alu1RT T HI POINT VENTS PRESS 70 2SO LSS NO EcoNc ARY HE AT GO TO CPIO4 TRANSFER i
l 36 i ASLISMr 1
CLOSE EuCV iN CHS uo0C l
37 GOToCPt03 l
TH ANSF ER LPs ESTASLISH SUCTION TO Suu, ON LO LO LEVEL OMS COOLWG ON SwST 29 FURTHER ACTION STOP ALL RC*'s OpCCTED BYSUPv l
76 CONTINUC LPt COOLING E.07-20 Ef(D t
I e